Substation: Date : 24/9/2561
Checked : Description.: CT.CALCULATION
Prepared : Document No.:
CT BURDEN CALCULATION
CT DATA
CT NO CT Ratio Class Burden Knee point Voltage Internal resistance at 75C
1 150/5A 5P20 3.75 VA 19.78 V 0.048
2 250/5A 5P20 5VA 24.725 0.071
3 800/5A 5P20 5VA 29.304 0.136
4 1500/5A 5P20 10VA 60.439 0.267
5 1600/5A 5P20 10VA 64.46 0.287
6 2500/5A 5P20 15VA 91.575 0.426
CABLE DATA
Cross section = 4 sq.mm. Length = 3
Resistance = 4.61 Ω/km
Find Rcable
Rcable= 4.61 x 3/1000 Ω
Rcable= 0.01383 Ω
RELAY DATA
Over current relay BURDEN = 0.09 VA
Find RRELAY
2
RRELAY = S/I
= 0.09 / 5
RRELAY = 0.018 Ω
2
Actual burden of CT Sa = I x ( RRELAY + Rdim + Rcable )
Sa = 0.79575
(a) > (b), the CT is OK for through fault current without saturation. …...The result is ok.
(d) > (c), the knee point voltage of this CT is satisfy in this requirement …...The result is ok.