You are on page 1of 2

ELECTRICAL MAXIMUM LOAD DEMAND CALCULATION

Normal Voltage : 415 V


MOTOR DUTY CYCLE
/FEEDER Service Motor C=
Connected Load Working (Running) Maximum demand CONTINUOUS,
Sl. No. TAG No. Description RATING Voltage FEEDER TYPE /FEEDER P.F. L.F. D.F. in kW Load in kW load* I= REMARKS
PROVIDED (V) Efficiency INTERMITTE
(KW) NT
Total
Nos. Nos. Total Load in kVA
Load
A B C D E E1 F G H I J K L M N O P
DXJ (D XLX HXI)/F M /G

A PMCC LOADS AT PP-2 ECR , INCOMING SOURCE


FROM MCC-16(1000A BREAKER FEEDEER)
LOADS AT JH-05A A
1 FCC-2A BELT CONVEYOR 37.00 415 DOL STARTER 0.939 0.800 0.90 1.0 1 37.00 1 35.46 44.33 C ###
32A MCCB POWER
2 EH-01 ELECTRIC HOIST 4.49 415 FEEDER 0.900 0.85 0.40 1.0 1 4.49 1 2.00 2.35 I
LOADS AT NEW BIN BUILDING
1 FCC-3 BELT CONVEYOR 90.00 415 DOL STARTER 0.952 0.830 0.90 1.0 1 90.00 1 85.08 102.51 C ###
2 FRBC-1 REVERSIBLE BELT CONVEYOR 18.50 415 RDOL STARTER 0.926 0.800 0.90 1.0 1 18.50 1 17.98 22.48 C ###
3 MSG-1/2 MOTORIZED SLIDE GATE 2.20 415 DOL STARTER 0.867 0.740 0.60 1.0 2 4.40 2 3.04 4.11 I ###
4 BA-1/2 BIN ACTIVATOR 3.70 415 DOL STARTER 0.884 0.760 0.90 1.0 2 7.40 2 7.53 9.91 C ###
32A MCCB POWER
5 EH-02/03/04 ELECTRIC HOIST 4.49 415 0.900 0.85 0.40 1.0 3 13.47 3 5.99 7.04 I
FEEDER
ADDITIONAL LOADS
CONTROL SUPPLY LOADS FOR
PANEL SPACE HEATER,PANEL
1 …. ILLUMINATION 2.40 415 TRAFO FEEDER 0.900 0.85 1.00 1.0 1 2.40 1 2.67 3.14 C
SYSTEM,MOTOR SPACE
HEATER(415/240V-240V AC
SUPPLY)- 3KVA.
CONTROL SUPPLY LOADS FOR
2 …. CONTROL SUPPLY 2.40 415 TRAFO FEEDER 0.900 0.85 1.00 1.0 1 2.40 1 2.67 3.14 C
BUS(415/110V-110V AC
SUPPLY)- 3KVA.
POWER FEEDER FOR LIGHTING
63A MCCB POWER
3 …. TRANSFORMER(ILLUMINATIO 10.00 415 FEEDER 0.900 0.85 1.00 1.0 1 10.00 1 11.11 13.07 C
N SYSTEM)
POWER FEEDER FOR 63A 63A MCCB POWER
4 …. WELDING RECEPTACLE(LOOP 15.00 415 FEEDER 0.900 0.85 0.40 1.0 1 15.00 1 6.67 7.84 I
IN LOOP OUT)
6A MCB POWER IT WILL BE FED
5 BNWS-01/02 BIN WEIGHING SYSTEM 0.48 240 0.900 0.85 0.40 1.0 2 0.96 2 - - C
FEEDER FROM SLDB-1

SPARE
1 …. SPARE FEEDER FOR 2.2kW DOL 2.20 415 DOL 0.867 0.740 0.90 1.0 1 2.20 1 0.00 0.00 C
FEEDER
SPARE FEEDER FOR 3.7kW DOL
2 …. FEEDER 3.70 415 DOL 0.884 0.760 0.90 1.0 1 3.70 1 0.00 0.00 C

3 …. SPARE FEEDER FOR 18.5kW 18.50 415 RDOL 0.926 0.800 0.90 1.0 1 18.50 1 0.00 0.00 C
RDOL FEEDER
SPARE FEEDER FOR 37kW DOL
4 …. FEEDER 37.00 415 DOL 0.939 0.800 0.90 1.0 1 37.00 1 0.00 0.00 C

5 …. SPARE FEEDER FOR 90kW DOL 90.00 415 DOL 0.952 0.830 0.90 1.0 1 90.00 1 0.00 0.00 C
FEEDER
SPARE FOR 32A POWER 32A MCCB POWER
6 …. FEEDER 5.00 415 FEEDER 1.000 0.800 1.00 1.0 2 10.00 2 0.00 0.00 C

Page - 1 of 2
ELECTRICAL MAXIMUM LOAD DEMAND CALCULATION

Normal Voltage : 415 V


MOTOR DUTY CYCLE
/FEEDER Service Motor C=
Connected Load Working (Running) Maximum demand CONTINUOUS,
Sl. No. TAG No. Description RATING Voltage FEEDER TYPE /FEEDER P.F. L.F. D.F. in kW Load in kW load* I= REMARKS
PROVIDED (V) Efficiency INTERMITTE
(KW) NT
Total
Nos. Nos. Total Load in kVA
Load
A B C D E E1 F G H I J K L M N O P
DXJ (D XLX HXI)/F M /G
7 …. SPARE FOR 63A POWER 15.00 415 63A MCCB POWER 1.000 0.800 1.00 1.0 2 30.00 2 0.00 0.00 C
FEEDER FEEDER

8 …. SPARE FOR 800A POWER - 415 630A ACB POWER 1.000 0.800 1.00 1.0 1 0.00 1 0.00 0.00 C
FEEDER FEEDER
TOTAL LOAD 180.20 219.92
n=Efficiency
L.F.- Load factor *Maximum demand load in KVA = Working load in kW x L.F.x D.F. 219.92 KVA
D.F.- Diversity factor P.F. x Efficiency
220 kVA. X 1.2
eaker sizing CONSIDERING 20% MARGIN = 367 ~1000A ACB
(1.732x0.415)
NOTE:
1)INTERMITTENT, SHORT TIME LOAD IS CONSIDERED WITH LOADING FACTOR OF 0.6 ,EXCEPT FOR MOV WHICH IS CONSIDERED AS 0.2 & FOR HOIST WHICH IS CONSIDERED AS 0.4.
2)BELT WEIGH FEEDER (W.F.101/102)OF 7.5 kW RATING (1W+1S) WILL BE FED FROM MCC-10 EXISTING FEEDER AT IOGB BUILDING WITH NEW VFD.

Page - 2 of 2