Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Email: techserv@tycofp.com

Model AV-1-300 Alarm Check Valve, 300 psi (20,7 bar)


2-1/2, 4, 6, & 8 Inch (DN65, DN100, DN150 & DN200)
Vertical or Horizontal* Installation
General
Description
The TYCO Model AV-1-300 Alarm
Check Valves are divided seat ring,
rubber-faced clapper, waterflow alarm
check valves that are intended for
use in wet pipe (automatic sprinkler)
fire protection systems. They may be
installed vertically or horizontally*,
and they are designed to automati-
cally actuate electric and/or hydraulic
alarms when there is a steady flow of
water into the system that is equivalent
to the discharge rate of one or more
sprinklers.
A separately ordered Model RC-1
Retard Chamber (TFP920) is required
for installations subject to variable
pressures. It is used to help prevent
false alarms associated with pressure
variations in public water supplies.
The AV-1-300 Alarm Check Valve Trim
includes pressure gauges to monitor
system pressure conditions, a by-pass
check valve, a main drain valve, and
an alarm test valve. The bypass check
valve reduces the possibility of false
alarms by permitting slow as well as
small transient increases in water
supply pressure to be passed through
to the system without opening the
waterway clapper.
Nominal Groove x Groove Flange x Groove Flange x Flange
Valve Size
NOTICE
The TYCO Model AV-1-300 Alarm
2-1/2 Inch 22 lbs. 28 lbs.
Check Valves described herein must be (DN65) (10,0 Kg) (12,7 Kg) N/A
installed and maintained in compliance
with this document, as well as with the 4 Inch 38 lbs. 47 lbs. 57 lbs.
applicable standards of the National (DN100) (17,2 Kg) (21,3 Kg) (25,9 Kg)
Fire Protection Association, in addition
to the standards of any authorities 6 Inch 58 lbs. 70 lbs. 84 lbs.
having jurisdiction. Failure to do so may (DN150 (26,3 Kg) (31,8 Kg) (38,1 Kg)
impair the integrity of these devices.
8 Inch 102 lbs. 120 lbs. 149 lbs.
The owner is responsible for main- (DN200) (46,3 Kg) (54,4 Kg) (67,6 Kg)
taining their fire protection system and
devices in proper operating condition. TABLE A
The installing contractor or manufac- — AVAILABLE END CONNECTIONS —
turer should be contacted relative to
any questions. * 4, 6, and 8 Inch (DN100, DN150, and DN200) Valve Sizes

Page 1 of 22 APRIL 2011 TFP910


TFP910
Page 2 of 22

VALVE PARTS VALVE PARTS REPLACEMENT PARTS


NO. DESCRIPTION QTY. REF. NO. DESCRIPTION QTY. REF. NO. DESCRIPTION P/N
1 Valve Body . . . . . . . 1 NR 12 Handhole Cover (a) Repair Parts Kit,
2 Handhole Cover . . . 1 NR Hex Bolt, Includes 3 & 6
3 Handhole Cover 2-1/2 Inch Valve, 2-1/2 Inch Valve . . . . . . 92-200-1-216
Gasket . . . . . . . . . . 1 See (a) 1/2-13 UNC-2A 4 Inch Valve . . . . . . . . . 92-200-1-416
4 Seat Ring . . . . . . . . 1 NR x 1-1/4" Long . . . . . 4 CH 6 Inch Valve . . . . . . . . . 92-200-1-620
5 Clapper . . . . . . . . . . 1 See (b) 4 Inch Valve, 8 Inch Valve . . . . . . . . . 92-200-1-816
6 Clapper Facing . . . . 1 See (a) or (b) 1/2-13 UNC-2A (b) Clapper Assembly,
7 Clapper Washer . . . 1 See (b) x 1-3/4" Long . . . . . 4 CH Includes 5-9, 11
8 Lock Nut, 6 Inch Valve, 2-1/2 Inch Valve . . . . . . 92-200-1-218
2-1/2 Inch Valve . . . 1 See (b) 1/2-13 UNC-2A Includes 5-11
Self-Locking Hex x 1-3/4" Long . . . . . 6 CH 4 Inch Valve . . . . . . . . . 92-200-1-423
Cap Screw, 4, 6, & 8 8 Inch Valve, 6 Inch Valve . . . . . . . . . 92-200-1-623
Inch Valves . . . . . . . 1 See (b) 3/4-10 UNC-2A 8 Inch Valve . . . . . . . . . 92-200-1-823
9 Clapper Hinge Pin. . 1 See (b) x 2" Long. . . . . . . . . 6 CH
10 Clapper Hinge 13 Clapper Hinge Pin NOTES:
Pin Bushing, Square Head Pipe 1. F x F valve shown for reference;
2-1/2 Inch Valve . . . 2 NR Plug, 3/8" NPT, components for G x G and F x G
4, 6, & 8 Inch 4, 6, & 8 Inch valves are shared.
Valves . . . . . . . . . . . 4 NR Valves only . . . . . . . 1 CH 2. NR: Not Replaceable
11 Clapper Spring . . . . 1 See (b)
3. CH: Common Hardware

1
11
11

5
5

10
6
10
7
8 9 13
CLAPPER
ASSEMBLY 6 10
2-1/2 INCH 7 4
VALVE
8
CLAPPER
ASSEMBLY 2
3
4, 6, & 8 INCH
VALVES 12

The 2-1/2 Inch (DN65) Valves with NPT threaded ports have a 1-1/4 inch main drain connection. The 2-1/2 Inch (DN65) Valves with
ISO threaded ports have a DN40 main drain connection.

The 4, 6, and 8 Inch (DN100. DN150, and DN200) Valves with NPT threaded ports have a 2 inch main drain connection. The 4, 6,
and 8 Inch (DN100. DN150, and DN200) Valves with ISO threaded ports have a DN50 inch main drain connection.

FIGURE 1
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
— ASSEMBLY —
TFP910
Page 3 of 22

FLOW RATE IN LITRES PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
400 600 1000 2000 3000 5000 7000 10000 15000
4.0
IN POUNDS PER SQUARE INCH (PSI)

NOMINAL PRESSURE DROP IN BAR


3.0 0,20
NOMINAL PRESSURE DROP

(1 PSI = 0,06895 BAR)


5)

)
6

100

150
2.0 DN

(DN

(DN
H(
INC

0)
CH

CH

20
0,10

N
4 IN

6 IN
/2

(D
0,09
2-1

H
0,08

NC
0,07

8I
1.0
0.9 0,06
0.8
0.7 0,05
100 200 300 400 500 700 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)

The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe
with C=120, is as follows
14 feet of 2-1/2 inch Sch. 40 pipe for the 2-1/2 inch AV-1-300 Valve calculated on a typical flow rate of 250 GPM.
23 feet of 4 inch Sch. 40 pipe for the 4 inch AV-1-300 Valve calculated on a typical flow rate of 600 GPM.
24 feet of 6 inch Sch. 40 pipe for the 6 inch AV-1-300 Valve calculated on a typical flow rate of 1500 GPM.
23 feet of 8 inch Sch. 30 pipe for the 8 inch AV-1-300 Valve calculated on a typical flow rate of 2500 GPM.

GRAPH A
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
— NOMINAL PRESSURE LOSS VERSUS FLOW —

Flange Drilling Specification


Nominal Dimensions in Inches and (mm)
Nominal
Valve ANSI B16.1 ISO 2084 ISO 2084 JIS B 2210 AS 2129
Size (Class 125) 1 (PN10) 2 (PN16) 3 (10K) (Table E)
Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty.
A B N A B N A B N A B N A B N
2-1/2 Inch 5.50 0.75 5.71 0.71 5.51 0.75 5.00 0.71
4 4 4 4
(DN65) (139,7) (19,0) (145,0) (18,0) (140,0) (19,0) (127,0) (18,0)
USE
4 Inch 7.50 0.75 7.09 0.71 6.89 0.75 7.00 0.71
8 ISO 2084 8 8 8
(DN100) (190,5) (19,0) (180,0) (18,0) (175,0) (19,0) (178,0) (18,0)
(PN16)
6 Inch 9.50 0.88 9.45 0.87 9.45 0.91 9.25 0.87
8 8 8 8
(DN150) (241,3) (22,2) (240,0) (22,0) (240,0) (23,0) (235,0) (22,0)
8 Inch 11.75 0.88 11.61 0.87 11.61 0.87 11.42 0.91 11.50 0.87
8 8 12 12 8
(DN200) (298,5) (22,2) (295,0) (22,0) (295,0) (22,0) (290,0) (23,0) (292,0) (22,0)
1
Dim. A Same drilling as for B16.5 (Class 150) and B16.42 (Class 250).
Bolt Circle 2
Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10).
Diameter 3
Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16).
Dim. B
Bolt Hole
Diameter

Qty. N
Number of
Bolt Holes

TABLE B
— FLANGE DRILLING SPECIFICATIONS —
TFP910
Page 4 of 22

Technical WATERFLOW

Data
PRESSURE
ALARM SWITCH
ONCE RETARD
CHAMBER OVERFLOWS,
Approvals WATERFLOW PRESSURE
UL and C-UL Listed, ALARM SWITCH AND
FM Approved RETARD
WATER MOTOR
ALARM ACTUATE
CHAMBER UPON SPRINKLER
Working Water Pressure Range WATERFLOW FLOW, WATERWAY
20 to 300 psi (1,4 to 20,7 bar) TO WATER CLAPPER OPENS
MOTOR ALARM WATERFLOW
Friction Loss 7/32"
TO SYSTEM
Refer to Graph A. (5,6 mm) SYSTEM
ORIFICE PRESSURE
Physical Characteristics RESTRICTION
INLET GAUGE
The body is ductile iron, the hand-hole ASSEMBLY
cover is ductile iron, and the seat ring
is bronze. The clapper for the 2-1/2 1/8"
(3,2 mm)
inch (DN65) valve size is stainless steel. ORIFICE SUPPLY
The clapper for the larger valve sizes OUTLET PRESSURE
is ductile iron. All valve sizes utilize an GAUGE
EPDM clapper facing.
WHEN FLOW THROUGH
Flanged connections are available RESTRICTION ASSEMBLY
drilled per ANSI, ISO, AS, and JIS INLET EXCEEDS OUTLET, MAIN ALARM
specifications as detailed in Table A. RETARD CHAMBER DRAIN CHECK
BEGINS TO FILL VALVE WATERFLOW VALVE
Threaded port connections for the
THROUGH SEAT
AV-1-300 Valves are available NPT RING GROOVE AND
threaded or threaded per ISO 7/1 as ALARM PORT
detailed in the Ordering Procedure
section. Valves with NPT threaded FIGURE 2
ports will readily accept the trim 2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200)
arrangements detailed in Figures 4 MODEL AV-1-300 ALARM CHECK VALVE
through 6. — OPERATION —

Operation
When the fire protection system is SCREEN
initially pressurized, water flows into
the system until the water supply and
system pressure become equalized, INLET RESTRICTION
and the torsion Spring closes the WITH 0.219" (5.6 mm)
Waterway Clapper in the Alarm Check ORIFICE
Valve. Once the pressures stabilize,
the Alarm Check Valve is in service
and the centrally located groove in the
DRAIN RESTRICTION
Seat Ring is sealed. Consequently, with
WITH 0.125" (3.2 mm)
the Alarm Check Valve set for service, ORIFICE
there is no flow through the alarm port
to the alarm devices (that is, water
motor alarm and/or pressure alarm FIGURE 3
switch). RESTRICTION ASSEMBLY
(Provided with Alarm Check Valve Trim)
When there is a steady flow of water
into the sprinkler system due to a
sprinkler operation, the Waterway
Clapper opens as shown in Figure 2. to be actuated as long as the Waterway A transient surge in supply pressure
Water is then permitted to flow into Clapper remains open. Water in the that is sufficient only to open the
the centrally located groove in the alarm lines will automatically drain out Waterway Clapper momentarily will not
Seat Ring and out through the alarm through the 1/8 inch (3,2 mm) Drain cause a false alarm, and a portion of
port towards the Restriction Assembly Orifice in the Restriction Assembly the increase in pressure will be trapped
(Figure 3). When the flow through the (Figure 3) when the Waterway Clapper within the system, thus reducing the
Inlet Restriction of the Restriction closes (due to a stop in the flow of possibility of another opening. Any
Assembly exceeds the flow through water into the sprinkler system). water in the alarm line is automatically
the Outlet Restriction, the Retard drained, further reducing the possi-
Chamber (where provided for systems For variable pressure systems, slow
bility of a false alarm due to a succes-
with variable pressure), begins to fill. as well as small transient increases in
sive transient surge in supply pressure.
water supply pressure may continue to
Subsequently, the Water Motor alarm build up in the system (via the Bypass
and/or the pressure alarm switch will Check Valve) without opening the
be actuated. The alarms will continue Waterway Clapper.
TFP910
Page 5 of 22

Design Installation 6. The check valve in the exter-


nally mounted bypass around
Criteria NOTICE
the Waterway Clapper must be
installed with its arrow pointed up,
In planning installation of the TYCO Proper operation of the TYCO Model and the drain check valve must be
Model AV-1-300 Alarm Check Valves, AV-1-300 Alarm Check Valves depends installed with its arrow pointing
consideration must be given to the upon the trim described in this data towards the drain.
disposal of the large quantities of water sheet installed in accordance with the 7. It is recommended that a vent
that may be associated with draining following instructions. Failure to follow
the system or performing a flow test. connection (which may also be
the appropriate trim installation instruc- used as an end-of-line Inspec-
Valves installed in the vertical position tions may prevent the device from tor’s Test Connection), be piped
must have the flow going up. Valves functioning properly as well as void from a cross main or branch line
installed in the horizontal position must listings/approvals and the manufactur- at the point most remote from the
be positioned so that the drain connec- er’s warranties. alarm valve. The vent line should
tion points down. The Alarm Check Valves must be be connected to the top of a cross
The sprinkler system designer must installed in readily visible and acces- main or to the end of a branch line
be aware that the configuration of the sible locations. and be located at the highest level
piping network and its tendency to trap of a multi-level installation.
It is recommended that provision be
pockets of air (such as in the case of a made for viewing the alarm line drain The vent connection can be used
peaked-roof gridded system) can affect to bleed-off excessive air from the
water by locating the main drain outlet
the performance of the alarm system. system, and therefore, minimize
Although a slight amount of trapped in a readily visible area.
the possibility of a false alarm
air is desirable to prevent significant Wet pipe fire protection systems must due to a transient surge in supply
pressure increases due to thermally be maintained at a minimum tempera- pressure. The contraction/expan-
induced expansion of the water, a large ture of 40°F/4°C. sion associated with an exces-
quantity of trapped air in a system may
1. Trim the Alarm Check Valve in sive amount of trapped air could
result in the possibility of an intermit-
tent alarm. accordance with Figure 4, 5, or 6, also cause the Waterway Clapper
as applicable. Apply pipe-thread to cycle open and shut during
The possibility of an intermittent alarm sealant sparingly to male threads an inspector’s test or during a
condition is a consequence of the fact only. discharge by a single sprinkler.
that the flow out of the system through
the test valve or a single sprinkler is 2. The Alarm Vent Trim illustrated
very small relative to the flow that can in Figure 8 must be installed if
be passed through the valve. This a water motor alarm is not to be
difference increases with valve size. used.
If the system were free of trapped 3. Plug unused alarm connections.
air, flow in would equal flow out and
the Waterway Clapper would always 4. Suitable provision must be made
stabilize at some open position (as for disposal of alarm line and
needed to accommodate the required system drainage water. Drainage
flow). With trapped air in the system, water must be directed so that it
however, the Waterway Clapper first will not cause damage or result in
opens wider since the system initially dangerous conditions.
demands greater flow until the air
5. The alarm line drain must be
pockets are compressed (back to
nearly the supply pressure), and then arranged so that there will be no
it will tend to return closer to the Seat danger of freezing.
Ring. If the volume of the air pockets
is excessive, flow into the system can
be momentarily reduced to nearly zero
(once the air pockets are compressed)
and the Waterway Clapper may close,
causing flow to the alarms to be
shutoff.
After the Waterway Clapper has
closed, sufficient water must flow out
of the system before the Waterway
Clapper will again open. A repetition
of the above described condition is
termed an intermittent alarm.
Using a vent (which can also serve
as an end-of-line Inspector’s Test
Connection) piped from the top of a
cross main or end of a branch line at
the point most remote from the alarm
valve, and filling the system slowly in
accordance with the steps described
in the Setting Procedure section, can
prevent an excessive amount of air
from being trapped.
TFP910
Page 6 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 17 1/2" x 1/4" x 1/2" Tee. . . . 2 CH
Water Pressure Gauge . . 2 92-343-1-005 18 1/2" x 1/2" x 3/4" Tee. . . . 1 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 19 1-1/4" x 1-1/4" x 1/2" Tee 1 CH
3 1/2" Swing Check Valve . 2 46-049-1-004 20 1/4" x 1" Nipple . . . . . . . . 2 CH
4 1/2" Globe Valve . . . . . . . 1 46-047-1-004 21 1/4" x 2-1/2" Nipple . . . . . 1 CH
5 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 22 1/2" x 1-1/2" Nipple . . . . . 7 CH
6 Restriction Assembly . . . . 1 92-210-2-005 23 1/2" x 2" Nipple . . . . . . . . 2 CH
7 1-1/4" Angle Valve . . . . . . 1 46-048-1-007 24 1/2" x 2-1/2" Nipple . . . . . 1 CH
8 External By-Pass Tube . . 1 92-304-1-017 25 1/2" x 3" Nipple . . . . . . . . 1 CH
9 Alarm Test Tube . . . . . . . 1 92-304-1-047 26 1/2" x 4" Nipple . . . . . . . . 1 CH
10 1/2" NPT x 1/2" Tube 27 1/2" x 6" Nipple . . . . . . . . 1 CH
Connector . . . . . . . . . . . . 2 CH 28 1-1/4" x 2-1/2" Nipple. . . . 1 CH
11 1/2" NPT x 5/8" Tube 29 1-1/4" x 3-1/2" Nipple. . . . 1 CH
Connector . . . . . . . . . . . . 2 CH
12 1/4" Plug . . . . . . . . . . . . . 2 CH
13 1/2" Union . . . . . . . . . . . . 1 CH NOTES:
14 1/4" 90° Elbow . . . . . . . . . 1 CH 1. All Fittings and Nipples are galvanized
15 1/2" 90° Elbow . . . . . . . . . 1 CH (Standard Order).
16 1/2" Tee . . . . . . . . . . . . . . 2 CH 2. CH: Common Hardware.

1/2 INCH NPT


CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
3/4 INCH NPT
LOCATION CONNECTION FOR
WATER MOTOR EXTERNAL
FOR OPTIONAL BY-PASS
ELECTRICALLY ALARM
TUBE ALARM
SUPERVISED
8 TEST TUBE
N.O. ALARM 1/2 INCH NPT ALARM 9
11
CONTROL CONNECTION TEST VALVE 3 10
VALVE FOR WATERFLOW (NORMALLY 23 1
SYSTEM
PRESSURE ALARM CLOSED) 11
PRESSURE
SWITCH
MODEL RC-1 20 GAUGE
RETARD 3/4 INCH NPT 17 12
CHAMBER CONNECTION FOR 1
18 25 SUPPLY
WATER MOTOR 16 2
ALARM 10 22 PRESSURE
ORDERED 4 GAUGE
SEPARATELY LOCATION 23 14 12
(FOR VARIABLE FOR OPTIONAL 20
5 16 17 21
PRESSURE ELECTRICALLY 22 27 24 2
SYSTEMS) 26
SUPERVISED 22
N.O. ALARM
CONTROL 6 MODEL AV-1
VALVE ALARM VALVE,
MAIN 2-1/2 INCH (DN65)
DRAIN VALVE 28 GROOVE x GROOVE
22 (NORMALLY SHOWN
RESTRICTION 7
CLOSED)
ASSEMBLY, 29
SEE FIGURE 3
19

1-1/4 INCH NPT


15 22 13 22 3 22 CONNECTION
TO DRAIN

FIGURE 4 — PART 1 OF 3
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER
—FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-050)—
TFP910
Page 7 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 22 1/2" x 3" Nipple . . . . . . . . 2 CH
Water Pressure Gauge . . 2 92-343-1-005 23 1/2" x 3-1/2" Nipple . . . . . 1 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 24 1/2" x 5" Nipple . . . . . . . . 1 CH
3 1/2" Swing Check Valve . 2 46-049-1-004 25 1/2" x 5-1/2" Nipple . . . . . 1 CH
4 1/2" Globe Valve . . . . . . . 1 46-047-1-004 26 1/2" x 6-1/2" Nipple . . . . . 1 CH
5 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 27 Select Nipple per Table . . 2 CH
6 Restriction Assembly . . . . 1 92-210-2-005 28 Select Nipple per Table . . 2 CH
7 2" Angle Valve . . . . . . . . . 1 46-048-1-009 29 2" x 3" Nipple. . . . . . . . . . 2 CH
8 1/4" Plug . . . . . . . . . . . . . 2 CH
9 1/2" x 1/4" Reducing
Bushing . . . . . . . . . . . . . . 1 CH Select Appropriate Nipple Sizes
10 1/2" Union . . . . . . . . . . . . 3 CH Nipple per AV-1 Alarm Check Valve Size
11 1/2" 90° Elbow . . . . . . . . . 4 CH Number
4 Inch (DN100) 6 Inch (DN150)
12 1/2" 45° Elbow . . . . . . . . . 1 CH
13 1/2" x 1/4" x 1/2" Tee. . . . 1 CH 27 1/2" x 1-1/2" 1/2" x 2-1/2"
14 1/2" x 1/2" x 3/4" Tee. . . . 1 CH 28 1/2" x 3-1/2" 1/2" x 4-1/2"
15 1/2" Tee . . . . . . . . . . . . . . 1 CH
16 2" x 2" x 1/2" Tee . . . . . . . 1 CH
17 1/4" x Close Nipple . . . . . 1 CH NOTES:
18 1/4" x 4" Nipple . . . . . . . . 1 CH 1. Install subassemblies in alphabetical order.
19 1/2" x Close Nipple . . . . . 4 CH 2. All Fittings and Nipples are galvanized
20 1/2" x 1-1/2" Nipple . . . . . 5 CH (Standard Order).
21 1/2" x 2" Nipple . . . . . . . . 2 CH 3. CH: Common Hardware.

1/2 INCH NPT 3/4 INCH NPT


CONNECTION CONNECTION FOR
FOR WATERFLOW WATER MOTOR
PRESSURE ALARM ALARM
SWITCH

LOCATION 1/2 INCH NPT 1/2" x 1-1/2" ALARM


FOR OPTIONAL CONNECTION (4 INCH VALVE) TEST VALVE
ELECTRICALLY FOR WATERFLOW or (NORMALLY
1/2" x 2-1/2" 1/2" x 3-1/2" 1 SYSTEM
SUPERVISED PRESSURE ALARM CLOSED) (4 INCH VALVE)
(6 INCH VALVE) PRESSURE
N.O. ALARM SWITCH or
1/2" x 4-1/2" GAUGE
CONTROL 11
3/4 INCH NPT (6 INCH VALVE) 2 8
VALVE 21
CONNECTION FOR 9
4
WATER MOTOR
ALARM
27
23 F 18 E
MODEL RC-1
RETARD 10 1 SUPPLY
14 15
I J 28 PRESSURE
CHAMBER 26
25 GAUGE
5
ORDERED
19 G 2 8

SEPARATELY LOCATION 22
20
(FOR VARIABLE FOR OPTIONAL H 11 17 D
PRESSURE ELECTRICALLY 12 13
SYSTEMS) 20
SUPERVISED 3 20
N.O. ALARM
22
A 10
CONTROL 24
20 21
VALVE L B
6 11
7
RESTRICTION 19 29 MODEL AV-1
ASSEMBLY,
C MAIN ALARM VALVE,
M DRAIN VALVE 6 INCH (DN150)
SEE FIGURE 3
(NORMALLY FLANGE x FLANGE
10 N 29 CLOSED) SHOWN
16
11 2 INCH NPT
19 19 3 20 K CONNECTION
TO DRAIN

FIGURE 4 — PART 2 OF 3
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER — SEMI-PREASSEMBLED
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-951)—
TFP910
Page 8 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 22 1/2" x 2" Nipple . . . . . . . . 1 CH
Water Pressure Gauge . . 2 92-343-1-005 23 1/2" x 3" Nipple . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 24 1/2" x 3-1/2" Nipple . . . . . 2 CH
3 1/2" Swing Check Valve . 1 46-049-1-004 25 1/2" x 4-1/2" Nipple . . . . . 2 CH
4 3/4" Swing Check Valve . 1 46-049-1-005 26 1/2" x 6-1/2" Nipple . . . . . 1 CH
5 1/2" Globe Valve . . . . . . . 1 46-047-1-004 27 3/4" x Close Nipple . . . . . 2 CH
6 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 28 3/4" x 1-1/2" Nipple . . . . . 1 CH
7 Restriction Assembly . . . . 1 92-210-2-005 29 3/4" x 2-1/2" Nipple . . . . . 1 CH
8 2" Angle Valve . . . . . . . . . 1 46-048-1-009 30 3/4" x 3" Nipple . . . . . . . . 1 CH
9 1/4" Plug . . . . . . . . . . . . . 2 CH 31 3/4" x 4-1/2" Nipple . . . . . 1 CH
10 1/2" Union . . . . . . . . . . . . 2 CH 32 2" x 3" Nipple. . . . . . . . . . 1 CH
11 3/4" Union . . . . . . . . . . . . 1 CH 33 2" x 3-1/2" Nipple. . . . . . . 1 CH
12 1/2" 90° Elbow . . . . . . . . . 2 CH
13 1/2" 45° Elbow . . . . . . . . . 1 CH
14 1/2" Tee . . . . . . . . . . . . . . 1 CH
15 1/2" x 1/2" x 3/4" Tee. . . . 1 CH
16 3/4" x 1/4" x 3/4" Tee. . . . 2 CH
17 3/4" x 3/4" x 1/2" Tee. . . . 1 CH NOTES:
18 2" x 2" x 1/2" Tee . . . . . . . 1 CH 1. Install subassemblies in alphabetical order.
19 1/4" x 1-1/2" Nipple . . . . . 2 CH 2. All Fittings and Nipples are galvanized
20 1/2" x Close Nipple . . . . . 3 CH (Standard Order).
21 1/2" x 1-1/2" Nipple . . . . . 3 CH 3. CH: Common Hardware.

1/2 INCH NPT 3/4 INCH NPT


CONNECTION CONNECTION FOR
FOR WATERFLOW WATER MOTOR
PRESSURE ALARM ALARM
SWITCH

LOCATION 1/2 INCH NPT ALARM


FOR OPTIONAL CONNECTION SYSTEM
TEST VALVE
ELECTRICALLY FOR WATERFLOW (NORMALLY PRESSURE
SUPERVISED PRESSURE ALARM CLOSED) GAUGE
N.O. ALARM SWITCH
CONTROL
VALVE 3/4 INCH NPT 22
12 G B 19
16 9
CONNECTION FOR 1
WATER MOTOR F C
27
ALARM 24 11
MODEL RC-1 27 2
RETARD 10 5
15 14 25
CHAMBER 26 24 4
25 29 9
6 1
20 D 31
ORDERED
30 2
SEPARATELY LOCATION 19
(FOR VARIABLE FOR OPTIONAL E 16 SUPPLY
PRESSURE ELECTRICALLY 13 28 PRESSURE
SYSTEMS) SUPERVISED MAIN 17 GAUGE
N.O. ALARM DRAIN VALVE
23 (NORMALLY
CONTROL 21 CLOSED)
VALVE I
7
8
RESTRICTION 21 32
A MODEL AV-1
ASSEMBLY, ALARM VALVE,
SEE FIGURE 3 J 8 INCH (DN200)
FLANGE x GROOVE
10 K 33
SHOWN
18
12 2 INCH NPT
20 20 3 21 H CONNECTION
TO DRAIN

FIGURE 4 — PART 3 OF 3
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER — SEMI-PREASSEMBLED
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-952)—
TFP910
Page 9 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 18 1/4" 90° Elbow . . . . . . . . . 1 CH
Water Pressure Gauge . . 2 92-343-1-005 19 1/2" Tee . . . . . . . . . . . . . . 2 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 20 1/2" x 1/4" x 1/2" Tee. . . . 2 CH
3 1/2" Swing Check Valve . 1 46-049-1-004 21 1/2" x 1/2" x 3/4" Tee. . . . 1 CH
4 1/2" Globe Valve . . . . . . . 1 46-047-1-004 22 1-1/4" x 1-1/4" x 1/2" Tee 2 CH
5 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 23 1/4" x 1" Nipple . . . . . . . . 2 CH
6 Restriction Assembly . . . . 1 92-210-2-005 24 1/4" x 2-1/2" Nipple . . . . . 1 CH
7 1-1/4" Angle Valve . . . . . . 1 46-048-1-007 25 1/2" x 1-1/2" Nipple . . . . . 3 CH
8 External By-Pass Tube . . 1 92-304-1-017 26 1/2" x 2" Nipple . . . . . . . . 2 CH
9 Alarm Test Tube . . . . . . . 1 92-304-1-047 27 1/2" x 2-1/2" Nipple . . . . . 1 CH
10 1/2" NPT x 1/2" Tube 28 1/2" x 3" Nipple . . . . . . . . 1 CH
Connector . . . . . . . . . . . . 2 CH 29 1/2" x 4" Nipple . . . . . . . . 1 CH
11 1/2" NPT x 5/8" Tube 30 1/2" x 5" Nipple . . . . . . . . 1 CH
Connector . . . . . . . . . . . . 2 CH 31 1-1/4" x 2-1/2" Nipple. . . . 2 CH
12 Support Bar . . . . . . . . . . . 1 92-304-1-014 32 1-1/4" x 8-1/2" Nipple. . . . 1 CH
13 Jam Nut . . . . . . . . . . . . . . 1 92-640-1-037
14 PVC Nipple . . . . . . . . . . . 1 92-640-1-009 NOTES:
15 Support Bracket. . . . . . . . 1 92-343-1-006 1. All Fittings and Nipples are galvanized
16 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 (Standard Order).
1/2 INCH NPT 17 1/4" Plug . . . . . . . . . . . . . 2 CH
CONNECTION 2. CH: Common Hardware.
FOR WATERFLOW
PRESSURE ALARM
SWITCH
3/4 INCH NPT
LOCATION CONNECTION FOR
FOR OPTIONAL WATER MOTOR EXTERNAL
ELECTRICALLY ALARM BY-PASS
SUPERVISED TUBE ALARM
N.O. ALARM 1/2 INCH NPT 8 TEST TUBE
ALARM 11 9
CONTROL CONNECTION 3
TEST VALVE 10
VALVE FOR WATERFLOW 26 1
(NORMALLY
PRESSURE ALARM SYSTEM
CLOSED) 11
SWITCH PRESSURE
MODEL RC-1 23 GAUGE
RETARD 3/4 INCH NPT 20 17
CHAMBER CONNECTION FOR 1
21 WATER MOTOR 28 SUPPLY
19 2
ALARM 10 25 PRESSURE
ORDERED 4 GAUGE
SEPARATELY LOCATION 26 18 17
(FOR VARIABLE FOR OPTIONAL 23
5 19 24
PRESSURE ELECTRICALLY 25 20
SYSTEMS) 30 27 29 2
SUPERVISED 25 31
N.O. ALARM 7
CONTROL 6 13 MODEL AV-1
VALVE ALARM VALVE,
14 15
2-1/2 INCH (DN65)
GROOVE x GROOVE
RESTRICTION MAIN SHOWN
ASSEMBLY, SUPPORT DRAIN VALVE
16
SEE FIGURE 3 BRACKET (NORMALLY
CLOSED)
32
DRIP 31 12
FUNNEL
22 22

1-1/4 INCH NPT 1-1/4 INCH NPT


CONNECTION SUPPORT CONNECTION
TO DRAIN BAR TO DRAIN

FIGURE 5 — PART 1 OF 3
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER
—FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-053)—
TFP910
Page 10 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 22 1/2" x 1-1/2" Nipple . . . . . 4 CH
Water Pressure Gauge . . 2 92-343-1-005 23 1/2" x 2" Nipple . . . . . . . . 2 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 24 1/2" x 3" Nipple . . . . . . . . 1 CH
3 1/2" Swing Check Valve . 1 46-049-1-004 25 1/2" x 3-1/2" Nipple . . . . . 1 CH
4 1/2" Globe Valve . . . . . . . 1 46-047-1-004 26 1/2" x 5" Nipple . . . . . . . . 1 CH
5 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 27 1/2" x 5-1/2" Nipple . . . . . 1 CH
6 Restriction Assembly . . . . 1 92-210-2-005 28 1/2" x 6-1/2" Nipple . . . . . 1 CH
7 2" Angle Valve . . . . . . . . . 1 46-048-1-009 29 Select Nipple per Table . . 2 CH
8 Drip Funnel Connector . . 1 92-211-1-005 30 Select Nipple per Table . . 2 CH
9 Drip Funnel Bracket . . . . 1 92-211-1-003 31 2" x 3" Nipple. . . . . . . . . . 1 CH
10 Drip Funnel . . . . . . . . . . . 1 92-343-1-007
11 1/4" Plug . . . . . . . . . . . . . 2 CH Select Appropriate Nipple Sizes
12 1/2" x 1/4" Reducing Nipple per AV-1 Alarm Check Valve Size
Bushing . . . . . . . . . . . . . . 1 CH Number
4 Inch (DN100) 6 Inch (DN150)
13 1/2" Union . . . . . . . . . . . . 2 CH
14 1/2" 90° Elbow . . . . . . . . . 3 CH 29 1/2" x 1-1/2" 1/2" x 2-1/2"
15 1/2" 45° Elbow . . . . . . . . . 1 CH 30 1/2" x 3-1/2" 1/2" x 4-1/2"
16 1/2" x 1/4" x 1/2" Tee. . . . 1 CH
17 1/2" x 1/2" x 3/4" Tee. . . . 1 CH NOTES:
18 1/2" Tee . . . . . . . . . . . . . . 2 CH 1. Install subassemblies in alphabetical order.
19 1/4" x Close Nipple . . . . . 1 CH 2. All Fittings and Nipples are galvanized
20 1/4" x 4" Nipple . . . . . . . . 1 CH (Standard Order).
21 1/2" x Close Nipple . . . . . 3 CH 3. CH: Common Hardware.

1/2 INCH NPT 3/4 INCH NPT


CONNECTION CONNECTION FOR
FOR WATERFLOW WATER MOTOR
PRESSURE ALARM ALARM
SWITCH

LOCATION 1/2 INCH NPT 1/2" x 1-1/2" ALARM


FOR OPTIONAL CONNECTION (4 INCH VALVE) TEST VALVE
ELECTRICALLY FOR WATERFLOW or (NORMALLY
1/2" x 2-1/2" 1/2" x 3-1/2" 1 SYSTEM
SUPERVISED PRESSURE ALARM CLOSED) (4 INCH VALVE)
(6 INCH VALVE) PRESSURE
N.O. ALARM SWITCH or
1/2" x 4-1/2" GAUGE
CONTROL 14
3/4 INCH NPT (6 INCH VALVE) 2 11
VALVE 23
CONNECTION FOR 12
4
WATER MOTOR
ALARM
29
25 F 20 E
MODEL RC-1
RETARD 13 1 SUPPLY
17 18
I J 30 PRESSURE
CHAMBER 28
27 GAUGE
5
ORDERED
21 G 2 11

SEPARATELY LOCATION 24
22
(FOR VARIABLE FOR OPTIONAL H 14 19 D
PRESSURE ELECTRICALLY 15 16
SYSTEMS) 22
SUPERVISED 3 22
18
N.O. ALARM 21 A 13
CONTROL 26
22 21 23
VALVE
6 8 B
7 14
RESTRICTION 10 31 MODEL AV-1
ASSEMBLY,
C MAIN ALARM VALVE,
9 DRAIN VALVE 6 INCH (DN150)
SEE FIGURE 3
K (NORMALLY FLANGE x FLANGE
DRIP CLOSED) SHOWN
FUNNEL
1-1/4 INCH NPT
CONNECTION 2 INCH NPT
TO DRAIN CONNECTION
TO DRAIN

FIGURE 5 — PART 2 OF 3
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER — SEMI-PREASSEMBLED
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-954)—
TFP910
Page 11 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 20 1/4" x 1-1/2" Nipple . . . . . 2 CH
Water Pressure Gauge . . 2 92-343-1-005 21 1/2" x Close Nipple . . . . . 3 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 22 1/2" x 1-1/2" Nipple. . . . . 1 CH
3 3/4" Swing Check Valve . 1 46-049-1-005 23 1/2" x 2" Nipple . . . . . . . . 1 CH
4 1/2" Globe Valve . . . . . . . 1 46-047-1-004 24 1/2" x 3-1/2" Nipple . . . . . 2 CH
5 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 25 1/2" x 4-1/2" Nipple . . . . . 2 CH
6 Restriction Assembly . . . . 1 92-210-2-005 26 1/2" x 6-1/2" Nipple . . . . . 1 CH
7 2" Angle Valve . . . . . . . . . 1 46-048-1-009 27 3/4" x Close Nipple . . . . . 2 CH
8 Drip Funnel Connector . . 1 92-211-1-005 28 3/4" x 1-1/2" Nipple. . . . . 1 CH
9 Drip Funnel Bracket . . . . 1 92-211-1-003 29 3/4" x 2-1/2" Nipple . . . . . 1 CH
10 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 30 3/4" x 3" Nipple . . . . . . . . 1 CH
11 1/4" Plug . . . . . . . . . . . . . 2 CH 31 3/4" x 4-1/2" Nipple . . . . . 1 CH
12 1/2" Union . . . . . . . . . . . . 1 CH 32 2" x 3" Nipple. . . . . . . . . . 1 CH
13 3/4" Union . . . . . . . . . . . . 1 CH
14 1/2" 90° Elbow . . . . . . . . . 1 CH
15 1/2" 45° Elbow . . . . . . . . . 1 CH NOTES:
16 1/2" Tee . . . . . . . . . . . . . . 2 CH 1. Install subassemblies in alphabetical order.
17 1/2" x 1/2" x 3/4" Tee. . . . 1 CH 2. All Fittings and Nipples are galvanized
18 3/4" x 1/4" x 3/4" Tee. . . . 2 CH (Standard Order).
19 3/4" x 3/4" x 1/2" Tee. . . . 1 CH 3. CH: Common Hardware.

1/2 INCH NPT 3/4 INCH NPT


CONNECTION CONNECTION FOR
FOR WATERFLOW WATER MOTOR
PRESSURE ALARM ALARM
SWITCH

LOCATION 1/2 INCH NPT ALARM


FOR OPTIONAL CONNECTION SYSTEM
TEST VALVE
ELECTRICALLY FOR WATERFLOW (NORMALLY PRESSURE
SUPERVISED PRESSURE ALARM CLOSED) GAUGE
N.O. ALARM SWITCH
CONTROL
VALVE 3/4 INCH NPT 23
14 G B 20
18 11
CONNECTION FOR 1
WATER MOTOR F C
27
ALARM 24 13
MODEL RC-1 27 2
RETARD 12 4
17 16 25
CHAMBER 26 24 3
25 29 11
5 1
21 D 31
ORDERED
30 2
SEPARATELY LOCATION 20
(FOR VARIABLE FOR OPTIONAL E 18 SUPPLY
PRESSURE ELECTRICALLY 15 28 PRESSURE
SYSTEMS) SUPERVISED MAIN 19 GAUGE
16 21 DRAIN VALVE
N.O. ALARM
(NORMALLY
CONTROL 22 21 CLOSED)
VALVE
6 8
7
RESTRICTION 10 32
A MODEL AV-1
ASSEMBLY, ALARM VALVE,
9
SEE FIGURE 3 8 INCH (DN200)
H FLANGE x GROOVE
DRIP SHOWN
FUNNEL 2 INCH NPT
CONNECTION
1-1/4 INCH NPT TO DRAIN
CONNECTION
TO DRAIN

FIGURE 5 — PART 3 OF 3
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER — SEMI-PREASSEMBLED
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-955)—
TFP910
Page 12 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 21 1/2" x 5" Nipple . . . . . . . . 1 CH
Water Pressure Gauge . . 2 92-343-1-005 22 1/2" x 5-1/2" Nipple . . . . . 1 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 23 Select Nipple per Table . . 2 CH
3 1/2" Swing Check Valve . 2 46-049-1-004 24 Select Nipple per Table . . 2 CH
4 1/2" Globe Valve . . . . . . . 1 46-047-1-004 25 Select Nipple per Table . . 2 CH
5 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 26 2" x 2-1/2" Nipple. . . . . . . 2 CH
6 Restriction Assembly . . . . 1 92-210-2-005
7 2" Globe Valve . . . . . . . . . 1 46-047-1-009
8 1/4" Plug . . . . . . . . . . . . . 2 CH Select Appropriate Nipple Sizes
9 1/2" Union . . . . . . . . . . . . 3 CH Nipple per AV-1 Alarm Check Valve Size
10 1/2" 90° Elbow . . . . . . . . . 5 CH Number
4 Inch (DN100) 6 Inch (DN150)
11 1/2" x 1/4" x 1/2" Tee. . . . 1 CH
12 1/2" x 1/2" x 3/4" Tee. . . . 1 CH 23 1/2" x 1-1/2" 1/2" x 2-1/2"
13 1/2" Tee . . . . . . . . . . . . . . 1 CH 24 1/2" x 3-1/2" 1/2" x 4-1/2"
14 2" x 2" x 1/2" Tee . . . . . . . 1 CH 25 1/2" x 7" 1/2" x 8"
15 1/4" x Close Nipple . . . . . 1 CH
16 1/4" x 4" Nipple . . . . . . . . 1 CH
17 1/2" x 1-1/2" Nipple . . . . . 8 CH NOTES:
18 1/2" x 2" Nipple . . . . . . . . 3 CH 1. All Fittings and Nipples are galvanized
19 1/2" x 3" Nipple . . . . . . . . 2 CH (Standard Order).
20 1/2" x 3-1/2" Nipple . . . . . 1 CH 2. CH: Common Hardware.

3/4 INCH NPT 1/2 INCH NPT SYSTEM


CONNECTION CONNECTION PRESSURE
FOR WATER FOR WATERFLOW GAUGE
MOTOR PRESSURE SUPPLY
ORDERED 1
ALARM ALARM SWITCH PRESSURE
SEPARATELY
(FOR VARIABLE 8 2 GAUGE
PRESSURE 1
LOCATION SYSTEMS)
FOR OPTIONAL 8 2
ELECTRICALLY ALARM 15
SUPERVISED TEST VALVE 16
N.O. ALARM (NORMALLY 11 HANDHOLE
MODEL RC-1
CONTROL CLOSED) COVER MUST
RETARD
VALVE BE AT LEAST
CHAMBER
30 INCHES
24 19 AWAY FROM
1/2 INCH NPT 4 A WALL
CONNECTION 20
FOR WATERFLOW
PRESSURE
ALARM
SWITCH 1/2" x 1-1/2" 10 1/2" x 3-1/2"
(4 INCH (4 INCH
18
VALVE) VALVE)
3/4 INCH NPT or or
9
CONNECTION 1/2" x 2-1/2" 1/2" x 4-1/2"
FOR WATER (6 INCH (6 INCH
MOTOR 12 VALVE) VALVE)
ALARM 23 26
22
1/2" x 7" 7 MODEL AV-1
(4 INCH ALARM VALVE,
LOCATION VALVE) 13
or 17 6 INCH (DN150)
FOR OPTIONAL
ELECTRICALLY 1/2" x 8" 3 FLANGE x FLANGE
SUPERVISED (6 INCH SHOWN
17 VALVE) 17
N.O. ALARM
CONTROL 21 MAIN
6 25
VALVE 18 19 26 DRAIN VALVE
10 (NORMALLY
17 14 CLOSED)
17 9
RESTRICTION 18
ASSEMBLY, 10
9
SEE FIGURE 3 17 5
10 17 17 2 INCH NPT
10 3
CONNECTION
TO DRAIN

FIGURE 6 — PART 1 OF 2
HORIZONTAL CLOSED DRAIN TRIM — SPECIAL ORDER
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-057)—
TFP910
Page 13 of 22

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa 22 1/2" x 3-1/2" Nipple . . . . . 2 CH
Water Pressure Gauge . . 2 92-343-1-005 23 1/2" x 4-1/2" Nipple . . . . . 2 CH
2 1/4" Gauge Test Valve . . 2 46-005-1-002 24 1/2" x 9-1/2" Nipple . . . . . 1 CH
3 1/2" Swing Check Valve . 1 46-049-1-004 25 3/4" x Close Nipple . . . . . 2 CH
4 3/4" Swing Check Valve . 1 46-049-1-005 26 3/4" x 1-1/2" Nipple . . . . . 1 CH
5 1/2" Globe Valve . . . . . . . 1 46-047-1-004 27 3/4" x 2-1/2" Nipple . . . . . 1 CH
6 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 28 3/4" x 3" Nipple . . . . . . . . 1 CH
7 Restriction Assembly . . . . 1 92-210-2-005 29 3/4" x 4-1/2" Nipple . . . . . 1 CH
8 2" Globe Valve . . . . . . . . . 1 46-047-1-009 30 2" x 2-1/2" Nipple. . . . . . . 1 CH
9 1/4" Plug . . . . . . . . . . . . . 2 CH 31 2" x 3" Nipple. . . . . . . . . . 1 CH
10 1/2" Union . . . . . . . . . . . . 2 CH
11 3/4" Union . . . . . . . . . . . . 1 CH
NOTES:
12 1/2" 90° Elbow . . . . . . . . . 3 CH
13 1/2" Tee . . . . . . . . . . . . . . 1 CH 1. All Fittings and Nipples are galvanized
14 1/2" x 1/2" x 3/4" Tee. . . . 1 CH (Standard Order).
15 3/4" x 1/4" x 3/4" Tee. . . . 2 CH 2. CH: Common Hardware.
16 3/4" x 3/4" x 1/2" Tee. . . . 1 CH
17 2" x 2" x 1/2" Tee . . . . . . . 1 CH
18 1/4" x 1-1/2" Nipple . . . . . 2 CH SYSTEM
19 1/2" x 1-1/2" Nipple . . . . . 5 CH PRESSURE
1 GAUGE
20 1/2" x 2" Nipple . . . . . . . . 2 CH
21 1/2" x 3" Nipple . . . . . . . . 1 CH SUPPLY
PRESSURE
9 2 GAUGE
1
3/4 INCH NPT 1/2 INCH NPT 18 25
CONNECTION CONNECTION 9
15
FOR WATER FOR WATERFLOW 29 2
MOTOR PRESSURE 25
ALARM ALARM SWITCH 18
ORDERED 11 4
SEPARATELY 15
(FOR VARIABLE 27
LOCATION
FOR OPTIONAL PRESSURE 26 HANDHOLE
ELECTRICALLY SYSTEMS) COVER MUST
16
SUPERVISED BE AT LEAST
N.O. ALARM MODEL RC-1 30 INCHES
CONTROL RETARD AWAY FROM
VALVE CHAMBER A WALL
23 28

5
1/2 INCH NPT
CONNECTION 22
FOR WATERFLOW
PRESSURE
ALARM 12
SWITCH ALARM
20 TEST VALVE
(NORMALLY
3/4 INCH NPT 10 CLOSED)
CONNECTION
FOR WATER 22
MOTOR 14
ALARM 31
MODEL AV-1
13 ALARM VALVE,
23
LOCATION 8 INCH (DN200)
FOR OPTIONAL RESTRICTION FLANGE x
ELECTRICALLY ASSEMBLY, MAIN GROOVE
SUPERVISED SEE FIGURE 3 DRAIN VALVE 8 SHOWN
N.O. ALARM (NORMALLY
CONTROL 19 24 CLOSED) 30
VALVE 7 20 21
17
19

10
19 6 19
12 19 2 INCH NPT
3
12 CONNECTION
TO DRAIN

FIGURE 6 — PART 2 OF 2
HORIZONTAL CLOSED DRAIN TRIM — SPECIAL ORDER
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-058)—
TFP910
Page 14 of 22

Vertical Closed Drain Trim


Dimensions in Inches and (mm)
Dimension
With RC-1 Without RC-1
A B A 16-1/2 (419) 13-1/2 (343)
PLAN VIEW B 10-1/2 (267) 10-1/2 (267)
D
GxG& C 10-1/2 (267) 10 (254)
RC-1 FxG 8-7/8 (225) 8-7/8 (225)
D
E 12-1/4 (311) 12-1/4 (311)
F
E F 16-1/2 (419) N/A
G 3 (75) 3 (75)

ELEVATION VIEW

Vertical Open Drain Trim


Dimensions in Inches and (mm)
Dimension
With RC-1 Without RC-1
A B A 15-1/2 (394) 13-1/2 (343)
PLAN VIEW D B 10-1/2 (267) 10-1/2 (267)
GxG& C 10-1/2 (267) 10 (254)
RC-1 FxG
D 8-7/8 (225) 8-7/8 (225)
E 12-1/4 (311) 12-1/4 (311)
F
E F 16-1/2 (419) N/A
G 3 (75) 3 (75)

ELEVATION VIEW

FIGURE 7 — PART 1 OF 3
INSTALLATION DIMENSIONS
—FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES—
TFP910
Page 15 of 22

C Vertical Closed Drain Trim


Dimensions in Inches and (mm)
Dimension With RC-1 Without RC-1
4 Inch (DN100) 6 Inch (DN150) 4 Inch (DN100) 6 Inch (DN150)
A 19 (483) 19 (483) 19 (483) 19 (483)
A B 10-1/2 (267) 11-1/4 (286) 10-1/2 (267) 11-1/4 (286)
B
PLAN VIEW C 10-1/2 (267) 11-1/2 (292) 10-1/2 (267) 11-1/2 (292)
RC-1 D (G x G) 10-1/4 (260) 12-1/4 (311) 10-1/4 (260) 12-1/4 (311)
D (F x F) 10 (254) 12 (305) 10 (254) 12 (305)
F D (F x G) 10 (254) 12 (305) 10 (254) 12 (305)
E
D E 12-1/2 (318) 15 (381) 12-1/2 (318) 15 (381)
F 15-1/2 (394) 15-1/2 (394) 11-1/2 (292) 11-1/2 (292)
G G 3 (75) 2-3/4 (70) 3 (75) 2-3/4 (70)

ELEVATION VIEW

C Vertical Open Drain Trim


Dimensions in Inches and (mm)
Dimension With RC-1 Without RC-1
4 Inch (DN100) 6 Inch (DN150) 4 Inch (DN100) 6 Inch (DN150)
A 19 (483) 19 (483) 19 (483) 19 (483)
A B 10-1/2 (267) 11-1/4 (286) 10-1/2 (267) 11-1/4 (286)
B
PLAN VIEW C 10-1/2 (267) 11-1/2 (292) 10-1/2 (267) 11-1/2 (292)
RC-1 D (G x G) 10-1/4 (260) 12-1/4 (311) 10-1/4 (260) 12-1/4 (311)
D (F x F) 10 (254) 12 (305) 10 (254) 12 (305)
F D (F x G) 10 (254) 12 (305) 10 (254) 12 (305)
E
D E 12-1/2 (318) 15 (381) 12-1/2 (318) 15 (381)
F 15-1/2 (394) 15-1/2 (394) 11-1/2 (292) 11-1/2 (292)
G 3 (75) 2-3/4 (70) 3 (75) 2-3/4 (70)
G

ELEVATION VIEW

RC-1 Horizontal Closed Drain Trim


Dimensions in Inches and (mm)
D Dimension With RC-1 Without RC-1
B
4 Inch (DN100) 6 Inch (DN150) 4 Inch (DN100) 6 Inch (DN150)
A (G x G) 10-1/4 (260) 12-1/4 (311) 10-1/4 (260) 12-1/4 (311)
A (F x F) 10 (254) 12 (305) 10 (254) 12 (305)
A (F x G) 10 (254) 12 (305) 10 (254) 12 (305)
E
B 15 (381) 15 (381) 10-1/2 (267) 11-1/2 (292)
C 3-1/4 (83) 3-1/4 (83) 3-1/4 (83) 3-1/4 (83)
C A
D 14 (356) 15 (381) 14 (356) 15 (381)
ELEVATION VIEW PLAN VIEW E 13-3/4 (349) 14-3/4 (375) 13-3/4 (349) 14-3/4 (375)

FIGURE 7 — PART 2 OF 3
INSTALLATION DIMENSIONS
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES—
TFP910
Page 16 of 22

Vertical Closed Drain Trim


Dimensions in Inches and (mm)
Dimension
With RC-1 Without RC-1
D 18-1/2 (470) 15-3/4 (400)
A
FxF
A B FxG& B 16-1/8 (410) 16-1/8 (410)
PLAN VIEW GxG 12 (305) 12 (305)
C
D 14 (356) 14 (356)
RC-1
E 16-1/2 (419) 16-1/2 (419)
F E F 15-1/2 (394) N/A
G 2-1/2 (64) 2-1/2 (64)

G
ELEVATION VIEW

Vertical Open Drain Trim


Dimensions in Inches and (mm)
Dimension
With RC-1 Without RC-1
D
FxF A 18-1/2 (470) 15-3/4 (400)
A B FxG& 16-1/8 (410) 16-1/8 (410)
B
PLAN VIEW GxG
C 12 (305) 12 (305)
RC-1 D 14 (356) 14 (356)
E 16-1/2 (419) 16-1/2 (419)
F E F 15-1/2 (394) N/A
G 3-1/2 (89) 3-1/2 (89)

G
ELEVATION VIEW

RC-1

Horizontal Closed Drain Trim


D
Dimensions in Inches and (mm)
B Dimension
With RC-1 Without RC-1
A 14 (356) 14 (356)
B 15 (381) 12 (305)
C 1-1/2 (38) N/A
E D 19-1/2 (495) 19-1/2 (495)
A
FxF E 16-1/2 (419) 16-1/2 (419)
C
FxG&
GxG
ELEVATION VIEW PLAN VIEW

FIGURE 7 — PART 3 OF 3
INSTALLATION DIMENSIONS
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES—
TFP910
Page 17 of 22

5. Slowly open the main control valve Responsibility lies with the owner for
NO. DESCRIPTION QTY. P/N
until the sound of flowing water the inspection, testing, and mainte-
1 3/4" x 1/4" Hex just begins and then open the nance of their fire protection system
Bushing . . . . . . . . . 1 CH valve one more turn. and devices in compliance with this
2 3/32" Vent document, as well as with the appli-
Fitting . . . . . . . . . . 1 92-032-1-002 6. Close the remote branch line vent
cable standards of the National Fire
3 1/4" x 5'-0" connection after the discharge
Protection Association (for example,
Tubing . . . . . . . . . . 1 CH of aerated water ceases, and the
NFPA 25), in addition to the standards
outlet has flowed full for at least
of any authority having jurisdiction.
PRESSURE 15 seconds.
Contact the installing contractor or
SWITCH 7. Fully open the main control valve. product manufacturer regarding any
8. Open the end-of-line Inspec- questions.
1 tor’s Test Connection (or Alarm Automatic sprinkler systems are
3 Test Valve, if acceptable to the recommended to be inspected, tested,
(ROUTE TO authority having jurisdiction) and and maintained by a qualified Inspec-
DRAIN) verify that the system alarms tion Service in accordance with local
operate. requirements and/or national codes.
2
MODEL RC-1 (GREEN 9. Close the end-of-line Inspector’s The TYCO Model AV-1-300 Alarm
RETARD TINT) Test Connection (or Alarm Test Check Valves do not require any
CHAMBER Valve). regularly scheduled maintenance. It is
recommended, however, that proper
10. Verify that water ceases to flow operation of the alarms be periodically
Trim kit is ordered separately when a
from the alarm line drain. If water verified in accordance with a procedure
Water Motor Alarm (P/N 52-201-2-012) continues to flow, follow the
is not installed. that is acceptable to the authority
corrective procedure described in having jurisdiction. Any impairment
the Care and Maintenance section. must be immediately corrected.
FIGURE 8 The Restriction Assembly has a
ALARM VENT TRIM KIT 1/8 inch (3,2 mm) diameter drain Inspection Procedure
orifice. Sufficient time must be It is recommended that the following
allowed for drainage of the Retard inspection procedure be performed at

Setting Chamber and the piping to the


water motor alarm.
least quarterly by a qualified Inspection
Service.

Procedure 11. After verification that the flow of


water out of the alarm line drain
1. Notify the proper authorities
and all personnel who may be
Steps 1 through 11 are to be performed affected that an alarm test is to be
when initially setting the Model has stopped, the alarm valve is set
and is ready for service. performed.
AV-1-300 Alarm Check Valve or after
system operation due to a fire. 2. Open the end-of-line Inspec-

NOTICE
Care and tor’s Test Connection (or Alarm
Test Valve, if acceptable to the

Filling the system with water will result Maintenance authority having jurisdiction) and
verify that the system alarms
in operation of the associated alarms. The following procedures and operate in accordance with the
Consequently, notification must first be inspections should be performed as requirements of the authority
given to the owner and fire department, indicated, in addition to any specific having jurisdiction. Verify that
central station, or other signal station to requirements of the NFPA. Any impair- the water motor alarm and/or the
which the alarms are connected. ment must be immediately corrected. pressure alarm switch properly
Notify the proper authorities and all actuate and within the elapsed
personnel who may be affected that NOTICE time required by the authority
an alarm test is to be performed. having jurisdiction.
Performing the care and maintenance
After placing a fire protection system procedures will result in operation of 3. Verify that water is flowing out
in service, notify the proper authorities the associated alarms. Consequently, of the alarm line drain at a rate
and advise those responsible for moni- notification must first be given to the consistent with the 1/8 inch (3,2
toring proprietary and/or central station owner and fire department, central mm) diameter drain orifice in the
alarms. station, or other signal station to which Restriction Assembly.
the alarms are connected. 4. Close the end-of-line Inspector’s
1. Open the 1/4 inch Gauge Test
Valves for the Supply and System Before closing a fire protection system Test Connection (or Alarm Test
Pressure Gauges. main control valve for maintenance Valve).
work on the fire protection system 5. Verify that water ceases to flow
2. Check to see that the Hand-hole that it controls, obtain permission to
Cover bolts are tight. If not, cross- from the alarm line drain.
shut down the affected fire protec-
tighten them. tion system from the proper authori- 6. Clean the 1/2 inch Strainer
3. Close the Alarm Test Valve. ties and notify all personnel who may (located in the valve trim) as well
be affected by this decision. as the 3/4 inch Strainer (located at
4. Open the remote cross main the connection to the water motor
or branch line vent connection. alarm, as applicable). Be sure to
(Refer to Step 7 in the Installation replace the strainer baskets and
section.) tighten the caps securely.
TFP910
Page 18 of 22

NOTICE valve, and then repair or replace Loss of Excess System


Cleaning of the Strainers after each the Alarm Test Valve as necessary. Pressure
operation of the alarms is especially 6. If it appears that the leakage noted For variable pressure systems, the
important in the case of water supplies in Step 5 is from the Alarm Port, System Pressure Gauge normally
(such as lakes and rivers) having a drain the system in accordance indicates a pressure greater than that
large quantity of suspended matter. with the prescribed procedure. shown by the Supply Pressure Gauge.
A clogged alarm line can prevent After the system has been drained, Also, the value should be close to that
operation of the alarms. remove the Handhole Cover. of the peak supply pressure that has
7. Notify all authorities responsible occurred after the system was placed
7. While holding the Spring down by in service.
for monitoring the installation that the coils, remove the Hinge Pin.
the fire protection system has been Remove the Spring and Waterway
returned to service. Clapper Assembly. NOTICE
For variable pressure systems, loss of
Sprinkler System Drain-Down 8. Using a light, check for and excess system pressure will increase
Draining the sprinkler system must be remove any debris that may have the likelihood of a false alarm.
done in accordance with the following become lodged within the Seat
procedure: Ring groove. Inspect the Seat Ring Follow the procedure indicated below
seat for any damage. If the Seat to correct a loss of excess system
1. Close the main control valve, if this pressure condition.
has not already been done. Ring has become dented across
the seat then the Alarm Check 1. Check for signs of continued
2. Open the remote cross main Valve will have to be replaced. It is leakage from the alarm line drain.
or branch line vent connection. impractical to re-face a Seat Ring If rust stains and/or water deposits
(Refer to Step 7 in the Installation in the field. indicate that continued leakage has
section.) been taking place, take corrective
9. Check for and remove any
3. Open the Main Drain Valve. Check debris that may have become action according to the procedure
first to see that the drainage water lodged in the Clapper Facing. If described in the sub-section
discharge will not cause damage a minor imperfection remains in entitled “Leakage from Alarm Line
or result in dangerous conditions. the Clapper Facing, then turn it Drain”.
4. Wait until the Supply Pressure over after thoroughly cleaning 2. If there are no signs of continued
Gauge reads zero pressure and both surfaces with a clean cloth. leakage from the alarm line drain,
the sound of draining water has Replace the Clapper Facing if close the main control valve, slowly
stopped before performing any necessary. Be sure to securely remove the plug from the supply
maintenance work on the fire re-tighten the retaining fastener pressure gauge test valve to relieve
protection system. for the Clapper Washer. the supply pressure, and then
10. Replace the Spring and Waterway slowly open the union in the exter-
Leakage from Alarm Line Clapper Assembly as shown in nally mounted bypass.
Drain Figure 1. While holding the coils
Follow the steps indicated below until 3. Check for leakage past the Bypass
of the Spring down, re-insert the Check Valve. If there is leakage,
water ceases to flow from the alarm Hinge Pin. Be sure that the Hinge
line drain. After each step check if debris may have become lodged
Pin is pushed all the way to the between its clapper and seat. Drain
leakage has stopped. rear of the valve. the system in accordance with the
1. Open the Main Drain Valve. Let 11. Replace the Handhole Cover. prescribed procedure and then
the water flow for about 5 seconds Return the Alarm Valve to clean or replace the Bypass Check
and then close the Main Drain operation in accordance with the Valve as required.
Valve. This should flush any loose steps described in the Setting
debris that may have become 4. Re-assemble the externally
Procedure section. mounted bypass, replace the plug
trapped between the Clapper
Facing and the Seat Ring or in the Clogged Alarm Line Drain into the Gauge Test Valve, and
seating area of the Drain Valve. If water either does not flow or only return the fire protection system to
dribbles out of the alarm line drain operation in accordance with the
2. Repeat Step 1 if the rate of during an alarm test, then it is likely steps described in the Operation
continued flow out of the drain that the screen protecting the Restric- section.
was noticeably reduced. tion Assembly drain orifice (Ref. Figure 5. If there are no signs of leakage
3. Open the Alarm Test Valve and 3) has become clogged. past either the Alarm Check Valve
allow water to flow for about 5 Clapper per Step 1 or the Bypass
seconds before re-closing the NOTICE Check Valve per Step 2, inspect the
valve. This should flush any loose sprinkler system for leakage.
For variable pressure systems, a
debris that may have become
clogged alarm line drain will increase
trapped in the seating area of the
the likelihood of a false alarm.
Alarm Test Valve.
First break the union downstream of
4. Repeat Step 3 if the rate of
the Drain Restriction and remove the
continued flow out of the drain
Drain Restriction for cleaning by back-
was noticeably reduced.
flushing the screen. Re-install the Drain
5. Determine whether the water is Restriction and re-assemble the drain
flowing from the Alarm Port (Figure line.
1) or past the Alarm Test Valve.
If the leakage is past the Alarm
Test Valve, close the main control
TFP910
Page 19 of 22

Excess Pressure Due To


Thermal Expansion
Limited
Wet pipe sprinkler systems subject
to ambient temperatures in excess of
Warranty
100°F/38°C can experience significant Products manufactured by Tyco Fire
increases in system pressure due to Suppression & Building Products
the thermal expansion of the water. In (TFSBP) are warranted solely to the
particular, a gridded wet-pipe system original Buyer for ten (10) years against
with a relatively small air pocket and defects in material and workmanship
no relief valve can be subjected to an when paid for and properly installed
increase of more than 100 psi (6,9 bar), and maintained under normal use
due to an increase in ambient tempera- and service. This warranty will expire
ture of approximately 50°F/28°C. ten (10) years from date of shipment
by TFSBP. No warranty is given for
As necessary, install a pressure relief products or components manufac-
valve, in accordance with the require- tured by companies not affiliated by
ments of the authority having jurisdic- ownership with TFSBP or for products
tion, to automatically relieve the excess and components which have been
pressure that could otherwise be subject to misuse, improper instal-
created in wet-pipe systems exposed lation, corrosion, or which have not
to significant increases in ambient been installed, maintained, modified or
temperature. repaired in accordance with applicable
False Alarms Standards of the National Fire Protec-
Follow the step below when repeated tion Association, and/or the standards
false alarms occur in a variable of any other Authorities Having Juris-
pressure system. diction. Materials found by TFSBP to
be defective shall be either repaired
1. Check for and correct the cause of or replaced, at TFSBP’s sole option.
continued leakage out the alarm TFSBP neither assumes, nor authorizes
line drain. any person to assume for it, any other
2. Check for and clean a clogged obligation in connection with the sale of
alarm line drain. products or parts of products. TFSBP
shall not be responsible for sprinkler
3. Check for and correct the cause of system design errors or inaccurate or
a loss in excess system pressure. incomplete information supplied by
4. Drain the sprinkler system and re-fill Buyer or Buyer’s representatives.
it using the steps described in the In no event shall TFSBP be liable, in
Setting Procedure section. contract, tort, strict liability or under
5. Intermittent Alarms any other legal theory, for incidental,
indirect, special or consequential
If the pressure alarm switch gives a damages, including but not limited to
steady signal, but the water motor labor charges, regardless of whether
generates an intermittent alarm, check TFSBP was informed about the possi-
for binding in the water motor alarm bility of such damages, and in no
drive shaft. event shall TFSBP’s liability exceed an
If the water motor alarm and/or the amount equal to the sales price.
pressure alarm switch provide an inter- The foregoing warranty is made in
mittent alarm, it is likely the conse- lieu of any and all other warranties,
quence of an excessive amount of express or implied, including warran-
air being trapped within the sprinkler ties of merchantability and fitness for a
system. Drain down the sprinkler particular purpose.
system and refill it using the steps
described in the Setting Procedure This limited warranty sets forth the
section. exclusive remedy for claims based
on failure of or defect in products,
A discontinuance of an alarm may also materials or components, whether the
be caused by the Clapper closing due claim is made in contract, tort, strict
to a sudden drop in supply pressure liability or any other legal theory.
or the shut-off of a pump in the supply
line. These types of problems can only This warranty will apply to the full
be corrected by maintaining a steady extent permitted by law. The invalidity,
supply pressure. in whole or part, of any portion of this
warranty will not affect the remainder.
TFP910
Page 20 of 22

Ordering AV-1-300 Valve Trim Other Model AV-1-300


Configurations
Standard Order
Procedure Specify: Vertical, Closed Drain Galva- Other AV-1-300 Alarm Check Valves
are valves ordered with any combina-
Contact your local distributor for avail- nized Trim for (size) Model AV 1-300
Alarm Check Valve, P/N (specify). tion of flange, threaded port, or groove
ability. When placing an order, indicate outside diameter not offered under
the full product name. Refer to Table Vertical Closed Drain, Galvanized “Standard AV-1-300 Alarm Check
A (Page 3) for Flange Drilling Speci- (See Figure 3.) Valve” offerings.
fications. The Price Book provides 2-1/2 inch . . . . . . . . . . . . P/N 52-204-2-050
part numbers for factory pre-trimmed 4 or 6 inch* . . . . . . . . . . . P/N 52-204-2-951 Valves with NPT threaded ports are
8 inch*. . . . . . . . . . . . . . . P/N 52-204-2-952 intended for use with the AV-1-300
Model AV-1-300 Valves. *Provided semi-preassembled Valve Trim described in this data sheet.
Standard AV-1-300 Valves with ISO threaded ports are
Alarm Check Valve Special Order intended for use with special order trim
(Assumes American Standard Flange Specify: (Vertical or Horizontal), that is provided by local distributors
Drilling, American Threaded Ports, and (Closed or Open) Drain Galvanized Trim to meet the specific needs of certain
American Groove Outside Diameter, as for (size) Model AV-1-300 Alarm Check localities. Contact your local distrib-
applicable) Valve, P/N (specify). utor regarding valves and valve trim for
Vertical Open Drain, Galvanized specific localities.
Specify: (size in inches) Model (See Figure 4.)
AV-1-300 Alarm Check Valve with (end 2-1/2 inch . . . . . . . . . . . . P/N 52-204-2-053 Specify: (size) Model AV-1-300 Alarm
connections), P/N (specify). 4 or 6inch*. . . . . . . . . . . . P/N 52-204-2-954 Check Valve with (connections) with
8 inch*. . . . . . . . . . . . . . . P/N 52-204-2-955 (NPT or ISO) threaded ports, P/N (see
2-1/2 Inch Valves *Provided semi-preassembled below).
2.88 inch (73,0 mm) Groove O.D. x Horizontal Closed Drain, Galvanized
2.88 inch (73,0 mm) Groove O.D. (See Figure 5.) 2-1/2 Inch Valves with NPT Ports
2-1/2 Inch G x G . . . . . . . P/N 52-203-1-110 4 or 6 inch. . . . . . . . . . . . P/N 52-204-2-057 ISO (PN16) Flange x
8 inch. . . . . . . . . . . . . . . . P/N 52-204-2-058 2.88 inch (73,0 mm)
ANSI Flange x Groove O.D. . . . . . . . . . . P/N 52-203-1-251
2.88 inch (73,0 mm) Groove O.D. Accessories
2-1/2 Inch F x G. . . . . . . . P/N 52-203-1-210 Order the following accessories, as ANSI Flange x
applicable. 3.00 inch (76,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-220
4 Inch Valves
Model RC-1 ISO (PN16) Flange x
4.50 inch (114,3 mm) Groove O.D. x Retard Chamber. . . . . . . P/N 52-211-1-002
4.50 inch (114,3 mm) Groove O.D. 3.00 inch (76,1 mm)
Required for variable pressure water sup- Groove O.D. . . . . . . . . . . P/N 52-203-1-331
4 Inch G x G . . . . . . . . . . P/N 52-203-1-113
ply conditions
AS Flange x
ANSI Flange x 2.88 inch (73,0 mm)
Alarm Vent Trim. . . . . . . . P/N 52-201-2-012
4.50 inch (114,3 mm) Groove O.D. Groove O.D. . . . . . . . . . . P/N 52-203-1-611
4 Inch F x G. . . . . . . . . . . P/N 52-203-1-413 Required when a water motor alarm is not
installed AS Flange x
ANSI Flange x ANSI Flange 3.00 inch (76,1 mm)
4 Inch F x F. . . . . . . . . . . P/N 52-203-1-013 Model PS10-2A Potter Groove O.D. . . . . . . . . . . P/N 52-203-4-410
Electric Waterflow Pressure JIS Flange x
Alarm Switch. . . . . . . . . . P/N 54-281-1-002
6 Inch Valves 2.88 inch (73,0 mm)
Required for electric signal indicating Groove O.D. . . . . . . . . . . P/N 52-203-1-710
6.62 inch (168,3 mm) Groove O.D. x waterflow
6.62 inch (168,3 mm) Groove O.D. JIS Flange x
6 Inch G x G . . . . . . . . . . P/N 52-203-1-115 Model WMA-1 Water 3.00 inch (76,1 mm)
Motor Alarm . . . . . . . . . . P/N 52-630-1-001 Groove O.D. . . . . . . . . . . P/N 52-203-1-810
ANSI Flange x Required for a mechanical waterflow alarm 3.00 inch (76,1 mm) Groove O.D x
6.62 inch (168,3 mm) Groove O.D. 3.00 inch (76,1 mm)
6 Inch F x G. . . . . . . . . . . P/N 52-203-1-615 Optional 600 PSI Water Groove O.D. . . . . . . . . . . P/N 52-203-1-120
Pressure Gauge . . . . . . . P/N 92-343-1-004
ANSI Flange x ANSI Flange 2-1/2 Inch Valves with ISO Ports
6 Inch F x F. . . . . . . . . . . P/N 52-203-1-015
Replacement Parts ISO (PN16) Flange x
2.88 inch (73,0 mm)
8 Inch Valves Valve Groove O.D. . . . . . . . . . . P/N 52-203-1-211
8.62 inch (219,1 mm) Groove O.D x Specify: (description) for use with (size)
Model AV-1-300 Alarm Check Valve, ISO (PN16) Flange x
8.62 inch (219,1 mm) Groove O.D. 3.00 inch (76,1 mm)
8 Inch G x G . . . . . . . . . . P/N 52-203-1-916 P/N (see Figure 1).
Groove O.D. . . . . . . . . . . P/N 52-203-1-311
ANSI Flange x Trim 3.00 inch (76,1 mm) Groove O.D x
8.62 inch (219,1 mm) Groove O.D. Specify: (description) for use with Model 3.00 inch (76,1 mm)
8 Inch F x G. . . . . . . . . . . P/N 52-203-1-816 AV-1-300 Alarm Check Valve, Groove O.D. . . . . . . . . . . P/N 52-203-4-120
P/N (see Figure 3, 4, or 5).
2.88 inch (73,0 mm) Groove O.D x
ANSI Flange x ANSI Flange 2.88 inch (73,0 mm)
8 inch F x F. . . . . . . . . . . P/N 52-203-1-016 Groove O.D. . . . . . . . . . . P/N 52-203-1-921
TFP910
Page 21 of 22

4 Inch Valves with NPT Ports 6 Inch Valves with NPT Ports 8 Inch Valves with NPT Ports
ISO (PN16) Flange x ANSI Flange x ISO (PN10) Flange x
4.50 inch (114,3 mm) 6.50 inch (165,1 mm) 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-493 Groove O.D. . . . . . . . . . . P/N 52-203-1-625 Groove O.D. . . . . . . . . . . P/N 52-203-1-896
ISO (PN16) Flange x ISO (PN16) Flange x ISO (PN16) Flange x
ISO (PN16) Flange. . . . . . P/N 52-203-4-013 6.62 inch (168,3 mm) 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-695 Groove O.D. . . . . . . . . . . P/N 52-203-4-266
AS Flange x
AS Flange. . . . . . . . . . . . P/N 52-203-4-313 ISO (PN16) Flange x ISO (PN10) Flange x
6.50 inch (165,1 mm) ISO (PN10) Flange. . . . . . P/N 52-203-4-016
AS Flange x Groove O.D. . . . . . . . . . . P/N 52-203-5-215
4.50 inch (114,3 mm) ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-4-413 ISO (PN16) Flange x ISO (PN16) Flange. . . . . . P/N 52-203-4-118
ISO (PN16) Flange. . . . . . P/N 52-203-4-015
JIS Flange x AS Flange x
JIS Flange. . . . . . . . . . . . P/N 52-203-4-713 AS Flange x AS Flange. . . . . . . . . . . . P/N 52-203-4-316
AS Flange. . . . . . . . . . . . P/N 52-203-4-315
JIS Flange x AS Flange x
4.50 inch (114,3 mm) AS Flange x 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-813 6.62 inch (168,3 mm) Groove O.D. . . . . . . . . . . P/N 52-203-4-416
Groove O.D. . . . . . . . . . . P/N 52-203-4-415
4 Inch Valves with ISO Ports JIS Flange x
AS Flange x JIS Flange. . . . . . . . . . . . P/N 52-203-1-716
ISO (PN16) Flange x 6.50 inch (165,1 mm)
ISO Flange . . . . . . . . . . . P/N 52-203-4-113 JS Flange x 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-425
Groove O.D. . . . . . . . . . . P/N 52-203-4-816
ISO (PN16) Flange x JIS Flange x
4.50 inch (114,3 mm) JIS Flange. . . . . . . . . . . . P/N 52-203-4-715 8 Inch Valves with ISO Ports
Groove O.D. . . . . . . . . . . P/N 52-203-4-213
JIS Flange x ISO (PN10) Flange x
4.50 inch (114,3 mm) Groove O.D x 6.62 inch (168,3 mm) ISO (PN10) Flange. . . . . . P/N 52-203-4-116
4.50 inch (114,3 mm) Groove O.D. . . . . . . . . . . P/N 52-203-4-815 ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-1-923
JIS Flange x ISO (PN16) Flange. . . . . . P/N 52-203-4-117
6.50 inch (165,1 mm) ISO (PN10) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-5-815 8.62 inch (219,1 mm)
6.50 inch (165,1 mm) Groove O.D x Groove O.D. . . . . . . . . . . P/N 52-203-4-216
6.50 inch (165,1 mm) ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-1-124 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-226
6 Inch Valves with ISO Ports
8.62 inch (219,1 mm) Groove O.D. x
ISO (PN16) Flange x
8.62 inch (219,1 mm)
ISO (PN16) Flange. . . . . . P/N 52-203-4-115
Groove O.D. . . . . . . . . . . P/N 52-203-1-926
ISO (PN16) Flange x
6.62 inch (168,3 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-215
ISO (PN16) Flange x
6.50 inch (165,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-225
6.62 inch (168,3 mm) Groove O.D. x
6.62 inch (168,3 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-925
6.50 inch (165,1 mm) Groove O.D. x
6.50 inch (165,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-125
TFP910
Page 22 of 22

Copyright © 2009, 2011 Tyco Fire Suppression & Building Products. All rights reserved.