“To caleulaethe ful current, the following steps are performed: 8) Angle tine diagram ofthe ereit containing al element is dawn 1) Asingle tine impedance diagram comtining one phase and neural i drawn (©) Tho tol impedance upto the 1) The short circuit current ted using: Mvabase ‘Short sitet MVA = pu en Shore circult MvAx 1000 VExViine Short circuit eurent= 23.2 Single Phase to Ground Fault For single phase to ground fault calculation, two conditions must be fulfilled the use ‘of symmetrical component and separation of circuits into positive, negative and zero sequence networks, This makes calculation for single phase to ground fault more challenging compared to thre phase fal contained in cach component ae considera. Fr transformers and genera sequence diagrams are highly depend on ground comections and cement type “Transformer impedance is contained in positive and negative sequence networks. On the ‘therhand the vollage sources are allen the positive sequence network for generators Figure 23 and 24 show example ofa sequence network fora generator and transfomer respectively, Fat current for a single fine o ground can be determined using: MW, Iph= 3x ine RV (2-4 22424) @3) Where, Zo= Zs + 320