You are on page 1of 8

Worldwide

www.tyco-fire.com
Contacts

Model BFV-300 Butterfly Valve


Wafer Style

General The owner is responsible for main-


taining their fire protection system
Description and devices in proper operating con-
dition. Contact the installing contrac-
The TYCO Model BFV-300 Wafer Style tor or product manufacturer with any
Butterfly Valves are indicating type questions.
valves designed for use in fire protec-
tion systems where a visual indication Technical
of open valve condition is required.
They are used, for example, as system,
sectional and pump water control
Data
valves, and are suitable for installation Approvals
between ANSI Class 125/150 flanges UL and ULC Listed
as well as PN10/16 flanges without the FM Approved
need for flange gaskets. CE Certified
VdS Approved
For applications requiring supervision Russian Fire Certificate
of the open state of the valve, the Gear CNPP R1 Listed – APSAD
Operators for the Model BFV-300 But- Listed by California State Fire Marshall
terfly Valves feature two sets of factory For specific information about approvals,
installed internal switches each having see Tables A, B, and C.
SPDT contacts, see Figure 3. The
Note: All laboratory listings and approvals
supervisory switches transfer their
are for indoor and outdoor use.
electrical contacts when there is move-
ment from the open or closed disc Sizes
position during the first two revolutions 2 in. to 12 in. (DN50 to DN300)
of the handwheel.
UL/ULC/FM Maximum Working
Note: If the butterfly valve is required in a Pressure
foam system, verify the valve is compatible 2 in.–8 in. (DN50–DN200). . . . . 300 psi (20,7 bar)
by referring to the foam concentrate 10 in.–12 in. (DN250–DN300). . 175 psi (12,1 bar)
manufacturer technical literature for VdS Maximum Working Pressure
information about foam compatibility, and 2 in.–8 in. (DN50–DN200). . . . . 300 psi (20,7 bar) Silicone Free Model Availability
acceptable system equipment materials 10 in. (DN250) �������������������������� 232 psi (16,0 bar) Silicone free models are available. Contact
of construction. 12 in. (DN300) ��������������������������� 175 psi (12,1 bar) TYCO sales for information.
Maximum Working Temperature Control Valve Seat Leakage Class
NOTICE 212°F (100°C) in accordance with UL 1091 IEC 60534-4
The Model BFV-300 Wafer Style But- Materials of Construction CLASS VI (Type C) Control Valve Seat
terfly Valves described herein must be Body ��������������������������������������������������Ductile Iron Leakage according to ANSI/FCI 70-2-2006
installed and maintained in compliance Body Coating ���������������������� RILSAN PA11 Black (ASME B16.104)
with this document, as well as with the Disc ����������������������������������������������������Ductile Iron
applicable standards of the NATIONAL Disc Seal. . . . . . . . . . . . . . . EPDM Encapsulated
Upper & Lower Stem �������������������� Stainless Steel
FIRE PROTECTION ASSOCIATION, in Handwheel ����������������������������������������Ductile Iron
addition to the standards of any other Actuator, 2 in.–6 in. (DN50–DN150):
authorities having jurisdiction. Failure • IP65, bronze traveling nut gearbox, ductile
to do so may impair the performance iron housing
of these devices. Actuator, 8 in.–12 in. (DN200–DN300):
• IP65, brass segmented gearbox, ductile iron
housing

IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.

Page 1 of 8 JANUARY 2021 TFP1516


TFP1516
Page 2 of 8

Nominal Dimensions
Nominal Inches Weight
Valve Size (mm) Lbs.
Inches (kg)
(DN) A B C D E F G H
2 1.50 10.63 2.85 4.90 4.92 4.28 1.99 1.34 13.45
(DN50) (38) (270) (72,5) (124,5) (125) (108,6) (50,5) (34) (6,1)
2-1/2 1.81 11.67 3.35 5.45 4.92 4.28 1.99 1.65 13.4
(DN65) (46) (296,5) (85) (138,5) (125) (108,6) (50,5) (41,9) (6,1)
3 1.81 12.27 3.58 5.81 4.92 4.28 1.99 2.34 14.1
(DN80) (46) (311,7) (91) (147,7) (125) (108,6) (50,5) (59,5) (6,4)
— 1.81 12.27 3.58 5.81 4.92 4.28 1.99 2.34 14.1
(DN80) (46) (311,7) (91) (147,7) (125) (108,6) (50,5) (59,5) (6,4)
4 2.16 13.92 4.29 6.75 4.92 4.28 1.99 3.25 15
(DN100) (55) (353,5) (109) (171,5) (125) (108,6) (50,5) (82,6) (6,8)
5 2.4 16 5.16 7.93 5.91 5.79 2.32 4 26.2
(DN125) (61) (406,6) (131) (201,5) (150) (147) (58,9) (101,6) (11,9)
6 2.4 17.07 5.71 8.44 5.91 5.79 2.32 5.22 24.5
(DN150) (61) (433,6) (145) (214,5) (150) (147) (58,9) (132,6) (11,1)
8 2.48 19.63 6.69 9.29 8.86 8.19 2.76 7.3 44.1
(DN200) (63) (498,5) (170) (236) (225) (208) (70) (185,4) (20)
— 2.48 19.63 6.69 9.29 8.86 8.19 2.76 7.3 44.1
(DN200) (63) (498,5) (170) (236) (225) (208) (70) (185,4) (20)
10 2.91 23.01 8.27 11.1 11.14 8.19 2.91 9.05 63.9
(DN250) (74) (584,5) (210) (282) (283) (208) (74) (230) (29)
12 3.03 25.16 9.5 12.2 11.14 8.19 2.91 11.53 86.42
(DN300) (77) (639) (241,5) (310) (283) (208) (74) (292,8) (39,2)
SEGMENTED
HANDWHEEL GEAR OPERATOR
8 TO 12 INCH
E (DN200 TO DN300)
INDICATOR VALVE SIZES
C D FLAG
(VALVE
CLOSED)

B HANDWHEEL
INDICATOR HANDWHEEL
DISC GASKET FLAG
(VALVE
OPEN)
A

BODY

H TRAVELLING NUT TRAVELLING NUT


ELECTRICAL
CONNECTOR GEAR OPERATOR GEAR OPERATOR
2 TO 4 INCH 5 TO 6 INCH
(DN50 TO DN100) (DN125 TO DN150)
VALVE SIZES VALVE SIZES
FIGURE 1
MODEL BFV-300 WAFER STYLE BUTTERFLY VALVE
NOMINAL DIMENSIONS
TFP1516
Page 3 of 8

No. Part Material Qty. No. Part Material Qty. No. Part Material Qty.
ASTM Spring Pin ASTM
01 Body 1 14 Stem Housing Fe 1 28 1
A-536 Ø4 x 0.8t x 35 A-228
ASTM ASTM
02 Upper Stem AISI 410 1 15 Spring Pin 1 29 Handwheel 1
A-228 A-536
ASTM ASTM
03 Lower Stem AISI 410 1 16 Indicator 1 30 Bolt (Round) 3
A-619 A-167
ASTM
04 Disc EPDM 1 17 O-Ring NBR 1 31 Plate Washer 4
A-167
05 O-Ring (P12) EPDM 4 18 Cover Gasket Paper 1 32 Switch Assembly — 1
Oiless B/R Spring Pin ASTM ASTM
06 — 4 19 1 33 T/R Bolt 2
(MB1410) Ø5 x 1T x 25 A-228 A-307
End Cap Tapping Screw
07 EPDM 1 20 O-Ring (P10) EPDM 1 34 S10C 1
2-1/2 – 4 Inch ST3.5 x 7.5
ASTM
08 Gear Box 1 21 Worm Shaft AISI 410 1 35 Tooth Washer 4# S10C 1
A-536
Traveling Nut ASTM
Bronze 1 22 Bushing (1) FD-0205-45 1 36 Lever 1
2 – 6 Inch A-619
09
Segment Gear C3604BD 1 23 Collar FD-0205-45 1 37 Connector — 1
8 – 12 Inch
ASTM
10 Bushing (2) FD-0205-45 1 24 Spring Washer A-167 4 38 Sticker — 1
ASTM Hex Bolt ASTM
11 Cover 1 25 2 39 Sticker — 1
A-619 M8 x 20L A-167
Hex Bolt ASTM
12 Bushing Fe 1 26 M8 x 25L A-167 2 40 Gasket EPDM 2
Headless Wrench ASTM Spring Pin ASTM
13 1 27 Gasket Paper 1 41 1
Bolt M5 x 7L A-307 Ø3 x 0.6T x 25 A-228

35 34 37 33

36 30

32

38, 39
28
31
30
19,
29 20 41 17 14 12 18
16
11
15
21 10
13
22 09
27
23 08
25
24 05
26
25 02
40
01

04 03

06 07

FIGURE 2
MODEL BFV-300 WAFER STYLE BUTTERFLY VALVE
ASSEMBLY
TFP1516
Page 4 of 8

FLOW RATE IN LITERS PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
400 600 800 1000 2000 4000 6000 10000 20000
9.0 0,60
8.0
7.0 0,50
6.0 0,40
5.0
0,30
4.0
IN POUNDS PER SQUARE INCH (PSI)

NOMINAL PRESSURE DROP IN BAR


50)

3.0
NOMINAL PRESSURE DROP

65) 0,20
DN

DN

(1 PSI = 0,06895 BAR)


(
CH

H(

80)

)
2 IN

2.0
100
INC

(DN

(DN
/2

CH

)
125
2-1

3 IN

CH

0,10
(DN

)
0,09
4 IN

150
CH
0,08

(DN
5 IN

1.0 0,07

CH
0.9 6 IN 0,06

)
0.8

200

)
0,05

250
0.7

(DN

)
DN

300
0.6 0,04

CH

H(

DN
8 IN
0.5

INC

H(
0,03

INC
10
0.4

12
0.3
100 200 300 400 600 800 1000 2000 3000 4000 6000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
MODEL BFV-300 WAFER STYLE BUTTERFLY VALVE
NOMINAL PRESSURE DROP VERSUS FLOW

YELLOW YELLOW

S-1
FIRE ALARM COMMON (WHITE) COMMON (WHITE) END OF LINE
CONTROL PANEL RESISTOR
SUPERVISORY RED RED OR
CIRCUIT NEXT DEVICE

MODEL BFV-300 GREEN


GEAR OPERATOR OPERATOR CASE
CONTACT RATINGS: GROUND
16A 125V/250 VAC BLUE
5A 24VDC
SWITCH S-1, 2 LEADS PER CONTACT
SWITCH S-2, 1 LEAD PER CONTACT S-2

COMMON (BLACK) ORANGE


VOLTAGE AUX. DEVICE
SOURCE (BELL OR HORN)

FIGURE 3
MODEL BFV-300 BUTTERFLY VALVE OPEN POSITION — SUPERVISORY SWITCH OPEN POSITION
INTERNAL SWITCH WIRING DIAGRAM
TFP1516
Page 5 of 8

Nominal Part Number Agency Listing/Approval


Max.
Valve Size Flange BFV-300 BFV-300
Inches PSI Face CA Fire CNPP PAVUS Russian
(bar) with without CE UL ULC FM VdS Marshall Fire
(DN) Internal Switch Internal Switch Cert.
2 300 ANSI 16.5, BS PN16 59300W020WS 59300W020NS ✓ ✓ ✓ ✓ ✓ ✓
(DN50) (20,7)
2-1/2 300 ANSI 16.5, BS PN16 59300W025WS 59300W025NS ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
(DN65) (20,7)
3 300 ANSI 16.5 59300W030WS 59300W030NS ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
(DN80) (20,7)
— 300 BS PN16 59300W036WS 59300W036NS ✓ ✓ ✓ ✓ ✓ ✓ ✓
DN80 (20,7)
4 300 ANSI 16.5, BS PN16, 59300W040WS 59300W040NS ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
(DN100) (20,7) AS 2129 Table F
5 300 ANSI 16.5, BS PN16 59300W050WS 59300W050NS ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
(DN125) (20,7)
6 300 ANSI 16.5, BS PN16, 59300W060WS 59300W060NS ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
(DN150) (20,7) AS 2129 Table F
8 300 ANSI 16.5, BS PN10 59300W080WS 59300W080NS ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
(DN200) (20,7)
— 300 BS PN16 59300W086WS 59300W086NS ✓ ✓ ✓ ✓ ✓ ✓ ✓
DN200 (20,7)
10 175 ANSI 16.5, 59300W100WS 59300W100NS ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
(DN250) (12,1) BS PN10/16
12 175 ANSI 16.5, 59300W120WS 59300W120NS ✓ ✓ ✓ ✓ ✓ ✓
(DN300) (12,1) BS PN10/16
TABLE A
MODEL BFV-300 WAFER STYLE BUTTERFLY VALVE
WITH OR WITHOUT INTERNAL SUPERVISORY SWITCHES
PART NUMBER SELECTION AND AGENCY LISTINGS/APPROVALS

Nominal Part Number Agency Listing/Approval


Max.
Valve Size Flange BFV-300 BFV-300C
PSI
Inches Face Supv. Switch Supv. Switch CE VdS CNPP
(bar)
(DN) OPEN CLOSED
2 300 ANSI 16.5, BS PN16 59300W020AWS 59300W020AWSC ✓ ✓ ✓
(DN50) (20,7)
2-1/2 300 ANSI 16.5, BS PN16 59300W025AWS 59300W025AWSC ✓ ✓ ✓
(DN65) (20,7)
3 300 ANSI 16.5 59300W030AWS 59300W030AWSC ✓ ✓ ✓
(DN80) (20,7)
— 300 BS PN16 59300W036AWS 59300W036AWSC ✓ ✓ ✓
DN80 (20,7)
4 300 ANSI 16.5, BS PN16, 59300W040AWS 59300W040AWSC ✓ ✓ ✓
(DN100) (20,7) AS 2129 Table F
5 300 ANSI 16.5, BS PN16 59300W050AWS 59300W050AWSC ✓ ✓ ✓
(DN125) (20,7)
6 300 ANSI 16.5, BS PN16, 59300W060AWS 59300W060AWSC
(DN150) (20,7) AS 2129 Table F ✓ ✓ ✓
8 300 ANSI 16.5, BS PN10 59300W080AWS 59300W080AWSC ✓ ✓ ✓
(DN200) (20,7)
— 300 BS PN16 59300W086AWS 59300W086AWSC ✓ ✓ ✓
DN200 (20,7)
10 175 ANSI 16.5, 59300W100AWS 59300W100AWSC ✓ ✓ ✓
(DN250) (12,1) BS PN10/16
12 175 ANSI 16.5, 59300W120AWS 59300W120AWSC ✓ ✓ ✓
(DN300) (12,1) BS PN10/16
TABLE B
MODEL BFV-300 WAFER STYLE BUTTERFLY VALVE
WITH CNPP-APSAD LARGE 100 X 100 MM FLAG AND INTERNAL OPEN AND CLOSED SUPERVISORY SWITCHES
PART NUMBER SELECTION AND AGENCY LISTINGS/APPROVALS
TFP1516
Page 6 of 8

Part Number
Nominal Bernstein
Gear Bernstein
Valve Size Mounting Bernstein GC-SU1Z
Operator i88-IP65
Inches Bracket with i88-IP65 Ex IP-66/67 ATEX
Type LED Switch
(DN) Mounting Bolts Regular Switch (Ex II2G Ex dIIC T6 Gb)
24V Switch
2 – 4
(DN50 – DN100) Travelling 59300SPBRACKET10
5 – 6 Nut
59300SPBRACKET20
(DN125 – DN200)
59300SPSW 59300SPSWLED 59300SPSWATEX
8 59300SPBRACKET25
(DN200) Segmented
10 – 12 Gear
59300SPBRACKET30
(DN250 – DN300)
Notes:
1. Install a single switch in either bracket mounting position to monitor Open or Closed valve condition

Bernstein Switch
Wiring Diagram

TABLE C
MODEL BFV-300 WAFER STYLE BUTTERFLY VALVE WITHOUT INTERNAL SUPERVISORY SWITCHES
ACCESSORY EXTERNAL SUPERVISORY SWITCHES AND MOUNTING BRACKETS
PART NUMBER SELECTION

Installation and studs must meet the minimum


strength requirements of ASTM A307
Be certain to keep flange faces as
parallel as possible during and after
The TYCO Model BFV-300 Wafer Style (Grade B), and the nuts must meet the tightening bolts or studs. After final
Butterfly Valves may be installed with minimum strength requirements of tightening, again check the valve for
flow in either direction and can be ASTM A563 (Grade A). full opening and closing.
positioned either horizontally or verti- Prior to installation, close the valve. As applicable, see Figure 3 for the
cally. They are designed for installa- Spread the flanges apart to allow the internal switch wiring diagram.
tion between the faces of ANSI Class valve to slip easily between the flanges.
125 and 150 flanges as well as PN10/16 Conduit and electrical connections
Make sure the pipe flange faces are
flanges without the need for flange are to be made in accordance with
clean of any foreign material such as
gaskets. The Series BFV-300 are self- the authority having jurisdiction and/
scale, metal shavings, or welding slag.
sealing between mating flanges; there- or the National Electrical Code. With
Insert the valve between the flanges
fore, they do not require the use of reference to Figure 3, the supervisory
(without flange gaskets). Do not apply
additional gaskets. switch is intended for connection to
lubricant to the seat faces as this may
the supervisory circuit of a fire alarm
The Model BFV-300 may be installed damage the seat material. Be sure to
control panel in accordance with NFPA
with any pressure class or schedule of center the valve and do not damage
72. The auxiliary switch is intended for
pipe or tubing no greater than sched- the liner. Relax the separation of the
the unsupervised connection to aux-
ule 40 that is listed or approved for flanges, install, and hand-tighten all
iliary equipment in accordance with
fire protection service and installed in flange bolts. Slowly open the valve,
NFPA 70, National Electric Code.
accordance with the manufacturers checking for free movement of the disc.
instructions. If valve opens freely, leave the valve in Note: For outdoor applications with
the open position, and using a cross- internal supervisory switches, it is rec-
The wafer bodies have locating lugs to draw sequence, tighten all flange bolts ommended that wiring connections
ensure proper centering of the valve until the valve is metal-to-metal with be made at a temperature above 15°F
body when flange bolts are installed. both mating flanges. Recommended (-9°C), in order to insure sufficient flex-
See Figure 2 for bolt diameter. Bolts tightening torques are listed in Table F. ibility of the wire lead insulation.
TFP1516
Page 7 of 8

Nominal Valve Size Nominal Recommended


Inches Part Number Flange Size Minimum Torque
(DN) ANSI Inches Ft.-Lbs
2–4 (DN) (Nm)
59300SPHWHEEL10
(DN50–DN100) 2–4 20–30
5–6 (DN50–DN100) (27,1–40,7)
59300SPHWHEEL20
(DN125–DN150) 5–8 33–50
8 (DN125–DN200) (44,7–67,8)
59300SPHWHEEL30
(DN200) 10–12 53–75
10–12 (DN250–DN300) (71,8–101,7)
59300SPHWHEEL40
(DN250–DN300)
TABLE F
TABLE D RECOMMENDED MATING
BFV-300 WAFER STYLE BUTTERFLY VALVE FLANGE BOLT TORQUES
REPLACEMENT HANDWHEEL
PART NUMBER SELECTION
Ordering
Nominal Valve Size
Inches Part Number
Procedure
(DN) Contact your local distributor for avail-
2–4 ability. When placing an order, indicate
59300SPFLAG10
(DN50–DN100)
the full product name and Part Number
5–6
(DN125–DN150) 59300SPFLAG20 (P/N).
8–12
(DN200–DN300) 59300SPFLAG30 Butterfly Valves
TABLE E Model BFV-300 with Internal
BFV-300 WAFER STYLE BUTTERFLY VALVE Open Supervisory Switches
INDICATOR FLAG Specify: (specify size) Model BFV-300
PART NUMBER SELECTION Wafer Style Butterfly Valve, Inter-
nal Open Supervisory Switches,
P/N (specify per Table A)
Care and Limited Model BFV-300 without
Maintenance Warranty Supervisory Switches
Specify: (specify size) Model BFV-300
The TYCO Model BFV-300 Wafer Style For warranty terms and conditions, visit Wafer Style Butterfly Valve, P/N (specify
Butterfly Valves must be maintained www.tyco-fire.com. per Table A)
and serviced in accordance with this Model BFV-300 with Internal
section. Open Supervisory Switches,
Before closing a fire protection system APSAD Approved
control valve for maintenance or Specify: (specify size) Model BFV-300
inspection work on either the valve or Wafer Style Butterfly Valve, Internal
fire protection system which it con- Open Supervisory Switches, APSAD
trols, permission to shut down the Approved, P/N (specify per Table B)
affected fire protection systems must
Model BFV-300 with Internal
be obtained from the proper authorities
and all personnel who may be affected Closed Supervisory Switches,
by this decision must be notified. APSAD Approved
Specify: (specify size) Model BFV-300
The owner is responsible for the Wafer Style Butterfly Valve, Internal
inspection, testing, and maintenance of Open Supervisory Switches, APSAD
their fire protection system and devices Approved, P/N (specify per Table B)
in accordance with the applicable stan-
dards of the NATIONAL FIRE PRO- Accessories
TECTION ASSOCIATION, for example,
NFPA 25, in addition to the standards External Supervisory Switch and
of any authority having jurisdiction. Mounting Bracket
Contact the installing contractor or Note: Accessory external supervisory
product manufacturer with any ques- switches and mounting brackets are
tions. Any impairment must be imme- applicable only to valves without factory-
diately corrected. installed internal supervisory switches.
It is recommended that automatic See Table C for switch models and part
sprinkler systems be inspected, tested, numbers.
and maintained by a qualified Inspec- Specify: (specify size) Model BFV-300
tion Service. Wafer Style Butterfly Valve Exter-
nal Switch Mounting Bracket, P/N
(specify), with (specify quantity) Bern-
stein External Switch (specify model),
P/N (specify)

TFP1516
Page 8 of 8

Replacement Parts
Note: Only items described in this section
are offered as replacement parts.
Handwheel
Replacement handwheel includes pin.
Specify: Handwheel, (specify size)
Model BFV-300 Wafer Style Butterfly
Valve, P/N (specify per Table D)
Indicator Flag
Specify: Indicator Flag, (specify size)
Model BFV-300, P/N (specify per
Table E)

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;