You are on page 1of 12

Renewable Energy 167 (2021) 530e541

Contents lists available at ScienceDirect

Renewable Energy
journal homepage: www.elsevier.com/locate/renene

Field experiments on the effects of an earth-to-air heat exchanger on


the indoor thermal environment in summer and winter for a typical
hot-summer and cold-winter region
Haibin Wei a, b, Dong Yang a, b, *, Jinhui Du a, b, Xin Guo a, b
a
School of Civil Engineering, Chongqing University, Chongqing, 400045, China
b
National Centre for International Research of Low-carbon and Green Buildings, Chongqing University, Chongqing, 400045, China

a r t i c l e i n f o a b s t r a c t

Article history: An earth-to-air heat exchanger (EAHE) is a shallow geothermal energy utilization technology, which can
Received 13 August 2020 significantly reduce the building energy consumption. This study aims to investigate the effects of an
Received in revised form EAHE on the indoor thermal environment in hot-summer and cold-winter regions. A full-scale experi-
11 November 2020
ment was conducted for a continuous 24 h period using two identical buildings (with and without an
Accepted 21 November 2020
Available online 24 November 2020
EAHE) exposed to the same outdoor conditions on typical summer and winter days. Experimental results
show that the EAHE provides an average outdoor air temperature reduction of 9.12  C under cooling
conditions and increase of 5.53  C under heating conditions. Moreover, the average outdoor air relative
Keywords:
Earth-to-air heat exchanger
humidity increases by 46.89% and decreases by 27.41% in the cooling and heating conditions, respec-
Building energy tively; the corresponding average EAHE coefficients of performance (COP) are 7.03 and 4.26, respectively.
Indoor thermal environment Compared to that of the building without EAHE, the average indoor air temperature of the building with
Ventilation EAHE decreases by 5.9  C in summer and increases by 4.29  C in winter, and the average walls’ internal
surface temperature decreases by approximately 6  C and increases by approximately 5.8  C. Moreover,
the EAHE system reduces the average building cooling and heating loads by 55.4 and 40.43 W/m2,
respectively.
© 2020 Elsevier Ltd. All rights reserved.

1. Introduction owing to its simple structure and low maintenance operability [5].
Owing to the high thermal inertia of soil, the underground soil
Energy consumption in the building sector accounts for temperature variation lags behind the outdoor air temperature, and
approximately 40% of the total global energy consumption, and a the soil temperature becomes nearly constant at sufficiently large
major portion of this (approximately 32e33%) is used for space depths (typically 3 m); the soil temperature is lower/higher than
heating, ventilating, and air conditioning systems [1]. Most of the the outdoor air temperature in summer/winter. EAHEs use the
energy required for these purposes is derived from non-renewable underground soil as a heat source/sink and ventilation air as a heat
fossil fuels, such as coal, oil, and natural gas, which can cause exchange medium. The outdoor air is drawn through pipes buried
serious problems like environmental pollution and energy short- in the soil and exchanges heat with the surrounding soil directly
ages. Accordingly, renewable energy alternatives have been widely [6]. The air is pre-cooled in summer and pre-heated in winter
investigated to achieve indoor thermal comfort and reduce energy before entering the interior building spaces, which could reduce
consumption and carbon emissions [2e4]. In recent years, earth-to- both the cooling and heating loads of buildings and in turn reduce
air heat exchangers (EAHEs), also called ground air tubes or earth- the electricity consumption.
air-tube ventilation systems, have attracted considerable attention The effectiveness of EAHE ventilation systems is closely related
as a shallow geothermal energy efficient utilization technology to their thermal performance, and various experimental, analytical,
and simulation studies have been conducted on this aspect in the
last few decades [7]. Hollmuller et al. [8] developed an analytical
solution for the heat diffusion of a cylindrical EAHE with a har-
* Corresponding author. School of Civil Engineering, Chongqing University,
Chongqing, 400045, China.
monic inlet air temperature and adiabatic or isothermal boundary
E-mail address: yangdong@cqu.edu.cn (D. Yang). conditions. Bansal et al. [9,10] investigated horizontal EAHE

https://doi.org/10.1016/j.renene.2020.11.112
0960-1481/© 2020 Elsevier Ltd. All rights reserved.
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

temperature rise of 14.0  C was provided by the EAHE and a further


Nomenclature 12.1  C increase was provided by the heat recovery unit; overall, the
outdoor air could reach an acceptable temperature. Benhammou
d diameter of the buried pipe (m) et al. [19] developed a dynamic model to examine the combined
m air mass flow rate (kg/s) effect of thermal insulation and the EAHE on the thermal perfor-
Q heating/cooling capacity of EAHE (W) mances of buildings in desert regions. Based on the time lag and the
QR reduction of building cooling/heating load by decrement factor theory, Rosti et al. [20] investigated the optimum
EAHE (W) thermal insulation configuration in buildings with EAHE. Their
T temperature ( C) results showed that walls with an external single-layer insulation
V velocity of airflow in pipe (m3/s) and two layers of insulation (middle and external) showed the best
W energy consumption of the flowing air (W) performance for the buildings fitted with the EAHE. Compared to a
traditional ventilation system, the reduction in the building energy
Subscripts consumption using EAHEs can reach 7 and 9 kW h/m2 per year
in EAHE inlet when the pipes were buried at depths of 0.6 and 2 m, respectively
out EAHE outlet [21]. Ascione et al. [22] reported that, compared to a mechanical
s soil ventilation system, the EAHE ventilation system could contribute to
1 Room 1 a building energy reduction of approximately 29% in winter and
2 Room 2 36e46% in summer for the Mediterranean climate. Al-Ajmi et al.
[23] proposed a numerical model to determine the efficiency of an
Greek symbols EAHE system for residential buildings located in the hot and dry
Cp air specific heat (J/(kg K)) climate of Kuwait. Results showed that the EAHE system could
ra air density (kg/m3) decrease the cooling load by 1700 W and reduce the indoor air
h heat exchange efficiency of EAHE (%) temperature by 2.8  C. Moreover, Yang et al. noted that the effects of
coupling EAHEs with the building thermal mass could also main-
Abbreviations tain a comfortable indoor thermal environment and proposed the
COP coefficient of performance corresponding theoretical model for the buoyancy-driven natural
EAHE earth-to-air heat exchanger ventilation [24] and mechanical ventilation [25].
According to the literature review, the current research on EAHE
is mainly divided into two main trends: the EAHE thermal perfor-
mance and the flow performance of EAHE [3,5,26,27]. However, the
systems with two different pipe materials in India for both winter two trends are both focused on examining/improving the cooling/
and summer conditions. Their experimental results indicated that heating capacity and energy efficiency of the EAHE itself. It is worth
the performance of the EAHE system was not significantly affected noting that the effects of EAHEs on the indoor environment are also
by the material of the buried pipe, but was significantly affected by important. Although researchers have made efforts to investigate
the air velocity through the buried pipe. Liu et al. [11] proposed a EAHEs applications under various climatic conditions, the thermal
vertical EAHE system and developed a numerical model to evaluate performance of EAHEs in hot-summer and cold-winter regions can
its thermal performance [12]. To improve the performance of hardly be assessed. In addition, most of the previous studies
EAHEs further, an EAHE system was integrated with a layer of phase focused on the heat transfer performance of EAHEs, and only few
change material to stabilize the outlet air temperature [13]. Wei studies were conducted from the perspective of integrating EAHEs
et al. [14] developed a full-scale experimental platform to investi- with the building indoor environment.
gate the cooling capability of EAHEs with four configuration pa- To overcome the above-mentioned limitations, in this study, a
rameters in hot and humid climate. Their results indicated that full-scale experimental apparatus was constructed to investigate
increases in depth and decreases in diameter cause decreases in the the effects of EAHEs on the indoor thermal environment in hot-
air temperature/moisture content, and that the air temperature summer and cold-winter regions. This study was conducted dur-
decays exponentially with increasing pipe length. Pakari et al. [15] ing the cooling and heating season under the climatic conditions of
experimentally studied the performance of an EAHE with a short- Chongqing, a city in southwest China. The experimental study was
grass ground cover under hot and dry desert climate. Their re- conducted to evaluate the performance of the EAHE system and its
sults indicated that with an airflow velocity of 9.24 m/s, the inlet air cooling/heating potential for regulating the indoor thermal envi-
temperature was reduced from 40.6 to approximately 34.1  C, and ronment. The variation in the air temperature, relative humidity,
the corresponding coefficient of performance obtained was 13.4. thermal capacity, coefficient of performance (COP), and heat
Wei et al. [16] and Yang et al. [17] presented theoretical models for transfer efficiency of an EAHE were analyzed.
evaluating the heat transfer performances of flat rectangular and
circular EAHEs in harmonically fluctuating thermal environments, 2. Experimental methods
and they compared the differences in their thermal performances.
The results indicated that the outlet air temperature fluctuation 2.1. Experimental apparatus
amplitudes of the flat rectangular EAHE was lower, the phase shift
was larger, and the EAHE pipe wall temperature was more stable The full-scale test apparatus was installed in Chongqing, which
compared to those of the circular EAHE. has a typical hot/humid and cold/humid climate [28]. Generally, the
In addition, EAHEs have been applied in several types of build- outdoor air temperature is higher/lower than the thermal comfort
ings, including office buildings, commercial buildings, residential range in summer/winter, and the outdoor air relative humidity is
buildings, and agricultural greenhouses, in various climates. For high throughout the year. This brings a fresh air load to the building
example, Li et al. [18] developed a fresh air handling system indoor environment. Fig. 1 shows the experimental apparatus,
comprising two double-layered horizontal U-shaped EAHEs and a which consists of the EAHE ventilation system and two tested
heat recovery unit to study its feasibility and application in severe buildings. In the experiment, No. II system was selected for building
cold regions. Their experimental results indicated that an average ventilation.
531
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Fig. 1. Schematic of the full-scale test apparatus.

2.1.1. EAHE system addition, the building floors were insulated with 0.02 m-thick
From Fig. 1, it can be seen that the EAHE system included three rubber and plastic to reduce heat transfer interference from the
main components: the vertical inlet component, vertical outlet ground. The pre-cooled/pre-heated air was sent to Room 1 using
component, and horizontal main component. The EAHE consisted the roof air supply terminus, and the indoor air was exhausted
of a PVC pipe with a diameter of 0.16 m, and wall thickness of through the leakages of the door and windows. An indoor heat
0.0032 m. It is well known that the temperature of the soil at a source load of 66 W was applied to the two rooms, which is caused
depth of approximately 2e3 m remains fairly constant [29,30]. The by the devices of the computer and data recorder. During the
burial depth of the horizontal component pipe was set to 3 m. The experiment test operation, all the doors and windows of the two
length of the vertical inlet and outlet components were both 3 m, rooms were closed, and shading measures were adopted to prevent
and the length of the main horizontal component was 40 m. To the solar radiation heat gain through the windows. In addition, the
alleviate the thermal interaction between the air inside the vertical occupancy regime of the rooms was empty during the test.
components and surrounding soil, the vertical inlet and outlet
components of the buried pipes were both insulated with a 0.02 m-
thick rubber and plastic layer. Therefore, only the horizontal com- 2.2. Measurement layout
ponents of the buried pipes cooled/heated the flowing air during
the operation period. The pipes were separated by a distance of As shown in Fig. 1, nine type-T thermocouples (T2-1 to T2-9)
0.7 m, which is approximately eight times the pipe radius, to were located in the center of the buried pipe along the horizontal
eliminate the interaction between the thermal waves of different part to measure the EAHE air temperature variation. All the tem-
pipes; thus, each pipe can be treated independently [23,25]. The perature measurement points inside the pipe were set approxi-
vertical outlet component of the EAHE was connected to Room 1 mately 5 m from one another. The measurement points for the
and directly supplied the outdoor fresh air into the building interior original soil temperature were set at depths of 1, 2, and 3 m, which
space. The vertical inlet component of the EAHE was equipped with were labeled as TS-10, TS-11, and TS-12, respectively. To obtain the
a blower, in which the outdoor air was driven into the buried pipe building surface temperature variation, eight type-T thermocouples
and exchanged heat with the surrounding soil. In addition, the (TW1-1 to TW1-8 and TW2-1 to TW2-8) were attached to the
horizontal components of the buried pipes were set at a small slope external and internal surfaces of the two tested buildings (as shown
along the flow direction for the condensate water collection and in Fig. 3). In addition, eight type-T thermocouples (TB1-1 to TB1-8
drainage. and TB2-1 to TB2-8) were distributed within the space of the two
test buildings to measure the indoor air temperature. All the ther-
mocouples were calibrated prior to the experiments and connected
2.1.2. Tested buildings to an Agilent data logger (Keysight 34980 A, USA) for data collec-
Two identical light buildings (Room 1 and Room 2) were tion. The air relative humidity variations at the EAHE inlet/outlet
considered in the present study. Each building has dimensions of and the indoor space were measured by humidity/temperature
3 m (length)  3 m (width)  2.7 m (height). Room 1 was connected data loggers. The relative humidity and temperature data were
to the vertical outlet component of the EAHE, and Room 2, as a recorded every min during the tests. The power consumption of the
reference room, was not equipped with any ventilation and cool- blower (HP12038HSL, 0e350 m3/h, China) was measured using a
ing/heating systems. The two tested buildings were adjacent to power meter, while the airflow velocity inside the buried pipe was
each other and insulated with 0.02 m-thick rubber and plastic, and measured by a hot wire anemometer. The air velocity through the
0.05 m-thick glass fiber to avoid any thermal interference (as EAHE buried pipe was regulated using a frequency convertor. In
indicated in Fig. 2). The details of the materials used in constructing addition, the ring method of equivalent area was adopted to mea-
the buildings are given in Table 1. The building envelopes for the sure the mean velocity, and the mean velocity was obtained by
two rooms were the same; they were composed of a 0.05 m-thick averaging the velocities measured at the measuring points in the
glass fiber and exposed to the same outdoor environment. In cross sections [18,31,32]. The detailed specifications of the
532
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Fig. 2. Pictures of the field experiments.

Table 1
Properties of the construction components of the test buildings (from inside to outside).

Envelope component Material Thickness (m) Thermal conductivity (W/m K) Heat transfer coefficient (W/m2 K)

Roof Iron sheet 0.002 52.00


Glass fiber 0.05 0.036 0.72
Iron sheet 0.002 52.00
Wall Iron sheet 0.002 52.00
Glass fiber 0.05 0.036 0.72
Iron sheet 0.002 52.00
Floor Rubber and plastic 0.02 0.034 1.24
Asbestos cement 0.02 0.093
Window Glass 0.01 0.76 2.4
Polystyrene 0.1 0.1

Fig. 3. Temperature measurement diagram of indoor air and wall surface.

equipment are presented in Table 2. external/internal wall surface were also investigated. An airflow
velocity of 4.2 m/s was fixed during the above experiments, the
corresponding building changes of air per hour was 12.5.
3. Results and discussion

In order to investigate the thermal performance of the EAHE on 3.1. Thermal behavior of EAHE
the indoor thermal environment in hot-summer and cold-winter
regions, the experiments for the cooling mode and heating mode 3.1.1. Temperature of ambient air and soil
were conducted continuously for 24 h from 11:00 on 2019/9/12 to Fig. 4 (a) and (b) illustrate the variation in the ambient air and
11:00 on 2019/9/13 and from 17:00 on 2020/1/18 to 17:00 on 2020/ soil temperature over 24 h during the summer and winter opera-
1/19, respectively. During the experimental test, EAHE system was tion periods, respectively. The measurement points of the soil
ventilated all day. Based on the experimental results, the variations temperature corresponded to the soil depth of 1, 2 and 3 m. It is
in the air temperature and relative humidity of the EAHE were clearly seen that during the summer and winter periods, the vari-
analyzed. The temperature variations in the indoor air and ation in the original soil temperature at different depths is lower
533
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Table 2
Accuracy and range of the instruments used in this study.

Measured parameter Instrument Type Range and accuracy

Temperature Type T thermocouple Omega TT-T-24, USA 0e350  C, ±0.5  C


Relative humidity Humidity/temperature logger HIOKI-LR5001, Japan 40e85  C, ±0.5  C
0%e100rh, ±5%rh
Air velocity Thermal anemometer Testo-480, Germany 0e10 m/s, ±0.03 m/s
Electric consumption Digital power meter PM9805, China 0e2000W, ±5%W

than that of the outdoor air temperature mainly due to the strong mainly due to the thermal response of the soil around the buried
thermal inertia of the soil. In addition, the temperature distribution pipe. As the pipe length increases from 0 to 40 m, the initial average
of the soil has an obvious stratification by depth. In summer, the air temperature of 32.37  C decreases continuously to 23.28  C
shallower soil temperature is higher than that of the deeper soil. (change of 9.1  C). The maximum reduction in the air temperature
The opposite trend is observed in winter. Fig. 4 (a) reveals that between the inlet and outlet of the EAHE is 15  C, which occurs at
during the summer operation period, the outdoor air temperature 15:04 and can be attributed to the reduction from 38.47  C at the
varies within a range of 27.79e38.51  C (the temperature difference inlet to 23.47  C at the outlet. The minimum reduction in the air
and average being 10.72 and 32.37  C, respectively). The original temperature is found to be 4.82  C, which occurs at 2:41; this can be
soil temperature at the depths of 1, 2, and 3 m vary in the range of attributed to the reduction from 27.89  C at the inlet to 23.06  C at
25.41e25.82  C, 22.52e22.88  C, and 20.04e20.32  C, respectively, the outlet. During the cold winter operation period, as shown in
and the corresponding average temperatures are 25.63, 22.74, and Fig. 5 (b), the reasons for the EAHE air temperature variation in
20.21  C, respectively. Fig. 4 (b) shows that during the winter winter are similar to those in summer. As the pipe length increases
operation period, the outdoor air temperature varies within a range from 0 to 40 m, the average air temperature increases continuously
of 3.95e15.54  C (the temperature difference and average being from 8.53 to 14.06  C (change of 5.53  C). The maximum increase in
11.59 and 8.53  C, respectively). The original soil temperatures at the air temperature between the inlet and outlet of the EAHE is
the depths of 1, 2, and 3 m vary in the range of 11.71e12.01  C, 9.11  C, which occurs at 7:21; this can be attributed to the increase
14.92e15.24  C, and 16.51e16.76  C, respectively; the correspond- from 3.96  C at the inlet to 13.07  C at the outlet. The minimum
ing average temperatures are 11.87, 15.1, and 16.68  C, respectively. increase in the air temperature between the inlet and outlet of the
The EAHE ventilation system is designed for the cooling/heating of EAHE is 0.8  C, which occurs at 15:11; this is attributed to the
buildings to reduce the energy consumption and peak demand; the reduction from 15.64  C at the inlet to 14.37  C at the outlet, which
results reveal that the soil temperature range is suitable for is due to the air temperature being higher than the soil temperature
achieving this purpose. during the daytime. From the results reported in Fig. 5 (a) and (b), it
can be seen that the EAHE can effectively exploit the shallow
3.1.2. Temperature variation along pipe length geothermal soil as a natural heat sink/source in summer/winter to
Fig. 5 (a) and (b) show the variation in the air temperatures cool/heat the outdoor air temperature and stabilize the outlet air
along the horizontal pipe length of the EAHE over 24 h during the temperature.
summer and winter periods, respectively. During the hot summer
operation period, as shown in Fig. 5 (a), the temperature difference 3.1.3. Relative humidity at inlet/outlet of EAHE
along the pipe length is small at night, whereas the distinct tem- Fig. 6 (a) and (b) show the variation in the air relative humidity
perature variations can be observed during the daytime. This is at the inlet/outlet of EAHE over 24 h during the summer and winter
mainly because the outdoor air temperature is close to the soil operation periods, respectively. As can be seen from Fig. 6 (a),
temperature at the depth of 3 m at night, whereas it is much higher during the summer operation period, the relative humidity of the
than the soil temperature during the day. In addition, the air inlet and outlet air of EAHE changes from 31.8 to 67.5% (average of
temperature fluctuation amplitudes at different pipe lengths 51.08%) and from 82 to 97.97% (average of 90.38%), respectively.
gradually attenuate, and the phase shift has a small lag, which is This corresponds to an increase in the average relative humidity of

Fig. 4. Variation in the ambient air and soil temperature during the operation period: (a) summer and (b) winter.

534
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Fig. 5. Variation in the air temperatures along the horizontal pipe length of EAHE during the operation period: (a) summer and (b) winter.

the outlet air of 46.89%. Fig. 6 (b) shows that during the winter over 24 h during the summer and winter operation periods,
operation period, the relative humidity of the EAHE inlet and outlet respectively. During the summer, the temperature at the external
air varies from 47.3 to 90.8% (average of 85.52%) and from 49.3 to surface of the roof wall varies within a range of 23.72e70.47  C,
69.5% (average of 58.11%). This indicates that the average relative corresponding to a temperature difference of 46.75  C. The tem-
humidity of the outlet air decreased by 27.41%. The air relative peratures at the external surfaces of the eastern and western walls
humidity was a significantly different between the inlet and outlet vary within a range of 24.55e53.84  C and 22.93e60.33  C,
of the EAHE, and the air relative humidity at the EAHE outlet does respectively, corresponding to temperature ranges of 29.29 and
not reach a saturated state in summer and winter. This means that 37.4  C, respectively. The temperatures of the southern and
humidification and condensation do not occur during the heat northern external walls vary from 24.58 to 52.45  C and from 23.35
transfer process inside the EAHE and that mainly a sensible heat to 38.71  C, respectively; their corresponding temperature ranges
transfer occurred in the cooling/heating process. This is mainly are 27.87 and 15.36  C, respectively. Ref. [19] indicated that the
because the velocity of airflow in the buried pipe is too large, temperature at the external surface of each external wall is pro-
causing an insufficient heat exchange between the flowing air and portional to the intensity of the solar radiation incident on it. It can
the surrounding soil. At the outlet of the EAHE, the air temperature be shown clearly that all temperature curves vary in the same
does not reach the corresponding dew point temperature, and the manner during the night (from 18:00 on 2019/9/12 to 7:00 on 2019/
air relative humidity does not reach a saturated state in summer 9/13) and all the external surface temperatures are lower than the
and winter. Previous studies [14,18,32] have shown that the air outdoor air temperature.
relative humidity of the EAHE outlet can be adjusted by the buried During the winter operation period, the temperature at the
depth, pipe length, diameter, and airflow velocity parameters. external surface of the roof wall varies from 7.8 to 38.03  C
(temperature difference of 45.83  C), as shown in Fig. 7 (b). The
3.2. Thermal behavior of buildings temperatures at the external surfaces of the eastern and western
walls vary from 0.87 to 16.56  C and from 0.87 to 25.2  C,
3.2.1. External surface temperature respectively, corresponding to temperature ranges of 18.43 and
Fig. 7 (a) and (b) present the variation in the temperature at the 26.07  C, respectively. The temperatures of the southern and
external surface of the building envelope in different orientations northern external walls vary from 0.69 to 28.4  C and from 0.97

Fig. 6. Variation in the air relative humidity at the inlet/outlet of EAHE during the operation period: (a) summer and (b) winter.

535
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Fig. 7. Variation in the temperature at the external surfaces of the building envelope in different orientations: (a) summer and (b) winter.

to 15.02  C, respectively, and corresponding to temperature ranges 23.81e33.38  C with temperature range and average value of
of 29.09 and 15.99  C, respectively. The external surface tempera- approximately 9.57 and 26.98  C, respectively.
tures of the vertical walls facing east, west, south, and north vary in For the building without the EAHE, as shown in Fig. 8 (b), the
the same manner from 17:00 on 2020/1/19 to 13:30 on 2020/1/20 temperatures at the internal surfaces of the roof and south wall
and differently from 13:30 on 2020/1/20 to 17:00 on 2020/1/20. In oscillate in the same manner within a range of 25.89e46.54  C (the
addition, all the external surface temperatures are lower than the corresponding temperature range and average value are approxi-
outdoor air temperature, which is mainly due to the cold sky ra- mately 20.65 and 33.54  C, respectively). The internal surface
diation in winter. temperatures of the east and north walls oscillate in the same
manner within a range of 25.74e42.96  C (their corresponding
3.2.2. Internal surface temperature temperature difference and average value are approximately 17.22
Fig. 8 (a) and (b) show the variation in the temperatures at the and 32.7  C, respectively). By comparing the results of Fig. 8 (a) and
internal surface of the building envelop in different orientations (b), it is found that the average value of the building internal surface
during the summer operation period with and without the EAHE, temperatures with EAHE is approximately 6  C lower than that
respectively. It is evident that all the temperatures at the internal without the EAHE, and the corresponding temperature range of the
surface vary as a sinusoidal function with a period of 24 h, but their internal surface temperature of the building wall is reduced by
fluctuation amplitudes are different. For the building with the approximately 9.5  C. This indicates that the EAHE ventilation
EAHE, as shown in Fig. 8 (a), the temperature at the internal surface system can help reduce and stabilize the internal surface temper-
of the roof wall varies within a range of 23.84e34.74  C (the tem- ature in summer and winter.
perature difference and average of approximately 10.9 and 27.66  C, Fig. 9 (a) and (b) show the variation in the temperatures at the
respectively). The internal surface temperature of the south wall internal surface of the building envelop with and without the EAHE,
varies as that of the roof, but with slightly lower fluctuation respectively, in different orientations during the winter operation
amplitude and maximal values; it oscillates within a range of period. From Fig. 9 (a), it can be seen that all the internal surface
23.9e33.65  C (the temperature difference and average of 9.75 and temperatures of the building with EAHE oscillate in the same
27.27  C, respectively). The internal surface temperatures of the manner within a range of 9.75e16.97  C (the temperature differ-
west and north walls oscillate in the same manner within a range of ence and average are approximately 7.2 and 12.41  C, respectively).

Fig. 8. Variation in the temperatures at the internal surfaces of the building envelop in different orientations in summer: (a) with EAHE and (b) without EAHE.

536
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

From Fig. 9 (b), it can be seen that for the building without EAHE, all indoor air temperature is reduced by approximately 8.8  C. In
the internal surface temperatures also oscillate in the same manner addition, the average indoor air relative humidity is decreased by
within a range from 2.71e13.72  C, except between 13:30 and 17:00 approximately 21.2% when using the EAHE.
on 2020/1/20. Their corresponding temperature range and average Fig. 11 (a) and (b) show the frequency of occurrence of the in-
are approximately 11.01 and 6.62  C, respectively. By comparing the door air temperature with and without EAHE during the summer
results of Fig. 9 (a) and (b), it is found that the average value of the and winter operation periods, respectively. It can be seen from
building internal surface temperature with EAHE are approxi- Fig. 11 (a) that during the summer operation period, when the EAHE
mately 5.8  C higher than that without EAHE, and the corre- is not employed, the indoor temperature is greater than 28  C for
sponding range of the internal surface temperature of building wall more than 67.18% of the 24 h period; in contrast, when the EAHE
is reduced by approximately 3.8  C. This indicates that the EAHE ventilation system is used, the indoor air temperature exceeds
ventilation system can help increase and stabilize the internal 28  C for only 32.89% of the 24 h period. From Fig. 11 (b), it can be
surface temperature in winter. seen that during the winter operation period, when the EAHE
ventilation measure is not adopted, the indoor temperature is less
3.2.3. Temperature and relative humidity of indoor environment than 12  C for more than 82.99% of the 24 h period; in contrast,
Fig. 10 (a) and (b) show that a comparison between the indoor when the EAHE ventilation system is used, the indoor air temper-
air temperature and relative humidity of the buildings with and ature is below 12  C for only 22% of the 24 h period. Therefore, the
without the EAHE during the summer and winter operation pe- EAHE ventilation measure can effectively improve the thermal
riods, respectively. As shown in Fig. 10 (a), during the summer comfort of the indoor environment.
operation period, the indoor air temperature of the building
without EAHE oscillates within a range of 25.97e43.16  C (the
temperature difference and average are 17.19 and 32.74  C, 4. Performance evaluation of EAHE
respectively). For the building with EAHE, the indoor air tempera-
ture oscillates within a range of 23.89e32.21  C (the temperature 4.1. Thermal capacity and coefficient of performance of EAHE
difference and average are 8.32 and 26.86  C, respectively). Fig. 10
(a) also indicates that the indoor air relative humidity of the The heating/cooling capacity of EAHE is determined as follows
building with and without EAHE varies within a range of [16,19,33]:
51.7e84.1% (average of 71.48%) and 31.6e70.7% (average of 53.63%), 
mCp ðTin  Tout Þ Summer
respectively. Furthermore, the results indicate that compared to the Q¼ (1)
mCp ðTout  Tin Þ Winter
building without the EAHE, the average indoor air temperature and
range are reduced by approximately 5.9 and 8.9  C when using the
where Q is the EAHE heating/cooling capacity (W), Cp is the air
EAHE. In addition, the average indoor air relative humidity is
specific heat (1005 J/(kg K)), Tin is the inlet air temperature of EAHE
increased by approximately 17.85% when using the EAHE.
( C), Tout is the outlet air temperature of EAHE ( C). The air mass
As shown in Fig. 10 (b), during the winter operation period, the
flow rate through the buried pipe is m ¼ ra pd2 V=4, ra is the air
indoor air temperature of the building without the EAHE oscillates
density (1.29 kg/m3), V is the air velocity (m3/s), d is the diameter of
within a range of 3.61e18.33  C (the temperature difference and
the buried pipe (m).
average are 14.72 and 8.6  C, respectively). For the building with
The coefficient of performance (COP) of the EAHE is based on the
EAHE, the indoor air temperature oscillates within a range of
amount of cooling/heating produced by EAHE and the total elec-
10.54e16.48  C (the temperature difference and average are 5.94
tricity consumptions required for circulating air through heat
and 12.89  C, respectively). Fig. 10 (b) also indicates that the indoor
exchanger, and determined by Ref. [19,34]:
air relative humidity of the building with and without the EAHE
varies within a range of 47.3e69.8% (average of 61.15%) and Q
55.2e89.2% (average of 82.35%), respectively. Furthermore, the re- COP ¼ (2)
W
sults indicate that compared to the building without the EAHE, the
average indoor air temperature is increased by approximately where W is the blower power consumption (W).
4.29  C when using the EAHE, and the corresponding range of the Fig. 12 (a) and (b) show the variation in the thermal capacity and

Fig. 9. Variation in the temperatures at the internal surface of the building envelop in different orientations in winter: (a) with EAHE and (b) without EAHE.

537
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Fig. 10. Variation in the indoor air temperature and relative humidity with and without EAHE during the operation period: (a) summer and (b) winter.

Fig. 11. Frequency of occurrence of the indoor air temperature with and without EAHE: (a) summer and (b) winter.

COP of the EAHE during the summer and winter operation periods,
respectively. The average energy consumption of the blower is 8
>
> Tin  Tout
approximately 110 W during the summer and winter operation >
<  100% Cooling
Tin  Ts
periods. As shown in Fig. 12 (a), during the summer operation h¼ (3)
>
> Tout  Tin
period, the cooling capacity and COP of the EAHE vary in the range >
:  100% Heating
of 409.11e1272.63 W and 3.72e11.57, respectively, and their cor- Ts  Tin
responding average values of 773.59 W and 7.03. As shown in Fig. 12
(b), during the winter operation period, the heating capacity and where h is the heat exchange efficiency of EAHE (%), Ts is the soil
COP of the EAHE vary from 67.52 to 772.67 W and from 0.62 to original temperature at the pipe buried depth ( C). The corre-
7.02, respectively, and their corresponding average values of sponding soil original temperature can be obtained according to
469.07 W and 4.26. As the average COPs of the EAHE in summer and section 3.1.1.
winter are almost 7.03 and 4.26, respectively, the cooling and Fig. 13 shows the relation of the heat transfer efficiency (h) and
heating energy provided by the EAHE is almost seven and four inlet air temperature for the EAHE during the summer and winter
times greater than the electrical energy consumed by the system, operation periods. It can be seen that under the heating mode, the
respectively. Thus, it can be concluded that the integration of the heat transfer efficiency decreases sharply with the increase in the
EAHE in buildings is an economic technique permitting the air EAHE inlet temperature. When the EAHE inlet temperature varies
conditioning of buildings with a lower cost. from 3.95 to 15.54  C, h varies from 71.48% to 0, and h is zero when
the inlet air temperature is very close to the original soil temper-
ature (15.54  C). In contrast, under the cooling mode, the heat
transfer efficiency shows a slow growth with the increase in the
4.2. Heat transfer efficiency of EAHE EAHE inlet temperature. The variation range of heat transfer effi-
ciency under the cooling mode is much narrower than that under
The heat transfer efficiency of EAHE system is the ratio of actual the heating mode. When the EAHE inlet temperature varies from
temperature drop/rise of EAHE outlet air to the maximum possible 27.79 to 38.51  C, h varies from 62.82 to 81.71%, which maintains a
temperature drop/rise of EAHE outlet air, the theoretical heat ex- high level as the inlet air temperature is higher than the soil tem-
change efficiency of EAHE was calculated using the following perature in this range. Ref. [32] presented a similar relation be-
equation [35,36]: tween the heat transfer efficiency and inlet air temperatures of the
538
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Fig. 12. Variation in the thermal capacity and COP of EAHE: (a) summer and (b) winter.

Generally, the reduction in the cooling/heating load by the EAHE


depends on the building parameters, EAHE engineering parame-
ters, and outdoor environmental conditions. The results of simple
calculations showed that the reduction in the cooling/heating load
using the EAHE exhibits harmonic changes with time due to the
combined effects of the building cooling/heating load and the EAHE
ventilation system. Fig. 14 (a) shows that during the summer
operation period, the reduction in the cooling load by EAHE varies
within a range of 160.77e984.39 W with an average value of
498.58 W, leading to an energy saving of 11.97 kWh for the
continuous 24 h period. Fig. 14 (b) indicates that during the winter
operation period, the reduction in the heating load by EAHE varies
within a range of 191.94e599.93 W with an average value of
363.9 W and a corresponding energy saving of 9.17 kWh for the
continuous 24 h period. The results indicate that the average
reduction in the cooling and heating loads of the building can be
reduced by approximately 55.4 and 40.43 W/m2 using the EAHE,
respectively.

5. Conclusions
Fig. 13. Relation of the heat transfer efficiency and inlet air temperature.
A full-scale experiment was performed to investigate the effects
of an EAHE on the indoor thermal environment in a typical hot-
EAHE during the summer and winter operation periods, except for summer and cold-winter region. Experiments were performed in
the change rate. In addition, the heat transfer efficiency of the EAHE a typical summer and winter day for 24 h each. According to the
system depends on several parameters, e.g., EAHE engineering experimental data, the thermal behavior of the EAHE and building
parameters, the inlet air temperature, and, in particular, the soil were quantified. The following conclusions can be drawn:
temperature [32]. In addition, the soil temperature distribution
around the buried pipe is also dependent on the operation mode, 1. The EAHE could significantly pre-cool and pre-heat the inhaled
time duration, and outside weather conditions. air in the hot-summer and cold-winter region, respectively. It is
seen that, at the pipe outlet, a decrease in the air temperature of
4.3. Reduction in building heating/cooling load 9.12  C in a summer day and an increase of 5.53  C in a winter
day could be obtained. Compared to that of the outdoor air
In order to evaluate the potential of EAHE for reducing the temperature, the corresponding temperature range at the pipe
building cooling/heating load, it can be calculated by following outlet are reduced by 8.27 in summer and 8.95  C in winter,
equation: respectively, the corresponding average air relative humidity
increased by 46.89% and decreased by 27.41%, respectively.

mCp ðT2  T1 Þ Summer 2. Compared to the building without EAHE, the average values of
QR ¼ (4)
mCp ðT1  T2 Þ Winter the indoor air temperature of the building with EAHE decreased
by 5.9  C under cooling mode and increased by 4.29  C under
where QR is the reduction in the building cooling/heating load by heating mode, and the corresponding range of the indoor air
EAHE (W), T1 and T2 are the indoor air temperature for the Room 1 temperature is decreased by 8.9  C in each case. The average
and Room 2 ( C), respectively. temperatures of the internal surface of external walls decrease
Fig. 14 (a) and (b) show the reduction in the cooling and heating by approximately 6  C in summer and increases by approxi-
loads from the building obtained using the EAHE ventilation system mately 5.8  C in winter, and the corresponding range of the
during the summer and winter operation periods, respectively. internal surface temperature of external walls decrease by
539
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Fig. 14. Variation in the reduction in the building cooling/heating load by the EAHE from the building: (a) summer and (b) winter.

approximately 9.5  C and 3.8  C in summer and winter, Science Foundation of China (NSFC) under Grant No. 51578087, the
respectively. Project No. XmT2018037 funded by Chongqing Special Postdoctoral
3. During the summer operation period, the EAHE inlet tempera- Science Foundation, the Project No. cstc2019jcyj-bshX0079 spon-
ture varies from 3.95e15.54  C, and the heat transfer efficiency sored by Natural Science Foundation of Chongqing, 2020CDJQY-
(h) varies from 71.48% to 0. The average cooling capacity and A062 and 2018CDXYCH0015 supported by the Fundamental
COP of the EAHE are 773.59 W and 7.03, respectively. During the Research Funds for the Central Universities.
winter operation period, the EAHE inlet temperature and h
varies from 27.79 to 38.51  C and 62.82 to 81.71%, respectively.
References
The average value of the heating capacity and COP of EAHE are
469.07 W and 4.26, respectively. [1] P. Nejat, F. Jomehzadeh, M.M. Taheri, M. Gohari, M.Z. Abd Majid, A global
4. The EAHE ventilation system could reduce the indoor cooling review of energy consumption, CO2 emissions and policy in the residential
and heating load by 11.97 kWh and 9.17 kWh for the continuous sector (with an overview of the top ten CO2 emitting countries), Renew.
Sustain. Energy Rev. 43 (2015) 843e862.
24 h period, respectively. The average reductions of the building [2] F. Zhang, J.Y. Cai, J. Ji, K.D. Han, W. Ke, Experimental investigation on the
cooling and heating loads per unit floor area are approximately heating and cooling performance of a solar air composite heat source heat
55.4 W/m2 and 40.43 W/m2, respectively. In the summer oper- pump, Renew. Energy 161 (2020) 221e229.
[3] L. Amanowicz, J. Wojtkowiak, Approximated flow characteristics of multi-pipe
ation period, the frequency of occurrence of the indoor air earth-to-air heat exchangers for thermal analysis under variable airflow
temperature above 28  C decreased from 67.18% without EAHE conditions, Renew. Energy 158 (2020) 585e597.
to 32.89% with EAHE, whereas in the winter operation period, [4] D. Yang, R. Shi, H.B. Wei, J.H. Du, J.L.B. Wang, Investigation of the performance
of a cylindrical PCM-to-air heat exchanger (PAHE) for free ventilation cooling
the frequency of occurrence of the indoor air temperature below
in fluctuating ambient environments, Sustain. Cities Soc. 51 (2019) 101764.
12  C decreased from 82.99% without EAHE to 22% with EAHE. [5] R.S. Brum, J.V.A. Ramalho, M.K. Rodrigues, L.A.O. Rocha, L.A. Isoldi, E.D. Dos
Santos, Design evaluation of earth-air heat exchangers with multiple ducts,
Renew. Energy 135 (2019) 1371e1385.
The experimental results proved that the EAHE ventilation
[6] J. Lin, H. Nowamooz, S. Braymand, P. Wolff, C. Fond, Impact of soil moisture on
system has a significant potential for reducing the building cooling the long-term energy performance of an earth-air heat exchanger system,
and heating energy demand in hot-summer and cold-winter re- Renew. Energy 147 (2020) 2676e2687.
gions. The findings of this study can be utilized as guidelines by [7] J.J. Gao, A.B. Li, X.H. Xu, W.J. Gang, T. Yan, Ground heat exchangers: applica-
tions, technology integration and potentials for zero energy buildings, Renew.
energy policymakers, design engineers, and inhabitants for the Energy 128 (2018) 337e349.
deployment of passive techniques. In addition, although the initial [8] P. Hollmuller, Analytical characterisation of amplitude-dampening and phase-
investment cost of EAHEs is relatively high, economic benefits can shifting in air/soil heat-exchangers, Int. J. Heat Mass Tran. 46 (2003)
4303e4317.
be obtained through the energy-saving operation of EAHE, which [9] V. Bansal, R. Misra, G.D. Agrawal, J. Mathur, Performance analysis of earth-
also reduces greenhouse gas emissions. pipe-air heat exchanger for summer cooling, Energy Build. 42 (2010)
645e648.
[10] V. Bansal, R. Misra, G.D. Agrawal, J. Mathur, Performance analysis of earth-
CRediT authorship contribution statement pipe-air heat exchanger for winter heating, Energy Build. 41 (2009)
1151e1154.
[11] Z.X. Liu, Z. Yu, T.T. Yang, S.S. Li, M. El Mankibi, L. Roccamena, D. Qin,
Haibin Wei: Experiment, Writing - original draft. Dong Yang: G.Q. Zhang, Experimental investigation of a vertical earth-to-air heat
Formal analysis, Methodology, Supervision. Jinhui Du: Experiment. exchanger system, Energy Convers. Manag. 183 (2019) 241e251.
Xin Guo: Experiment, Writing - review & editing. [12] Z.X. Liu, Z. Yu, T.T. Yang, L. Roccamena, P.C. Sun, S.S. Li, G.Q. Zhang, M. El
Mankibi, Numerical modeling and parametric study of a vertical earth-to-air
heat exchanger system, Energy 172 (2019) 220e231.
Declaration of competing interest [13] Z.X. Liu, Z. Yu, T.T. Yang, M. El Mankibi, L. Roccamena, Y. Sun, P.C. Sun, S.S. Li,
G.Q. Zhang, Experimental and numerical study of a vertical earth-to-air heat
exchanger system integrated with annular phase change material, Energy
The authors declare that they have no known competing Convers. Manag. 186 (2019) 433e449.
financial interests or personal relationships that could have [14] H.B. Wei, D. Yang, J.L.B. Wang, J.H. Du, Field experiments on the cooling
appeared to influence the work reported in this paper. capability of earth-to-air heat exchangers in hot and humid climate, Appl.
Energy 276 (2020) 115493.
[15] A. Pakari, S. Ghani, Performance evaluation of a near-surface earth-to-air heat
Acknowledgments exchanger with short-grass ground cover: an experimental study, Energy
Convers. Manag. 201 (2019) 112163.
[16] H.B. Wei, D. Yang, Performance evaluation of flat rectangular earth-to-air heat
The authors acknowledge support from the National Natural exchangers in harmonically fluctuating thermal environments, Appl. Therm.

540
H. Wei, D. Yang, J. Du et al. Renewable Energy 167 (2021) 530e541

Eng. 162 (2019) 114262. [27] L. Amanowicz, J. Wojtkowiak, Thermal performance of multi-pipe earth-to-air
[17] D. Yang, Y.H. Guo, J.P. Zhang, Evaluation of the thermal performance of an heat exchangers considering the non-uniform distribution of air between
earth-to-air heat exchanger (EAHE) in a harmonic thermal environment, parallel pipes, Geothermics 88 (2020) 101896.
Energy Convers. Manag. 109 (2016) 184e194. [28] Design Standard for Energy Efficiency of Public Buildings (GB 50189-2015),
[18] H. Li, L. Ni, G. Liu, Z.S. Zhao, Y. Yao, Feasibility study on applications of an Beijing, 2015 ([in Chinese]).
Earth-air Heat Exchanger (EAHE) for preheating fresh air in severe cold re- [29] M.R. Akhtari, I. Shayegh, N. Karimi, Techno-economic assessment and opti-
gions, Renew. Energy 133 (2019) 1268e1284. mization of a hybrid renewable earth-air heat exchanger coupled with electric
[19] M. Benhammou, B. Draoui, M. Hamouda, Improvement of the summer cooling boiler, hydrogen, wind and PV configurations, Renew. Energy 148 (2020)
induced by an earth-to-air heat exchanger integrated in a residential building 839e851.
under hot and arid climate, Appl. Energy 208 (2017) 428e445. [30] D. Yang, H.B. Wei, R. Shi, J.L.B. Wang, A demand-oriented approach for inte-
[20] B. Rosti, A. Omidvar, N. Monghasemi, Optimum position and distribution of grating earth-to-air heat exchangers into buildings for achieving year-round
insulation layers for exterior walls of a building conditioned by earth-air heat indoor thermal comfort, Energy Convers. Manag. 182 (2019) 95e107.
exchanger, Appl. Therm. Eng. 163 (2019) 114362. [31] Ministry of Housing and Urban-Rural Development of the People Republic of
[21] P. Tittelein, G. Achard, E. Wurtz, Modelling earth-to-air heat exchanger China, Standard for Energy Efficiency Test of Public Buildings (JGJ/T177-2009),
behaviour with the convolutive response factors method, Appl. Energy 86 China Architecture and Building Press, Beijing, China, 2010.
(2009) 1683e1691. [32] H. Li, L. Ni, G. Liu, Y. Yao, Performance evaluation of Earth to Air Heat Ex-
[22] F. Ascione, D. D’Agostino, C. Marino, F. Minichiello, Earth-to-air heat change (EAHE) used for indoor ventilation during winter in severe cold re-
exchanger for NZEB in Mediterranean climate, Renew. Energy 99 (2016) gions, Appl. Therm. Eng. 160 (2019) 114111.
553e563. [33] T.M. Yusof, H. Ibrahim, W.H. Azmi, M.R.M. Rejab, The thermal characteristics
[23] F. Al-Ajmi, D.L. Loveday, V.I. Hanby, The cooling potential of eartheair heat and performance of a ground heat exchanger for tropical climates, Renew.
exchangers for domestic buildings in a desert climate, Build. Environ. 41 Energy 121 (2018) 528e538.
(2006) 235e244. [34] L.H. Yang, B.H. Huang, C.Y. Hsu, S.L. Chen, Performance analysis of an earth-air
[24] H.B. Wei, D. Yang, Y.H. Guo, M.Q. Chen, Coupling of earth-to-air heat ex- heat exchanger integrated into an agricultural irrigation system for a green-
changers and buoyancy for energy-efficient ventilation of buildings consid- house environmental temperature-control system, Energy Build. 202 (2019)
ering dynamic thermal behavior and cooling/heating capacity, Energy 147 109381.
(2018) 587e602. [35] K.K. Agrawal, R. Misra, G. Das Agrawal, Thermal performance analysis of
[25] D. Yang, J.P. Zhang, Theoretical assessment of the combined effect of building slinky-coil ground-air heat exchanger system with sand-bentonite as back-
thermal mass and earth-air-tube ventilation on the indoor thermal environ- filling material, Energy Build. 202 (2019) 109351.
ment, Energy Build. 81 (2014) 182e199. [36] C.Y. Hsu, P.C. Huang, J.D. Liang, Y.C. Chiang, S.L. Chen, The in-situ experiment
[26] L. Amanowicz, Influence of geometrical parameters on the flow characteristics of earth-air heat exchanger for a cafeteria building in subtropical monsoon
of multi-pipe earth-to-air heat exchangers-experimental and CFD in- climate, Renew. Energy 157 (2020) 741e753.
vestigations, Renew. Energy 226 (2018) 849e861.

541

You might also like