MDP

POLE CB RATING KAIC


CKT No. LOAD DESCRIPTION VA RATING VOLT CONDUCTOR SIZE CONDUIT
POLE 1Ø AT RATING
1 WELDING MACHINE 1 2000 230 2 8.70 30 35 2 - 5.5mm² THHN + 3.5mm² E 20mmØPVC
2 WELDING MACHINE 2 2000 230 2 8.70 30 35 2 - 5.5mm² THHN + 3.5mm² E 20mmØPVC
3 GRINDER MACHINE 800 230 2 3.48 30 35 2 - 5.5mm² THHN + 3.5mm² E 20mmØPVC
4 CIRCULAR SAW 500 230 2 2.17 30 30 2 - 5.5mm² THHN + 3.5mm² E 20mmØPVC
5 CONVENIENCE OUTLET 800 230 2 3.48 20 30 2 - 3.5mm² THHN + 2.0mm² E 15mmØPVC
6 LIGHTING OUTLET 150 230 2 0.65 15 30 2 - 3.5mm² THHN + 2.0mm² E 15mmØPVC
7 SPACE 500 230
8 SPACE 500 230
TOTAL 7250 27.17
TOTAL CURRENT: MAIN CIRCUIT BREAKER PROTECTION:
IT= 27.2 Use: 50AT/50AF, 2P, 230V, 60Hz
For Meralco Application:
KVA = 7.250 KVA
DEMAND FACTOR = 80 PERCENT
POWER FACTOR = 85 PERCENT
KW = KVA X 0.85 (pf)
KW = 7.250 X 0.85 = 6.162 KW x .8 (DEMAND FACTOR) = 4.930 KW
Main Feeder Conductors:
2 - 8.0mm² THHN + 8.0mm² TW E in 32mmØ Conduit