Professional Documents
Culture Documents
■ General
The VJQ7 is a plug-in type analog to pulse converter
that converts DC current or DC voltage signal into iso-
lated transistor-contact pulse or contactless AC switch
pulse.
The VJQ7 converter features:
• Either pulse output, communication function (RS-485),
or alarm output (2 relay contacts) is selectable as
Output-2. Output frequency: 0.001Hz≤F100≤2kHz
• Various parameters such as input ranges can be set However, 1kHz or less for contactless AC
and modified through a PC (VJ77) or Handy Terminal switch
(JHT200 and the like). 0Hz ≤ F 0< F100
F0 is 0% of output frequency.
■ Model and Suffix Codes F100 is 100% of output frequency.
Frequency can be set in increments of 0.00001
VJQ7-0 - 0 (Hz or kHz) within 4 significant digits.
Model Output range unit: Either Hz or kHz is selectable.
Low–level output cutoff point: 0.0001Hz to 100% of
Output output frequency
1 : 1 output
2 : 2 outputs Maximum permissible load:
Open collector: 30V DC/200mA
Power Supply
6 : 100 to 240V AC/DC (–15, +10%) 50/60Hz
Contactless AC switch: 100V AC/200mA
7 : 15 to 30V DC (±20%) Pulse width type: Either 50% duty, fixed on-state
pulse width, or fixed off-state pulse width
Input
A : 0 to 50mA DC, span is 5mA or more is selectable.
1 : –10 to +10V DC, span is 0.1V or more Pulse width time: 0.1 to 500ms, settable by 0.1ms
Output frequency available for fixed pulse width:
Output-1
1 : Open collector 1
x 1000[Hz]
3 : Contactless AC switch Set value of pulse width (ms) x 2
GS 77J01Q17-01E
©Copyright Dec. 1999
5th Edition Nov. 2014
<<Contents>> <<Index>> 2
PC-link communication: Communication protocol Input range is -1 to +1 V (L range), span is under 0.5 V;
with a PC, graphic panel, UT link module accuracy (%)=±0.1% x 0.5 V / input span [V]
of FA-M3 When current input, apply [input range x input resis-
MODBUS communication: Communication protocol tance] to the above, and add 0.1% of resistance error.
with a PC (SCADA). Accuracy limitation by output range
Ladder communication: Communication protocol When F100 ≤ 1kHz, zero elevation is 50% or more;
with ladder communication module of F100/2
Accuracy (%)= x 0.1
FA-M3 and programmable controller of F100-F0
other manufacturers When F100>1kHz, zero elevation;
● Alarm Output F100/2
Accuracy (%)= x 0.2
Signal type: Relay contact F100-F0
Output signal: N. O. contact output (contact ON at F0 is 0% of output frequency, F100 is 100% output frequency.
excitation) 2 points, COM common When both input and output have accuracy limitation,
Contact capacity: 30 V DC, 1 A total accuracy is their sum.
Alarm operating direction: High limit alarm or low limit alarm Response speed: One cycle of output pulse + 150ms
Relay operating direction setting: Excitation or (for 50% duty), 63% response (10 to 90%)
non-excitation at normal status Alarm output: 350ms (input change 10
Alarm setting range: 0 to 100% of input range to 90%, alarm setting point 50%, time till
Setting resolution: 0.1%, 4 significant digits alarm output, when alarm delay setting
Hysteresis setting range: 0 to 100% of input range and hysteresis are min.)
Setting resolution: 0.1%, 4 significant digits Effect of Power Supply Voltage Fluctuation: ±0.1% or
Alarm on- delay setting: Delay time from alarm condi- less of span for power supply voltage fluc-
tion completion to output tuation of 85 to 264V AC (47 to 63 Hz),/
(Ex. Outputted when alarm status continues DC, 12 to 36V DC.
for 1 second or more after input value is over Effect of Ambient Temperature Change: ±0.2% or less
alarm point in case of set value “1 second.”) of span for change of 10°C
Setting range: 0 to 999 seconds
Setting resolution: 1 second (however, add about 0.2
seconds to setting time to prevent wrong
■ Safety and EMC Standards
operation) Safety: Approved by CAN/CSA C22.2 No.61010-
Alarm off-delay setting: Delay time from alarm normal 1(CSA), approved by UL61010-1.
condition completion to output Installation category: CAT. II
(Ex. Released when normal status contin- Pollution degree: 2
ues for 2 seconds or more after input value As for the apparatus authorized, power supply volt-
comes back to normal status from alarm age is limited to 15 V to 30 V DC, and the circuit to
status in case of set value “2 seconds.”) connect is limited to a class 2.
Setting range: 0 to 999 seconds Models that have contactless AC switch output are
Setting resolution: 1 second (however, add about 0.2 not certified.
seconds to setting time to prevent wrong Category Description Remarks
operation) For measurements performed on circuits
CAT.I not directly connected to MAINS.
Alarm operation display: Front LED lights at alarm, 2 LEDs For measurements performed on circuits Appliances, portable
CAT.II directly connected to the low voltage equipments, etc.
installation.
■ Items Available to Be Set For measurements performed in the
CAT.III building installation.
Distribution board,
circuit breaker, etc.
The following items can be set through a PC (VJ77 PC- For measurements performed at the source Overhead wire,
based parameters setting tool) or Handy Terminal: CAT.IV of the low-voltage installation. cable systems, etc.
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 77J01Q17-01E 5th Edition Nov.17,2014-00
<<Contents>> <<Index>> 3
■ Power Supply and Isolation ■ Accessories
Power Supply Rated Voltage: Tag Number Label: 1 sheet
100 to 240 V AC/DC 50/60 Hz Range Label: 1 sheet
15 to 30 V DC Shunt Resistor: 1 (when current input is specified)
Power Supply Input Voltage: 100 to 240 V AC/DC
(–15, +10%) 50/60 Hz ■ Items to Specify When Ordering
15 to 30 V DC (±20%) Shipped after setting the input range, output frequency,
Power Dissipation: 24 V DC 2.4 W, 110 V DC 2.4 W output range unit, low-level output cutoff point, pulse
100 V AC 4.5 VA, 200 V AC 6.3 VA width type, pulse width time as specified.
Insulation Resistance: 100 MΩ/500 V DC between
input, output-1, output-2, power supply • Model and Suffix Code: e.g. VJQ7-026-A110
• Input range: e.g. 4 to20 mA DC
and ground mutually
• Output frequency: e.g. 0 to 10 Hz
Withstand Voltage: 2000 V AC / minute between • Low cut point (Hz): e.g. 0.0001
input, (output-1, output-2), power supply, • Pulse width type: e.g. Duty of 50%
and ground mutually * When specifying “Duty of 50%” for pulse width type,
1000 V AC / minute between input and the specification of pulse width (ms) is unnecessary.
output-2 at alarm output
1000 V AC / minute between output-1 and output-2 ■ Factory Setting
Factory settings are as follows:
■ Environmental Conditions • Input range: 4 to 20mA DC (for current input), or 1 to
Temperature: 0 to 50 °C 5V DC (for voltage output)
Humidity: 5 to 90% RH (no condensation) • Output frequency: 0 to 10Hz
Ambient Condition: Avoid installation in such environments • Low cut point (Hz): 0.0001
• Pulse width type: fixed on-state pulse width
as corrosive gas like sulfide hydrogen, dust, sea • Pulse width (ms): 30
breeze and direct sunlight
● When output-2 is specified as communication
Installation altitude 2000m or less above sea level.
output
• Address No.: 01
■ Mounting and Appearance • Baud rate: 9600 bps
Construction: Compact plug-in type • Parity: Even
Material: Modified Polyphenylene Oxide (Case body) • Data length: 8 bit
Mounting Method: Wall, DIN rail, or dedicated VJ • Stop bit: 1 bit
• Protocol: PCLINK
mounting base (only when Output-2 is
analog output) mountings ● When output-2 is specified as alarm output
Connection Method: M3 screw terminal • Alarm operating direction: High limit alarm (alarm-1),
External Dimension: 29.5x76x124.5mm (WxHxD) low limit alarm (alarm-2)
• Relay operating direction: Excitation at alarm (alarm-1 / 2)
Weight: Approx. 170 g • Alarm setting: 100% (alarm-1), 0% (alarm-2)
• Hysteresis: 3% (alarm-1 / 2)
• Alarm on-delay: 0 second (alarm-1 / 2)
• Alarm off- delay: 0 second (alarm-1 / 2)
■ Terminal Arrangement
Terminal Output-2 Output-2 Output-2
Signal
3 2 1 No. Analog output Communication output Alarm output
1 Input (+)
6 5 4
2 Output-2 (+) B (+) ALM1
3 Input (–)
4 N.C.
5 Output-2 (Note 1) (–) A (–) COM
6 Output-2 (Note 1) N.C. COM ALM2
7 Output-1 (+)
9 8 7 8 GND GND
9 Output-1 (–)
11 10 10 Supply (L+)
11 Supply (N–)
Note 1: In case of one output type, output-2 is N.C.
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 77J01Q17-01E 5th Edition Nov.17,2014-00
<<Contents>> <<Index>> 4
■ Block Diagram
Insulation circuit
+ +
1 Input Microcomputer 7
processing Output-1
INPUT R circuit Output-1
– circuit
3
4 9 –
R: 100 Ω
External resistor
at current input 4 L+
10
Supply
Power N–
supply 11
circuit
Handy
GND
Terminal 8
or PC (VJ77)
2 +
Output-2
Output-2
Insulation circuit circuit
5 –
6 N.C.
Communication
circuit 5 A– 5 COM
(common)
Relay
6 COM 6 Alarm-2
■ External Dimensions
Unit : mm
Shunt resistor
(24.5)
(at current input)
Connector for communication 2-4.2x5 holes
Alarm
lamp DIN rail
(Note 2)
ALM1
70.8
59
72
ALM2
11-M3
screw
6
4
26
10.5 84 (30) 22
124.5 (4) 29.5
Note 2: Only when output-2 is alarm output
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 77J01Q17-01E 5th Edition Nov.17,2014-00