Professional Documents
Culture Documents
net/publication/296919950
CITATIONS READS
14 740
3 authors, including:
Some of the authors of this publication are also working on these related projects:
Nighttime cooling for concentrating solar power plants using radation View project
All content following this page was uploaded by Douglas T. Reindl on 09 December 2016.
C
structed from readily available catalog
data and to identify opportunities for re-
ommercial and industrial refrigeration systems usually consist of ducing energy costs. The motivation for
separate components from different manufacturers. A typical selecting this particular site resulted from
owner concerns that system energy costs
refrigeration system consists of heat exchangers, such as
were higher than expected.
evaporator(s), condenser(s) and liquid suction; compressor(s); refrigerant The components in the system were
feed control devices, such as expansion valves; refrigerant filters; and ves- instrumented to measure refrigerant pres-
sures and temperatures at numerous
sels (high-side receivers and low-side accumulators). points throughout both the odd and even
loops as well as the secondary fluid flow
In some systems, a secondary fluid rate tube-side direct-expansion refriger- rate, supply, and return temperatures.
such as ethylene glycol-water also may ant circuits. A parallel rack of three recip- These data were recorded with a data ac-
be used to avoid long runs of refrigerant rocating compressors serves each refrig- quisition system at two-second time in-
piping that would increase system refrig- erant circuit. (The two independent re- tervals over several hours and a range of
erant inventory. The components for a frigeration loops are designated as odd ambient conditions.
system must be selected and integrated and even throughout this article.) During the course of this investiga-
by the design engineer based on infor- On the shell side of the evaporator, a tion, the lack of agreement between the
mation from component manufacturers secondary fluid (ethylene glycol-water model (based on component manufac-
that includes catalog equipment perfor- solution) is cooled to the design supply turer performance data) and actual sys-
mance and application engineering rec- temperature of 14°F (10°C) prior to be- tem data resulted in the discovery of a
ommendations. Guidelines for the process ing pumped remotely for cooling two number of operational problems. These
of component selection and integration separate skating rinks. Heat is rejected operational problems were not expected
are provided by ASHRAE.1,2 However, from the refrigeration system by a two- because the system is new, the operators
there are a number of details in this pro- circuit induced draft single speed evapo- at the site check the equipment daily and
cess than can lead to non-optimal sys- rative condenser. As originally designed, it functions adequately to meet the re-
tem configurations and operation. the evaporative condenser fan cycles on frigeration loads. This article describes
A case study was performed on a re- and off as necessary to maintain the methods implemented to detect and re-
frigeration system serving an indoor skat- saturated condensing pressure between solve these operational problems.
ing arena in Madison, Wis., that has
25,000 ft2 (2323 m2) of ice. The HCFC-22
based system, which was installed in the About the Authors
winter of 1996, consists of six semi-her- Kyle Brownell is a product development engineer for Greenheck Fan Corporation, Schofield, Wis. He has
metic reciprocating compressors having a masters in mechanical engineering from the University of Wisconsin-Madison.
a total capacity of 103 tons (355 kW). The
Sanford Klein, P.h.D., is a professor of mechanical engineering at the University of Wisconsin-Madison
shell-and-tube evaporator has two sepa-
and is a member of the Solar Energy Laboratory there. He is a corresponding member to TC 8.3, Absorption
and Heat Operated Machines and TC 3.5, Desiccant and Sorption Technology.
Douglas Reindl, Ph.D., P.E., is an assistant professor in the department of engineering professional
development and director of the HVAC&R Center at the University of Wisconsin. He is currently chair of TC 6.9,
Thermal Storage and vice chair of Guideline 2.
40 ASHRAE Journal February 1999
REFRIGERATION SYSTEM
the valves on the even loop remained frost free. This frosting The expansion valve is sized to deliver liquid, which has a much
was the first indication that the odd loop compressors were higher density and therefore requires a smaller area for flow to
operating with a lower suction pressure, and thus a lower suc- admit a given amount of refrigerant.
tion temperature, resulting in increased frost formation on the In direct-expansion refrigeration systems, the refrigerant
valve. After this observation, a pressure gauge was installed to control device modulates the flow of refrigerant to the evapo-
measure the pressure drop across the suction line filter. The rator in response to the superheat generated at the evaporator
measured pressure drop was 3 to 5 psi (20 to 35 kPa) higher outlet. In this system, the design superheat is 7°F to 8°F (3.9°C
than the expected 3 psi (20 kPa) drop for the filter at its rated to 4.4°C). Figure 4 shows that the superheat on the even loop
refrigerant flow rate. is maintained at design operating conditions while the odd
Figure 2 shows the contrasts of the dirty filter (bottom) with loop with vapor in the liquid line fluctuates between 10°F and
the clean replacement filter (top). As ap- 30°F (5.5°C to 16.7°C). The uncon-
parent by visual inspection, the filter trolled superheat is an indication that
was severely contaminated with debris. the expansion valve is out of control
The additional pressure drop caused by (i.e. hunting), resulting in the evapo-
the suction line filter (approximately 4 rator being starved of refrigerant on
psi [28 kPa]) was included in the com- the odd loop.
puter model developed for the system. In this case, when the valve is always
The additional annual operational cost wide open, the outlet superheat and thus
resulting from the dirty suction line fil- the mass flow of refrigerant, is controlled
ter was estimated to be $2,290 in the only by the pressure drop across the
Madison climate, representing about valve. As can be seen by comparing Fig-
5% of the annual operating cost. This ures 3 and 4, the superheat increases as
operating cost penalty could have been the pressure drop decreases, indicating
avoided by installing proper monitor- the mass flow of refrigerant is decreas-
ing equipment on the system (see ing with decreasing pressure drop. As
sidebar). the pressure drop increases, the super-
heat decreases, indicating the mass flow
Problem 2: Low Refrigerant of refrigerant is increasing with increas-
Charge ing pressure drop.
As illustrated in Figure 1, the sys- To isolate the cause of vapor in the
tem has two separate refrigeration odd loop liquid line, the liquid line pres-
loops with separate charges of refrig- Figure 2: Clean (top) and dirty (bottom) sure just ahead of the expansion valve
erant that cannot mix. All refrigeration refrigerant suction line filters. was measured using a pressure gage
systems are designed and operated to and compared to the transducer pres-
deliver liquid refrigerant to the expansion device, in this case, sure measurement at the outlet of the condenser. From this
a thermostatic expansion valve. A sufficient charge of refriger- information, a pressure drop was determined and compared to
ant must be provided in the system to fill the volume of the the calculated pressure drop between these two points due to
piping and components between the condenser and a portion fluid frictional effects. The calculated pressure drop and mea-
of the high-pressure receiver with liquid refrigerant. sured pressure drop were in close agreement so the problem
Assuming the system is initially supplied with a proper charge was determined to be a low refrigerant charge and not exces-
of refrigerant, a low charge will occur, eventually, only if refrig- sive liquid line pressure drop.
erant leaks to the atmosphere from some point in the system. To effectively resolve the problem of low refrigerant charge
To ensure that the refrigerant is in a liquid state prior to enter- in the odd loop, a refrigerant leak check was performed on the
ing the expansion valve, a sight glass is installed in the liquid entire system. A small leak in a diaphragm of the head (dis-
line just upstream of the expansion valve. Vapor bubbles charge) pressure controller was identified and repaired. Once
present in the sight glass are one indicator of low refrigerant the leak repair was made, a total of 135 lbs (61 kg) of HCFC-22
charge. Vapor formation in the liquid line can also occur due to were added to the system.
excessive pressure drop in the liquid line. The effect of low refrigerant charge on the system perfor-
A visual inspection of the site glass revealed that bubbles mance was calculated using actual operating data. The coef-
were present in the odd loop. In addition, the evaporator pres- ficient of performance (COP) for the system, when it is oper-
sure and compressor suction superheat temperature were moni- ating as designed with an evaporator pressure of approxi-
tored using the data acquisition equipment. Fluctuating pres- mately 40 psia (275 kPa) and a condenser discharge pressure
sure and/or high suction superheat indicates that the evapora- of approximately 235 psia (1620 kPa), is about 1.7. The low
tor is being starved of refrigerant. Figure 3 depicts actual data refrigerant charge in one bank reduced the refrigeration sys-
showing how the odd loop evaporator pressure fluctuates due tem performance by approximately 33%. The reduction in sys-
to the presence of vapor in the liquid line. The evaporator pres- tem performance translates directly into increased annual
sure in the even loop, which is operating normally, is also shown. system energy costs. Since only one of the two refrigerating
February 1999 ASHRAE Journal 43
Figure 3: Evaporator pressure variation over time for even Figure 4: Refrigerant superheat at outlet of evaporator for
and odd loops. the even and odd loops.
loops had this problem, the performance of the overall sys- the sidebar is approximately $420 per bank. The pressure
tem was reduced by 17%, which equates to an annual operat- switch needs to be wired into the existing alarm system.
ing cost penalty of $7,800. Assuming an installation cost of $2,000 for these compo-
This unnecessary operating cost could have been nents, the net savings for the site (due to early detection
avoided by installing proper monitoring equipment on the and resolution of problems) could have been $7,439,
system (see sidebar). For the site investigated, the material assuming that the problems which were detected and cor-
cost of the necessary monitoring components described in rected existed for one year.
static expansion valves. The floating head made this project successful. Financial Brownell, K.A. Investigation of the Field
control strategy would cause the fan to support for this research project was pro- Performance for Industrial Refrigeration Sys-
cycle on and off at conditions of extremely vided through a grant from the Energy tems, M.S. Thesis, Mechanical Engineering,
low outside air temperatures so that a mini- Center of Wisconsin. Ruth Urban from Solar Energy Laboratory, University of Wis-
mum pressure difference across the ther- the Energy Center of Wisconsin was in- consin-Madison, 1998.
mostatic expansion valve is maintained. For strumental in facilitating the smooth ex-
the ice arena system investigated, the ad- ecution of the project. James Elleson from Cox, D. 1998. Rink Tec International, Little
ditional condenser fan and pump power Elleson Engineering provided key field Canada, Minn. Private communication. n
required is greatly exceeded by the reduc- support in the data collection phase of
tion in power needed to operate the com- this program. Kathy Burkeland and Randy
pressors. Poppe from Madison Gas and Electric ar-
Although not specifically analyzed, ranged for power monitoring during the
floating head pressure control strategies data collection phase of the project. This
will also prolong component life. Since float- project would not have been possible
ing head pressure reduces compressor op- without the cooperation of Fritz Kronke,
erating pressure ratios, wear and tear on Facility Director of the Madison Parks De-
pistons, cranks, connecting rods and wrist partment. Darrel Cox of Rink Tec provided Please circle the appropriate number on the
pins are greatly reduced. In addition, con- information on the system design and Reader Service Card at the back of the
denser fan starts and stops are minimized operating sequences. publication.
prolonging fan belt and motor life. Extremely Helpful ....................................................... 458
Bibliography
Helpful ....................................................................... 459
Acknowledgements 1998 ASHRAE HandbookRefrigeration.
The authors would like to acknowledge Somewhat Helpful ..................................................... 460
several organizations and individuals that 1997 ASHRAE HandbookFundamentals. Not Helpful ................................................................ 461