DV-5 Deluge Valve


Diaphragm Style

General
Description
The TYCO 1-1/2 inch to 8 inch (DN40
to DN200), DV-5 Deluge Valves are dia-
phragm type valves designed for ver-
tical or horizontal installation and for
fire protection system service. They
are used as automatic water control

TE
valves in deluge, preaction, and special
types of fire protection systems such
as foam-water and double interlock
systems. When properly trimmed, the
DV-5 Valves are also able to provide
actuation of fire alarms upon system
operation.
LE
NOTICE
These valves are to be used only for
hydraulically calculated systems.
The diaphragm style design of the DV-5
O
Valve allows external resetting, provid-
ing for easy resetting of a deluge or
preaction system without having to
open a valve handhole cover to man-
BS

ually reposition a clapper and/or latch


mechanism. Simply re­pressurizing the
diaphragm chamber resets the valve. End Connections Available and Weights
The one-piece, diaphragm style design
End Connection Nominal Valve Size
of the DV-5 also allows internal and
external coating of the valve to provide
O

1-1/2 Inch 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch


corrosion resistance. The internal Inlet Outlet (DN40) (DN50) (DN80) (DN100) (DN150) (DN200)
corrosion resistance offered by the
RILSAN coating makes the DV-5 suit- 9 lb 12 lb
able for most seawater and brackish Thread Thread N/A N/A N/A N/A
(4,1 kg) (5,4 kg)
water supplies when utilized in deluge
systems. The external corrosion resis- 8 lb 10 lb 31 lb 61 lb 99 lb 150 lb
tance of the RILSAN coating permits Groove Groove1
(3,6 kg) (4,5 kg) (14,1 kg) (27,7 kg) (44,9 kg) (68,1 kg)
the use of the DV-5 in corrosive atmo-
spheres associated with many types 39 lb 74 lb 107 lb 170 lb
Flange Groove1 N/A N/A
of industrial processing plants and (17,7 kg) (33,6 kg) (48,5 kg) (77,8 kg)
outdoor installations.
47 lb 80 lb 115 lb 190 lb
Flange Flange N/A N/A (21,3 kg) (36,3 kg) (52,3 kg) (87,5 kg)
Notes:
1. The Grooved Outlet is recommended for use in Preaction Systems to accommodate the use of a Groove x
Groove Riser Check Valve. Refer to Technical Data Sheet TFP1410, TFP1415, TFP1420, TFP1460, or TFP1465
as applicable.

IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.

Page 1 of 8 AUGUST 2018 TFP1305


TFP1305
Page 2 of 8

NOTES:
VALVE PARTS REPLACEMENT PARTS
No. Description Qty. Repair Parts
1. NR - Not Replaceable No. Description P/N
2. CH - Common Hardware
1 Valve Body . . . . . . . . . . . 1 NR (a) Diaphragm Kit,
2 Diaphragm . . . . . . . . . . . 1 (a) 3. Valve Bodies of 4, 6 and 8 Inch (DN100, Includes Item 2:
3 Diaphragm Cover. . . . . . . 1 NR DN150 & DN200) valves are equipped 1-1/2 Inch (DN40) Valve . . . . 92-477-1-105
4 Flat Washer, Metric: with studs and Valve Covers are secured 2 Inch (DN50) Valve . . . . . . . 92-477-1-107
1-1/2 Inch (DN40) Valve, by Hex Nuts and Hex Bolts. 3 Inch (DN80) Valve . . . . . . . 92-477-1-109
M12 . . . . . . . . . . . . . . . . . 4 CH 4 Inch (DN100) Valve . . . . . . . 92-477-1-101
2 Inch (DN50) Valve &
4. V-Ring is attached to Diaphragm of 4, 6 6 Inch (DN150) Valve . . . . . . . 92-477-1-103
3 Inch (DN80) Valve, and 8 Inch (DN100, DN150 & DN200) 8 Inch (DN200) Valve . . . . . . . 92-477-1-111
M16 . . . . . . . . . . . . . . . . . 4 CH valves at factory. If, during internal valve
4 Inch (DN100) Valve & inspection, V-Ring is discovered to be
6 Inch (DN150) Valve, detached from Diaphragm, be advised
M16 . . . . . . . . . . . . . . . . . 8 CH that V-Ring is a required valve component
8 Inch (DN200) Valve, and that detachment will not affect normal
M20 . . . . . . . . . . . . . . . . . 8 CH valve operation or performance. Should
5 Hex Bolt, Metric: V-Ring become detached, reinstall
1-1/2 Inch (DN40) Valve,
M12 x 30 mm. . . . . . . . . . 4 CH
between Diaphragm and Diaphragm
2 Inch (DN50) Valve & Cover concentrically as shown. STUDS
3 Inch (DN80) Valve, (NOTE 3)
NOTE: Do not apply adhesives, lubricants, 2
M16 x 50 mm. . . . . . . . . . 4 CH
4 Inch (DN100) Valve,
or other substances to Diaphragm, V-Ring, (NOTE 4)
M16 x 50 mm. . . . . . . . . . 6 CH or Valve Body.
6 Inch (DN150) Valve,

TE
M16 x 55 mm. . . . . . . . . . 6 CH
8 Inch (DN200) Valve,
M20 x 70 mm. . . . . . . . . . 6 CH
6 Hex Nut, Metric:
4 Inch (DN100) Valve &
6 Inch (DN150) Valve, 4
M16 . . . . . . . . . . . . . . . . . 2 CH 6
8 Inch (DN200) Valve,
M20 . . . . . . . . . . . . . . . . . 2 CH
LE (NOTE 3)
1

DIAPHRAGM
ORIENTATION
ORIENT
O
TAB
DIAPHRAGM TAB V-RING
PERPENDICULAR (NOTE 4)
5
TO VALVE BODY
CENTERLINE 4 3
BS

FIGURE 1
DV-5 DELUGE VALVE
ASSEMBLY

Flange Drilling Specification


O

Nominal Nominal Dimensions in Inches and (mm)


Valve Dim. A
ANSI B16.1 ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129 Bolt Circle
Size 1 (Class 125) 2 (PN10) 3 (PN16) 4 (10K) (Table E) Diameter
A B N A B N A B N A B N A B N
3 Inch 6.00 0.75 6.30 0.75 Dim. B
4 8 N/A N/A Bolt Hole
(DN80) (152,4) (19,0) (160,0) (19,0)
USE Diameter
4 Inch 7.50 0.75 7.09 0.75 6.89 0.60 7.00 0.71
8 ISO 7005-2 8 8 8
(DN100) (190,5) (19,0) (180,0) (19,0) (175,0) (15,0) (178,0) (18,0)
(PN16) Qty. N
6 Inch 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 Number of
8 8 8 8
(DN150) (241,3) (22,2) (240,0) (23,0) (240,0) (19,0) (235,0) (22,0) Bolt Holes
8 Inch 11.75 0.88 11.61 0.91 11.61 0.91 11.50 0.87
8 8 12 N/A 8
(DN200) (298,5) (22,2) (295,0) (23,0) (295,0) (23,0) (292,0) (22,0)

Notes:
1. Flange end 1-1/2 & 2 Inch (DN40 & DN50) DV-5 Valves are not offered.
2. Same drilling as for B16.5 (Class 150) and B16.42 (Class 250).
3. Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10).
4. Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16).
TABLE A
DIMENSIONAL SPECIFICATIONS
FOR SELECTION OF FLANGE DRILLING
TFP1305
Page 3 of 8

Port Sizes in NPT per ANSI B1.20.1 *


Port Description Port 1-1/2 Inch 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch
(DN40) (DN50) (DN80) (DN100) (DN150) (DN200)
Diaphragm Chamber Supply P1 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Water Supply Pressure & Alarm Test P2 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Alarm Actuation & System Drain P3 3/4" 3/4" 3/4" 1" 1" 1"
Main Drain P4 3/4" 3/4" 1-1/4" 2" 2" 2"
Diaphragm Chamber Supply Automatic Shut-Off Valve Actuation P5 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
* Valves are available with ports threaded per ISO 7-1

SYSTEM OPEN TO ATMOSPHERE WATERFLOW TO SYSTEM


DIAPHRAGM
CHAMBER
ALARM PORT
OPEN TO WATERFLOW
ATMOSPHERE TO AUTOMATIC
ALARM PORT SHUT-OFF
WATERFLOW VALVE
TO ALARM

VALVE DIAPHRAGM

TE
WATERWAY VALVE CHAMBER
DIAPHRAGM WATERWAY OPEN TO
SEAT ATMOSPHERE

DIAPHRAGM
RETRACTS
LE DIAPHRAGM
OPENING
CHAMBER
WATER VALVE
SUPPLY
SUPPLY WATERWAY
PORT
PRESSURE
& ALARM
250 PSI MAX. WATER SUPPLY WATERFLOW FROM WATER SUPPLY
TEST PORT
O
FIGURE 2A FIGURE 2B
SET POSITION OPERATED POSITION

DRAIN FROM SYSTEM RESIDUAL DRAIN FROM SYSTEM


BS

DIAPHRAGM
AUTOMATICALLY
SYSTEM FLEXES TO
SYSTEM
O

DRAIN ITS SEATED


DRAIN
PORT POSTION
DIAPHRAGM
CHAMBER
VALVE OPEN TO
WATERWAY ATMOSPHERE

MAIN
DRAIN
PORT

WATER SUPPLY SHUT OFF WATER SUPPLY SHUT OFF


FIGURE 2C FIGURE 2D
SYSTEM DRAIN POSITION RESIDUAL DRAIN POSITION

FIGURE 2
DV-5 DELUGE VALVE
SET AND OPEN POSITIONS
TFP1305
Page 4 of 8

NOTICE
The DV-5 Deluge Valves de­ s cribed
Materials of
8"
(204 mm)
herein must be installed and main-
tained in compliance with this docu-
Construction
ment and with the applicable standards
of the NATIONAL FIRE PROTEC­TION NOTICE
1-1/2 Inch (DN40) ASSOCIATION (NFPA), in addition to The RILSAN coating for the DV-5 Valve
Groove x Groove & Thread x Thread the standards of any other authorities provides corrosion resistance and is
having jurisdiction. Failure to do so intended to extend the life of the DV-5
may impair the performance of these Valve when exposed to internal and
devices. external corrosive conditions. Al­though
8-5/8" the RILSAN coating is intended to
The owner is responsible for maintain­ resist corrosion, it is recommended
(220 mm)
ing their fire protection system and that the end user or other technical
devices in proper operating condi- expert familiar with conditions at the
tion. Contact the installing contrac- proposed installation be consulted with
2 Inch (DN50) tor or product manufacturer with any respect to the suitability of this coating
Groove x Groove & Thread x Thread questions. for a given corrosive condition.

Technical Deluge systems using a seawater or


brackish water supply require special
12-3/4"
(324 mm)
Data considerations in order to extend the
life of the valve and trim. This type of

TE
Approvals system ideally should be configured
UL and C-UL Listed for hydraulically with a primary source of clean fresh
calculated systems, and FM Approved, water (e.g., a pressurized water tank)
3 Inch (DN80) when trimmed per the following Techni- and only upon system operation is the
Groove x Groove, Flange x Flange, cal Data Sheets: secondary water supply (seawater or
& Flange x Groove brackish water) allowed to enter the
• Deluge Systems: system. After the system operation,
LE
TFP1310 -Wet Pilot Actuation
the system should then be thoroughly
TFP1315 -Dry Pilot Actuation
TFP1320 -Electric Actuation flushed with clean fresh water. Follow­
15-3/4"
ing this recommendation will increase
• Single Interlock Preaction Systems: the service life of the DV-5 Valve and
(400 mm) TFP1410 -Wet Pilot Actuation*
TFP1415 -Dry Pilot Actuation* Valve Trim.
O
TFP1420 -Electric Actuation Body
*UL and C-UL only
4 Inch (DN100) RILSAN polyamide 11 coated ductile
Groove x Groove, Flange x Flange, • Double Interlock Preaction Systems: iron per ASTM A536-77, Grade
& Flange x Groove TFP1460 -Electric/Pneumatic 65-45-12
BS

TFP1465 -Electric/Electric
Handhole Cover
Deluge Valve RILSAN polyamide 11 coated ductile
Components for the 1-1/2 inch to 8 inch iron per ASTM A536-77, Grade
18-1/8" (DN40 to DN200), DV-5 Del­uge Valves 65-45-12
(460 mm) are shown in Figure 1. The DV-5 Valves
are for vertical or horizontal installa- Diaphragm
O

tions, and they are rated for use at a Nylon fabric reinforced, natural rubber
maximum service pressure of 250 psi per ASTM D2000
6 Inch (DN150) (17,2 bar). V-Ring
Groove x Groove, Flange x Flange, Natural rubber per ASTM D2000
& Flange x Groove
The take-out dimensions are shown in
Figure 3, and the flanged connections Diaphragm Cover Fasteners
are available drilled per ANSI, ISO, AS, Galvanized carbon steel
and JIS specifications (Ref. Table A).
Threaded port connections of the DV-5
22-1/2" Valves are available NPT threaded or
(570 mm) threaded per ISO 7/1 as detailed in the
Ordering Procedure section. Valves
with NPT threaded ports will readily
accept the trim arrangements detailed
in Technical Data Sheets referenced
8 Inch (DN200) under “Approvals”.
Groove x Groove, Flange x Flange,
& Flange x Groove

FIGURE 3
DV-5 DELUGE VALVE
TAKE-OUT DIMENSIONS
TFP1305
Page 5 of 8

FLOW RATE IN LITRES PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
200 400 600 1000 2000 3000 5000 7000 10000 15000
9.0 0,600
8.0
7.0 0,500

6.0
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

0,400
5.0 40)
DN

0,300
50)
H(

4.0
INC

DN (

NOMINAL PRESSURE DROP IN BAR


/2

CH

3.0
1 -1

0,200

80)
2 IN

DN

(1 PSI = 0,06895 BAR)


)
100
(
CH

DN
2.0
3 IN

(
CH

)
150
4 IN

(DN
0,100

)
200
TE
0,090

CH

(DN
0,080

6 IN

CH
1.0 0,070

8 IN
0.9 0,060
0.8
0.7 0,050
LE
0.6 0,040
0.5
0,030
0.4
O
0,022
0.3
50 100 200 400 600 1000 2000 3000 4000
BS

FLOW RATE IN GALLONS PER MINUTE (GPM)

The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe with C=120, is
as follows:
16 feet of 2 inch Sch. 40 pipe for the 2 inch DV-5 Valve calculated on a typical flow rate of 175 GPM.
20 feet of 3 inch Sch. 40 pipe for the 3 inch DV-5 Valve calculated on a typical flow rate of 350 GPM.
O

29 feet of 4 inch Sch. 40 pipe for the 4 inch DV-5 Valve calculated on a typical flow rate of 600 GPM.
46 feet of 6 inch Sch. 40 pipe for the 6 inch DV-5 Valve calculated on a typical flow rate of 1500 GPM.
72 feet of 8 inch Sch. 30 pipe for the 8 inch DV-5 Valve calculated on a typical flow rate of 2500 GPM.

GRAPH A
DV-5 DELUGE VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW

Operating Diaphragm Chamber is pressurized


through the trim connections from the
provided in the applicable trim arrange-
ments. This results in a rapid pressure
Principles inlet side of the system’s main control
valve. Opening an actuation device, for
drop in the Diaphragm Chamber and
the force differential applied through
The TYCO DV-5 Deluge Valve is a example the solenoid valve in the Elec- the Diaphragm to hold the Diaphragm
diaphragm style valve that depends tric Actuation Trim (Ref. Technical Data in the set position is reduced below
upon water pressure in the Dia- Sheet TFP1320), releases water from the valve trip point. The water supply
phragm Chamber (Ref. Figure 2A) to the Diaphragm Chamber faster than it pres­sure then forces the Diaphragm
hold the Diaphragm closed against can be replenished through an 1/8 in. open, permitting water to flow into the
the water supply pressure. When (3,2 mm) restriction provided by the system piping.
the DV-5 Valve is set for service, the diaphragm chamber supply connection
TFP1305
Page 6 of 8

Installation Drop in Water Supply Pressure


Below Normal Range
Annual Operation Test Procedure
Proper operation of the DV-5 Valve (i.e.,
opening of the DV-5 Valve as during a
NOTICE NOTICE fire condition) must be verified at least
If the water supply pressure is signif- once a year as follows:
Proper operation of the DV-5 Deluge
Valves depends upon their trim being icantly reduced below the normally
installed in accordance with the instruc- expected static pressure range (as NOTICE
tions given in their respective Techni- could occur in the case of a water main Operation tests for DV-5 Valves used
cal Data Sheet. Failure to follow the break or repair), and there is a subse- in double interlock preaction systems
appropriate trim diagram may prevent quent drop in the diaphragm chamber must be performed as outlined in
the DV-5 Valve from functioning prop- water pressure below its normal range TFP1460 or TFP1465, as applicable.
erly, as well as void listings, approvals, (due, for example, to a leak in a piping
connection to or from the diaphragm Step 1. If water must be prevented
and the manufacturer’s warranties. from flowing beyond the riser, perform
The DV-5 Valve must be installed in a chamber or, a leak in the diaphragm
chamber check valve caused by dirt or the following steps:
readily visible and accessible location.
The DV-5 Valve, associated trim, and debris in the check valve seal area), a • Close the Main Control Valve.
wet pilot lines must be maintained at a deluge valve such as the DV-5 could
inadvertently trip, if its water supply • Open the Main Drain Valve.
minimum temperature of 40°F (4,4°C).
Heat tracing of the DV-5 Valve or its pressure is quickly restored. • Open the Main Control Valve one
associated trim is not permitted. Heat A drop in the water supply pressure turn beyond the position at which
tracing can result in the formation of to below its normal range (as in the water just begins to flow from the
hardened mineral deposits that are case of an interrupted water supply Main Drain Valve.
capable of preventing proper operation. condition) constitutes an emergency

TE
• Close the Main Drain Valve.
Before a system hydrostatic test is per- impairment as defined by NFPA 25.
formed refer to the Installation section Should this condition occur, immedi- Step 2. Determine the type of actua­
of Technical Data Sheets TFP1310, ately close the main control valve and tion/detection system, and operate the
TFP1315, TFP1320, TFP1410, TFP1415, utilize the following procedure to reset DV-5 Valve accordingly.
TFP1420, TFP1460, or TFP1465. the system:
NOTICE
Care and
LE
Step 1. Prior to the water supply pres-
sure being restored to the closed main Be prepared to quickly perform Steps
3, 4, and 5 if water must be prevented
Maintenance
control valve, note the pressure indi-
cated by the diaphragm chamber from flowing beyond the riser.
pres­s ure gauge and determine if • Wet Pilot Actuation — Open the
The following procedures and inspec­ the pres­ s ure is within the normally
tions must be performed as indicated, Inspector’s Test Connection.
O
expected range.
in addition to any specific require­ments • Dry Pilot Actuation — Open the
of the NFPA. Any impairment must be Step 2. If the diaphragm chamber pres- Inspector’s Test Connection.
immediately corrected. sure is below the normal range, check
for and correct any source of leakage • Electric Actuation — Test the
BS

Before closing a fire protection system from the diaphragm chamber prior to deluge releasing panel (automatic
main control valve for maintenance resetting the system. control unit) in accordance with
work on the fire protection system the manufacturer’s instructions to
that it controls, obtain permission to Step 3. After the water supply pressure energize the solenoid valve.
shut down the affected fire protection is restored to the main control valve,
system from the proper authorities reset the DV-5 Deluge Valve in accor- Step 3. Verify that the DV-5 Valve has
and notify all personnel who may be dance with the Valve Setting Procedure tripped, as indicated by the flow of
O

affected by this action. section. water into the system.


The owner is responsible for the inspec- Step 4. Close the system’s Main
tion, testing, and maintenance of their NOTICE Control Valve.
fire protection system and devices in For fire protection systems subject to Step 5. Close the Diaphragm Chamber
compliance with this document, as well an emergency impairment caused by Supply Control Valve.
as with the applicable standards of the an interrupted water supply condition,
NATIONAL FIRE PROTECTION ASSO- it is recommended that consideration Step 6. Reset the DV-5 Deluge Valve in
CIATION (e.g., NFPA 25), in addition to be given to installing a low water supply accordance with the Valve Setting Pro-
the standards of any other authorities pressure switch with the appropriate cedure provided in TFP1310, TFP1315,
having jurisdiction. Contact the install- alarm/indications to monitor the water TFP1320, TFP1410, TFP1415, or
ing contractor or product manufacturer supply pressure. TFP1420, as applicable.
with any questions. Internal Valve Inspection
Automatic sprinkler systems should Once every five years during the
be inspected, tested, and main- an­n ual operational test procedure
tained by a qualified Inspection and prior to the DV-5 Valve being
Service in accordance with local reset, the interior of the DV-5 Valve
requirements and/or national code. must be cleaned and inspected for
When the system is using either a wear and damage. Damaged or worn
seawater of brackish water sup­ p ly, parts must be replaced. (Replacement
in­ternal and external inspection of the of the Diaphragm every ten years is
DV-5 Valve and Trim is essential. Parts recommended.)
showing any signs of corrosion must
be replaced to ensure the integ­rity of
the system.
TFP1305
Page 7 of 8

oriented; otherwise, the DV-5 cannot ANSI Flange x


3.50 inch (88,9 mm)
Nominal Torque be properly set. Groove O.D. �������������������������������� 52-477-1-412
Valve Sizes lb-ft Under-tightening the Diaphragm Cover 4 Inch G x G
Inches (N·m) Bolts can result in internal and external 4.50 inch (114,3 mm)
(DN)
Groove O.D. x 4.50
leakage. inch (114,3 mm)
1-1/2 22
Groove O.D. �������������������������������� 52-477-1-913
(DN40) (29,82) The V-Ring is attached to the Dia-
phragm at the factory. If, during an 4 Inch F x F
2 29 ANSI Flange x
(DN50) (39,32) internal valve inspection, the V-Ring ANSI Flange �������������������������������� 52-477-1-013
is discovered to be detached from the 4 Inch F x G
3 54 Diaphragm, be advised that the V-Ring ANSI Flange x
(DN80) (73,21) is a required valve component and that 4.50 inch (114,3 mm)
detachment will not affect normal valve Groove O.D. ������������������������������� 52-477-4-613
4 65 6 Inch G x G
(DN100) (88,13) operation or performance. Should the 6.62 inch (168,3 mm)
V-Ring become detached, reinstall Groove O.D. x 6.62
6 72 it between the Diaphragm and Dia- inch (168,3 mm)
(DN150) (97,62)
phragm Cover concentrically as shown Groove O.D ���������������������������������� 52-477-1-915
8 87 in Figure 1. 6 Inch F x F
(DN200) (117,96) ANSI Flange x
NOTE: Do not apply adhesives, lubri- ANSI Flange �������������������������������� 52-477-1-015
TABLE B cants, or other substances to the Dia- 6 Inch F x G
DIAPHRAGM COVER BOLTS phragm, V-Ring, or Valve Body. ANSI Flange x
6.62 inch (168,3 mm)
MAXIMUM TORQUE
Limited
Groove O.D. ������������������������������� 52-477-4-615

TE
8 Inch G x G
8.62 inch (219,1 mm)
When reinstalling the Diaphragm Cover,
complete the following steps to assure Warranty Groove O.D. x 8.62
inch (219,1 mm)
the Diaphragm Cover Fasteners (Hex Groove O.D ���������������������������������� 52-477-1-916
For warranty terms and conditions, visit
Bolts) are uniformly and securely 8 Inch F x F
www.tyco-fire.com. ANSI Flange x
tightened.
ANSI Flange �������������������������������� 52-477-1-016
LE
Step 1. Align Diaphragm and Dia-
phragm Cover in proper orientation Ordering 8 Inch F x G
ANSI Flange x
with valve body (Ref. Figure 1) and hold
in place Procedure 8.62 inch (219,1 mm)
Groove O.D. �������������������������������� 52-477-1-416

Step 2. Assemble Flat Washers onto Replacement Valve Parts


NOTICE Specify: (description) for use with
O
Hex Bolts
Refer to Table A for Flange Drilling (specify) size DV-5 Deluge Valve, P/N
Step 3. Apply LOCTITE No. 242 (or Specifications. (see Figure 1)
equivalent) to Hex Bolt threads
Part Numbers for factory pre-trimmed See Page 8 for Other DV-5 Deluge
BS

Step 4. Insert Hex Bolts through Dia- DV-5 Valves are provided in the Price Valves
phragm Cover and Diaphragm, hand- Book.
tighten into valve body
Step 5. Using crossdraw sequence to Standard DV-5 Deluge Valve
assure uniformity, wrench-tighten Hex (American Standard Flange
Bolts to appropriate torque values (Ref. Drilling, Threaded Ports, and
Table B) Groove Outside Diameter, as
O

Step 6. Inspect to assure all Hex Bolts applicable)


are securely tightened Specify: (specify size inch) DV­5 Deluge
Valve with (specify end con­nections),
P/N (specify):
NOTICE
1-1/2 Inch G x G
If the water supply contains chemicals 1.90 inch (48,3 mm)
which tend to attack a Nylon fabric Groove O.D. x 1.90
reinforced, natural rubber or the five inch (48,3 mm)
Groove O.D. �������������������������������� 52-477-1-919
year inspection indicates a build-up
1-1/2 Inch T x T
of debris within the valve that could NPT x NPT ����������������������������������52-477-1-069
affect its proper operation, then the 2 Inch G x G
frequency of the internal valve inspec- 2.37 inch (60,3 mm)
tion procedure must be appropriately Groove O.D. x 2.37
increased. inch (60,3 mm)
Groove O.D. �������������������������������� 52-477-1-910
If the system has a seawater or brack- 2 Inch T x T
ish water supply, then the frequency of NPT x NPT ����������������������������������52-477-1-060
the internal valve inspection procedure 3 Inch G x G
must be appropriately increased. (An 3.50 inch (88,9 mm)
Groove O.D. x 3.50
annual internal valve inspection for a inch (88,9 mm)
system having a seawater or brackish Groove O.D. �������������������������������� 52-477-1-912
water supply is recommended.) 3 Inch F x F
ANSI Flange x
With reference to Figure 1, make ANSI Flange �������������������������������� 52-477-1-012
certain that the Diaphragm is correctly 3 Inch F xG
TFP1305
Page 8 of 8

Other DV-5 Deluge Valves JIS Flange x Other 8 Inch Valves with ISO Ports
4.50 inch (114,3 mm) ISO (PN10) Flange x
NOTICE Groove O.D. ��������������������������������52-477-4-813 ISO (PN10) Flange �����������������������52-477-1-116
Other 4 Inch Valves with ISO Ports ISO (PN16) Flange x
Other DV-5 Deluge Valves are valves ISO Flange x ISO (PN16) Flange ���������������������� 52-477-1-126
ordered with any combination of flange, ISO Flange ���������������������������������� 52-477-4-113 ISO (PN10) Flange x
threaded port, or groove out­side diam- ISO Flange x 8.62 inch (219,1 mm)
eter not offered under “Standard DV-5 4.50 inch (114,3 mm) Groove O.D. �������������������������������� 52-477-1-216
Groove O.D. ��������������������������������52-477-4-213
Deluge Valve” offer­ings. ISO (PN16) Flange x
4.50 inch (114,3 mm) 8.62 inch (219,1 mm)
Valves with NPT threaded ports are Groove O.D x Groove O.D. �������������������������������� 52-477-1-226
intended for use with the “Standard 4.50 inch (114,3 mm) 8.62 inch (219,1 mm)
Groove O.D. ��������������������������������52-477-1-923 Groove O.D. x
DV-5 Valve Trim” offered and detailed
Other 6 Inch Valves with NPT Ports 8.62 inch (219,1 mm)
in Technical Data Sheets TFP1310, ANSI Flange x Groove O.D. ��������������������������������52-477-1-926
TFP1315, TFP1320, TFP1410, TFP1415, 6.50 inch (165,1 mm)
TFP1420, TFP1460, and TFP1465. Groove O.D. ������������������������������� 52-477-4-225
Valves with ISO threaded ports are ISO Flange x
intended for use with special order trim 6.62 inch (168,3 mm)
Groove O.D. ������������������������������� 52-477-5-625
that is provided by local dis­tributors
ISO Flange x
to meet the specific needs of certain 6.50 inch (165,1 mm)
localities. Please contact your local dis- Groove O.D. ��������������������������������52-477-5-215
tributor regarding valves and valve trim ISO Flange x
for specific localities. ISO Flange ���������������������������������� 52-477-5-115
6.50 inch (165,1 mm)
Specify: (specify size) DV-5 Deluge Groove O.D x

TE
Valve with (specify) connec­tions with 6.50 inch (165,1 mm)
(specify NPT or ISO) threaded ports, Groove O.D. ��������������������������������52-477-1-935
P/N (specify): AS Flange x
AS Flange ������������������������������������52-477-4-315
Part Numbers for Other DV-5 AS Flange x
6.62 inch (168,3 mm)
Deluge Valves Groove O.D. ��������������������������������52-477-4-415
Other 1-1/2 Inch Valves with ISO Ports
ISO Thread x AS Flange x
LE
ISO Thread ���������������������������������� 52-477-1-169 6.50 inch (165,1 mm)
Groove O.D. ��������������������������������52-477-5-415
Other 2 Inch Valves with ISO Ports
ISO Thread x JIS Flange x
ISO Thread ���������������������������������� 52-477-1-160 JIS Flange ������������������������������������52-477-4-715
Other 3 Inch Valves with NPT Ports JIS Flange x
6.62 inch (168,3 mm)
O
ISO Flange x
3.50 inch (88,9 mm) Groove O.D. ��������������������������������52-477-4-815
Groove O.D. �������������������������������� 52-477-1-252 JIS Flange x
ISO Flange x 6.50 inch (165,1 mm)
ISO Flange ���������������������������������� 52-477-1-132 Groove O.D. ��������������������������������52-477-5-815
BS

AS Flange x Other 6 Inch Valves with ISO Ports


AS Flange ������������������������������������ 52-477-1-512 ISO Flange x
ISO Flange ���������������������������������� 52-477-4-115
AS Flange x
3.50 inch (88,9 mm) ISO Flange x
Groove O.D. �������������������������������� 52-477-1-612 6.62 inch (168,3 mm)
Groove O.D. ������������������������������� 52-477-4-625
JIS Flange x
JIS Flange ������������������������������������ 52-477-1-712 ISO Flange x
6.50 inch (165,1 mm)
O

JIS Flange x Groove O.D. ��������������������������������52-477-4-215


3.50 inch (88,9 mm)
Groove O.D. �������������������������������� 52-477-1-812 6.62 inch (168,3 mm)
Groove O.D. x
Other 3 Inch Valves with ISO Ports 6.62 inch (168,3 mm)
ISO Flange x Groove O.D. ��������������������������������52-477-1-925
ISO Flange �����������������������������������52-477-1-112
6.50 inch (165,1 mm)
ISO Flange x Groove O.D. x
3.50 inch (88,9 mm) 6.50 inch (165,1 mm)
Groove O.D ���������������������������������� 52-477-1-212 Groove O.D. ��������������������������������52-477-1-945
3.50 inch (88,9 mm) Other 8 Inch Valves with NPT Ports
Groove O.D x ISO (PN10) Flange x
3.50 inch (88,9 mm) 8.62 inch (219,1 mm)
Groove O.D. ��������������������������������52-477-1-922 Groove O.D. �������������������������������� 52-477-1-256
Other 4 Inch Valves with NPT Ports ISO (PN10) Flange x
ISO Flange x ISO (PN10) Flange ���������������������� 52-477-1-136
4.50 inch (114,3 mm)
Groove O.D. ��������������������������������52-477-5-213 ISO (PN16) Flange x
ISO (PN16) Flange ���������������������� 52-477-1-146
ISO Flange x
ISO Flange ���������������������������������� 52-477-5-113 AS Flange x
AS Flange ������������������������������������ 52-477-1-516
AS Flange x
AS Flange ������������������������������������52-477-4-313 AS Flange x
8.62 inch (219,1 mm)
AS Flange x Groove O.D. �������������������������������� 52-477-1-616
4.50 inch (114,3 mm)
Groove O.D. ��������������������������������52-477-4-413 JIS Flange x
JIS Flange ������������������������������������ 52-477-1-716
JIS Flange x
JIS Flange ������������������������������������52-477-4-713 JIS Flange x
8.62 inch (219,1 mm)
Groove O.D. �������������������������������� 52-477-1-816

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700