You are on page 1of 15

Release 

Notes
( 9521-VPx ) Provides unified access to virtually all manufacturing/plant data sources, and produces web-based reports.
Version 8.31.00 (released 1/2022)

Catalog Number FactoryTalk VantagePoint EMI Server 

These release notes describe version information for FactoryTalk VantagePoint EMI Server, version 8.31.00 (released 1/2022).

Requirements
This release has the following requirements.

The following are the system requirements for FactoryTalk VantagePoint version 8.31.00.

FactoryTalk VantagePoint works within the system requirements of all Rockwell Automation® software products. For the latest information regarding software
platform support, refer to Rockwell Automation Product Compatibility and Download Center.

The hardware required with FactoryTalk VantagePoint depends on the demands an application places on the system. The greater the demand, the more
powerful system is required. In any application, faster processors and more memory will result in better performance. In addition, there should always be
sufficient disk space to provide virtual memory that is at least twice the size of the physical memory.

Before installing, ensure your system meets the following requirements.

System Server

Items Descriptions
Microsoft Windows Server 2012 R2
Operating Datacenter (64-bit)
System Microsoft Windows Server 2012 R2 SP1
Datacenter (64-bit)
Microsoft Windows Server 2016 Datacenter
(64-bit)
Microsoft Windows Server 2016 Standard
(64-bit)
Microsoft Windows Server 2019 Datacenter
LTSC (64-bit)
Microsoft Windows Server 2019 Standard
LTSC (64-bit)
Note: The VantagePoint IIS Application Pools are
set to 32-bit mode only.
Microsoft SQL Server 2012 Standard SP3
Software (64-bit)
Microsoft SQL Server 2012 Express SP3
Microsoft SQL Server 2016 Standard SP2
Microsoft SQL Server 2016 Express SP1
Microsoft SQL Server 2019 Express
Microsoft SQL Server 2019 Standard
Microsoft Office 2013 SP1 (32-bit only)
Microsoft Office 2016 (32-bit only)
Microsoft Office 2019 (32-bit only)
Microsoft Internet Explorer 11
Microsoft Edge 95 or later (Internet Explorer
mode)
Microsoft .Net Framework 4.8 full version
(included with install)
Microsoft .Net Framework 3.5 (added when
installing and configuring IIS)
2.5 GHz
Hardware 2 GB Hard Drive Space
4096 MB RAM
Full Client

Items Descriptions
Microsoft Windows 10 Enterprise (64-bit)
Operating Microsoft Windows Server 2012 R2
Systems Datacenter (64-bit)
Microsoft Windows Server 2016 Datacenter
(64-bit)
Microsoft Windows Server 2016 Standard
(64-bit)
Microsoft Windows Server 2019 Datacenter
LTSC (64-bit)
Microsoft Windows Server 2019 Standard
LTSC (64-bit)
Note: Embedded versions are not supported.
Microsoft Internet Explorer 11
Web Browser Microsoft Edge 95 or later (Internet Explorer
mode)
Note:
The Metro App for Internet Explorer 11 is not
supported.
You can use VantagePoint Mobile on Google
Chrome 91 or later or Internet Explorer 11.
Microsoft Office 2013 SP1 (32-bit)
Software Microsoft Office 2016 (32-bit)
Microsoft Office 2019 (32-bit)
Microsoft .Net Framework 4.8
Adobe Reader (for viewing
Eventing/ReportSet reports)
1.5 GHz
Hardware 100 MB Hard Drive Space
1024 MB Ram
Browser Client

Items Descriptions
Microsoft Windows 10 Enterprise (64-bit)
Operating Microsoft Windows Server 2012 R2
System Datacenter (64-bit)
Microsoft Windows Server 2016 Datacenter
(64-bit)
Microsoft Windows Server 2016 Standard
(64-bit)
Microsoft Windows Server 2019 Datacenter
LTSC (64-bit)
Microsoft Windows Server 2019 Standard
LTSC (64-bit)
Note: Embedded versions are not supported.
Microsoft Internet Explorer 11
Web Browser Microsoft Edge 95 or later (Internet Explorer
mode)
Note:
The Metro App for Internet Explorer 11 is not
supported.
You can use VantagePoint Mobile on Google
Chrome 91 or later or Internet Explorer 11.
Microsoft .Net Framework 4.8
Software Adobe Reader (for viewing
Eventing/ReportSet reports)
1.5 GHz
Hardware 100 MB Hard Drive Space
1024 MB Ram
Mobile Client

Items Descriptions
Android tablets and smart phones with OS
Supported 5.0 using Google Chrome
Devices Apple iPad 4 or later or iPhone 5 or later
with iOS 9.1 or 10.x using Safari
Note: A tablet is required to use the Import and
Configure features.
Google Chrome 91 or later
Web Browsers Microsoft Internet Explorer 11
Microsoft Edge 95 or later
Note:
The Metro App for Internet Explorer 11 is not
supported.
Product compatibility

FactoryTalk VantagePoint is compatible with the following Rockwell Automation products:

FactoryTalk Historian SDK 1.4.7.618
FactoryTalk Services Platform 6.20.00
FactoryTalk Activation Manager 4.04.12

Rockwell Automation Test Environment

Rockwell Automation tests software products under a standard configuration of operating systems and antivirus software. For additional information, see the
Knowledgebase Document ID: PN24 - Rockwell Software Products and Antivirus Software.

Security requirements

To help meet secure system design requirements, review these publications:

Configure System Security Features User Manual (publication SECURE-UM001)
System Security Design Guidelines (publication SECURE-RM001)
Converged Plantwide Ethernet (CPwE) Design and Implementation Guide (publication ENET-TD001)

Features
This release includes the following system features.

FactoryTalk VantagePoint version 8.31.00 has the following enhanced features.

Installation

When installing FactoryTalk VantagePoint version 8.31.00, we recommend that you use FactoryTalk Alarms and Events version 2.90.00 or later. If
using versions prior to 2.90.00, you need to upgrade FactoryTalk Alarms and Events to 2.90.00 or later.

Upgrade

When upgrading FactoryTalk VantagePoint from a previous version to 8.31.00, you can do one of the following options based on the version of
FactoryTalk Alarms and Events.
If the version is prior to 2.90.00, you need to upgrade FactoryTalk Alarms and Events to version 2.90.00 or later and re-deploy database
objects.
If the version is from 2.90.00 through 6.20.00, you need to re-deploy database objects.
If using FactoryTalk Alarms and Events SSRS to generate reports, you need to update the query statements to ensure that the data you
queried are from the AllEvent table instead of the ConditionEvent table.

New operating system support

Microsoft Windows Server 2019 Datacenter LTSC
Microsoft Windows Server 2019 Standard LTSC

New database support

Microsoft SQL Server 2019 Express
Microsoft SQL Server 2019 Standard

New Transport Layer Security support

TLS 1.2

New software support

Microsoft Office 2019 (32-bit only)

Corrected Anomalies in This Release
This release corrects the following anomalies.

FactoryTalk VantagePoint version 8.31.00 has no corrected anomalies.

Known Anomalies in This Release
This release has the following known anomalies.

FactoryTalk VantagePoint version 8.31.00 has no known anomalies.

Functional Changes
This release has the following functional changes from the previous release.
FactoryTalk VantagePoint version 8.31.00 has the following functional changes:

Use Mobile Dashboard to generate reports

Xcelsius is no longer supported since FactoryTalk VantagePoint version 8.10.00. We recommend that you use Mobile Dashboard to generate reports.

Application Notes
This release has the following application notes.

The following are the application notes for FactoryTalk VantagePoint version 8.31.00.

Synchronize FactoryTalk Historian connectors after the VantagePoint upgrade to version 7.00, 8.00, 8.10, 8.20, 8.30, or 8.31

After upgrading VantagePoint to version 7.00, 8.00, 8.10, 8.20, 8.30, or 8.31, we recommend that you synchronize your FactoryTalk Historian connectors to
get the correct values of historian tags' properties.

Improved transparency in data presentation between VantagePoint and InSQL

VantagePoint has taken the following approach towards the InSQL data presentation:

The presentation of data aggregation types

In version 3.1.5, while fully supporting available InSQL versions, VantagePoint recognized only two data aggregations of type delta, and cyclic that
were provided with InSQL 8.0 at that time. VantagePoint presented InSQL data using these aggregations in a transparent way, without imposing its
own interpretation of them. At the same time, it ignored any other aggregations available with other versions of InSQL.

In the successive versions, VantagePoint has supported all aggregations that were provided with InSQL, mapping them to its own aggregations.

The presentation of data interpolation types

VantagePoint has imposed its own interpretation of InSQL data and has presented it always as either the linear or stairstep interpolation, ignoring the
data interpolation types available in InSQL (linear, stairstep, and default).

If you want to do any of the following:

Use the delta and cyclic aggregations in the way they were available in VantagePoint 3.1.5.
Use all the interpolation types available in InSQL (linear, stairstep, and default)

You need to overwrite the settings in VantagePoint Manager.

To overwrite the InSQL data presentation settings
1.  In VantagePoint Manager, go to System > Sources > InSQL.
2.  Right-click the InSQL connector for which you want to define the data presentation rules, and then click Edit.

The Edit dialog box appears.

3.  In the Description box, add the following options of the data presentation rules:

overrideGuiSettings

It is the primary option. Only when it is turned on, the other two options become effective.

Use either of the following settings:

True - Choose this setting to turn on the overwriting of the InSQL data presentation configuration available in VantagePoint Manager.
False - Choose this setting to turn off the overwriting of the InSQL data presentation configuration available in VantagePoint Manager.

vp315Behavior

This option is effective only when overrideGuiSettings is on.

Use either of the following settings:

<True - Choose this setting to use the inSQL-related configuration of VantagePoint 3.1.5.

The setting forces VantagePoint to present data either as raw data, or to use the delta, and cyclic aggregations that were originally supported by
InSQL 8.0. All other aggregations will be ignored.

For details on data aggregations in InSQL 8.0, see the product documentation.
False - Choose this setting to use the InSQL connector configuration as defined in the current version of VantagePoint.

wwInterpolationType

This option is effective only when overrideGuiSettings is on.

Use one of the following settings:

Default - Choose this setting to use the InSQL default interpolation settings.

The default interpolation enforces the InSQL interpolation policy for each tag separately.
Linear - Choose this setting to force VantagePoint to present InSQL data using the linear interpolation, disregarding how they are actually
defined in InSQL.

The linear interpolation joins each point of data with a smooth straight line.
Stairstep - Choose this setting to force VantagePoint to present the InSQL data using the stairstep interpolation, disregarding how they are
actually defined in InSQL.
The stairstep interpolation joins each data point with a straight horizontal line until a new value is reached.

Note:
The interpolation settings will have effect only on the Linear and
Interpolative aggregations in VantagePoint.
It is important that you separate each entry with a semicolon.

General issues
Review the following for additional information about issues you may encounter.

Issues Description

In a mixed Workgroup / Domain Environment The first time a new client connects to a VantagePoint server across
user credentials must be cachedIn a mixed a security boundary where the connecting client’s logged-on user is
Workgroup / Domain Environment user not a valid user in the server’s security context; the client will be
credentials must be cached prompted to enter a valid user name and password. Upon entering
valid credentials, you must select the Remember my password
check box to ensure the proper function of the VantagePoint
system. After this initial login, you will never again be prompted for a
password, unless your password changes. Note that this procedure
is not required and the user should not be prompted if the client is a
valid user on the server’s Domain/Workgroup.
Avoid copying one connector, such as InSQL, into a similar
Copy operation should not be used to copy a connector type, such as ODBC. Doing so will result in an error when
connector into another connector trying to use the connectors.

Solution: Delete the connector that you copied under the original
connector, and restart IIS on the VantagePoint server.
A user with VantagePoint user rights is not able to delete a folder or
Delete operation does not work on Folders or its contents. This is seen when a VantagePoint user tries to delete
Items when permissions are granted to folders or contents of folders that are directly below the My
VantagePoint User Enterprise node in the Model Browser.

This issue reflects the way permissions are granted on items that
contain other items. In order to delete an item, two conditions must
be true:
The user must have Delete permission for the item.
The user must have Write permission on the parent item.

These rules are required since the deletion of an item changes the
parent item's collection or reference property that holds the item.

Solution: Create folders for VantagePoint users that are two nodes
down from the MyEnterprise root folder. (e.g. MyEnterprise >
NoDeleteFolder > User Can Delete1, 2, 3 etc.)
After uninstalling VMWare Tools version 7.2.9 and either performing
MFC71U.dll not found error after uninstalling an IISReset or rebooting the machine, you will receive the following
VMware Tools version 7.2.9 error message indicating a problem with the Rockwell Activation
tool.

Error Message: 'flexsvr.exe-Unable to Locate Component"- "This
application failed to start because MFC71U.DLL was not found.
Reinstalling the application may fix the problem."

Solution: Copy the MFC71U.dll to the C:\Windows\System32
directory. A copy of the MFC71U.dll is located on the VantagePoint
DVD in the Resources folder.

Clients must be installed in Local Intranet Zone VantagePoint only supports clients located in the Local Intranet
Zone, so you must add the Portal URL to this zone. To add the URL
to the Local Intranet Zone, in Internet Explorer, select Internet
Options > Security tab > Local Intranet. Click Sites, and then
click Advanced, and add the Portal URL.
The machine that hosts the VantagePoint server cannot launch
Clients from previous VantagePoint versions clients from previous versions of VantagePoint because the policy
cannot be launched from the VantagePoint files use assembly rebinding for core assemblies.
server
Solution: Use a machine that is not hosting the VantagePoint
server to launch clients from previous versions of VantagePoint.
If the host header setting has been configured in IIS or if a fully
Error: Json Service: Unauthorized exception qualified domain name is used for your site, Json returns an error
with FQDN or Host Header in IIS message.

Solution: To resolve this issue, see
http://support.microsoft.com/kb/896861/en-us
FactoryTalk VantagePoint supports only the SMTP Service
Sending emails over SSL using port 465 is not Extension for Secure SMTP over Transport Layer Security. In this
supported mode, the SMTP session begins on an unencrypted channel, then a
STARTTLS command is issued by the client to the server to switch
to secure communication using SSL. We recommend that you use
the port number 587.

An alternate connection method where an SSL session is
established up front before any protocol commands are sent is not
currently supported. This connection method is sometimes called
SMTP/SSL, SMTP over SSL, or SMTPS and by default uses port
465.

Installation and administration issues
Review the following for additional information about issues you may encounter.

Installation Issues Description

Unable to configure the FactoryTalk Directory. Access (Windows 2012 R2) If FactoryTalk Services Platform is
Denied error during FactoryTalk Services Platform installed after FactoryTalk Activation Manager, this error
install occurs. You can ignore this error and click OK to continue
the install; and FactoryTalk Services Platform will install
correctly.

VantagePoint server installs to the Root of the Default The default web directory for IIS will typically be located on
Web Directory the C:\ drive. If you have limited space on this drive, you may
want to install VantagePoint on a different drive. In order for
VantagePoint to install on a different drive, you will need to
first change the location of default web directory to the
desired location. This is done through the Properties dialog
box on the Default Web Site.
During the VantagePoint installation, on some systems, a
Files in Use dialog appears during VantagePoint Files in Use dialog may appear, but the list of files consists
installation with a list of process ID of a list of process IDs.

Solution: To continue installation, click Retry twice.

Cannot change drive if drive is full when installing VantagePoint installs on the default system drive. Prior to
VantagePoint installing VantagePoint, ensure that the default system drive
contains at least 1 GB of free disk space.
This issue occurs if you have .NET 4.0 installed on the client
"Application cannot be started. Contact the Application machine.
vendor" error when installing a client
Solution: Upgrade to .NET 4.5 on the client machine.

Upgrade Issues Description
Upgrading a large VantagePoint system may take a long
Upgrading a large VantagePoint system may take a time to complete. During this time, attempts to access the
long time to complete VantagePoint system may result in timeout errors.

After the indexes have been rebuilt and SQL Server is idle
again, the VantagePoint system behaves normally.
This error occurs if the following DLLs were moved into the
An HTTP status 503 error: "The type initializer for incuity web application so that licensing does not occur in
'DataWorks.MI.Core.MiddleTier.Licensing.ClientLicense' the Incuity service. This is no longer supported.
threw an exception" appears after upgrade DataWorks.MI.Core.Branding.MiddleTier.dll
DataWorks.MI.Core.Branding.Service.dll

Solution: Remove these two files from
C:\Inetpub\wwwroot\Incuity\bin.
After upgrading to the latest version of VantagePoint, Charts
Charts and Grids do not work after upgrading to and Grids no longer work.
VantagePoint
Solution: Re-install Charts and Grids.

Administration Issues Description
The VantagePoint server creates a log file detailing certain
VantagePoint log files are not deleted activity on the server. A new log file is created by default
each day at midnight. The archived log files are not deleted.
You should periodically check to ensure that the log files are
not consuming too much of the available disk space. You
can delete the log files using Windows Explorer. The old log
files have a file extension ending in the date. Do not delete
the logging configuration files (LoggingConfig.xml). Log files
are created in the following directories:

C:\Inetpub\wwwroot\Incuity\Logging

C:\Inetpub\wwwroot\IncuityOffice\Logging

C:\Inetpub\wwwroot\IncuityPortal\Logging

C:\Program Files\Incuity\bin\Logging (on 32-bit operating
systems)

C:\Program Files (x86)\Incuity\bin\Logging (on 64- bit
operating systems)
The VantagePoint server applications are installed in the
For continuous server operation, IIS Default Application default application pool of IIS which means that the
Pool Recycle Time needs to be disabled applications are recycled every 29 hours. While this does
not hurt VantagePoint, it can lead to gaps of a few minutes
in the history of tags that are stored by VantagePoint
storage. It also requires that a new instance of Excel be
started the first time an Excel report is requested after a
server restart. Every time this happens, report rendering will
take significantly longer than normal.

On the Windows Server operating system, the recycling of
the Web applications can be disabled in the application pool
that hosts the Web application. The VantagePoint web
applications are installed into the default application pool.
The recycling should only be disabled if there is no risk that
other web applications in the same application pool will be
affected. Preferably, the VantagePoint and VantagePoint
Office web applications should be moved to a dedicated
application pool as described in the Tech Note 'Creating
Application Pools'. See Using the Default Application Pool
for VantagePoint and IIS in the online help.

Type packages designed for Sample Content must not Sample content instances AND the type packages that are
be used for official modeling specific for the sample content are usually deleted as part of
the upgrade to the next (future) version. You must not use
types in the sample type packages for official modeling
since the resulting instances or derived type packages will
likely be deleted as part of a future upgrade.
This issue arises when VantagePoint is running on Server1
Cannot change Incuity System User when Current User while the IncuityStore database is running on Server2.
is not an Admin for the IncuityStore
When you install VantagePoint, you get the chance to
specify the database credentials used for setting up the
IncuityStore database. These credentials are often different
from the current Administrator that is running the install.

When you later want to change the Incuity System user
account, two groups of operations are required:
1.  Changes to the VantagePoint server's file system,
registry, etc.
2.  Changing the owner of the IncuityStore db.

For the latter, it must be possible to specify db credentials
as offered during the install. However, the configuration UI of
VantagePoint Manager does not offer an entry form for db
credentials.

Solution: Create an account on the VantagePoint server
that is also an administrator on the machine running SQL
Server. Log into the VantagePoint server with this account;
and run VantagePoint Manager.
If you move the database used by a database connector, the
After moving a database, the password no longer works password no longer works after the move.

Solutions:
Under System > Security > Mappings, you will
need to retype the password for the connector.
Export and then import the RSA key container. See
Importing and Exporting Protected Configuration RSA
Key Containers for more information.

When adding or removing a feature using Add/Remove
UAC error when adding or removing features using Programs, if UAC is on, and you are logged on as a user
Add/Remove Programs that is part of the Administrators group but not the local
Administrator, a blank error dialog box appears.

Solutions: You can resolve this issue using any of the
following methods:
Use the VantagePoint installer (setup.exe) to modify
the current install.
Log in as the local Administrator before using
Add/Remove Programs.
Disable UAC before using Add/Remove Programs.

When launching the Historian SDK, you receive the following
Error when launching Historian SDK error "The program can't start because rsdbgutils.DLL is
missing from your computer."

Solution: You will need to install the FactoryTalk Services
Platform.

If you do not want to install the FactoryTalk Services
Platform, you can dismiss the error and the Historian SDK
will launch successfully.

Connector issues
Review the following for additional information about issues you may encounter.

FactoryTalk Connector Issues Description

Support for a single FactoryTalk directory The FactoryTalk Connector in VantagePoint supports connectivity to
a single Factorytalk Directory. This means that if your organization
uses multiple FactoryTalk Directories, VantagePoint will only be
able to access data from the sources that are part of the single
FactoryTalk Directory that you specify when configuring a
FactoryTalk connector (to Live, History, and Alarm & Event data).
Data sources that are associated with other FactoryTalk Directories
will not be accessible using the FactoryTalk connector. They may
be accessible using a 3rd party connector that is available for
VantagePoint. Please contact us for an update on this issue and
possible workarounds.
When creating a FactoryTalk connector and browsing for LiveData
Error when browsing for LiveData tags tags, you receive the following error "String reference not set to an
instance of a String. Parameter name: s."

Solution: You will need to install the OPC Core Components from
the VantagePoint DVD and perform an IISRESET.

FactoryTalk EnergyMetrix Connector Issues Description
To display the Rate and Usage report for a given meter type, the
Rate and Usage report fails if non-standard meter type must have tags with standardized names.
tagnames are used on the EnergyMetrix server
Meter Type Standardized
Tagnames
- Air Flow
Connector.FTEnergyMetrix.AirMeter Rate
- Air Usage
- Air Usage
Totalizer
- Real Energy
Connector.FTEnergyMetrix.ElectricMeter Net

- Real Energy
Net Totalizer
- Real Power
Demand
- Gas Flow
Connector.FTEnergyMetrix.GasMeter Rate
- Gas Usage
- Gas Usage
Totalizer
- Steam Flow
Connector.FTEnergyMetrix.SteamMeter Rate

- Steam
Usage
- Steam
Usage
Totalizer
- Water Flow
Connector.FTEnergyMetrix.WaterMeter Rate

- Water Usage
- Water Usage
Totalizer
 

FactoryTalk Historian Connector Issues Description
When importing FactoryTalk Historian tags, an "Unable to access
FactoryTalk Historian import fails with Unable to SCM Manager. 5" error message displays under the following
access SCM Manager scenarios:
In a workgroup environment
If the VantagePoint server is running as a user that does not
have administrator privileges
After an IISReset has been done

Solution: It is safe to ignore this error by closing the dialog box
and importing again. Subsequent imports will not give this error.

FactoryTalk Metrics Connector Issues Description

Error when inserting a Database Query When inserting a Database Query (IncuityLinkedQuery function) in
(IncuityLinkedQuery function) in the Excel Add- the Excel Add-In using a FactoryTalk Metrics query that contains
In using a FactoryTalk Metrics query that parameters as the source, if you click the Edit Item button on the
contains parameters as the source Insert Query page, a "Value cannot be null" error displays.

IndustrialSQL Server Connector Issues Description
VantagePoint will not create an InSQL connector for IndustrialSQL
Adding IndustrialSQL Server connector fails if Server 8.0 if the Service Pack is not installed. At the time of this
Service Pack is not installed release, an error message does not warn the user of the problem,
however it is recorded in the VantagePoint log.

Solution: Install the Service Pack for IndustrialSQL Server, and
create the connector.
If a double type tag value is invalid on the Industrial SQL (InSQL)
Double type tag value becomes zero if it is server, after importing the tag to FactoryTalk VantagePoint, the
invalid on the Industrial SQL (InSQL) server value becomes zero. First identified in FactoryTalk VantagePoint
version 8.20.00.

Solution: There is currently no workaround for this issue.

ProficyHistorian Connector Issues Description
The following types of tags from the ProficyHistorian server are not
Unsuported tags in VantagePoint supported in the VantagePoint system and are not mapped to
VantagePoint tag types when importing data:
UnsignedSingleInteger, for OLEDB Provider version 4.5 and
earlier
Byte, for OLEDB Provider version 4.5 and earlier
Boolean, for OLEDB Provider version 4.5 and earlier
UnsignedDoubleInteger
UnsignedQuadInteger
BLOB
Time
QuadInteger
Undefined

You can view information about ProficyHistorian tags which are not
mapped to VantagePoint tag types in the log file located in
C:\Inetpub\wwwroot\Incuity\Logging\.

OPC DA Connector Issues Description

Attempting to import items from an OPC DA Some OPC DA servers do not contain a tag dictionary (the optional
server finishes, but no items are added IOPCBrowseServerAddressSpace interface) containing the
necessary information about the items VantagePoint would typically
import. In these cases, it is necessary to use the 'Import from file'
operation of the OPC DA connector. This operation accepts a well
formatted XML string as an import parameter and can be invoked by
script. For more information on constructing this XML string or using
a script to add items to your OPC DA connector, see Creating
Aliases for OPC Items in the online help.
Creating an OPC DA connector to a Linx Classic controller fails.
OPC DA connector cannot browse Linx Classic
tags Solution: Add the controller to a FactoryTalk Directory and create a
FactoryTalk connector to the Linx Classic tags or use FactoryTalk
Gateway.

ProductionCentre Connector Issues Description
When you use the TimeOfDay operator to compare time values, you
Using the TimeOfDay operator to compare must enter the time values in ProductionCentre format:
values requires the ProductionCentre time
format YYYY-MM-DDThh:mm:ss.SSS

where
YYYY is the year
MM is the month
DD is the day
T is the date and time separator
hh is the hour in a 24-hour format
mm is the minutes
ss is the seconds
SSS is the milliseconds

Example of a correct query command:

<XmlQuery Command="GetAreas">

<Filter>

<SearchConstraint FilterAttribute="CREATIONTIME"

Operator="TimeOfDayEqual"

Values="2000-01-01T23:29:45.000">

</SearchConstraint>

</Filter>

</XmlQuery>
When you use the TimeOfDay operator to compare time values,
Using the TimeOfDay operator to compare ProductionCentre will truncate the values to seconds. For
values will result in truncated values in ProductionCentre, the milliseconds value equals 0.
ProductionCentre
Solution: There is currently no workaround for this issue.
When you use the Equal operator in the SearchConstraint section
Using the Equal operator to compare values in a to compare values in a comma separated list, ProductionCentre will
comma separated list causes ProductionCentre use only the first value from the list, and display the result in the
to use only the first value for comparison query result set.

If you want to include values in a comma separated list in a query,
you must use the In operator.

Example of a correct query command:

<XmlQuery Command="GetAtRows">

<Filter Name="CPG_SetList" MaxResultCount="*">

<SearchConstraint Column="Key" Operator="In"
Values="77,78,79">

</SearchConstraint>

</Filter>

</XmlQuery>
When you create a query for a large amount of data, a timeout
Creating a query for large amount of data may message may appear.
cause a timeout message to appear in
ProductionCentre By default, the number of items displayed in the query result set is
10000, as defined in the MaxResultCount attribute. Changing the
default value may cause timeout.
When you create an SQL query with the ExecuteSql command and
Creating a query with the ExecuteSql command the Join function to get data from at least two tables, the result set
with data from more than one table will return an will display incorrect data. This is due to the fact that both tables
incorrect query result set in ProductionCentre contain columns with the same names (e.g., both contain the
Name, Description, and Key columns), which cannot be
distinguished in the query result set.

If you want to combine the results of more than one table, you must
use the CombineXmlQuery special query.
When you query data from a table which contains duplicate column
Creating queries from data tables with duplicate names distinguished only by the letter case (e.g., Name, NaMe,
column names results in displaying values nAMe), the result set will not be displayed correctly in
incorrectly in ProductionCentre VantagePoint.

You should disregard this because the query returns correct results
when used in Microsoft Excel. The results are only displayed
incorrectly in the data grid of a query result set in the VantagePoint
model.
When you query data from a table that contains certain columns
The query result set displays incorrect with lists of keys, and you set the WithContainedObject attribute to
information for the WithContainedObject false so that the lists of keys from these columns are not retrieved,
attribute set to "false" they are displayed in the query result set anyway.

The issue applies to the following columns in the following queries:

Columns In queries
Retrieving mulitiple objects,
WorkInstructionKeys for example:
- GetAreas
- GetEquipment
- GetProcessBoms
RouteStepKeys GetParameters
 

Excel add-in issues
Review the following for additional information about issues you may encounter.

Issue Description
This problem can occur with "non-standard" installations of Office.
Error: "The VantagePoint Office feature will not The problem can be seen when installing the VantagePoint server or
be installed because Microsoft Excel has not the VantagePoint client tools. If Microsoft Excel is installed and the
been installed on your machine" error occurs, verify that the following Registry Key exists on your
machine:

Office 2010:

HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Office\14.0\

Excel\InstallRoot Path=<PathValue>

If this registry key does not exist, you can create the key manually
and provide a value for Path that points to your Excel.exe. Rerun
the Client Install to complete installation of the VantagePoint Excel
Add-In feature.
Xcelsius 2008 enables ’Live Office Compatibility’. As a result, the
Double-clicking an Excel file or selecting the Excel advanced general option 'Ignore Applications that Use
Excel shortcut from the VantagePoint Start Dynamic Data Exchange (DDE)' gets selected. To resolve this
Menu does not work issue:
1.  Select Excel Office > Excel Options > Advanced.

2.  In the General Section, clear the Ignore other
applications that use Dynamic Data Exchange (DDE)
check box.

After running Xcelsius, if you open Excel, the workbook does not
Excel workbook does not display at full size display at full size. 
after running Xcelsius (Dashboard Builder)
Solution: Click the maximize button for the Excel workbook to
display full size.
In Excel, if you create a conditional formula to execute a hyperlink
Hyperlinks are not removed if they exist in a cell condition, the hyperlink will not be removed if the false condition
with a conditional expression and the false occurs.
condition occurs
Solution: Prior to publishing the report, delete all hyperlinks in
cells with these conditional formulas. To delete hyperlinks, right-
click and select Delete hyperlinks.
UDFs now return values when the function is array-entered into the
Limitations for UDFs when the function is array- maximum number of rows (1,048,576); however, the following
entered into the maximum number of rows limitations exist:
(1,048,576) In some cases, a 'system out of memory' or a message
recommending you use 64-bit Office may occur when the
UDF is close to the maxiumum number of rows.
When requesting >350K rows, if you use ‘interpolative’
sampling with one tag, narrow history, fewer tags than
requested are returned. Note that this is not an issue if you
use more than one tag.

When using multiple History functions to show tag values in an
The TimeStamp information shows the incorrect Excel worksheet, the TimeStamp information of the functions may
start time show different start time. First identified in FactoryTalk
VantagePoint v8.10.00.

Solution: To show the correct start time in the TimeStamp
information, select multiple tags to run a single History function.

FactoryTalk services issues
Review the following for additional information about issues you may encounter.

Issue Description
FactoryTalk has an option to restrict which client computers can
Remote Desktop Console session prevents connect to the directory. This option can cause VantagePoint to fail
creation of a FactoryTalk connector to log into the directory if the following conditions occur:
VantagePoint System Account is configured to run as a
user account that belongs to the server's Administrators
group.
Any user account that belongs to the VantagePoint server's
Administrators group logs onto the VantagePoint server via
remote desktop from a client computer whose name is not
in the directory.

Solution: To avoid this issue, do the following:
Do not configure VantagePoint to run as an administrator.
Do not log into a remote desktop console if VantagePoint is
configured to run as a user with administrative access.

When performing a Live Data import, VantagePoint assumes that
LiveData import does not validate that an ACD the selected ACD file is correct for the selected controller.
file for the selected controller is correct VantagePoint performs no validation of the ACD file, and tags that
are not found in the OPC server are not brought into VantagePoint.

Solution: When performing a LiveData import, make sure that
VantagePoint points to the correct ACD file for the selected
controller.

License issues

Issue Description
While using a VantagePoint client application, you may receive a
VantagePoint client application displays ’Failed 'Failed to initialize the type repository' error. This error occurs
to initialize the type repository’ error because the same user has logged into the VantagePoint system
from multiple locations. This is a violation of the VantagePoint
licensing system.

Solution: After receiving this error, you must wait 20 minutes for
the session from one of these locations to expire. After one of the
location sessions has expired, you can continue to use the
application.
If the VantagePoint system encounters a license violation, it may
VantagePoint may display two error messages display two error messages. After closing the first license error
when you have a license violation message dialog box, you may receive the following error message
"Object reference not set to an instance of an object".

Solution: Close the second error message dialog box and resolve
the licensing issue.

Portal issues
Review the following for additional information about issues you may encounter.

Issue Description
While using VantagePoint, a redirected Portal home page
VantagePoint Portal redirected home page does not does not display.
display
Solution: Add the redirected VantagePoint Portal home
page site to the Local Intranet Zone prior to browsing to it.
To add the home page to the Local Intranet Zone:
1.  In Internet Explorer, select Internet Options >
Security > Local Intranet.

2.  Clear the Require server verification (https:) for
all sites in this zone, if needed.

3.  Click Sites, and then click Advanced, and add
the URL.

Trend and XY Plotter reports will not display unless the To view Trend and XY Plotter reports in the Portal, you
Portal is in the Intranet Zone must add the Portal URL to the Local Intranet Zone. To
add the URL to the Local Intranet Zone, in Internet
Explorer, select Internet Options > Security tab >
Local Intranet. Click Sites, and then click Advanced,
and add the Portal URL.
This issue only occurs if you are prompted for credentials
Error occurs when generating Trend, XY Plot, or when logging into VantagePoint on Windows 8.1
Dashboard reports on Windows 8.1 systems.

Solution: Ensure that you have applied Windows
Updates to the system. Then, select the Enable
Protected Mode check box under Security Level for
this zone for the Local Intranet Zone under Internet
Options > Security > Local Intranet.

Trend must finish loading the interactive control before When selecting a trend in the Portal, an image of the
switching to another item in the Model Browser trend displays while the interactive trend control loads. In
most cases, this occurs quickly, and is not noticeable.
However, you cannot select another report in the Model
Browser tree until the interactive control finishes loading.
Depending on the configuration of your VantagePoint
Downtime Summary report may generate with an error server, the Downtime Summary report
MyEnterprise.Samples.v4.Advanced.Production.Reports.Line
Downtime Summary may fail to execute properly. The
report uses a SQL Query object that is configured in the
IncuitySample database connector.

By default, the IncuitySample database connector is
”locked down” so that users without elevated privileges
have limited access to the connector or child objects of
the connector. In this case, the user in question is the
VantagePoint Office user (used to generate Excel Reports
in the Portal). If this user is not an administrator (or if the
security settings of the IncuitySample database
connector has not been altered), this report will generate
with an error.

For recommendations about configuring database security
for the IncuitySample database, please see
http://<ServerName>/VantagePointPortal/PortalInfoPages/IncuitySampleDB/DBConnectorSecurity.html
Under MyEnterprise.Samples v4.Support.Report
Some composite reports in the Report Library cannot be Library.Composite, the ControlLoop, DowntimeEquipment,
generated for a new installation EquipmentTimePeriod, and Standard Equipment reports
are used by a previous version of VantagePoint. If you are
not upgrading VantagePoint from a previous version,
these reports will be empty.

Solution: Use the ControlLoop_v4,
DowntimeEquipment_v4, EquipmentTimePeriod_v4, and
Standard Equipment_v4 reports instead.
If you have used Content Type Rules based on inherited
Some reports have been reordered in the Model Browser types for items that display in the Portal, in previous
releases, child types displayed first, followed by parent
types. This was a defect that has been resolved, and the
Portal now orders these items based on parent types first,
followed by child types.

For example, previously, the first report under Line 1
(MyEnterprise.Samples v4.Advanced.Production.Chicago
Plant.Lines) was the Line Report, and the last report was
the Equipment Trend. In this release, the first report under
Line 1 is Equipment Trend, and the Line Report is the
third report in the list.

It is not possible to reorder these reports to the original
display that sorted by child types first.
A StatusItems folder now displays in the Model Browser,
StatusItems folders now display in the Model Browser and in some cases, will include duplicate content from
other nodes. For example, under MyEnterprise.Samples
v4.Advanced.Production.Chicago Plant, a StatusItems
folder now appears with Lines 1 and 2. This content is
also available in its original location under the Lines folder.

Solution: To hide the StatusItems folders:
1.  Select System > Applications > Portal >
Settings > ContentViewer > ContentTypes.

2.  Right-click each folder below ContentTypes, and
select Edit.

3.  Clear the PropagateToSubTypes check box, and
click OK.

4.  In the Portal, select Reports > MyEnterprise to
verify that the StatusItems folders have been
removed.

On Windows 2008 with IE 10 installed, when using the
(Windows 2008, IE 10 only) When using the Lock Full Lock Full Screen option, external websites open in new
Screen option to view reports, external websites open in windows, and in some cases, the website will open in the
new windows main Portal window.

Solution: Add the external website to the Trusted Sites. To
do so:
1.  In Internet Explorer, select Internet Options >
Security > Trusted Sites.

2.  Clear the Require server verification (https:) for
all sites in this zone, if needed.
3.  Click Sites and add the URL.

When the content rotator is used in Internet Explorer
Memory leak while using the content rotator in Internet there is a memory leak.
Explorer
Solution: It is recommend to run the content rotator
(except for any activeX control) in Chrome version 73. We
also recommend using 60 seconds or more for the
AutoRotationInterval time if running the content rotator in
Chrome. Note that on some browser versions, a faster
update rate may cause a small memory leak.

Security issues
Review the following for additional information about issues you may encounter.

Issue Description
If you change a user's Windows local or domain group, this change
Changing a user's Windows local or domain is not reflected in VantagePoint. The VantagePoint server is not
group is not reflected by VantagePoint notified by Windows when the group membership of a local or
domain group changes.

Solution: For VantagePoint to recognize a change in a user’s
Windows local or domain group, you must restart IIS after making
the change.

Storage issues
Review the following for additional information about issues you may encounter.

Issue Description

Size-based aging strategy is not supported in A size-based aging strategy for Storage Servers is planned for a
this release future release of VantagePoint, and is not supported in this release.

Floating point numbers for VantagePoint tags Floating point numbers in VantagePoint are typically stored with 8-
can result in rounding errors bit precision resulting in rounding errors such as the following: a
55.22, value in the database is 55.2200012207031.

After renaming an Incuity tag and performing an If you rename an Incuity tag, any values created with the old name
IISRESET, only the last value is retrieved and values created with the renamed tag can be retrieved until an
IISRESET is performed. Afterwards, only the last value entered can
be retrieved.

Trend and XY Plotter issues
Review the following for additional information about issues you may encounter.

Issue Description

How to improve performance in the Portal By default, each web service call into the VantagePoint server is
controls (Trend and XY Plotter) individually authenticated. In Intranet environments, this level of
security and the associated performance overhead is typically too
much. For this reason, the VantagePoint client install configures
the system to allow the authentication of a web service call into a
given VantagePoint server to be reused for subsequent calls into
the same server.
If the "System objects: Default owner for objects created by
Unable to view Trends in the Portal on Windows members of the Administrators group" Group Policy on your
computer is set to Administrators, attempting to open a trend in the
Portal may result in an error message.

Solution: Apply the Microsoft Hotfix in
http://support.microsoft.com/kb/954494, or reset the computer's
Group Policy to the default setting of "Object Creator."

Eventing and Report Set issues
Review the following for additional information about issues you may encounter.

Issue Description
An option in the Report Set allows you to automatically print a
Automatic printing of reports report when it is generated. You can configure this feature to print
to any printer available on the network including virtual-printers such
as PDFCreator, which prints to a PDF document on disk.

Review the following for issues related to automatic printing:
Printing to PDFCreator is supported for PDFCreator version
1.2.3 but not for version 1.7.
Trend, XY Plotter, and SSRS reports cannot be printed
automatically.

QueryProvider The QueryProvider does not support NameSpaceFilter for folders
with " and * in the name.
Run all reports in a folder When the Report set source is selected as "Run all reports in a
folder" and if there is an asterisk (*) character in the folder name,
Reports will not be visible in public catalog.

Mobile issues
Review the following for additional information about issues you may encounter.

Issues on All Devices Description
This issue may occur if:
"Communication error" may appear The signal strength for your wireless network is low, you
may see a "Communication error" while using a device. You
can refresh the site or press Retry to continue, and should
check your wireless network to see if the signal strength is
an issue.
The VantagePoint server has run out of licenses and no
more are available. You can verify that this has occurred by
reviewing the Windows Event log.

Review the following:
Hyperlink and Portal Report widget issues When browsing to a hyperlink in the model or adding a
hyperlink to a Portal Report, an authentication window
prompts you to log in. This only happens the fist time you
access a hyperlink. Re-enter your credentials and the report
appears and any new hyperlinks will work without prompting
for credentials.
On iOS devices only, scrolling is disabled for hyperlinks and
websites.

Web site does not load in mobile site; page is Some web sites do not support being rendered in an iframe, which
blank is what the Portal and Mobile site use to display content. If a site
does not support iframes, the page will be blank in the mobile site.

Displays created under folders do not support If you create a display under a folder or item that derives from a
the Show in Portal option core.folder type, when saving the display, the Show in Portal
option is not available.

Tag collection that contains a period results in If you navigate to a tag collection that contains a period, when
No Items Found error message and a broken selected, the breadcrumb changes to ?/ and the screen indicates
breadcrumb that no items were found even though there are items in the
collection.
When you are browsing, searching or selecting large data
Performance limitations on devices with small collections (for example, instances including multiple members) on
amount of RAM devices with small amount of the random-access memory (RAM),
any of the following may happen:
The page that you are currently viewing may get reloaded.
The web browser may crash.

If you create in Studio 5000 Logix Designer a member, use one of
Importing members with restricted names fails the restricted expressions listed below as its name, and then
import it, the import will fail.

The restricted expressions that cause the import failure are:
Name
CreatedOn
Description
FullyQualifiedName
IconIndex
ModifiedOn
TypeName

Phone Issues Description
If the View name on the Model page contains a forward slash(/),
Cannot create a display if the view name you cannot create a display.
contains a forward slash
Workaround: On a tablet or desktop, rename the view and remove
the forward slash. You can also use the rename feature in Manager
to rename the view.

On iPhones, buttons on the Action Bar may Buttons on the Action Bar may look as if they have been pressed
appear to be pressed or disabled when they are or are disabled even though they are available. You can tap the
available screen to make them change to white, or can tap them to perform
an action.
In Portrait mode on the iPhone, a cell containing a value box
Occasionally, value boxes do not display on the appears, but the actual value box does not appear.
iPhone in Portrait mode
Workaround: Rotate the phone to landscape mode and back to
portrait mode. The value box now appears.

Some reports created with the Portal Report Some reports created with the Portal Report widget do not display
widget do not display correctly on the iPhone in correctly on the iPhone in Landscape mode. You will need to rotate
Landscape mode the phone to Portrait mode.

Tablet or Desktop Issues Description
This issue occurs when using IE 11.0.9600.16663.
When importing tags, details on the Summary
page do not expand to the width of the browser Solution: Upgrade to IE 11.0.9600.18376CO.
in IE

Adding tags to the Trend Report widget removes Attempting to add tags to an existing Trend Report widget removes
tags in the original report the original tags in the report.

When editing a display, you do not see the tags This occurs if the tags exist under a location that has been hidden
that are being used from all views using a navigation rule.
If you want to add a tag parameter to an Excel Report, you must
Using tag parameters in Portal Report widget know the exact FQN of an existing tag parameter used in the report
and enter that in the Name field. Otherwise, the report will continue
to use the existing tag parameters.

Solution: To locate the FQN
1.  Open Manager.

2.  Navigate to the report and select ParametersTypes.
3.  Copy or type the FQN name into the Name field.

Netbios name resolution is not supported on iOS and Android
Linked content such as SSRS reports, etc., do operating systems so linked content such as SSRS reports will not
not display on Android and iOS display by default.

Solution: Use the full computer name that includes the domain or
the IP address to view the mobile site.

  

Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in alignment with the movement
toward inclusive language in technology. We are proactively collaborating with industry peers to find alternatives to such terms and making changes to our
products and content. Please excuse the use of such terms in our content while we implement these changes.

Copyright © 2022 Rockwell Automation, Inc. All rights reserved.
Rockwell Automation, Allen-Bradley, and FactoryTalk are trademarks of Rockwell Automation, Inc.
To view a complete list of Rockwell Automation trademarks please click here.
Trademarks not belonging to Rockwell Automation are property of their respective companies.