Professional Documents
Culture Documents
Manual
Electronics
Type CPX−FB11
Manual
526 422
en 0503b
[689 002]
Contents and general instructions
Original . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . de
Edition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . en 0503b
Designation . . . . . . . . . . . . . . . . . . . . . . . P.BE−CPX−FB11−EN
Contents
1. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−1
2. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−1
D. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D−1
Designated use
Target group
Service
Please consult your local Festo repair service if you have any
technical problems.
Danger categories
This manual contains instructions on the possible dangers
which may occur if the product is not used correctly. These
instructions are marked (Warning, Caution, etc.), printed on a
shaded background and marked additionally with a picto
gram. A distinction is made between the following danger
warnings:
Warning
This means that failure to observe this instruction may
result in serious personal injury or damage to property.
Caution
This means that failure to observe this instruction may
result in personal injury or damage to property.
Please note
This means that failure to observe this instruction may
result in damage to property.
Pictograms
Information:
Recommendations, tips and references to other sources of
information.
Accessories:
Information on necessary or sensible accessories for the
Festo product.
Environment:
Information on environment−friendly use of Festo products.
Text markings
Please note
This manual refers to the following versions:
MPA1 pneumatic and handheld as from software status 26.05.03 (R09) as from Rev. 1.3
type CPX−MMI−1
MPA2 pneumatics as from software status 26.05.03 (R09) as from Rev. 1.3
CPX−CP interface as from software status 12.10.05 (R16) as from Rev. 2.1
(Modular EDS)
Term/abbreviation Meaning
CP Compact Performance
CPX bus Data bus via which the CPX modules communicate with each other and
are supplied with the necessary operating voltage.
CPX modules Common term for the various modules which can be incorporated in a
CPXterminal
EDS library The features of the various field bus slaves are managed in the EDS library
(Electronic data sheets).
Field bus nodes Provide the connection to specific field buses. Transmit control signals to
the connected modules and monitor their ability to function.
I Digital input
I/O diagnostic interface The I/O diagnostic interface is a bus−independent diagnostic interface at
I/O level, permitting access to internal data of the CPX terminal.
I/O modules Common term for the CPX modules which provide digital inputs and
outputs (CPX input modules and CPX output modules).
O Digital output
Pneumatic interface The pneumatic interface is the interface between the modular electrical
periphery and the pneumatics.
Status bits Internal inputs which supply coded common diagnostic messages.
Chapter 1
Contents
1. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−1
Warning
Sudden unexpected movement of the connected actuators
and uncontrolled movements of loose tubing can cause
injury to human beings or damage to property.
Before carrying out installation and maintenance work,
switch off the following:
the compressed air supply
the operating and load voltage supplies.
Caution
The CPX field bus node may be damaged if it is not
handled correctly.
· Observe the regulations for handling electrostatically
sensitive components.
· Discharge yourself electrostatically before fitting or re
moving components in order to protect the components
against discharges of static electricity.
1 Bus status−
specific and 4 1
CPX−specific LEDs
2 Exchangeable
field bus
connection
(here Micro Style 3 2
connection)
3 Transparent
cover for the DIL
switches
4 Service interface
for handheld
Fig.1/1: Connecting and display elements on the CPX field bus node
2. Pull the field bus node carefully and without tilting away
from the contact rails of the manifold base.
2 Manifold block
3 Contact rails 1
4 Screws
3
2
1. Place the field bus node in the manifold base. Make sure
that the grooves with the power contact terminals on the
bottom of the field bus node lie above the contact rails.
Press the field bus node carefully and without tilting as
far as possible into the manifold sub−base.
In order to set the CPX field bus node, you must first remove
the cover over the DIL switches.
Caution
The CPX field bus node contains electrostatically sensitive
components.
· Do not therefore touch any contacts.
· Observe the regulations for handling electrostatically
sensitive components.
You will then prevent the electronics in the node from being
damaged.
1.2.1 Removing and fitting the cover over the DIL switches
Please note
Make sure that the seal is seated correctly.
When you have removed the cover for the DIL switches, you
will see five DIL switches in the field bus node (see Fig.1/3).
Baud rate
Station number
Procedure:
1 DIL switch 1:
Operating mode
and EDS mode
1 ON ON
2
2 DIL switch 2:
1 2 1 2
Reserved
3 DIL switch 3:
Diagnosis mode
7 8
or number of 5
5 6
I/Obytes
1 2 3 4
4 DIL switch 4: ON
Baud rate
5 DIL switch 5: 4
ON ON
3
Station number
1 2 1 2
Fig.1/3: DIL switches in the field bus node (further information on 1...5 on the
following pages)
Please note
If you configure the CPX terminal with modular EDS, the
field bus node must be installed as module 0 on the first
place.
The I/O diagnostic interface and the status Not permitted 3.1: OFF
bits are switched off 3.2: OFF
(+ 0 I/O bits) (default)
Recommended setting 1)
Tab.1/3: DIL switch 3 (diagnosis mode or number of I/O bytes with remote controller)
In the Remote I/O operating mode, you set with the DIL
switch 3 whether diagnostic information is to be transmitted
on a Polled" or Change of State" connection. Irrespective of
this setting, in this operating mode the 8 status bits are
always available via a Ptrobed I/O" connection.
7 8
5 6
3 4
1
2
1
1 Setting the station number
(8−element DIL switch, switch elements 1−6)
Please note
Station numbers may only be assigned once per field bus
line.
Recommendation:
Assign the station numbers in ascending order. Assign the
station numbers to suit the machine structure of your system.
Example
20 + 22 = 21 + 22 + 25 =
8
1+4=5 2 + 4 + 32 = 38
7
25 25
6
6
5
24 24
5
23 23
4
4
22 22
3
3
21 21
2
2
20 20
1
1
Tab.1/6: Examples of set station numbers
Sta 1 2 3 4 5 6 7 8 Sta 1 2 3 4 5 6 7 8
tion tion
no. no.
0 16 ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
1 ON 17 ON ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF
2 ON 18 ON ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF
3 ON ON 19 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
4 ON 20 ON ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF
5 ON ON 21 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
6 ON ON 22 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
7 ON ON ON 23 ON ON ON ON
OFF OFF OFF OFF OFF
8 ON 24 ON ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF
9 ON ON 25 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
10 ON ON 26 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
11 ON ON ON 27 ON ON ON ON
OFF OFF OFF OFF OFF
12 ON ON 28 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
13 ON ON ON 29 ON ON ON ON
OFF OFF OFF OFF OFF
14 ON ON ON 30 ON ON ON ON
OFF OFF OFF OFF OFF
15 ON ON ON ON 31 ON ON ON ON ON
OFF OFF OFF
Tab.1/7: Setting station numbers 0...31: Position of the DIL switch elements
Sta 1 2 3 4 5 6 7 8 Sta 1 2 3 4 5 6 7 8
tion tion
no. no.
32 ON 48 ON ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF
33 ON ON 49 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
34 ON ON 50 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
35 ON ON ON 51 ON ON ON ON
OFF OFF OFF OFF OFF
36 ON ON 52 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
37 ON ON ON 53 ON ON ON ON
OFF OFF OFF OFF OFF
38 ON ON ON 54 ON ON ON ON
OFF OFF OFF OFF OFF
39 ON ON ON ON 55 ON ON ON ON ON
OFF OFF OFF
40 ON ON 56 ON ON ON
OFF OFF OFF OFF OFF OFF OFF
41 ON ON ON 57 ON ON ON ON
OFF OFF OFF OFF OFF
42 ON ON ON 58 ON ON ON ON
OFF OFF OFF OFF OFF
43 ON ON ON ON 59 ON ON ON ON ON
OFF OFF OFF
44 ON ON ON 60 ON ON ON ON
OFF OFF OFF OFF OFF
45 ON ON ON ON 61 ON ON ON ON ON
OFF OFF OFF
46 ON ON ON ON 62 ON ON ON ON ON
OFF OFF OFF
47 ON ON ON ON ON 63 ON ON ON ON ON ON
OFF
Tab.1/8: Setting station numbers 32...63: Position of the DIL switch elements
Please note
If installation has not been carried out correctly and if high
baud rates are used, data transmission errors may occur
as a result of signal reflections and attenuations. Causes of
transmission faults may be:
missing or incorrect terminating resistor
incorrect screening/shield connection
branch lines too long
transmission over long distances
unsuitable cables.
Observe the cable specifications. Refer to your controller
manual for information on the type of cable to be used.
Please note
If the CPX terminal is fitted onto the moving part of a
machine, the field bus cable on the moving part must be
provided with strain relief. Please observe also the relevant
regulations in EN60204 part 1.
Please note
· Refer to the manuals for your control system or bus in
terface for information on the T−adapter and the maxi
mum branch line length which is permitted for your
controller.
· Take into account also the sum of the branch line lengths
when calculating the maximum permitted length of the
field bus cable.
Bus supply
Avoid long distances between the bus interfaces/logic supply
and the CPX terminal.
Caution
· Make sure the polarity is correct when you connect the
field bus interface and the power supply for the bus
interface/internal logics.
· Connect the screening/shield.
Please note
Bus slaves have different tolerances in respect to the inter
face supply, depending on the manufacturer. Note this
when planning the bus length and placing the power unit.
Recommendation:
Place the power unit approximately in the centre of the bus.
Please note
You must check the pin assignment of your scanner with
the relevant documentation.
Connect the field bus cable of your control system to the field
bus interface of the CPX terminal as described in the follow
ing sections.
Please note
Use blanking plugs to seal unused connections. You will
then comply with protection class IP65.
2 2 1. Screen
2. 24 V DC bus (max. 4A)
3. 0 V bus
3 1 1 3
5 5
4. CAN_H
5. CAN_L
4 4
Bus out
Bus in Blanking plug for
unused connection
1. 0 V bus
2. CAN_L
1 2 3 4 5 3. Screen
4. CAN_H
5. 24 V DC bus (max. 4 A)
If you connect the field bus via the terminal strip type
FBSD−KL−2x5POL from Festo, you can implement a T−tap
function (double row of screw terminals).
4 5 6
2
1 2 3 4 5
1 5
6 9
(View of the Sub−D plug of the CPX−FB11)
Please note
The screening connection at pin 5 of the Sub−D plug is
capacitively connected to the housing within the CPX
terminal. This prevents equalising currents from flowing
via the screening of the field bus cable (see Fig.1/6).
1 Capacitive 1 5
connection
6 9
2 Housing
1
type FBS−SUB−9−BU−2x4POL or
type FBS−SUB−9−BU−2x5POL−B
Please note
Note that only the Festo field bus plugs guarantee
compliance with protection class IP65.
Before using field bus plugs from other manufacturers:
· replace the two flat screws with bolts
(type UNC 4−40/M3x6).
Please note
The cable clip in the Festo field bus plug is connected inter
nally only capacitively with the metal housing of the sub−D
plug. This is to prevent equalising currents flowing through
the screening of the field bus cable (Fig.1/8).
FBS−SUB−9−BU−2x5POL−B
· Fasten the shield of the field bus cable under the clamp
strap of the Festo sub−D socket (see Fig.1/7).
With this field bus plug, you can use the screening core of a
5−core cable: Connect the screening core to the SLD" con
nection in the field bus plug.
1 2 3
SLD
0Vbus
24Vbus
7
CAN_H
CAN_L
4 5 6
FBS−SUB−9−BU−2x4POL
· Clamp the screening of the field bus cable under the cable
clip of the field bus plug (see Fig.1/8).
1 Screening
24Vbus
0Vbus
connection,
cableclip
1
2 Only connected
capacitively
4
3 CPX field bus
node 2 X
4 Pin assignment in
the field bus plug
CAN_H
CAN_L
BF PS
PL
SF
M
Fig.1/8: Field bus plug from Festo type FBS−SUB−9−BU−2x4POL, pin assignment and
screening connection
Please note
Fit a bus termination to both ends of a bus segment. This
also applies if the bus circuit or bus interface is at the
beginning of the bus cable.
If the CPX terminal is at the end of the field bus system, a bus
termination will be required.
Recommendation:
Fit a resistor (121, 0.25 W) for the bus termination between
the connections for CAN_L and CAN_H. Fig.1/9 shows this as
an example with the Open Style connection.
Warning
· For the power supply, use only PELV circuits as per
IEC/DIN EN 60204−1 (Protective Extra−Low Voltage,
PELV).
Take into account also the general requirements for
PELV circuits as per IEC/DIN EN 60204−1.
· Use only power sources which guarantee reliable electri
cal isolation of the operating voltage as per IEC/DIN
EN60204−1.
System supply, The CPX terminal is supplied with operating and load volt
additional power supply ages via the manifold bases with system supply, additional
and valve supply supply and valve supply types CPX−GE−EV−S..., CPX−GE−EV−Z...
or CPX−GE−EV−V...
M18 3
C A: 24 VEL/SEN A: not connected A: not connected
B: 24 VVAL / 24 VOUT B: 24 VOUT B: 24 VVAL
D C: Earth terminal C: Earth terminal C: Earth terminal
D: 0 VEL/SEN / D: 0 VOUT (leading) D: 0 VVAL (leading)
0 VVAL / 0 VOUT
B (leading)
Pin designation Pin designation Pin designation
7/8"−4PIN
A Pay attention to the in Pay attention to the in Pay attention to the in
formation on the plug. formation on the plug. formation on the plug.
7/8"−5PIN 5
VEL/SEN: Operating voltage for electronics/sensors
VOUT: Load voltage outputs
VVAL: Load voltage valves
Tab.1/14: Pin assignment for system supply, additional supply and valve supply
Chapter 2
Contents
2. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−1
2.1 Addressing
Please note
A maximum of 10 electric modules including the field
bus node plus a pneumatic interface or MPA pneumatic
module are permitted in a CPX terminal.
If you configure the CPX terminal with modular EDS, the
field bus node must be installed as module 0 on the first
place.
The CPX terminal has an address range of up to 64 bytes
of inputs and 64 bytes of outputs.
Modular EDS
Starting with the software version of 12 Oct. 2005 (R16), the
CPX−FB11 supports the configuration with modular EDS.
The main features of modular EDS are:
With modular EDS, each module type has its own EDS
files (see section 2.2.2).
Setting modular EDS If you wish to use modular EDS, set the EDS mode to
modular EDS with the DIL switch 1 (see section 1.2.2).
Electric modules
The individual modules are displayed with their identifier on
the handheld. In the case of the I/O modules, the identifier is
also shown in the LED viewing window. With the aid of this
identifier, you can read the type of module and therefore the
number of inputs and outputs occupied by the module.
Please note
A CPX terminal with field bus node FB11 makes 8 status
bits available. These 8 status bits must be transmitted
separately via a Strobed I/O" connection.
If necessary, an I/O diagnostic interface can be activated
by a DIL switch. If the interface is active, it will occupy
the first 16 inputs and outputs in the address range.
If you configure the CPX terminal with modular EDS, the
field bus node must be installed as module 0 on the first
place!
Counting mode:
1. I/O diagnostic interface 1) Can be activated by DIL switch. When activated, it will occupy
the first 16 inputs and outputs in the address range.
Configuration examples
Module no.: 0 1 2 3 4 5 6
8O 8O 4O 4O
1 2 3 4
Module no.: 0 1 2 3 4 5 6
8O 8O
2
4
4 Digital multi I/O I40 ... I47 O132 ... O139 I40 ... I47 O136 ... O143
module
CPX−8DE−8DA
Module no.: 0 1 2 3 4 5 6
ÓÓ ÓÓ
ÓÓ ÓÓ
8DI 8DI 4DO 8DI 8DO 2AO
ÓÓ
ÓÓ ÓÓ
ÓÓ
8O
ÓÓ ÓÓ
1 2 3
2 Pneumatic interface
(set with DIL switch to 1...8 valve coils)
4 Digital multi I/O I24 ... I31 O36 ... O43 I24 ... I31 O40 ... O47
module
CPX−8DE−8DA
Caution
If the CPX terminal is extended or converted at a later
stage, the input/output addresses may be shifted. This
applies in the following cases:
Additional modules are inserted between existing
modules.
Existing modules are removed or replaced by other mod
ules which have more or fewer input/output addresses.
Manifold bases (CPA) or pneumatic connection bases
(Midi/Maxi) for single−solenoid valves are replaced by
manifold bases/connection bases for double−solenoid
valves or vice versa (see pneumatics manual).
Additional manifold bases (CPA) or connection bases
(Midi/Maxi) are inserted between existing bases.
Status bits or the I/O diagnostic interface are activated/
deactivated.
Example terminal 3 Using example terminal 3 (see Fig.2/3), the next illustration
changed shows the effects of addressing changes.
Module no.: 0 1 2 3 4 5 6
ÓÓ ÓÓ
ÓÓ ÓÓ
4DI 8DI 4DO 8DI 8DO 2AO
ÓÓ
ÓÓ ÓÓ
ÓÓ
16 O
ÓÓ ÓÓ
1 2 3
1 Changed: Field bus node CPX−FB11 3 Changed: Pneumatic interface (now set
now with activated I/O diagnosis with DIL switch to 1...16 valve coils)
interface
0 Field bus node I0 ... I15 O0 ... O15 I0 ... I15 O0 ... O15
CPX−FB11 with
activated I/O
diagnosis interface
4 Digital multi I/O I16 ... I23 O52 ... O59 I16 ... I23 O56 ... O63
module
CPX−8DE−8DA
Please note
Observe here also the instructions in the manual for your
controller with DeviceNet module.
the field bus slaves are supplied with power, in order that
they can be recognised when the ACTUAL configuration is
ascertained.
www.festo.com/fieldbus
2. Unpack the EDS and icon files contained in the file into a
directory of your choice.
You will require the following information for the CPX terminal:
EDS DNIO..CPX−DE.EDS German (de) EDS files for CPX terminals fitted with different
types of equipment 1)
DNIO..CPX−EN.EDS English (en)
Tab.2/11: Configuration files for the CPX field bus node for DeviceNet
EDS CPX−FB11−RC.EDS English (en) EDS files for CPX terminals in the Remote
Controller operating mode
Tab.2/12: Configuration files for the CPX field bus node for DeviceNet
EDS file The EDS file contains all the necessary features of the CPX
terminal.
Symbol files Depending on the configuration program used, you can as
sign symbol files (format .ico or .bmp) to the CPX terminal.
The CPX terminal will then be represented accordingly in the
configuration program.
EDS cpx_...eds English There is an EDS file for every module type. It
contains the information needed for
configuration and parameterisation.
Tab.2/13: Configuration files (modular EDS) for the CPX terminal for DeviceNet
You must install at least the Chassis EDS and the EDS files of
the required modules.
Recommendation: Install all EDS files.
Please note
If the slave features are entered manually, individual para
meterisation of the CPX terminal is not possible.
When the EDS library has been extended, the CPX terminal is
entered in the slave list as a possible DeviceNet slave. It can
now be added to a network.
Please note
The following applies to an SLC 500 with an Allen−Bradley
scanner type 1747−SDN:
Change of State / Cyclic" can be used in combination
with the diagnosis via Strobed I/O" only starting with
software version V4.015 of the scanner.
Polled I/O" with Strobed I/O" is also supported by
earlier versions.
Please note
All steps listed refer to the Allen−Bradley scanner
1747−SDN as example. They apply accordingly to other
masters.
In online mode you can read out the number of available in
puts and outputs via the system data Rx size" and Tx size"
(see also section 2.3).
The CPX terminal appears in the input data with two separate
communication connections:
Module no.: 0 1 2 3 4 5 6
ÓÓ ÓÓ
ÓÓ ÓÓ
8DI 8DI 4DO 8DI 8DO 2AO
ÓÓ
ÓÓ ÓÓ
ÓÓ
8O
ÓÓ ÓÓ
1 2 3
2 Pneumatic interface
(set with DIL switch to 1...8 valve coils)
4 Digital multi I/O module I1.3.0 ... 1.3.7 O1.3.4 ... O1.3.11
CPX−8DE−8DA
Tab.2/15: Addressing example for scanner 1747−SDN with CPX example terminal 3 and
standard EDS
Please note
All steps listed refer to the Allen−Bradley scanner
1747−SDN as an example. They apply accordingly to other
masters.
1 CPX terminal with field bus node CPX−FB11 for modular EDS
2 CPX terminal in the network
Fig.2/11: Hardware list and network in RSNetWorx for DeviceNet (modular EDS)
With the I/O Summary" register, you can show the number
of occupied bytes of the inputs and outputs.
4 Digital multi I/O module I1.3.7 ... 1.3.15 O1.9.8 ... O1.9.15
CPX−8DE−8DA
Tab.2/16: Addressing for scanner 1747−SDN with CPX example terminal 2 (seeFig.2/2)
with modular EDS
2.3 Parameterisation
Caution
A different parameterisation will result in a different reac
tion. Check especially when replacing CPX terminals to see
which settings are necessary and make sure that these
settings, where applicable, are carried out (e.g. in the
start−up phase by the higher−order PLC/IPC).
Please note
The CPX terminal can only be parameterised if the system
parameter System start" has the setting System start
with default parameterisation and current CPX system
equipment".
Caution
In the case of CPX terminals on which the M LED lights up
permanently, parameterisation will not be restored auto
matically by the higher−order system if the CPX terminal is
replaced during servicing. In these cases, check before
replacement to see which settings are required and carry
out these settings.
The CPX terminal with field bus node CPX−FB11 can be para
meterised in various ways. The following table provides an
overview of the methods.
Parameterisation via The parameters are set Fast, simple para Parameterisation is
the configuration via the configuration meterisation during saved locally in the
program (e.g. program and trans commissioning for CPX terminal and is
RSNetWorx) mitted directly to the testing the para lost when the ter
DeviceNet slave. meters minal is replaced. 1)
Parameterisation via The parameters are set Parameters are The scanner must
the scanner auto via the configuration loaded again support ADR
matically after Power program and trans automatically after (automatic device
On (configuration mitted to the scanner. Power On and are replacement).
recovery via ADR) The parameters are therefore retained if
transmitted by the the CPX terminal is
scanner after Power On. replaced.
Recommendation:
Use the ADR function (automatic device replacement) or the
explicit message programming. If the parameters are trans
mitted to the CPX terminal after Power On, the settings will be
retained even if a CPX terminal is replaced.
Please note
The last parameterisation received in the CPX terminal is
always valid.
Please note
If the system parameter System start" has the setting
System start with saved parameterisation and saved CPX
system equipment", modified parameter settings in the
CPX terminal will become valid immediately after Power
On.
With the Groups" check box, you can display the parameters
and data grouped in folders.
1 4
3
2
Changing parameters Click on a value (Current Value) and change it in the list field
or in a separately opening window.
Transfer parameters In online mode you can transfer parameters and display
them online with the appropriate buttons (see 3in
Fig.2/18).
Note the following in online mode:
Transfer parameters In online mode you can transfer parameters with the
appropriate buttons (see 1in Fig.2/19).
Note the following in online mode:
104d 1 ... 32 100 ... 172 Modification of digital inputs, object WORD
125d 1 ... 32 100 ... 172 Modification of digital outputs, object WORD
126d 1 ... 32 100 ... 172 Modification of analogue outputs, object (various)
127d 1 ... 32 100 ... 172 Modification of analogue inputs, object (various)
Chapter 3
Contents
LED display The LEDs directly show con Fast on−the−spot" Section 3.2
figuration faults, hardware recognition of faults
faults, bus faults, etc.
Status bits Internal inputs which supply Fast access to fault Section 3.3 and
coded common diagnostic messages, irrespective of CPX system manual
messages. the module and master.
I/O diagnostic The I/O diagnostic interface Detailed fault recognition Section 3.4 and
interface is a bus−independent diag irrespective of the field bus CPX system manual
nostic interface at I/O level type used.
which permits access to in
ternal data of the CPX ter
minal (16inputs and 16 out
puts).
Diagnosis via Access to all system data of Detailed module−related and Appendix B.1
DeviceNet the CPX terminal via the field channel−related fault rec EDS file
bus. ognition as well as access to
the diagnostic memory in the
online mode of the program
ming/configuration software
and in the PLC user program.
Diagnosis via Diagnostic information can Fast on−the−spot" Manual for the
the handheld be shown on the CPX hand recognition of faults handheld
held in a user−friendly
manner by means of menus.
Please note
Note that the diagnostic information displayed depends on
the parameterisation of the CPX terminal.
You will find the meaning of the LEDs for the I/O modules,
pneumatic interfaces or pneumatics in the corresponding
manuals.
1 CPX−specific LEDs
PS: power system MS PS
NS PL 1
PL: power load
IO SF
SF: system fault M
M: modify
2 DeviceNet−specific MS PS
LEDs
NS PL 2
MS: module status IO SF
M
NS: network status
ON
No fault. Operating volt
OFF
age/sensor supply applied
LED lights up
ON
No fault. Load voltage None
OFF
applied
LED lights up
ON Load voltage at the system Eliminate undervoltage
OFF
supply or additional supply
outside the tolerance
LED flashes range
ON No fault.
OFF
LED is out
ON
Simple fault/information See description of fault numbers in
OFF
(fault class 1) the CPX system manual
LED flashes
ON Fault
OFF (fault class 2)
LED flashes
ON Serious fault
OFF
(fault class 3)
LED flashes
1) The system fault LED flashes depending on the class of fault which has occurred.
Fault class 1 (simple fault): flash once, pause
Fault class 2 (fault): flash twice, pause
Fault class 3 (serious fault): flash three times, pause
ON
System start with saved Be careful when replacing CPX valve
OFF
parameterisation and terminals with saved parameterisation.
LED lights up saved CPX equipment With these CPX valve terminals, para
status is set; meterisation is not carried out auto
parameters and CPX equip matically by the higher−order PLC/IPC
ment status are saved when the terminal is replaced. In
remanently; external para these cases check before replacing to
meterisation is blocked 1) see which settings are required and, if
necessary, carry out these settings.
ON Force is active 1) The Force function is enabled
OFF
(see system parameter Force mode",
function no. 4402).
LED flashes
1) The display of the Force function (LED flashes) has precedence over the display of the setting for
System start (LED lights up).
DeviceNet−specific LEDs
ON
Operating status normal None
OFF
lights up
green
flashes red
lights up red
ON CPX terminal is in self−test None
OFF
flashes
red−green
ON
The CPX terminal is online None (normal operating status)
OFF
and has a connection to
lights up the field bus.
green
ON One or several I/O con Check the physical connection to the
OFF nections" are in the scanner (bus cable).
time−out status
flashes red
ON The CPX terminal has a net LED self−test or device can no longer
OFF work access fault and is in communicate; check scanner; evalu
the status Communication ate fault message from scanner.
Flashes failed".
red/green
*) Test algorithm which ensures that station numbers on the network are not assigned twice.
The test is usually carried out automatically when the network connection is set up.
ON Logic supply for bus inter I/O control via DeviceNet, device is
OFF
face not applied not allocated by a scanner
is out
ON
One or more inputs/out None
OFF
puts is/are controlled via
lights up DeviceNet.
None of the inputs/outputs
has a fault.
ON One or more outputs is/are I/O control via DeviceNet, but device
OFF in the idle state and none is allocated by the scanner and the
of the outputs is active or scanner is in idle mode, e.g. program
flashes green faulty. ming mode.
ON One or more inputs/out Check the inputs/outputs and the
OFF puts is/are faulty, perhaps communication connection to the
in fault status. scanner.
flashes red
Please note
If status bits are to be transmitted via a Polled" or
Change of State" connection, you must set the DIL
switches on the field bus node accordingly (see Tab.1/3).
2 Fault at input
5 Short circuit/overload
6 Cable fracture
7 Other faults
Please note
In order to use the I/O diagnostic interface, you must
activate it with the DIL switch on the field bus node.
Group Description
Dat/Par PI Mod
Dat/Par Fct.Mod
Dat/Par MPA...
1 Group
SysDiag.Data
Example
In Fig.3/2 a fault is shown at module position 3. If the CPX
terminal were equipped as shown in the following diagram,
there would be a digital output module (4DO) in this position.
The relevant module diagnostic data would therefore be in
the group Dat/ParDig.Mod2.
1 2 3
Module
position: 0 1 2 3 4 5 6 7
ÓÓÓÓ
4DI 8DI 4DO 2AO 8DI 8DO 2AO
ÓÓÓÓ
ÓÓÓÓ
16 O
ÓÓÓÓ
1 First digital module 3 Third digital module
(digital module 0) (digital module 2)
2. Ascertain the number of the module in which Number of the module Module−independent
a fault has occurred. system object (114d)
3. Ascertain relevant module diagnostic data Fault number, channel Parameter Object
type and number of Module (100d or 102d)
the faulty channel
telegram failure
Warning
· Make sure that valves and outputs are put into a safe
state if the named faults occur.
An incorrect status of the valves and outputs can lead to
dangerous situations.
Please note
Please note the following if the outputs are reset after PLC
stop, field bus interruption or fault:
Single−solenoid valves move to the basic position.
Double−solenoid valves remain in the current position.
Mid−position valves move to the mid−position (depend
ing on valve type: pressurised, exhausted or blocked).
Appendix A
Contents
General information
Electrical isolation
DeviceNet interface Electrically isolated (optocoupler)
Field bus
Cable length
(depends on baud rate and cable type) Max. 500 m
Please note
Please note that the greater the number of parameters
contained in an EDS file, the longer is the time required for
transmission of the parameters.
Group Description
Group Description
MPA pneumatics 1) Dat/Par MPA Data and parameters of the MPA pneumatics module 0
Dat/Par MPA1 Data and parameters of the MPA pneumatics module 1
Dat/Par MPA... Data and parameters of the MPA pneumatics module ...
Pneumatic interface 2) Dat/Par PI Mod Data and parameters of the pneumatic interfaces
1) Only relevant for CPX terminals with MPA pneumatics
2) Only relevant for CPX terminals with CPA or Midi/Maxi pneumatics
Module 1 2 3 4 5
position: 0 1 2 3 4 5 6 7
16 O
6 7
1 First digital module (digital module 0) 5 Second MPA electronic module (MPA 1)
2 Second digital module (digital mod. 1) 6 First analogue module (ana. module 0)
3 Third digital module (digital module 2) 7 Second analogue module (analogue
module 1)
4 First MPA electronic module (MPA 0)
Fig.A/1: Numbering the modules (example with MPA pneumatics)
Module 1 2 3 4
position: 0 1 2 3 4 5 6
5 6
A.4.2 Channel assignment for Force, Fail safe and Idle parameters
The Force, Fail safe and Idle parameters for the various
channel types are respectively combined into groups
(standard EDS).
Identifier *) Description
DO Digital outputs/valves
DI Digital inputs
AO Analogue outputs
AI Analogue inputs
*) Channel type identifier in group names
8O
4 8
8 8
0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 2
ÓÓ ÓÓ
4DI 8DI 4DO 2AO 8DI 8DO 2AO
8O ÓÓ
ÓÓ ÓÓ
ÓÓ
4 8 8 ÓÓ ÓÓ
0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 2
ÓÓÓÓ
4DI 8DI 4DO 2AO 8DI 8DO 2AO
8O ÓÓ
ÓÓÓÓ
ÓÓ
ÓÓÓÓ
1 2
Appendix B
Contents
ÓÓ ÓÓ
ÓÓ
ÓÓÓÓ
ÓÓ Modification
Digital output
Modification
Digital input
Modification Modification
Function output Function input
16−bit input data
16−bit output
data
8−bit output data
System object
8−bit input data
General
parameters
Object
Message
Assembly Assembly
Router
Assembly Inputs Diagnostic byte outputs
Diagnostic trace
object
I/O Explicit
I/O Connection
Connection Message Diagnostic trace
status object
B.1.2 Overview
I/O Polling
05 (0x05) Reset
Pneumatic interface 16
104 Get Module fault number (see System manual USINT 2008 + m * 4 + 1
chapter 5 Possible fault numbers") (bit 0 ... 7)
109 Get/Set Input debouncing time (value range 0 ... 3) USINT 4828 + m * 64 + 1
0: 0.1 ms (bits 4, 5)
1: 3 ms (typical presetting)
2: 10 ms
3: 20 ms
110 Get/Set Signal extension time (value range 0 ... 3) USINT 4828 + m * 64 + 1
0: 0.5 ms (bits 6, 7)
1: 15 ms (typical presetting)
2: 50 ms
3: 100 ms
111 Reserved
112 Reserved
115 Reserved
...
118
Pneumatic interface
1st parameter (32 bits):
Activate monitoring wire fracture channel−by−channel;
placing in the 1st./2nd./3rd./4th. byte parameter of
object 100 (attributes 119, 120, 121 and 122).
Object class: 04
Instances: 100 ... 102
Description Instances
Sequence of transmission
Each new data range begins on the LSB (least significant bit)
of a word.
Sequence of transmission
Each new data range begins on the LSB (least significant bit)
of a word.
B.1.5 Channel assignment for Force, Fail safe and Idle parameters
The Force, Fail safe and Idle parameters for the various chan
nel types are each grouped together in objects.
Object Description
The assignment of the channels with the Force, Fail safe and
Idle parameters is identical to the assignment of the para
meters of the EDS file.
The Force, Fail safe and Idle parameters of the digital outputs
are split into words (16 bits) and distributed among the max.
32 instances of this object. There is no module orientation.
The existing digital outputs are assigned in blocks of 16 bits
in ascending order without gaps.
The Force, Fail safe and Idle parameters of the digital inputs
are also split into words (16 bits) like those of the digital out
puts and distributed among the max. 32 instances of this
object. There is no module orientation. The existing digital
inputs are assigned in blocks of 16 bits in ascending order
without gaps.
The Force, Fail safe and Idle parameters for the analogue out
puts are administered in this object. The first analogue out
put (channel 0) is administered in instance 1. The second
analogue output (channel 1) in instance 2 etc.
The Force, Fail safe and Idle parameters for the analogue in
puts are administered in this object. The first analogue input
(channel 0) is administered in instance 1. The second ana
logue input (channel 1) in instance 2 etc.
The Force, Fail safe and Idle parameters of the outputs of the
function modules are split into words (16 bits) and distrib
uted among the max. 32 instances of this object. There is no
module orientation. The existing outputs are assigned in
blocks of 16 bits in ascending order without gaps.
The Force, Fail safe and Idle parameters of the inputs of the
function modules are split into words (16 bits) and distrib
uted among the max. 32 instances of this object. There is no
module orientation. The existing inputs are assigned in
blocks of 16 bits in ascending order without gaps.
100 Get CPX operating mode (bit 0 ... 3) BYTE 0 (bit 0 ... 3)
0: Remote I/O without FEC
1: Remote I/O with FEC
2: Remote controller without bus node
3: Remote controller with bus node
102 Get Monitoring CPX terminal (bit 0 ... 7) BYTE 2 (bit 0 ... 7)
Specifies whether the monitoring of short
circuit/overload and undervoltage is active or
inactive.
Bit 0: Monitoring short circuit/overload in
the sensor supply
Bit 1: Monitoring short circuit at the outputs
Short circuit/overload at the outputs
Bit 2: Monitoring VOUT
Undervoltage at the outputs
Bit 3: Monitoring VOUT
Undervoltage at valves
Bit 4: Monitoring SCV (short circuit at valves)
Bit 5 ... 7: Reserved
0: Inactive
1: Active
103 Reserved
104 Reserved
110 Get Fault number (bit 0 ... 7) (see System manual USINT 1938 (bit 0 ... 7)
chapter 5 Possible fault numbers")
116 Reserved
117 Reserved
118 Reserved
119 Reserved
125 Reserved
126 Reserved
127 Reserved
128 Reserved
129 Reserved
130 Reserved
131 Reserved
132 Reserved
The 16−bit wide I/O diagnostic interface and the status bits
are mapped here.
101 Get/Set 16 output bits (order data) of the I/O diagnostic UINT
interface
102 Get 16 input bits (reply data) of the I/O diagnostic UINT
interface
100 Get Number of Trace entries in the diagnostic memory USINT 3482
(bit 0 ... 7)
Appendix C
Contents
ÓÓ ÓÓ
ÓÓ ÓÓ
ÓÓÓÓ Force Output Fault Output
Object Object
Message
Assembly Assembly
Assembly Router
Diagnostic byte outputs
Inputs
Diagnostic trace
object
I/O Explicit
I/O Connection
Connection Message Diagnostic trace
status object
Fig.C/1: DeviceNet object model of the CPX terminal for modular EDS
C.1.2 Overview
I/O Polling
05 (0x05) Reset
Object class: 04
Instances: 101 ... 103
Description Instances
Sequence of transmission
Each new data range begins on the LSB (least significant bit)
of a word.
Sequence of transmission
Each new data range begins on the LSB (least significant bit)
of a word.
The 16−bit wide I/O diagnostic interface and the status bits
are mapped here.
101 Get/Set 16 output bits (order data) of the I/O diagnostic UINT
interface
102 Get 16 input bits (reply data) of the I/O diagnostic UINT
interface
100 Get CPX operating mode (bit 0 ... 3) BYTE 0 (bit 0 ... 3)
0: Remote I/O without FEC
1: Remote I/O with FEC
2: Remote controller without bus node
3: Remote controller with bus node
102 Get Monitoring CPX terminal (bit 0 ... 7) BYTE 2 (bit 0 ... 7)
Specifies whether the monitoring of short
circuit/overload and undervoltage is active or
inactive.
Bit 0: Monitoring short circuit/overload in the
sensor supply
Bit 1: Monitoring short circuit at the outputs
Short circuit/overload at the outputs
Bit 2: Monitoring VOUT
Undervoltage at the outputs
Bit 3: Monitoring VOUT
Undervoltage at valves
Bit 4: Monitoring SCV (short circuit at valves)
Bit 5 ... 7: Reserved
0: Inactive
1: Active
103 Reserved
104 Reserved
110 Get Fault number (bit 0 ... 7) (see System manual USINT 1938 (bit 0 ... 7)
chapter 5 Possible fault numbers")
116 Reserved
117 Reserved
118 Reserved
119 Reserved
125 Reserved
126 Reserved
127 Reserved
128 Reserved
129 Reserved
130 Reserved
131 Reserved
132 Reserved
Newer modules from Use the general module−parameter object (see section C.1.7)
mid−2005 onward to parameterise modules with word or double−word para
meters.
104 Get Module fault number (see System manual USINT 2008 + m * 4 + 1
chapter 5 Possible fault numbers") (bit 0 ... 7)
109 Get/Set Input debouncing time (value range 0 ... 3) USINT 4828 + m * 64 + 1
0: 0.1 ms (bits 4, 5)
1: 3 ms (typical presetting)
2: 10 ms
3: 20 ms
110 Get/Set Signal extension time (value range 0 ... 3) USINT 4828 + m * 64 + 1
0: 0.5 ms (bits 6, 7)
1: 15 ms (typical presetting)
2: 50 ms
3: 100 ms
111 Reserved
112 Reserved
115 Reserved
...
118
119 Get/Set Monitoring wire fracture CPA channel 0...7 SINT 4828 + m * 64 + 6
120 Get/Set Wire fracture monitoring for CPA 8...15 SINT 4828 + m * 64 + 7
121 Get/Set Monitoring wire fracture for CPA 16...23 SINT 4828 + m * 64 + 8
122 Get/Set Monitoring wire fracture for CPA 24...31 SINT 4828 + m * 64 + 9
Newer modules from Use the general parameter module object to parameterise
mid−2005 onward modules with word or double−word parameters. Examples
for modules with word or double−word parameters are: the
analogue 4−input module CPX−4AE−I, the temperature mod
ule CPX−4AE−T or the CPX−CP interface.
Procedure for 1. Take the function no. of the parameter that you would
parameterisation like to set from the manual for the module.
64 4828 + m * 64 + 63
Module no./
Instance no.: (0) 1 2 3 4 5 6
4
8DI AI−I 8DI 8DO
8O 8O
1 2
Fig.C/2: Examples for parameterisation with the general module parameter object
3 4828 + m * 64 + 2
67
4 4828 + m * 64 + 3
68
5 4828 + m * 64 + 4
69
6 4828 + m * 64 + 5
70
7 Signal extension channel x 4828 + m * 64 + 6
71
8 ... 4828 + m * 64 + 7
Please note
For parameterisation with the general module parameter
object, a software status of at least R16 is required
(see Tab.0/1).
C.1.8 Channel assignment for Force, Fail safe and Idle parameters
The Force, Fail safe and Idle parameters for the various
channel types are each grouped together in objects.
Object Description
The assignment of the channels with the Force, Fail safe and
Idle parameters is identical to the assignment of the para
meters of the EDS file.
100 ... 115 Get/Set Force mode parameter byte 0 ... 15 BYTE
(Digital input modules)
116 ... 131 Get/Set Force state parameter byte 0 ... 15 BYTE
(Digital input modules)
132 ... 147 Get/Set Force mode parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
148 ... 163 Get/Set Force state parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
164 ... 167 Get/Set Force mode parameter analogue inputs WORD
channel 0 ... 3
168 ... 172 Get/Set Force state parameter analogue inputs WORD
channel 0 ... 3
Tab.C/6: Objects for forcing inputs (grey: example for forcing from Fig.C/3)
Module no./
Instance no.: (0) 1 2 3 4 5 6
4
8DI AI−I 8DI 8DO
8O 8O
1 2
100 ... 115 Get/Set Force mode parameter (byte 0 ... 15 BYTE
(Digital output modules)
116 ... 131 Get/Set Force state parameter byte 0 ... 15 BYTE
(Digital output modules)
132 ... 147 Get/Set Force mode parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
148 ... 163 Get/Set Force state parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
164 ... 167 Get/Set Force mode parameter analogue outputs WORD
channel 0 ... 3
168 ... 172 Get/Set Force state parameter analogue outputs WORD
channel 0 ... 3
100 ... 115 Get/Set Fault mode parameter byte 0 ... 15 BYTE
(Digital output modules)
116 ... 131 Get/Set Fault state parameter byte 0 ... 15 BYTE
(Digital output modules)
132 ... 147 Get/Set Fault mode parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
148 ... 163 Get/Set Fault state parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
164 ... 167 Get/Set Fault mode parameter analogue outputs WORD
channel 0 ... 3
168 ... 172 Get/Set Fault state parameter analogue outputs WORD
channel 0 ... 3
Tab.C/8: Objects for Fault mode and Fault state of the outputs
100 ... 115 Get/Set Idle mode parameter byte 0 ... 15 BYTE
(Digital output modules)
116 ... 131 Get/Set Idle state parameter byte 0 ... 15 BYTE
(Digital output modules)
132 ... 147 Get/Set Idle mode parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
148 ... 163 Get/Set Idle state parameter word 0 ... 15 WORD
(Technology modules, e.g. CP interface)
164 ... 167 Get/Set Idle mode parameter analogue outputs WORD
channel 0 ... 3
168 ... 172 Get/Set Idle state parameter analogue outputs WORD
channel 0 ... 3
Tab.C/9: Objects for Idle mode and Idle state of the outputs
100 Get Number of Trace entries in the diagnostic memory USINT 3482
(bit 0 ... 7)
Appendix D
Contents
D. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D−1
A
Abbreviations, product−specific . . . . . . . . . . . . . . . . . . . . XIV
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A−4
Additional power supply . . . . . . . . . . . . . . . . . . . . . . . . . 1−29
Address assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−8
Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−3
B
Baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−11, 1−17
Branch line lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−17
Bus configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−18
Bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−27
C
Cable
Field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−16
Connecting
Field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−16
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−28
Connection diagram for DeviceNet . . . . . . . . . . . . . . . . . 1−19
CP interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−11
D
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
DeviceNet Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . B−3, C−3
Diagnosis
Via I/O diagnostic interface . . . . . . . . . . . . . . . . . . . . . 3−13
Via LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−4
Via status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−12
E
EDS file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−21
EDS files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−21, A−5
EDS mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−9
Electrical connecting and display elements . . . . . . . . . . . 1−4
F
Field bus baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−17
Field bus cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−16
Field bus length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−17
Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−5
I
I/O diagnostic interface . . . . . . . . . . . . . . . . . . . . . . . . . . 3−13
ICO/BMP file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−21, 2−22
Idle mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−51
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . . . IX
Inputs
Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−7
L
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−4
M
Micro Style connection . . . . . . . . . . . . . . . . . . . . . . . . . . 1−20
Modular EDS files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−22
N
Notes on the use of this manual . . . . . . . . . . . . . . . . . . . . . . XI
O
Object model
Modular EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−3
Standard EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B−3
Open Style connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−21
Operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−9
Outputs
Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−7
P
Parameterisation
Automatically after Power On . . . . . . . . . . . . . . . . . . . 2−52
Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−43
On the DeviceNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−24
Prerequisite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−42
Via the PLC user program . . . . . . . . . . . . . . . . . . . . . . 2−54
With RSNetWorx . . . . . . . . . . . . . . . . . . . . . . . . . . 2−45, 2−48
PELV (Protected Extra−Low Voltage) . . . . . . . . . . . . . . . . 1−28
Pictograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
Pin allocation
Field bus interface . . . . . . . . . . . . . . . . . . . 1−20, 1−21, 1−23
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−28
Switching on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−19
R
RSNetWorx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−14
Modular EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−33
Standard EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−25
S
Screened connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−24
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VIII
Setting
Baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−11
Diagnostic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−10
EDS mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−9
Operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−9
Station number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−12
Software status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XI
Station numbers
Permitted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−12
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−13
Status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−12
Strain relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−16
Sub−D plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−23
Switch cover
Removing and fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−6
System supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−29
T
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VIII
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . A−3
Text markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
V
Valve supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−29
0310d