UNDERSTANDING CAP540 User Name Password

systemadministrator a10
ABB3 ABB3

Select the correct relay with correct


version. Here relay is REB551 ver 1.1 to
select REL561 ver 2.3 select REL561 V2.3

Slave number must match the slave


number set on the terminal via HMI
Configuration-Term Com-SPA-Front

605125819.doc Page 1 of 25
UNDERSTANDING CAP540 
Use Terminal
Configuration option

Select Terminal Configuration

Select Terminal Configuration by


Right click on relay type

Password is NEW

First via HMI do Configuration-IO


Modules-Reconfigure. After this do
Upload options for fresh terminal Else
do Upload Configuration for a
configured terminal.

605125819.doc Page 2 of 25
UNDERSTANDING CAP540 

Check the IO positioning via


HMI Service report-IO
Modules & set them over here.
After each selection click on
set. At the end, click on Save &
then exit by clicking on the ‘X’
button on top RHS corner.

Get the IO blocks by using this procedure.


Alternately, we can add then manually this way

605125819.doc Page 3 of 25
UNDERSTANDING CAP540 

Insert Worksheets either by


pressing “ins” key on
keyboard or via the edit
option

In this manner insert all the work sheets or


make a single worksheet. It is advisable to
make separate work sheets as this help us during trouble shooting.

605125819.doc Page 4 of 25
UNDERSTANDING CAP540 
After addition of work sheets the structure will look like this.

Double click on any work sheet where you want to insert the function blocks. Click
on the open WS
Click here or
press “F” key

Define the variables for different inputs (Left side) & various outputs (Right side). If
an input is not used then use a variable “FALSE”.

605125819.doc Page 5 of 25
UNDERSTANDING CAP540 

If you wish to see the names of the


signals in the service report, then write
the names here, by selecting the I/P or
O/P signal & pressing the key “P”

In this way, insert all the I/Os as well as all the function blocks. Interconnect the
various functional blocks with the help of the Technical reference manual & the
Application manual. Use the standard connection diagrams to understand how the
various function blocks are interconnected.

Once this is complete, then we have to compile the program & do a version update.

Click here

605125819.doc Page 6 of 25
UNDERSTANDING CAP540 

Error list will look like this. Double click on any error to find out what type of error is
present.

After this do update version, click yes to proceed.

After this download the configuration to the relay.

If the CAP 531 program is terminated abruptly, & if one tries to enter into terminal
configuration once again, the following message will be displayed.

605125819.doc Page 7 of 25
UNDERSTANDING CAP540 

With Windows Explorer go to the mentioned directory & delete the mentioned *.pwt
file.

To add new users :

605125819.doc Page 8 of 25
UNDERSTANDING CAP540 

Add new user along with the Authority


level, 10 means super user

Click here

Type new password


then click OK

605125819.doc Page 9 of 25
UNDERSTANDING CAP540 

Click here

Parameter Settings

To view the characteristics of the relay based on the settings done

Click here

605125819.doc Page 10 of 25
UNDERSTANDING CAP540 
Click here to
generate RIO file

Select the Zone impedances & click OK.

605125819.doc Page 11 of 25
UNDERSTANDING CAP540 

Disturbance Report :

605125819.doc Page 12 of 25
UNDERSTANDING CAP540 

605125819.doc Page 13 of 25
UNDERSTANDING CAP540 

605125819.doc Page 14 of 25
UNDERSTANDING CAP540 

605125819.doc Page 15 of 25
UNDERSTANDING CAP540 

To Compress a project :

605125819.doc Page 16 of 25
UNDERSTANDING CAP540 

The project name will


appear as default

If there exists a compressed


project, this message will appear.
Click NO to STOP, & YES to
proceed.

This compressed project is available in the CAP 540/Project dir.

605125819.doc Page 17 of 25
UNDERSTANDING CAP540 

To decompress a project :

Define any name

605125819.doc Page 18 of 25
UNDERSTANDING CAP540 

Select the compressed file *.PRJ or


*.ZIP. *.ZIP is made in previous
versions of CAP 540. *.PRJ is made
with ver. 2.3 of CAP 540

This message will appear if a


project already exists. Click
NO to STOP & YES to
continue

605125819.doc Page 19 of 25
UNDERSTANDING CAP540 

The new project is ready for use.

One can Compress a terminal also. This is done in the following way

605125819.doc Page 20 of 25
UNDERSTANDING CAP540 

Note that the file extension now is *.tml & not *.prj

In a similar manner, one can decompress a Terminal.

605125819.doc Page 21 of 25
UNDERSTANDING CAP540 

If the range of settings is less (i.e. suitable for rating of 5A, then do the following)

605125819.doc Page 22 of 25
UNDERSTANDING CAP540 

Select 5 & then 1 again then click ok.


Now the range will be for 1A (i.e. the maximum range).

You can clear the led from HMI or you have option through CAP 540:
- Right click at relay type.
- Disturbance handling.
- Clear led.

605125819.doc Page 23 of 25
UNDERSTANDING CAP540 

You can see the led indications through CAP 540:

- Right click at relay type.


- LED indication.
605125819.doc Page 24 of 25
UNDERSTANDING CAP540 
- Press start.

605125819.doc Page 25 of 25