FEATURES
3-or single phase voltage measurement with galvanic isolation
100..110..120VAC / 4.55..5..5.45VAC, 50/60Hz
Single-phase current measurement 5 or 1AAC on 3 VAC
Used in combination with the digital I/O interface UNS 0863
Connection with UNS 0863 via flat cable
Inputs via WAGO spring-clamp terminals
Standard dimensions for screwing onto aluminium board
SHORT DESCRIPTION
The interface UNS 0862 allows the measurement of the machine voltage and machine
current within the UNITROL-F excitation system.
In order to measure the actual voltage value, the 3-phase machine voltage is galvanically
isolated by means of transformers in V-connection and adapted to electronics level.
By a single phase actual measurement, the machine voltage must be connected to
terminals 2-3.
The single-phase current is also measured by means of transformers for galvanical
isolation and adaptation to electronics level.
On the secondary side, a variable load is present which transforms the current signal into
a proportional voltage.
The signals generated in this way are fed parallel to the two connectors X11 and X12.
Spring-clamp terminals are provided on the input side.
A flat cable is used for the connection to the I/O interface UNS 0863.
1 X11/X12:1/2
110V 5V
2 3/4
TABLE OF CONTENTS
FEATURES .................................................................................................................................... 1
SHORT DESCRIPTION.................................................................................................................. 1
1. DEVICE BLOCK DIAGRAM....................................................................................................... 3
2. FUNCTIONAL DESCRIPTION ................................................................................................... 3
2.1 Schematic Diagram .............................................................................................................. 3
2.2 Signal Connections .............................................................................................................. 4
3. CONFIGURATION ..................................................................................................................... 4
3.1 Load for Current Measurement ............................................................................................ 4
3.2 Flat Cable Connections ........................................................................................................ 4
4. COMMISSIONING AND FUNCTION CHECK ............................................................................ 4
5. TECHNICAL DATA .................................................................................................................... 5
5.1 Power Supply ....................................................................................................................... 5
5.2 Input Values ......................................................................................................................... 5
5.2.1 Machine Voltage Terminals 1-2-3...................................................................................... 5
5.2.2 Machine Current Terminals 5-6-7 ...................................................................................... 5
5.3 Output Values ...................................................................................................................... 5
5.3.1 Machine Voltage (X11/X12: 1 ...6)..................................................................................... 5
5.3.2 Machine Current IR (X11/X12: 7 ... 10).............................................................................. 5
5.4 Setting Values ...................................................................................................................... 6
5.4.1 Current Measurement ....................................................................................................... 6
5.5 Environmental Values .......................................................................................................... 6
5.5.1 Permissible Temperature Range ....................................................................................... 6
5.5.2 Climatic Stability................................................................................................................ 6
5.5.3 Mechanical Stability........................................................................................................... 6
5.5.4 EMC (Electromagnetic Compatibility) ................................................................................ 6
5.5.5 Altitude of Installation ........................................................................................................ 7
5.5.6 Protection Means .............................................................................................................. 7
5.5.7 Test Voltages .................................................................................................................... 7
5.6 Reliability.............................................................................................................................. 7
6. CONSTRUCTION DATA ............................................................................................................ 7
6.1 Dimensions .......................................................................................................................... 7
6.2 Weight.................................................................................................................................. 7
6.3 Connectors........................................................................................................................... 7
6.3.1 Inputs ................................................................................................................................ 7
6.3.2 Outputs ............................................................................................................................. 7
6.4 Location of Control Elements ............................................................................................... 8
6.5 Location of Control Elements on the Interface Board............................................................ 8
7. ORDERING INFORMATION ...................................................................................................... 8
HIEE 422027 E
-3- UNS 0862a-P, V.1
2. FUNCTIONAL DESCRIPTION
2.1 Schematic Diagram
1 T1
TP1
UR X11:1/2
110V
5V eff TP4
US
2 3/4
TP5
110V 5V eff UT
5/6
3 T2 X12:1/2
3/4
4 5/6
TP8
1A 10mA 3V eff IR
5 X11:7/8
3300 Ohm
330 Ohm
15V
5A
6 15V TP9
ZA
7 X11:9/10
X12:7/8
X12:9/10
HIEE 422027 E
-4- UNS 0862a-P, V.1
3. CONFIGURATION
3.1 Load for Current Measurement
In the basic configuration, a load resistor of 330 Ohms is used for measuring the current. This
together with the parallel permanently-installed 3k3 resistor, produces a total load of 300 Ohms.
The load resistor, which can be soldered in place, must conform to the standard XN 400323.
HIEE 422027 E
-5- UNS 0862a-P, V.1
5. TECHNICAL DATA
5.1 Power Supply
No external power supply
HIEE 422027 E
-6- UNS 0862a-P, V.1
HIEE 422027 E
-7- UNS 0862a-P, V.1
5.6 Reliability
Failure rate
Condition: GB, 40°C 164 FIT
6. CONSTRUCTION DATA
6.1 Dimensions
Dimensions(LxWxH) 110 x150 x 42 [mm]
Mounting:
PCB to be screwed onto standard aluminium module mounting
6.2 Weight
Mass 0.960 kg
6.3 Connectors
6.3.1 Inputs
Terminals 1 ... 7 (double clamps) Type WAGO 228533, 4 mm2
Double cage spring clamps for the connection of two conductors (wire or strand) per signal.
6.3.2 Outputs
X11/X12:
10-pin connector, construction form A in accordance with DIN 41651.
HIEE 422027 E
-8- UNS 0862a-P, V.1
TP
10 poles
10 poles
10 poles
10 poles
X12
X12
X11
X11
I/O Interface UNS 0863
Terminals
1 2 3 4 5 6 7
110 mm
X31 X32
TWIN
10 poles
10 poles
10 poles
10 poles
10 poles
10 poles
X11
X12
X11
X12
X12
X11
5 No 5
Yes
1 7 1 7
Interface board
UNC 4866
7. ORDERING INFORMATION
Order number: UNS 0862a-P, V.1 HIEE 405179 R1
HIEE 422027 E