TDC 6
Indoor voltage transformers
Description
The TDC 6 voltage, double-pole insulated transformers are Rated primary voltages ... 11 kV; 15 kV; 20 kV; 22 kV
casted in epoxy resin and designed mostly for insulation Other primary voltages based upon customer‘s request may be
voltages of 17,5 kV to 24 kV. delivered, too.
Other insulation values are to be the subject of an agreement Rated secondary voltages... 100 V; 110 V – 0.2; 0.5 and 1
between the manufacturer and the customer. accuracy classes (measuring winding), or 3P; 6P (protection
If no other value is required the transformers are winding)
manufactured with a voltage factor of 1.2 x Un. All the parts Other secondary voltages based upon customer‘s request may
of the primary winding of the transformer are insulated be delivered, too.
from the earth, including the terminals, to an insulation level Rated frequency ... 50 Hz; 60 Hz
identical with the rated insulation level. When operating in Design for two primary voltages is also possible, based on
a three-phase system the primary inlets of the transformer are a consultancy to be conducted with the manufacturer (change
connected across the respective lines, to the phase-to-phase over secondary side).
voltage, mostly in the „V“ type of connections. The majority The transformers are manufactured and delivered conformably
of transformers is equipped with one secondary winding, to the requirements and recommendations of the following
intended to be used for either the measurement or protection standards and regulations: IEC, VDE, ANSI, BS, GOST and
purposes. One of the terminals of each secondary winding ČSN.
has to be earthed during the transformer operation.
If not required otherwise, the secondary winding is lead out
into a casted secondary terminal board.
The transformer may be mounted in any position. The
transformers are fixed by four screws, The M8 bolted
earthing clamp is located on the transformer base plate.
The secondary, sealable terminal board is covered with
a transparent cover made of plastic material.
Dimensions
116
93 165 M10x15
280
Pg16 쏗14
20
22
ZEM M8
EARTH
352
285
50 225
A U
130
150
178
96
B V
14
30 쏗14
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated
transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings,
with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the
auxiliary (residual) winding.
2
Standartized transformers
3
1VLC000523 - Rev. 2, en 2011, 01.15.