CLAPPER
ASSEMBLY 6 10
2-1/2 INCH 7 4
VALVE
8
CLAPPER
ASSEMBLY 2
3
4, 6, & 8 INCH
VALVES 12
The 2-1/2 Inch (DN65) Valves with NPT threaded ports have a 1-1/4 inch main drain connection. The 2-1/2 Inch (DN65) Valves with
ISO threaded ports have a DN40 main drain connection.
The 4, 6, and 8 Inch (DN100. DN150, and DN200) Valves with NPT threaded ports have a 2 inch main drain connection. The 4, 6,
and 8 Inch (DN100. DN150, and DN200) Valves with ISO threaded ports have a DN50 inch main drain connection.
FIGURE 1
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
— ASSEMBLY —
TFP910
Page 3 of 22
)
6
100
150
2.0 DN
(DN
(DN
H(
INC
0)
CH
CH
20
0,10
N
4 IN
6 IN
/2
(D
0,09
2-1
H
0,08
NC
0,07
8I
1.0
0.9 0,06
0.8
0.7 0,05
100 200 300 400 500 700 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe
with C=120, is as follows
14 feet of 2-1/2 inch Sch. 40 pipe for the 2-1/2 inch AV-1-300 Valve calculated on a typical flow rate of 250 GPM.
23 feet of 4 inch Sch. 40 pipe for the 4 inch AV-1-300 Valve calculated on a typical flow rate of 600 GPM.
24 feet of 6 inch Sch. 40 pipe for the 6 inch AV-1-300 Valve calculated on a typical flow rate of 1500 GPM.
23 feet of 8 inch Sch. 30 pipe for the 8 inch AV-1-300 Valve calculated on a typical flow rate of 2500 GPM.
GRAPH A
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
— NOMINAL PRESSURE LOSS VERSUS FLOW —
Qty. N
Number of
Bolt Holes
TABLE B
— FLANGE DRILLING SPECIFICATIONS —
TFP910
Page 4 of 22
Technical WATERFLOW
Data
PRESSURE
ALARM SWITCH
ONCE RETARD
CHAMBER OVERFLOWS,
Approvals WATERFLOW PRESSURE
UL and C-UL Listed, ALARM SWITCH AND
FM Approved RETARD
WATER MOTOR
ALARM ACTUATE
CHAMBER UPON SPRINKLER
Working Water Pressure Range WATERFLOW FLOW, WATERWAY
20 to 300 psi (1,4 to 20,7 bar) TO WATER CLAPPER OPENS
MOTOR ALARM WATERFLOW
Friction Loss 7/32"
TO SYSTEM
Refer to Graph A. (5,6 mm) SYSTEM
ORIFICE PRESSURE
Physical Characteristics RESTRICTION
INLET GAUGE
The body is ductile iron, the hand-hole ASSEMBLY
cover is ductile iron, and the seat ring
is bronze. The clapper for the 2-1/2 1/8"
(3,2 mm)
inch (DN65) valve size is stainless steel. ORIFICE SUPPLY
The clapper for the larger valve sizes OUTLET PRESSURE
is ductile iron. All valve sizes utilize an GAUGE
EPDM clapper facing.
WHEN FLOW THROUGH
Flanged connections are available RESTRICTION ASSEMBLY
drilled per ANSI, ISO, AS, and JIS INLET EXCEEDS OUTLET, MAIN ALARM
specifications as detailed in Table A. RETARD CHAMBER DRAIN CHECK
BEGINS TO FILL VALVE WATERFLOW VALVE
Threaded port connections for the
THROUGH SEAT
AV-1-300 Valves are available NPT RING GROOVE AND
threaded or threaded per ISO 7/1 as ALARM PORT
detailed in the Ordering Procedure
section. Valves with NPT threaded FIGURE 2
ports will readily accept the trim 2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200)
arrangements detailed in Figures 4 MODEL AV-1-300 ALARM CHECK VALVE
through 6. — OPERATION —
Operation
When the fire protection system is SCREEN
initially pressurized, water flows into
the system until the water supply and
system pressure become equalized, INLET RESTRICTION
and the torsion Spring closes the WITH 0.219" (5.6 mm)
Waterway Clapper in the Alarm Check ORIFICE
Valve. Once the pressures stabilize,
the Alarm Check Valve is in service
and the centrally located groove in the
DRAIN RESTRICTION
Seat Ring is sealed. Consequently, with
WITH 0.125" (3.2 mm)
the Alarm Check Valve set for service, ORIFICE
there is no flow through the alarm port
to the alarm devices (that is, water
motor alarm and/or pressure alarm FIGURE 3
switch). RESTRICTION ASSEMBLY
(Provided with Alarm Check Valve Trim)
When there is a steady flow of water
into the sprinkler system due to a
sprinkler operation, the Waterway
Clapper opens as shown in Figure 2. to be actuated as long as the Waterway A transient surge in supply pressure
Water is then permitted to flow into Clapper remains open. Water in the that is sufficient only to open the
the centrally located groove in the alarm lines will automatically drain out Waterway Clapper momentarily will not
Seat Ring and out through the alarm through the 1/8 inch (3,2 mm) Drain cause a false alarm, and a portion of
port towards the Restriction Assembly Orifice in the Restriction Assembly the increase in pressure will be trapped
(Figure 3). When the flow through the (Figure 3) when the Waterway Clapper within the system, thus reducing the
Inlet Restriction of the Restriction closes (due to a stop in the flow of possibility of another opening. Any
Assembly exceeds the flow through water into the sprinkler system). water in the alarm line is automatically
the Outlet Restriction, the Retard drained, further reducing the possi-
Chamber (where provided for systems For variable pressure systems, slow
bility of a false alarm due to a succes-
with variable pressure), begins to fill. as well as small transient increases in
sive transient surge in supply pressure.
water supply pressure may continue to
Subsequently, the Water Motor alarm build up in the system (via the Bypass
and/or the pressure alarm switch will Check Valve) without opening the
be actuated. The alarms will continue Waterway Clapper.
TFP910
Page 5 of 22
FIGURE 4 — PART 1 OF 3
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER
—FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-050)—
TFP910
Page 7 of 22
SEPARATELY LOCATION 22
20
(FOR VARIABLE FOR OPTIONAL H 11 17 D
PRESSURE ELECTRICALLY 12 13
SYSTEMS) 20
SUPERVISED 3 20
N.O. ALARM
22
A 10
CONTROL 24
20 21
VALVE L B
6 11
7
RESTRICTION 19 29 MODEL AV-1
ASSEMBLY,
C MAIN ALARM VALVE,
M DRAIN VALVE 6 INCH (DN150)
SEE FIGURE 3
(NORMALLY FLANGE x FLANGE
10 N 29 CLOSED) SHOWN
16
11 2 INCH NPT
19 19 3 20 K CONNECTION
TO DRAIN
FIGURE 4 — PART 2 OF 3
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER — SEMI-PREASSEMBLED
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-951)—
TFP910
Page 8 of 22
FIGURE 4 — PART 3 OF 3
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER — SEMI-PREASSEMBLED
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-952)—
TFP910
Page 9 of 22
FIGURE 5 — PART 1 OF 3
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER
—FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-053)—
TFP910
Page 10 of 22
SEPARATELY LOCATION 24
22
(FOR VARIABLE FOR OPTIONAL H 14 19 D
PRESSURE ELECTRICALLY 15 16
SYSTEMS) 22
SUPERVISED 3 22
18
N.O. ALARM 21 A 13
CONTROL 26
22 21 23
VALVE
6 8 B
7 14
RESTRICTION 10 31 MODEL AV-1
ASSEMBLY,
C MAIN ALARM VALVE,
9 DRAIN VALVE 6 INCH (DN150)
SEE FIGURE 3
K (NORMALLY FLANGE x FLANGE
DRIP CLOSED) SHOWN
FUNNEL
1-1/4 INCH NPT
CONNECTION 2 INCH NPT
TO DRAIN CONNECTION
TO DRAIN
FIGURE 5 — PART 2 OF 3
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER — SEMI-PREASSEMBLED
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-954)—
TFP910
Page 11 of 22
FIGURE 5 — PART 3 OF 3
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER — SEMI-PREASSEMBLED
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-955)—
TFP910
Page 12 of 22
FIGURE 6 — PART 1 OF 2
HORIZONTAL CLOSED DRAIN TRIM — SPECIAL ORDER
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-057)—
TFP910
Page 13 of 22
5
1/2 INCH NPT
CONNECTION 22
FOR WATERFLOW
PRESSURE
ALARM 12
SWITCH ALARM
20 TEST VALVE
(NORMALLY
3/4 INCH NPT 10 CLOSED)
CONNECTION
FOR WATER 22
MOTOR 14
ALARM 31
MODEL AV-1
13 ALARM VALVE,
23
LOCATION 8 INCH (DN200)
FOR OPTIONAL RESTRICTION FLANGE x
ELECTRICALLY ASSEMBLY, MAIN GROOVE
SUPERVISED SEE FIGURE 3 DRAIN VALVE 8 SHOWN
N.O. ALARM (NORMALLY
CONTROL 19 24 CLOSED) 30
VALVE 7 20 21
17
19
10
19 6 19
12 19 2 INCH NPT
3
12 CONNECTION
TO DRAIN
FIGURE 6 — PART 2 OF 2
HORIZONTAL CLOSED DRAIN TRIM — SPECIAL ORDER
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-058)—
TFP910
Page 14 of 22
ELEVATION VIEW
ELEVATION VIEW
FIGURE 7 — PART 1 OF 3
INSTALLATION DIMENSIONS
—FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES—
TFP910
Page 15 of 22
ELEVATION VIEW
ELEVATION VIEW
FIGURE 7 — PART 2 OF 3
INSTALLATION DIMENSIONS
—FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES—
TFP910
Page 16 of 22
G
ELEVATION VIEW
G
ELEVATION VIEW
RC-1
FIGURE 7 — PART 3 OF 3
INSTALLATION DIMENSIONS
—FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES—
TFP910
Page 17 of 22
5. Slowly open the main control valve Responsibility lies with the owner for
NO. DESCRIPTION QTY. P/N
until the sound of flowing water the inspection, testing, and mainte-
1 3/4" x 1/4" Hex just begins and then open the nance of their fire protection system
Bushing . . . . . . . . . 1 CH valve one more turn. and devices in compliance with this
2 3/32" Vent document, as well as with the appli-
Fitting . . . . . . . . . . 1 92-032-1-002 6. Close the remote branch line vent
cable standards of the National Fire
3 1/4" x 5'-0" connection after the discharge
Protection Association (for example,
Tubing . . . . . . . . . . 1 CH of aerated water ceases, and the
NFPA 25), in addition to the standards
outlet has flowed full for at least
of any authority having jurisdiction.
PRESSURE 15 seconds.
Contact the installing contractor or
SWITCH 7. Fully open the main control valve. product manufacturer regarding any
8. Open the end-of-line Inspec- questions.
1 tor’s Test Connection (or Alarm Automatic sprinkler systems are
3 Test Valve, if acceptable to the recommended to be inspected, tested,
(ROUTE TO authority having jurisdiction) and and maintained by a qualified Inspec-
DRAIN) verify that the system alarms tion Service in accordance with local
operate. requirements and/or national codes.
2
MODEL RC-1 (GREEN 9. Close the end-of-line Inspector’s The TYCO Model AV-1-300 Alarm
RETARD TINT) Test Connection (or Alarm Test Check Valves do not require any
CHAMBER Valve). regularly scheduled maintenance. It is
recommended, however, that proper
10. Verify that water ceases to flow operation of the alarms be periodically
Trim kit is ordered separately when a
from the alarm line drain. If water verified in accordance with a procedure
Water Motor Alarm (P/N 52-201-2-012) continues to flow, follow the
is not installed. that is acceptable to the authority
corrective procedure described in having jurisdiction. Any impairment
the Care and Maintenance section. must be immediately corrected.
FIGURE 8 The Restriction Assembly has a
ALARM VENT TRIM KIT 1/8 inch (3,2 mm) diameter drain Inspection Procedure
orifice. Sufficient time must be It is recommended that the following
allowed for drainage of the Retard inspection procedure be performed at
NOTICE
Care and tor’s Test Connection (or Alarm
Test Valve, if acceptable to the
Filling the system with water will result Maintenance authority having jurisdiction) and
verify that the system alarms
in operation of the associated alarms. The following procedures and operate in accordance with the
Consequently, notification must first be inspections should be performed as requirements of the authority
given to the owner and fire department, indicated, in addition to any specific having jurisdiction. Verify that
central station, or other signal station to requirements of the NFPA. Any impair- the water motor alarm and/or the
which the alarms are connected. ment must be immediately corrected. pressure alarm switch properly
Notify the proper authorities and all actuate and within the elapsed
personnel who may be affected that NOTICE time required by the authority
an alarm test is to be performed. having jurisdiction.
Performing the care and maintenance
After placing a fire protection system procedures will result in operation of 3. Verify that water is flowing out
in service, notify the proper authorities the associated alarms. Consequently, of the alarm line drain at a rate
and advise those responsible for moni- notification must first be given to the consistent with the 1/8 inch (3,2
toring proprietary and/or central station owner and fire department, central mm) diameter drain orifice in the
alarms. station, or other signal station to which Restriction Assembly.
the alarms are connected. 4. Close the end-of-line Inspector’s
1. Open the 1/4 inch Gauge Test
Valves for the Supply and System Before closing a fire protection system Test Connection (or Alarm Test
Pressure Gauges. main control valve for maintenance Valve).
work on the fire protection system 5. Verify that water ceases to flow
2. Check to see that the Hand-hole that it controls, obtain permission to
Cover bolts are tight. If not, cross- from the alarm line drain.
shut down the affected fire protec-
tighten them. tion system from the proper authori- 6. Clean the 1/2 inch Strainer
3. Close the Alarm Test Valve. ties and notify all personnel who may (located in the valve trim) as well
be affected by this decision. as the 3/4 inch Strainer (located at
4. Open the remote cross main the connection to the water motor
or branch line vent connection. alarm, as applicable). Be sure to
(Refer to Step 7 in the Installation replace the strainer baskets and
section.) tighten the caps securely.
TFP910
Page 18 of 22
4 Inch Valves with NPT Ports 6 Inch Valves with NPT Ports 8 Inch Valves with NPT Ports
ISO (PN16) Flange x ANSI Flange x ISO (PN10) Flange x
4.50 inch (114,3 mm) 6.50 inch (165,1 mm) 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-493 Groove O.D. . . . . . . . . . . P/N 52-203-1-625 Groove O.D. . . . . . . . . . . P/N 52-203-1-896
ISO (PN16) Flange x ISO (PN16) Flange x ISO (PN16) Flange x
ISO (PN16) Flange. . . . . . P/N 52-203-4-013 6.62 inch (168,3 mm) 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-695 Groove O.D. . . . . . . . . . . P/N 52-203-4-266
AS Flange x
AS Flange. . . . . . . . . . . . P/N 52-203-4-313 ISO (PN16) Flange x ISO (PN10) Flange x
6.50 inch (165,1 mm) ISO (PN10) Flange. . . . . . P/N 52-203-4-016
AS Flange x Groove O.D. . . . . . . . . . . P/N 52-203-5-215
4.50 inch (114,3 mm) ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-4-413 ISO (PN16) Flange x ISO (PN16) Flange. . . . . . P/N 52-203-4-118
ISO (PN16) Flange. . . . . . P/N 52-203-4-015
JIS Flange x AS Flange x
JIS Flange. . . . . . . . . . . . P/N 52-203-4-713 AS Flange x AS Flange. . . . . . . . . . . . P/N 52-203-4-316
AS Flange. . . . . . . . . . . . P/N 52-203-4-315
JIS Flange x AS Flange x
4.50 inch (114,3 mm) AS Flange x 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-813 6.62 inch (168,3 mm) Groove O.D. . . . . . . . . . . P/N 52-203-4-416
Groove O.D. . . . . . . . . . . P/N 52-203-4-415
4 Inch Valves with ISO Ports JIS Flange x
AS Flange x JIS Flange. . . . . . . . . . . . P/N 52-203-1-716
ISO (PN16) Flange x 6.50 inch (165,1 mm)
ISO Flange . . . . . . . . . . . P/N 52-203-4-113 JS Flange x 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-425
Groove O.D. . . . . . . . . . . P/N 52-203-4-816
ISO (PN16) Flange x JIS Flange x
4.50 inch (114,3 mm) JIS Flange. . . . . . . . . . . . P/N 52-203-4-715 8 Inch Valves with ISO Ports
Groove O.D. . . . . . . . . . . P/N 52-203-4-213
JIS Flange x ISO (PN10) Flange x
4.50 inch (114,3 mm) Groove O.D x 6.62 inch (168,3 mm) ISO (PN10) Flange. . . . . . P/N 52-203-4-116
4.50 inch (114,3 mm) Groove O.D. . . . . . . . . . . P/N 52-203-4-815 ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-1-923
JIS Flange x ISO (PN16) Flange. . . . . . P/N 52-203-4-117
6.50 inch (165,1 mm) ISO (PN10) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-5-815 8.62 inch (219,1 mm)
6.50 inch (165,1 mm) Groove O.D x Groove O.D. . . . . . . . . . . P/N 52-203-4-216
6.50 inch (165,1 mm) ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-1-124 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-226
6 Inch Valves with ISO Ports
8.62 inch (219,1 mm) Groove O.D. x
ISO (PN16) Flange x
8.62 inch (219,1 mm)
ISO (PN16) Flange. . . . . . P/N 52-203-4-115
Groove O.D. . . . . . . . . . . P/N 52-203-1-926
ISO (PN16) Flange x
6.62 inch (168,3 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-215
ISO (PN16) Flange x
6.50 inch (165,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-225
6.62 inch (168,3 mm) Groove O.D. x
6.62 inch (168,3 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-925
6.50 inch (165,1 mm) Groove O.D. x
6.50 inch (165,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-125
TFP910
Page 22 of 22