Bulletin 241C: Mark Owned by The Cooling Technology Institute
Bulletin 241C: Mark Owned by The Cooling Technology Institute
3
DESIGN BENEFITS
Hot
Internal Tube Enhancement
Fluid In
The coils are manufactured from high quality steel tubing follow-
8.5’ & 12’ Wide Models ing the most stringent quality control procedures. Each circuit is
inspected to ensure the material quality and then tested before
being assembled into a coil. Finally, the assembled coil is pneu-
Patented EVAPAK Fill matically tested at 390 psig under water to ensure it is leak free.
The patented EVAPAK fill is specially designed to induce highly
To protect the coil against corrosion, it is placed in a heavy steel
turbulent mixing of the air and water for superior heat
frame and then the entire assembly is dipped in molten zinc
transfer. The fill section is constructed of polyvinyl chloride
(hot-dip galvanized) at a temperature of approximately 800°F.
(PVC) sheets which are thermally formed into a cross flute
design. The individual fill sheets are bonded together to Note: Closed circuit coolers should only be used on sealed,
form rigid fill blocks. The fill blocks are then pressurized systems. Continual aeration of the water in an
stacked within the unit’s protective open system can cause corrosion inside the tubes of the cooler
casing. The structural strength
of the assembled fill pack
enables it to be used as a Stainless Steel Coil Option
working platform. EVAPCO offers the optional
. Constructed with
EVAPAK fill is impervious to rot
type 304L Stainless Steel, the TITAN
and decay, and is self-
COIL is manufactured using
extinguishing with a flame
EVAPCO’s patented elliptical tube
spread rating of less than 25 per
ASTM Standard E-84. Sensi-Coil® design upgraded to Xtra
Tough construction featuring: Xtra
Durability, Xtra Corrosion
Resistance, and an Xtra long 5
YEAR Coil Warranty as standard. Sensi-Coil®
4
ENERGY EFFICIENT LOW SOUND
The ESWA stands apart as being the most energy efficient When comparing the cost of new equipment, energy
closed circuit cooler on the market today. This efficiency, in efficiency and consumption are important factors for
terms of lower fan horsepower, translates directly to lower determining the total product cost. Units having a
operating costs…significantly lower operating costs. With lower first cost but higher energy requirement are more
the ESWA installed, customers can realize immediate energy expensive to operate and normally end up costing the
savings which continue each and every year for the life of customer more over the life of the equipment.
the equipment. • Smaller Footprint, Lower Horsepower:
As an example, a typical induced-draft 200 ton** cooler
• Replace inefficient units:
can require a 12’ x 12’ footprint, 20 HP fan motor, and 5
The potential for energy savings alone is often enough HP pump. The same load can be accomplished in an
to justify replacing inefficient fluid coolers with high ESWA with an 8.5’ x 12’ footprint, 7.5 HP fan motor, and
efficiency models. As an example, a 250 ton centrifugal 7.5 HP pump.
fan fluid cooler with 80 HP worth of fan motors can be
**Calculated using 3 GPM of Water at 100°F / 90°F / 78°F per ton.
replaced by an ESWA model with a fan motor size of
only 15HP. This tremendous reduction in fan motor size
offers annual savings of $16,530 per year based on 3,500 Low Sound As Standard
hours of operation and an electric rate of $0.09/kWh. In addition to being the most energy efficient axial fan
fluid cooler, the ESW family is also the quietest. At a
distance of five feet above the fan, the ESWA has sound
12,000 levels that are up to 13dBA less than other axial fan fluid
coolers of equal capacity. Additionally, the coil sits just
10,000 20 HP
Reduction above the basin floor breaking the water fall and reducing
Annual Savings ($)
5
DESIGN BENEFITS
6
M A I N T E N A N C E A D VA N TA G E S
Easy Access
The cold water basin section is easily accessible from
ground level. The basin is provided with solid access panels
which are designed to protect the basin water and heat
transfer coil from direct exposure to sunlight and debris.
The access panels are light-weight and easy to remove.
With the access panels removed a service mechanic has
complete access to the basin floor, heat transfer coil, float
assembly and pump strainer.
7
M A I N T E N A N C E A D VA N TA G E S
With all periodic and routine maintenance for the drive system performed from the side
of the unit, EVAPCO drive systems are the most serviceable in the industry.
8
DRIVE SYSTEM
Fan Motors
TEFC Fan Motor All EVAPCO closed circuit coolers utilize totally enclosed fan
motors (T.E.F.C. or T.E.A.O.) designed specifically for
evaporative cooling applications. Premium efficient fan
motors which are compatible with variable frequency drive
(VFD) systems, come standard on all ESWA models.
Alternative fan motor options are available as follows:
9
Engineering Data & Dimensions
30-1/2”
ESWA Models 77-24H to 77-34K M ACCESS
DOOR
P
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm.
This required option is referred to as the High Flow coil configuration.
19-3/4”
M ACCESS
M DOOR
4 BFW
FLUID OUT
H
4 BFW
FLUID IN
2 MPT L
MAKE-UP A
2 MPT 3 MPT
OVERFLOW 20-1/8”
DRAIN
24-1/4 8‘ 11-1/2”
33-7/8
8‘ 5-1/2”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require factory internal crossover piping. Model numbers will
include “C” for units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
10
Selections for ESWA Closed Circuit Coolers are available from EVAPCO’s evapSelect® Equipment Selection
Program or the ESWA Thermal Performance Charts located on www.evapco.com.
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm. P
This required option is referred to as the High Flow coil configuration.
19-3/4”
M ACCESS
M DOOR
4 BFW
FLUID OUT
H
4 BFW
FLUID IN
2 MPT L
MAKE-UP A
2 MPT 3 MPT
OVERFLOW 20-1/8”
DRAIN
24-1/4 8‘ 11-1/2”
33-7/8
8‘ 5-1/2”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require factory internal crossover piping. Model numbers will
include “C” for units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
11
Engineering Data & Dimensions 30-1/2”
M ACCESS
DOOR
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm.
This required option is referred to as the High Flow coil configuration.
19-3/4”
M ACCESS
M DOOR
U
4 BFW
FLUID OUT
H
4 BFW
FLUID IN
2 MPT L
MAKE-UP A
2 MPT 3 MPT
OVERFLOW 20-1/8”
DRAIN
33-7/8 25-1/2” 11’ 11-3/4”
8‘ 5-1/2”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require factory internal crossover piping. Model numbers
will include “C” for units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer
during operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized
outlet to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW). Other
connection types such as grooved for mechanical coupling or flanged are also available as options.
12
Selections for ESWA Closed Circuit Coolers are available from EVAPCO’s evapSelect® Equipment Selection
Program or the ESWA Thermal Performance Charts located on www.evapco.com.
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm. P
This required option is referred to as the High Flow coil configuration.
19-3/4”
M ACCESS M ACCESS
M DOOR DOOR
4 BFW
FLUID OUT
H
4 BFW
FLUID IN
2 MPT
MAKE-UP L
A
3 MPT 20-1/8”
OVERFLOW
2 MPT
DRAIN 25-1/4” 18‘ 0”
33-7/8”
8‘ 5-1/2”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require factory internal crossover piping. Model numbers will
include “C” for units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
13
Engineering Data & Dimensions
ESWA Models 153-35H to 153-46K 30-1/2” 30-1/2”
M ACCESS M ACCESS
DOOR DOOR
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm.
P
This required option is referred to as the High Flow coil configuration.
19-3/4”
M ACCESS M ACCESS
M DOOR DOOR
4 BFW
FLUID OUT
H
4 BFW
FLUID IN
2 MPT
MAKE-UP L
A
3 MPT 20-1/8”
OVERFLOW
2 MPT
DRAIN 25-1/4” 18‘ 0”
33-7/8”
8‘ 5-1/2”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require factory internal crossover piping. Model numbers will
include “C” for units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
14
Selections for ESWA Closed Circuit Coolers are available from EVAPCO’s evapSelect® Equipment Selection
Program or the ESWA Thermal Performance Charts located on www.evapco.com.
P M
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm
per coil. This required option is referred to as the High Flow coil configuration.
7“
M ACCESS
DOOR
U
(2) 4 BFW
FLUID OUT
H
(2) 4 BFW
FLUID IN
2 MPT L
MAKE-UP A
3 MPT 22-7/8”
OVERFLOW
3 MPT
DRAIN 46-1/2” 25-1/4” 11’ 11-3/4”
11’ 10”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require crossover piping. Model numbers will include “C” for
units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
15
Engineering Data & Dimensions
ACCESS
ESWA Models 144-44J to 144-46M DOOR
P M
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm
per coil. This required option is referred to as the High Flow coil configuration.
7“
M ACCESS
DOOR
U
(2) 4 BFW
FLUID OUT
H
(2) 4 BFW
FLUID IN
2 MPT L
MAKE-UP A
3 MPT 22-7/8”
OVERFLOW
3 MPT
DRAIN 46-1/2” 25-1/4” 11’ 11-3/4”
11’ 10”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require crossover piping. Model numbers will include “C” for
units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
16
Selections for ESWA Closed Circuit Coolers are available from EVAPCO’s evapSelect® Equipment Selection
Program or the ESWA Thermal Performance Charts located on www.evapco.com.
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm
per coil. This required option is referred to as the High Flow coil configuration.
ACCESS
M DOOR
U
(2) 4 BFW
FLUID OUT H
(2) 4 BFW
FLUID IN
2 MPT L
MAKE-UP A
3 MPT 22-7/8”
OVERFLOW
3 MPT
DRAIN 46-1/2”
26-3/4” 18’ 0”
11’ 10”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require crossover piping. Model numbers will include “C” for
units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
17
Engineering Data & Dimensions ACCESS
DOOR
Note: The coil connections increase to 6” BFW when the flow rate exceeds 450 gpm
per coil. This required option is referred to as the High Flow coil configuration.
ACCESS
M DOOR
U
(2) 4 BFW
FLUID OUT H
(2) 4 BFW
FLUID IN
2 MPT L
MAKE-UP A
3 MPT 22-7/8”
OVERFLOW
3 MPT
DRAIN 46-1/2”
26-3/4” 18’ 0”
11’ 10”
1 Model numbers will end in “-Z” for units with Series Flow piping configuration. Series Flow will require crossover piping. Model numbers will include “C” for
units with stainless steel coil(s), “R” for units with low sound fan(s) and “S” for units with an option that negates CTI Certification.
2 Heaviest section is the lower section.
3 Gallons shown includes water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during
operation (12" would normally be sufficient).
4 When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet
to facilitate drainage to the remote sump.
5 Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions. Coil connections are 4 inch bevel for weld (BFW).
Other connection types such as grooved for mechanical coupling or flanged are also available as options.
18
NOTES:
19
W AT E R T R E AT M E N T S O L U T I O N S
20
W AT E R T R E AT M E N T S O L U T I O N S
Pulse~Pure® Non-Chemical
Water Treatment System
Smart Shield® Solid Chemical
Water Treatment System
Pulse~Pure®
Integrated
Controller
Pulse~Pure®
Chamber
Bio-Control
Feeder (BCF)
21
A P P L I C AT I O N S AND W AT E R Q U A L I T Y
22
OPTIONAL EQUIPMENT
23
OPTIONAL EQUIPMENT
24
STEEL SUPPORT/FREEZE PROTECTION
Plan Views
1
B
Remote Sump
8.5' to 12' by Others
WIDE
MODELS
End Elevations
25
F R E E Z E P R O T E C T I O N / H E AT L O S S
Freeze Protection for the Heat 2) Design flow should be maintained through the coil
whenever possible. If this is not possible, refer to Table 2
Exchanger Coil for minimum recommended flow rates.
Units installed in climates subject to freezing conditions must
be adequately protected against freezing of the heat If the coil is not protected with an antifreeze/glycol solution,
exchanger coil and pan water. automatic drain valves and air vents should be installed in
the coil supply and return piping. The drain valves and
The simplest and most effective way of protecting the heat piping should be heat traced and sized for quick drainage of
exchanger coil from freezing is to use an inhibited ethylene or the coil. The drain valves and air vents should be signaled to
propylene glycol solution. drain the coil if the fluid flow stops or drops below 40°F in
If a glycol solution cannot be used both of the following freezing conditions.
conditions must be met: Draining the coil as an emergency method of freeze
1) Maintain sufficient process heat load through the coil protection is acceptable, however it is not recommended as
such that the coil temperature is kept above 50°F. If the standard practice. Frequent draining of the coil exposes the
process load cannot support 50°F fluid, an auxiliary heat inner tube surface to oxygen which results in corrosion. If the
load should be applied when freezing conditions exist. coil is drained for emergency freeze protection, it should not
Refer to Table 1 for coil heat loss data. be left empty for extended periods of time.
ESWA 77-24 133,000 ESWA 102-36 215,000 ESWA 153-45 305,000 ESWA 216-24 380,000
ESWA 77-25 151,000 ESWA 102-44 179,000 ESWA 153-46 325,000 ESWA 216-25 429,000
ESWA 77-26 160,000 ESWA 102-45 201,000 ESWA 144-24 252,000 ESWA 216-26 457,000
ESWA 77-34 133,000 ESWA 102-46 215,000 ESWA 144-25 284,000 ESWA 216-34 380,000
ESWA 77-35 151,000 ESWA 153-24 270,000 ESWA 144-26 303,000 ESWA 216-35 429,000
ESWA 77-36 160,000 ESWA 153-25 305,000 ESWA 144-34 252,000 ESWA 216-36 457,000
ESWA 77-44 133,000 ESWA 153-26 325,000 ESWA 144-35 284,000 ESWA 216-44 380,000
ESWA 77-45 151,000 ESWA 153-34 270,000 ESWA 144-36 303,000 ESWA 216-45 429,000
ESWA 77-46 160,000 ESWA 153-35 305,000 ESWA 144-44 252,000 ESWA 216-46 457,000
ESWA 102-34 179,000 ESWA 153-36 325,000 ESWA 144-45 284,000
ESWA 102-35 201,000 ESWA 153-44 270,000 ESWA 144-46 303,000
26
S P E C I F I C AT I O N S
SECTION 23 65 00 – FACTORY-FABRICATED COOLING TOWERS F. Collection Basin Material: Galvanized Steel. Type 304
PART 1 – GENERAL Stainless Steel Optional:
1. Removable stainless-steel strainer with openings
1.1 RELATED DOCUMENTS smaller than nozzle orifices.
A. Drawings and general provisions of the Contract, 2. Joints: Bolted and sealed watertight or welded.
including General and Supplementary Conditions and 3. Overflow, makeup and side drain connections
Division 1 Specification Sections, apply to this section. 4. Flume plate between cells (for multiple-cell units) or
1.2 SUMMARY: Equalizer connection (for multiple- closed circuit cooler
A. This Section includes factory assembled and tested, closed system).
circuit, induced draft counterflow cooling tower (also G. Heat Transfer Coil: Heavy Gauge G-235 Galvanized Steel
known as a closed circuit cooler). encased in a steel framework, assembly hot-dip
1.3 SUBMITTALS galvanized after construction. Type 304 Stainless Steel
A. General. Submit the following: Optional. Coil assembly completely enclosed and
1. Certified drawings of the closed circuit cooler, sound protected from sunlight exposure, environmental
data, recommended steel support indicating weight elements and debris. Tubes sloped for free drainage of
loadings, wiring diagrams, installation instructions, the coil and designed for low pressure drop. Coil assembly
operation and maintenance instructions, and thermal pneumatically tested at 400 psig under water. Coil
performance guarantee by the manufacturer. connections beveled for weld, flanged (optional) or
grooved (optional).
1.4 QUALITY ASSURANCE H. Casing: Galvanized Steel. Type 304 Stainless Steel Optional:
A. Verification of Performance: 1. Casing panels shall totally encase the fill media to
1. Test and certify cooling tower thermal performance protect the fill from damage due to direct atmospheric
according to CTI Standard 201. contact.
2. Test and certify cooling tower sound performance 2. Fasteners: Corrosion resistance equal to or better than
according to CTI ATC-128. materials being fastened.
B. Meet or Exceed energy efficiency per ASHRAE 90.1. 3. Joints: Sealed watertight.
1.5 WARRANTY 4. Welded Connections: Continuous and watertight
A. Motor/Drive System: Five (5) year comprehensive warranty I. Fill Media: PVC; resistant to rot, decay and biological
against materials and workmanship including motor, fan, attack; formed, crossfluted bonded together for strength
bearings, mechanical support, sheaves, bushings and belt. and durability in block format for easy removal and
B. Unit: One (1) year from start-up, not to exceed eighteen replacement; suitable for use as a working surface; self
(18) months from shipment on the unit. extinguishing with flame spread rating of 5 per ASTM
E84-81a; able to withstand continuous operating
PART 2 - PRODUCTS temperature of 130ºF; and fabricated, formed and
installed by the manufacturer to ensure water breaks up
2.1 MANUFACTURERS
into droplets.
A. Manufactures: Subject to compliance with requirements,
J. Drift Eliminators: Same material as Fill. 0.001% drift rate.
provide cooling towers manufactured by one of the
K. Air Inlet Louvers: Formed PVC; designed “Sight Tight” to
following:
completely block direct sunlight from entering and water
1. EVAPCO, Inc.
from splashing out of the closed circuit cooler.
2. Approved Substitute
L. Water Level Control: Brass mechanical makeup water
2.2 MATERIALS valve and plastic float with an adjustable linkage.
A. Galvanized Sheet Steel complying with ASTM A 653/A
2.4 MOTORS AND DRIVES
653M and having G-235 designation.
A. General requirements for motors are specified in Division
B. Optional Type 304 and/or 316 Stainless Steel as specified.
15 Section “Motors”.
2.3 INDUCED-DRAFT, COUNTERFLOW CLOSED CIRCUIT COOLERS B. Enclosure Type: TEAO or TEFC
A. Description: Factory assembled and tested, induced draft C. Motor Speed: Premium Efficient VFD Duty (Option: 2-speed)
counterflow closed circuit cooler complete with coil, fill, D. Drive: Power Band Belt designed for 150% of the motor
fan, louvers, accessories, and rigging supports. nameplate HP.
B. Closed Circuit Cooler Characteristics and Capacities: Refer 1. Belt: Mutli-groove, solid back V-belt type neoprene
to the Closed Circuit Cooler schedule. reinforced with polyester cord.
C. Fan(s): 2. Sheaves: Aluminum alloy if located inside the airstream.
1. Type and Material: Axial propeller, individually 3. Bearings: Heavy duty, self-aligning pillow block
adjustable wide chord blade extruded aluminum bearings with lubrication lines extended to side access
installed in a closely fitted cowl with venturi air inlet door. Minimum L10 life for bearings shall be 75,000
for maximum efficiency, covered with a heavy gauge hours. Provide extended grease lines and fittings.
hot dipped Galvanized Steel fan guard. 4. Vibration Cutout Switch: Mechanical switch to de-
2. Maximum sound pressure level of ________ dB(A) energize fan motors if excessive vibration in NEMA 4
measured at 5 feet above the fan discharge during full enclosure.
speed operation in accordance with CTI Standard ATC-
2.5 MAINTENANCE ACCESS
128.
A. Internal Working / Service Platforms: Provide a complete
D. Water Distribution System: Non-corrosive materials.
internal working platform and ladder system for service of
1. Evenly distribute of water over fill material with
all drive components. A suitable working platform may be
pressurized spray tree.
constructed of the fill media for counterflow closed circuit
a. Pipes: Schedule 40 PVC, Non-corrosive Materials
coolers. If a crossflow cooler is used, provide an internal
b. Nozzles: Non-clogging, ABS Plastic, threaded into
walkway with ladder and elevated working platform to
branch piping.
allow for service and maintenance to motor and drive
2. Maximum pressure at inlet shall be ______ psig.
assembly.
E. IBC Compliance: The unit structure shall be designed,
B. Handrails/Grabrails: Galvanized steel pipe complying with
analyzed, and constructed in accordance with the latest
29 CFR 1910.23. If access to fan deck is required, supply a
edition of the International Building Code (IBC)
perimeter handrail with ladder from grade to fan deck.
Regulations for seismic loads up to ______ g and wind
C. Ladders: Aluminum, sloped “ships type” with grabrail or
loads up to ______ psf.
vertical complying with 29 CFR 1910.27.
27
EVAPCO PRODUCTS ARE MANUFACTURED WORLDWIDE
W
World Headquarters/
Research and
Re
Development Center
D
EVAPCO Facilities
Bulletin 241C
©2016 EVAPCO, Inc.
Member MCAA