Stray Current Control in DC Mass Transit
Stray Current Control in DC Mass Transit
ABSTRACT
Stray current control is essential in direct current (DC) mass transit systems where the
rail insulation is not of sufficient quality to prevent a corrosion risk to the rails
supporting and third-party infrastructure. Alternative current (AC) proved to be much
less dangerous than DC. Stray current, arising for instance from railways, cathodic
protection systems, may find a low resistance path by flowing through metallic
structures buried in the soil (pipelines, tanks, industrial and marine structures). For
instance, underground pipelines can pick up current strayed from a railways system at
some point remote from the traction power substation and discharge the current to the
soil and then back to rail near to the substation. Metal loss results at the anodic
points, where the current leaves the structure. Usually, the attack is extremely
localized and can have dramatic consequences, especially on pipelines. Among
various mitigation methods, the drainage bond method either of polarized type or of
forced type was widely adopted by the pipeline engineers. This paper describes the
results of a systematic field investigation of stray current associated with the subway
system and drainage method in Tehran.
RÉSUMÉ
La maîtrise de la circulation des courants vagabonds continus (DC) générés par les
systèmes de transport en commun est primordiale lorsque la qualité de l’isolation du
rail par rapport au ballast n’est pas suffisante afin d’éviter un risque de corrosion des
supports de rails et des infrastructures de tiers. Les courants alternatifs (AC) se sont
avérés beaucoup moins dangereux que les courants continus (DC). Les courants
vagabonds continus, générés par exemple par les systèmes de chemins de fer ou
les systèmes de protection cathodique, peuvent utiliser les structures métalliques
enfouies dans le sol (canalisations, réservoirs, ouvrages industriels et maritimes)
comme circuit électrique de faible résistance. Par exemple, des canalisations
souterraines peuvent capter des courants émis par les voies de chemin de fer dans
le sol loin des sous-stations alimentant en énergie de traction, courants qui peuvent
ressortir dans le sol au voisinage de la sous-station. Cette sortie de courant va
engendrer des pertes de métal au niveau des points anodiques ainsi créés où le
courant sort de la structure. Généralement, l'attaque est très localisée et peut avoir
des conséquences dramatiques en particulier sur les pipelines. Parmi les diverses
méthodes d'atténuation, les ingénieurs spécialisés en pipelines ont largement utilisé
la méthode de drainage des courants par liaison polarisée ou forcée. Cette
présentation décrit les résultats d'une investigation systématique de terrain réalisée
sur les courants vagabonds continus associés avec le système de métro et la
méthode de drainage à Téhéran.
RÉSUMÉ
a
Automa Srl (Monsano(AN), Italie, nathanael.poinsel@automaonline.com)
b
GAS NATURAL SDG S.A. (Barcelona, Espagne, aorta@gasnatural.com)
c
Automa Srl (Monsano(AN), Italie, giorgio.g@automaonline.com)
d
Automa Srl (Monsano(AN), Italie, ivano.m@automaonline.com)
e
Automa Srl (Monsano(AN), Italie, alessio.r@automaonline.com)
f
Automa Srl (Monsano(AN), Italie, roberto.b@automaonline.com)
ABSTRACT
Measure, store, transmit and manage. Monitoring a set of measuring stations seem a simple
and linear activity. But what about when the measuring stations are a few thousands,
distributed over several countries and continents?
What can we do to speed the installation process, improve maintenance, and prevent the
possibility of errors?
These are the types of problems that had to confront Automa, collaborating with its customers
and partners during the 18 months of testing and installation of the remote monitoring system
of Fenosa Gas Natural Group in Spain, Italy and Mexico.
This presentation aims to illustrate the iterative and shared design methodology that we used
to adapt the technical specifications required for the variety of situations encountered in the
field during a large-scale installation, defining a rational course of planning and verification
of post-sales activities.
Didier JACQUEMIN
RESUME
Le port de Boulogne-sur-Mer gère un quai de commerce appelé quai de l’Europe construit entre les années 1968
et 1972 qui est un ouvrage de type appontement en béton armé fondé sur deux files de piles colonnes sur la partie
avant et une gabionnade sur la partie arrière. Moins de 20 ans après sa construction, les palplanches de la
gabionnade présentent un nombre de perforations importantes localisées au niveau des basses eaux. Un
programme d’études a défini l’origine d’une corrosion accélérée par la présence de bactéries sulfato-réductrices.
Un programme de requalification est alors engagé et comporte 4 phases qui sont :
- La réalisation de mesures d’épaisseur résiduelle des palplanches permettant de connaître les zones faibles et
ainsi programmer leur renforcement.
- Le renforcement localisé des palplanches faibles par soudure réalisées en partie en mode hyperbare de tôles
de doublage.
- Le traitement par peinture de la zone des piles colonnes et de la gabionnade accessible à marée basse.
- La mise en œuvre d’un système de protection cathodique sur l’ensemble des parties métalliques.
Dans le cadre des études de requalification, différents systèmes de peinture sont testés en association avec une
protection cathodique.
La période d’études terminée, les travaux de confortement sont engagés avec dans un premier temps le
diagnostic et le renforcement et dans un second temps :
- La mise en œuvre du système de peinture qui se déroule en 1998 avec un polyuréthane/zinc monocomposant
appliqué humide sur humide. Le chantier demande une logistique particulière du fait des accès sous
l’ouvrage en fonction des mouvements de marées.
- La mise en œuvre de la protection cathodique par anodes sacrificielles se déroule après la réception de la
peinture. La particularité de ces travaux concerne la validation par un progiciel du dimensionnement de la
protection.
Une instrumentation de surveillance est installée après travaux et permet un suivi de la protection cathodique
pour trois profils répartis sur le linéaire de la gabionnade. Chaque profil comprend 3 boîtiers installés sur 3
niveaux correspondant à :
- la zone protégée par le système de peinture.
- la zone nue où sont installées les anodes sacrificielles.
- la zone enterrée.
En 2007, une inspection visuelle permet de constater que la peinture a un vieillissement correct. Par contre les
anodes du secteur môle Nord Est et de la fin du quai présentent une diminution très nette de la masse d’alliage.
En 2010, une nouvelle inspection confirme cette anomalie de consommation des anodes du secteur môle Nord
Est et de la fin du quai. L’acier nu reste couvert du dépôt calcomagnésien.
L’objectif de maintenir l’ouvrage en état d’exploitation normale pour une durée de 15 ans (début 2014) n’est pas
encore atteint. Néanmoins la garantie de durabilité du revêtement peinture est à ce jour dépassée avec un
comportement global très satisfaisant. Pour ce qui concerne la protection cathodique, l’efficacité est toujours
présente avec aucune résurgence de corrosion. Il reste à analyser le problème localisé de la surconsommation
dans le secteur du môle Nord Est.
1/2
49
Didier JACQUEMIN
ABSTRACT
The port of Boulogne-sur-Mer runs a business dock called dock of Europe built between the years
1968 and 1972. This is a pier-type structure of reinforced concrete based on two rows of batteries on
the front columns and cellular structures on the back. Less than 20 years after its construction, the
piles of cellular structures have a large number of perforations located at low water. A program of
study has concluded that the cause of accelerated corrosion is the presence of sulfate-reducing
bacteria. A requalification program was launched withs 4 phases that are:
- The implementation of measurements of residual thickness of the sheet piles to find weak areas and
thereby program their strengthening.
- Strengthening of localized small piles by welding of sheet linings carried out partly in hyperbaric
mode.
- A paint application on areas of cell columns and cellular structures accessible at low tide.
- The implementation of a cathodic protection system on all metallic parts.
In the studies for re-qualification, different paint systems were tested in combination with cathodic
protection.
After the study, remedial works are engaged with, first, the diagnosis and strengthening and second:
- The implementation of the paint system takes place in 1998 with a polyurethane / zinc-component
applied wet on wet. The site requires specific logistics because of access under the structure
according to the movements of tides.
- The implementation of cathodic protection with sacrificial anodes after reception of paint. A
specificity of these works is the validation using modeling software.
A monitoring instrumentation is installed after the works and allows monitoring of cathodic protection
for three profiles located on the linear cellular structures. Each profile includes 3 boxes installed on 3
levels corresponding to:
- The area protected by the paint system.
- The bare area where the sacrificial anodes are installed.
- The buried area.
In 2007, a visual inspection reveals that the painting has a proper aging. However anodes of sector
pier North East and the end of the dock have a clear diminution of the mass of alloy.In 2010, another
inspection confirms this anomalic anode consumption on sector Pier North East and the end of the
dock. The bare steel is covered with the calcareous deposits.
The objective of keeping the structure in a state of normal operation for a period of 15 years (early
2014) is not reached. Nevertheless, the guarantee of durability of the coating paint is so far exceeded
with a very satisfactory global behavior. With regard to cathodic protection, efficiency is always
present with no recurrence of corrosion. It remains to analyze the local problem of overconsumption
in the North East of the pier.
2/2
48
ABSTRACT
The long term anticorrosion protection of buried pipelines is linked to the ability of
coating materials to ensure a barrier effect against corrosive components such as
water and salts.
On the other hand, in order to withstand in-service stresses, the coating also needs to
have good adhesion on the steel substrate, even under drastic conditions that combine
high temperature and humidity.
As regards FBE (fusion bonded epoxy) coatings, it has already been demonstrated that
barrier performance is due to the hydrophobic nature of the coating and consequently
its ability to maintain a high glass transition temperature, despite humid and hot
surroundings.
In order to maintain adhesion under such conditions, good substrate preparation is the
key to success. Indeed, the usual recommendations are based on chemical pre-
treatments of steel, through the application of chromate or phosphate based products.
A new application process (SILPIPE patent pending) for FBEs, used either as
monolayer coatings or as primers in multilayer systems, is proposed. This process
includes a no-rinse chemical treatment with a solvent free and non-toxic product:
SILPIPE SCT.
This paper demonstrates the interest of this process through the adhesion performance
of FBE coatings immersed in hot water.
Keywords: FBE adhesion, wet adhesion, non-toxic chemical treatment of steel pipe.
48
RÉSUMÉ
La protection à long terme contre la corrosion des canalisations enterrées est liée à la
capacité des matériaux de revêtement à assurer un effet de barrière contre les
composants corrosifs comme l'eau et les sels.
D'autre part, afin de résister aux contraintes en service, le revêtement doit également
avoir une bonne adhérence sur le substrat en acier, même dans des conditions
drastiques qui combinent haute température et d'humidité.
En ce qui concerne les revêtements FBE (époxy poudre appliqué par fusion), il a déjà
été démontré que la performance de la barrière est due à la nature hydrophobe du
revêtement et par conséquent à la capacité à maintenir une température de transition
vitreuse élevée, malgré un environnement humide et chaud.
Afin de maintenir l'adhérence dans de telles conditions, la préparation du substrat est
la clé du succès. Ainsi, les recommandations habituelles sont basées sur des pré-
traitements chimiques de l'acier, par l'application de produits à base chromate ou de
phosphate.
Un nouveau procédé d’application (SILPIPE , brevet en instance) est proposé pour
les revêtements FBE, utilisés soit en tant que revêtements monocouches ou comme
primaires dans les systèmes multicouches. Ce procédé comprend un traitement
chimique sans rinçage avec un produit sans solvant et non toxique : SILPIPE SCT.
Cet article démontre l'intérêt de ce processus par les performances d'adhérence des
revêtements FBE immergés dans l'eau chaude.
ABSTRACT
The present document describes an innovative software tool for dimensioning galvanic
sacrificial zinc anodes used to prevent concrete steel reinforcement structure from
corrosion. Measurements and empirical research on simple model elements such as
walls, slabs, pillars or beams, that constitute the vast majority of construction work,
establish statistics and behavior of electrolytic phenomena which causes steel
corrosion within a concrete structure. Diverse fixed parameters configurations
experiments such as positioning, mass and induced current versus time determine
statistics about how sacrificial anode influences corrosion prevention. Holistic results
thus gathered, indentify mathematical modeling which rules the algorithm to
implement within the tridimensional object oriented programming. The computed
result can therefore help the user, from a simple model element, set criteria for
induced current and concrete structure definition, and visualize the result in a close
match to reality. He can know how many sacrificial anodes are required to prevent
steel corrosion and where they would be best positioned.
47
RÉSUMÉ
Thorsten WEILEKES
Avant l'apparition du dispositif de mesure universelle MiniLog2, les techniciens en protection cathodique
avaient toujours besoin de plusieurs appareils pour l'accomplissement des différents types de mesures.
ABSTRACT
Before the introduction of the MiniLog2 universal measurement device, technicians working for cathodic
protection measurement always needed several devices for fulfilling different kinds of measurement tasks.
MiniLog2 as switcher
As a basic preparation for cathodic protection measurements, one has to install a switcher at the rectifier
station, assuring the on- and off-switching of all feeding rectifiers in synchronized mode. The new MiniLog2
is able to switch 15 amps with its internal mechanical relay (18 amps electronically relay as option) and up
to 100 amps with an external slave relay. Many commonly used switching cycles are preset, but the user can
also manually setup its own switching cycle in 100ms steps.
By connecting the GPS antenna it is assured that the MiniLog2 stays synchronized within 10 ms. Without any
external re-synchronization, the special temperature regulated quartz build-in assures an accuracy of less
than +/-50ms per day.
When MiniLog2 is installed in places without mains, the internal chargeable lithium ion battery allows 30
days of continuously switching. Charging can be done by the included USB mains connector or the included
12V USB car adapter.
Clara CALVI
RÉSUMÉ
La télésurveillance est une technique qui évolue au même rythme que les
développements constants des technologies. Après 10 années de travaux en recherche
et développement et de réalisations dans le domaine appliqué à la télésurveillance des
systèmes de protection cathodique, TECNOSYSTEM a acquis un savoir-faire connu et
reconnu et bénéficie des retours d’expérience provenant de ses clients qui sont aussi
ses partenaires. C’est ainsi que TECNOSYSTEM a pu développer une nouvelle
plateforme internet avancée qui facilite une gestion innovante et intuitive des mesures
de protection cathodique.
C’est ainsi que sont fabriqués actuellement de façon industrielle des appareils
permettant d’effectuer et de transmettre une synthèse quotidienne des mesures de
courant et de potentiel DC en mode ON et OFF, ainsi que des mesures de l’influence
des courants alternatifs. Des enregistrements de mesures peuvent être aussi effectués.
Tous les appareils fonctionnent avec une couverture GSM s’étendant à tous les pays.
Le présent exposé présente ces appareils de dernière génération en s’appuyant sur les
aspects métrologiques, les garanties accordées et sur les différents systèmes de
protection : Confidentialité des données, protection contre la foudre …..
45
Clara CALVI
ABSTRACT
Remote monitoring is a technique which develops with the same rate as constant
developments in technology. After 10 years of work in research and development and
achievements in applied remote monitoring of cathodic protection systems,
TECNOSYSTEM has now a well-known and acknowledged expertise and benefits from
the feedback expressed by its customers who are also partners. Thus, TECNOSYSTEM
has been developing a new Internet platform that leads to advanced innovative and
intuitive management of cathodic protection measurements.
Successive developments of knowledge and expertise can now submit completely new
equipment that meet the needs expressed in the European standard in force and in
national guidelines or regulations.
Thus are currently industrially manufactured devices that are able to carry out and
transmit a daily report of measurements of current, ON and OFF DC potentials, and
alternating current influences. Recordings of measurements can be also carried out.
All TECNOSYSTEM devices work with GSM coverage extending to all countries.
This paper presents the latest generation of devices based on metrological aspects,
given guarantees and on the various systems of protection: confidentiality of data,
protection against lightning,....
44
Abstract
Les techniques mises en œuvre pour réaliser un système de protection cathodique sont de fait
en relation avec de nombreux sous-ensembles nécessairement isolés entre eux sous peine
d’affaiblir voire annuler la polarisation cathodique réalisant la protection contre la corrosion.
Ces sous-ensembles sont par exemple le poste de fourniture d’énergie, la salle de contrôle, les
abris d’instrumentation, les postes de soutirage de courants de protection ou de drainage des
courants vagabonds, les conduites enterrées etc.
Dans le cadre d’un risque de surtension électrique accidentelle, ces différents dispositifs sont
en général très éloignés les uns des autres et produisent des boucles naturelles pour les
câblages des courants forts et des courants faibles de grandes surfaces.
Il est notoire que les instrumentations et automatismes modernes sont sensibles à la qualité de
leur environnement électromagnétique.
Par conduction et par rayonnement, les effets de l’environnement (comme la foudre) peuvent
produire des tensions et des courants réputés parasites qui perturbent les circuits de mesures,
de transmissions de données et leur traitement, jusqu’à créer des désordres d’exploitation ou
des pannes et développer des risques électriques pour les personnes, les biens et
l’environnement.
La communication portera sur les techniques de protection contre les surtensions accidentelles
des appareillages sensibles dans des sites sous protection cathodique en milieu fortement
perturbés par la foudre et les courants industriels selon des expériences prestigieuses.
Elle décrira les modalités de la protection réglementaire qui se comportent comme des
barrières ultimes de protection, un rempart si l’on peut dire, ainsi que sur le durcissement en
Compatibilité Electromagnétique des Systèmes dont le rôle est de durcir les circuits à protéger
pour les rendre insensibles au milieu et non véhiculeurs des perturbations de tous ordres
créées par l’environnement.
44
ABSTRACT
The techniques used to install a cathodic protection system are in connection with many
subsets necessarily isolated from each other otherwise they may weaken or even eliminate the
cathodic polarization which provides protection against corrosion.
These subsets are, for example the energy supply system, the control room, instrumentation
shelters, cathodic protection stations or stray current drainage stations, buried pipelines and
so on.
To prevent hazards of accidental electrical overvoltage, these various devices are generally
very distant from each other and produce natural curls for cabling low and high currents of
large area systems.
It is well known that modern instrumentation and control systems are sensitive to the quality
of their electromagnetic environment.
By conduction and radiation, the effects of the environment (e.g. lightening) may produce
parasite voltages and currents that disrupt measurement, data transmission and processing
circuits, hat create operating disturbances or failures and develop electrical safety risks for
people, property and environment.
The paper will focus on techniques used to protect sensitive equipment on structures under
cathodic protection in areas highly disturbed by lightning and industrial currents according
to prestigious experiences.
It will describe the protection rules according to regulations that are the ultimate protection
barrier, as would be a rampart, as well as the hardening in Electromagnetic Compatibility of
Systems the function of which being to reinforce circuits to be protected in order to make
them insensitive to environment and not carriers of all kinds of disturbances created by the
environment.
43
RÉSUMÉ
ABSTRACT
Stéphane GASTAUD
RÉSUMÉ
____________________________________________________________
42
Stéphane GASTAUD
ABSTRACT
Philippe LE HÔ
RÉSUMÉ
Les conduites de transport (gaz, eau, pétrole,...) en acier sont protégées contre la
corrosion par une protection passive (revêtement brai, PE, PP,...).
Pour les tronçons particuliers comme les traversées de routes, les voies ferrées,...la
conduite de transport est installée dans une gaine (acier, béton, PVC,...) sans contact
direct avec le sol (électrolyte).
Les gaines sont parfois obturées mais peuvent laisser pénétrer la nappe phréatique, la
boue,... L'efficacité de la protection cathodique n'est pas avérée, ce qui peut présenter
un danger.
Ces tronçons représentent environ 1 % des canalisations (10 mètres pour un kilomètre
de conduite en moyenne).
Et pour finir, un appel à recourir le moins possible à l'emploi des gaines sera réalisé.
Philippe LE HÔ
ABSTRACT
The steel transport pipelines (gas, water, oil,...) are protected against corrosion by a
passive protection (bituminous coating, PE, PP ,...).
Any imperfections of coating lead to a contact of the metal with the soil. Cathodic
protection is effective in limiting the degradation of the metal in the soil.
For specific sections such as crossings of roads, railways, ... the pipeline is installed in
a casing (steel, concrete, PVC ,...) without direct contact with the soil (electrolyte).
The casings are sometimes plugged but can let ground water, mud, penetrating... The
effectiveness of cathodic protection is then not proven safe, which can present a
danger.
Sylvain FONTAINEa
a
GRTgaz, Compiègne, France, sylvain.fontaine@grtgaz.com
RÉSUMÉ
La normalisation, complétée par la certification du personnel, est essentielle pour garantir la qualité
de l’activité protection cathodique. En France, elle est gérée par la Commission A05L de l’AFNOR,
mais les travaux d’écriture des nouvelles normes ou de révision des normes existantes se font dans
le cadre du Comité Européen de Normalisation (CEN) et de l’ISO.
Un point complet de l’état des normes publiées ou en cours de préparation est réalisé. Le rôle,
parfois complexe, des différents comités techniques du CEN et de l’ISO agissant dans ce domaine
est schématisé.
La normalisation en protection cathodique est gérée en Europe par le comité technique CEN TC
219. Quatre groupes de travail préparent les normes pour ce comité. Le WG1 s’occupe des ouvrages
à terre, le WG2 des ouvrages en béton armé, le WG3 des ouvrages en mer et le WG4 de l’intérieur
des équipements. Certaines normes rédigées par les comités techniques du CENELEC dans le
domaine électrique interfèrent avec les préoccupations du CEN TC219.
A l’international l’ISO TC156, chargé de la corrosion, s’occupe de la protection cathodique par son
WG10. Celui-ci n’est pas moteur dans l’écriture de projets de normes mais organise des votes
parallèles en application des « Accords de Vienne » avec le CEN TC219 (leader) pour certains
projets (béton armé, principes généraux de la protection cathodique en mer, protection cathodique
des installations portuaires).
Par ailleurs, le comité technique ISO TC67 SC2, dédié aux pipelines des industries pétrolières,
pétrochimiques et gazières, rédige des normes de protection cathodique par son WG11. Le CEN
TC12, pendant de l’ISO TC67 en Europe, organise généralement les votes parallèles en application
des « Accords de Vienne » (ISO leader), sauf pour la protection cathodique, déléguée au CEN
TC219 le cas échéant.
Parmi les travaux en cours, la révision de la norme ISO 15589-1 sur les pipelines à terre est
particulièrement commentée, le but étant d’éditer une norme unique EN ISO qui pourrait aussi
remplacer la norme européenne EN 12954 en cours de révision également. De même, la norme ISO
15589-2 sur les pipelines offshore est aujourd’hui en révision et là encore devrait devenir une
norme EN ISO remplaçant la norme EN 12495. La procédure « UAP » devrait être utilisée pour
adoption de ces nouvelles normes ISO après leur parution.
La recommandation technique TS 15280 régissant le domaine de la corrosion des conduites
métalliques soumises à une tension électrique alternative. est en chantier pour transformation en
norme EN, avec la participation d’experts issus d’opérateurs de voies ferrées électrifiées et de
transport d’énergie électrique. En parallèle, un projet de norme (prEN 50443) est en préparation
depuis de très nombreuses années au sein du CENELEC avec la participation d’opérateurs de
conduites métalliques enterrées.
Un projet de norme sur la « protection cathodique des surfaces externes de la base en acier des
réservoirs aériens en contact avec le sol ou des fondations » est par ailleurs en cours d’enquête
CEN.
Mots-clés : protection cathodique, normalisation, AFNOR, CEN, ISO
40
Sylvain FONTAINEa
a
GRTgaz, Compiègne, France, sylvain.fontaine@grtgaz.com
ABSTRACT
RÉSUMÉ
La résistivité apparente est une grandeur physique qui résulte de la capacité d’une matière
hétérogène à laisser passer un courant électrique.
Dans le cas des sols, cette grandeur dépend principalement des paramètres de granulométrie, teneur
en eau et minéralisation. En fonction de ces paramètres, un échantillon de sol présentera des valeurs
parfois très différentes. On présente donc les gammes de valeurs représentatives des différents types
de sols communément rencontrés en environnement de canalisation terrestre.
Sur des zones de grande complexité, nous développons maintenant de nouvelles méthodes de
monitoring couplant des mesures continues de potentiel et de résistivité apparente.
ABSTRACT
The apparent resistivity is a physical quantity resulting from the ability of a heterogeneous
material to pass an electrical current.
In the case of soils, this magnitude depends mainly on parameters of particle size, water
content and mineralization. Based on these parameters, a soil sample present values can be
very different. It outlines the range of values representing different soil types commonly
found in terrestrial environment pipeline.
If recognition of the apparent resistivity of soil is necessary for the design of efficient
cathodic protection devices, the current practice does not take into account possible
variations of apparent resistivity as a function of climate cycles and external environmental
factors (changes parameters of the interstitial fluid by pollution, salinity changes ...). In
heterogeneous areas or complex changes in apparent resistivity, when not recognized early,
induce problems with the settings initially planned cathodic protection, both in terms of
current sources, but also on monitoring potentials.
Based on geophysical and laboratory tools, there are many ways to measure the apparent
resistivity of a volume of soil. These tools have different uses depending on the expected
results. A brief comparison of methods and instruments used to establish the limits of
existing equipment in the field and the laboratory. Depending on the outcomes and the
complexity of the soil, it is sometimes useful to combine several methods.
In areas of high complexity, we are now developing new monitoring methods combining
continuous measurements of potential and apparent resistivity.
The richness of this convergence opens up prospects for accuracy and performance, both in
recognition of soils that the optimization of cathodic protection.
La protection cathodique des conduites acier enterrées est assurée par des équipes au niveau local et une expertise au
niveau national. Ses opérateurs ont en charge la maintenance de l’ensemble des équipements de protection cathodique :
soutirage de courant, drainage de courant, système de mise à la terre pour la protection contre la corrosion des courants
alternatifs et prise de potentiel.
En 2006, GRTgaz a pris la décision de télésurveiller ses équipements de protection cathodique. Ainsi, dans un premier
temps, entre 2007 et 2010, après avoir sélectionné un prestataire de service en télémétrie, GRTgaz a procédé à la pose de
systèmes télémétriques sur l’ensemble de ses soutirages et de drainages de courant.
La norme EN 12954 définit des périodicités types pour réaliser les mesures sur le terrain pour assurer l’évaluation
générale et l’évaluation complète et détaillée de la protection cathodique. Mais la norme ne donne aucune directive
lorsqu’un système de télésurveillance est installé sur certains équipements de protection cathodique.
GRTgaz a décliné la norme EN 12954 dans ses procédures pour les contrôles à réaliser sur site sur chaque type
d’équipement de protection cathodique (en terme de type de mesure à réaliser et de fréquence de réalisation de ces
mesures), qu’il soit ou non équipé de système télémétrique. GRTgaz étudie actuellement les périodicités de contrôle de
fonctionnement sur site et celles d’évaluation sur site de l’efficacité d’un équipement en présence d’un système
télémétrique. S’il est admis qu’un système télémétrique permet d’espacer aisément les contrôles de fonctionnement
réalisés sur site par un opérateur, il est nécessaire de bien maîtriser le fonctionnement du système télémétrique pour
également espacer les contrôles d’efficacité réalisés sur site sur les équipements de protection cathodique. Ainsi, si la
périodicité d’une évaluation de l’efficacité est annuelle sur un équipement sans système télémétrique (tel qu’un soutirage
ou un drainage de courant), elle sera tri-annuelle pour GRTgaz lorsqu’il est équipé d’un système télémétrique. De même,
si elle est tri-annuelle pour un équipement tel qu’une prise de potentiel sans système télémétrique, elle sera de quatre ans,
voire 5 ans pour GRTgaz avec système télémétrique, si aucune anomalie n’est constatée à la première évaluation
d’efficacité. Mais cela suppose au départ que la protection cathodique de la conduite, dont les équipements de protection
cathodique sont télémesurés, soit efficace et qu’il n’y ait aucun problème d’influence électrique néfaste.
GRTgaz a donc choisi un système télémétrique répondant à ses exigences pour ses équipements de protection
cathodique : prise de mesure chaque seconde sur deux voies d’enregistrement 24 h sur 24 (chacune prenant soit une
tension, soit un courant). Le système télémétrique assure aujourd’hui le contrôle de fonctionnement et un premier niveau
d’évaluation de l’efficacité des soutirages et des drainages de courant ; il assurera demain celui des systèmes de mises à
la terre et après demain celui des prises de potentiel.
L’installation d’un système télémétrique sur les équipements de protection cathodique est un investissement conséquent.
Il est nécessaire que la société qui prend cette décision d’investissement y trouve un intérêt.
Les équipements de télésurveillance posés sur les équipements de protection cathodique offrent les avantages suivants :
1
38
ABSTRACT
GRTgaz was created in 2005 following the merger between Gaz de France and SUEZ. This subsidiary is the
former gas transport Direction of Gaz de France. It is run by 27,000 employees.
Cathodic protection of buried steel pipes is carried out by local teams and expertise is at national level. The
operators are responsible for the maintenance of all cathodic protection equipment: impressed current
stations, drainage stations, grounding systems for protection against AC corrosion and potential test points.
In 2006, GRTgaz decided to use remote monitoring equipment for cathodic protection equipment. Thus,
initially, between 2007 and 2010, after selecting a service provider in telemetry, GRTgaz carried out the
installation of telemetry systems on all its impressed current stations and drainage stations.
The standard EN 12954 defines typical measurements periodicities to carry out on site general assessment
and complete and detailed assessment of cathodic protection. But the standard does not provide guidance
where remote monitoring system is installed on some equipment for cathodic protection.
GRTgaz declined the standard EN 12954 in its procedures for checks to be carried out on site on each type of
cathodic protection equipment (in terms of type of action to achieve and frequency of these measurements),
whether or not equipped with telemetry system. GRTgaz is currently studying the frequency of on site
functional checks and those of on site evaluation of the effectiveness of equipment in the presence of a
telemetry system. If it is accepted that a telemetry system can easily space out functional checks carried out on
site by an operator, it is necessary to control carefully the operation of the telemetry system in order to also
space out the effectiveness assessments carried out on site on cathodic protection equipment. Thus, if the
periodicity of an evaluation of effectiveness is annual on an equipment without telemetry system (such as an
impressed current or a drainage station), it will become tri-annual for GRTgaz when equipped with a system
of telemetry. Similarly, if it is tri-annual for equipment such as a potential test point without telemetry system,
it will become four years or five years periodicity for GRTgaz with telemetry system, if no anomaly is
observed during the first assessment of efficiency. But this presupposes first that the cathodic protection of the
pipeline the equipment of which are telemetered be efficient and that there is no detrimental problem of
electrical influence
Thus, GRTgaz has chosen a telemetry system meeting its requirements for its cathodic protection equipment:
measurement taken each second over two recording channels 24 hours over 24 hours (each taking either a
voltage or a current). The telemetry system currently provides the functional checks and a first level of
assessment of the effectiveness of impressed current and drainage stations. It will ensure medium term that of
grounding systems and at longer term that of potential test points.
The installation of a telemetry system on the cathodic protection equipment is a significant investment. It is
necessary that the company making that decision to invest find its interest.
The remote monitoring equipment installed on the cathodic protection equipment offer the following benefits:
- Reduced risks on the road for cathodic protection operators
- Increase of working time of cathodic protection operators for cathodic protection operations of higher value
added such as analysis,
- Increase of reliability of operation of remotely monitored cathodic protection equipment,
- Better knowledge of the life of the remotely monitored cathodic protection equipment,
- Increase of the periodicity of on site checks of remotely monitored cathodic protection equipment reducing
maintenance costs of this equipment,
- Improved maintenance of data archiving by the exclusive and periodical introduction of computerized
databases of the telemetry system into the database dedicated to monitoring of the cathodic protection of the
gas transmission network.
2
37
ABSTRACT
In the 90ies, an extensive research and development program has been initiated by la
Direction Générale de l’Armement (DGA) of the French Ministry of Defence and
DCNS. This program led to the development of a new low driving voltage anodic
material, Al-0.1%Ga, for the cathodic protection of a high strength steel type. The
laboratory investigations were followed by an industrial development of Al-0.1%Ga
anodes that were later installed on a submerged marine structure, replacing the
conventional zinc anodes. The paper reviews the main properties and operating
parameters of the Al-0.1%Ga alloy based on laboratory investigations, long term
exposure tests and the experience feedback.
37
RÉSUMÉ
Dans les années 90, un vaste programme de recherche et développement a été engagé
par la Direction Générale de l’Armement (DGA) du Ministère français de la Défense
et DCNS. Ce programme a abouti à l'élaboration d'un matériau anodique à potentiel
électronégatif limité, Al-Ga 0,1%, pour la protection cathodique d’un type d’acier à
haute limite d’élasticité. Les investigations de laboratoire ont été prolongées par un
développement industriel d’anodes Al-Ga 0,1% qui ont ensuite été installées sur des
structures immergées en eau de mer, en remplacement d’anodes en zinc
traditionnelles. Le document passe en revue les principales propriétés et paramètres de
fonctionnement de l'alliage Al-Ga 0,1% sur la base des investigations de laboratoire,
des essais d'exposition à long terme et du retour d'expérience.
36
RÉSUMÉ
Les anodes sacrificielles en aluminium, activées à l’indium, sont les plus utilisées pour
la protection cathodique des ouvrages métalliques portuaires en environnement marin.
Ce procédé représente un tonnage important d’alliage métallique incluant des éléments
traces en contact avec les eaux côtières. La plupart de ces éléments qui se dissolvent en
continu dans le milieu demeure attachée à la surface de l’anode sous forme oxydée,
mais une partie est susceptible d’être transférée dans l’environnement, sous forme
dissoute ou particulaire. Une série d’analyses réalisées en environnement portuaire,
associée à des expérimentations en laboratoire ont permis d’étudier le transfert de
l’aluminium et des éléments traces constitutifs des anodes vers l’eau, les sédiments et
les mollusques (Mytilus edulis). Une première évaluation de la toxicité de l’aluminium
sur les larves d’organismes marins via des tests normalisés a également été effectuée.
Ces premiers résultats ouvrent des perspectives en termes de compréhension des
interactions entre durabilité des ouvrages et qualité du milieu marin en zone portuaire.
ABSTRACT
Aluminum sacrificial anodes, activated by indium, are currently used for cathodic
protection of steel structures immersed in harbour marine environment. This process
represents a significant tonnage of metallic alloy including trace elements in contact
with coastal waters. Most of these elements which are continuously released from the
anodes remains attached to the anodes surfaces as oxidized forms, but some of them
may be transferred directly into the environment as dissolved or particulate forms. A
series of tests performed in port environment, combined with laboratory experiments
have investigated the transfer of aluminum and trace elements constituting the anode
toward the water, sediment and molluscs (Mytilus edulis). An initial assessment of
aluminum toxicity on the larvae of marine organisms using standardized tests was also
performed. These first results are a first step in understanding the interactions
between structural durability and marine environmental quality in port areas.
RÉSUMÉ
La mise en place d’un revêtement de canalisation sur chantier reste sensible aux
conditions et aux moyens d’application ; ce revêtement doit être le plus imperméable
possible à l’eau et aux gaz, avoir une adhérence parfaite et réduire le risque de
corrosion microbienne (CIM). Un mastic ayant des propriétés de type fluide avec
aucun degré de comportement cristallin et d’excellentes caractéristiques de mouillage
peut cependant satisfaire à ces exigences : c’est le cas des revêtements visco-
élastiques.
En effet, étant donné que la bonne application d’un revêtement anticorrosion
détermine son efficacité à long terme, il est préférable d’utiliser des matériaux ayant
un comportement rhéologique permettant une application facile et tolérante. Le
revêtement visco-élastique STOPAQ®, élaboré à base d’une polyoléfine apolaire,
permet de protéger les canalisations enterrées et aériennes contre la corrosion en
remédiant aux principaux problèmes liés aux points suivants :
• Adhérence : le revêtement présente une très faible tension de surface et des
propriétés de mouillage et d’écoulement à froid permettant une adhésion au
niveau moléculaire. En cas de dommage, la rupture est cohésive et une couche
résiduelle reste solidaire de la canalisation et comble ses pores les plus fins.
• Préparation de surface : un état de surface de degré St2 / St3 est suffisant, le
décapage à l’abrasif n’est pas requis. Le revêtement visco-élastique se
caractérise par une faible température de transition vitreuse. Au dessus du point
de rosée, le revêtement peut être appliqué entre -30°C et +80°C.
• Milieu salin, sol agressif : des tests approfondis ont démontré l’absence de
corrosion sur une canalisation protégée par le revêtement visco-élastique et
enterrée pendant plus de 6 ans dans un milieu salin (avec de fortes teneurs en
chlorure et en soufre).
• Osmose : le revêtement visco-élastique est complètement inerte et amorphe, ses
propriétés d’imperméabilité, de polarité et d’adhérence empêchent les
phénomènes d’osmose.
• Bactéries : le revêtement est imperméable à l’eau et ses constituants ne
contiennent pas de nutriments d’azote. De plus, son élaboration s’effectue à
haute température, ce qui rend impossible le développement de bactéries à
l’interface revêtement/canalisation.
35
ABSTRACT
The application of a pipeline coating on site remains sensitive to the conditions and
methods of application; this coating should be impermeable to water and gases, have
an excellent adherence and reduce the risk of microbiological corrosion (MIC). A
sealant having the properties of fluid-like behavior with no degree of crystalline
behavior and excellent wetting characteristics, however, can meet these requirements:
this is the case of viscoelastic coatings.
Indeed, given that proper application of an anticorrosion coating determines its
effectiveness in the long term, it is preferable to use materials with rheological
behavior allowing easy ant tolerant application. The viscoelastic coating STOPAQ ®,
developed on the basis of a non polar polyolefin, helps protecting buried and air-
exposed pipelines against corrosion by addressing key issues related to:
• Adhesion: The coating has a very low surface tension and wetting properties and
cold flow for bonding at the molecular level. In case of damage, failure is cohesive
and a residual layer remains bonded to the pipe and fills its finest pores.
• Surface preparation: a surface of degree St2 / St3 is sufficient, abrasive blast-
cleaning is not required. The viscoelastic coating is characterized by low glass
transition temperature. Above the dew point, the coating can be applied between -30
°C to +80 °C.
• Saline environment, aggressive soil: extensive testing has shown the absence of
corrosion on a pipeline protected by the viscoelastic coating and buried for over 6
years in a saline environment (with high concentrations in chloride and sulfur).
• Osmosis: the viscoelastic coating is completely inert, amorphous, its barrier
properties, polarity and adhesion phenomena prevent osmosis.
• Bacteria: the coating is impervious to water and its components do not contain
nitrogen nutrients. Moreover, its manufacture takes place at high temperature, which
makes it impossible the development of bacteria.
34
RÉSUMÉ
Si la mesure du potentiel d’une structure marine sous protection cathodique est une
opération relativement aisée et courante permettant de multiplier les points de mesure
et de produire profils et cartographie de potentiel, celle de la densité de courant
nécessite l’installation de système à demeure ne permettant que des mesures locales
(cathode monitorée). Le capteur CADIP développé par l’Institut de la Corrosion en
collaboration avec DCNS, DGA et nke est basé sur la mesure du gradient de potentiel
généré par le courant de protection cathodique. Pour cela 2 électrodes de référence
appariées sont disposées dans un tube isolant ouvert aux extrémités. Lors de la mesure
ce tube est appliqué normalement à la surface de la structure, la différence de potentiel
entre les électrodes de référence est enregistrée. Ce gradient de potentiel est
proportionnel au courant canalisé par le tube isolant. Suite à un étalonnage du capteur
en laboratoire et à la mise au point d’une procédure de calibration, la densité de
courant de protection cathodique est calculée à partir de la mesure enregistrée. Les
résultats des études réalisées montrent que des densités de courant de l’ordre du
mA/m² peuvent être mesurées, ceci avec une précision et une répétabilité très
satisfaisante. Les applications potentielles du capteur CADIP sont l’évaluation de la
demande en courant de protection des structures protégées, avec pour objectif de
déterminer la durée de vie des systèmes de protection et l’évaluation de la qualité des
systèmes de peinture (taux de dégradation et localisation des dégradations), en y
associant la mesure du potentiel de protection.
ABSTRACT
ABSTRACT
The presented work was carried out with the objectives of supplying to Cathodic
Protection designers data collected in situ, i.e in the actual environment in which the
protected structure is installed. Sensors arrays have been deployed at six different
sites from 35 m to 900 m depth. The measurements are realized by a CPC sensor
which records the cathode potential and the coupling current between a cathode and
an anode..
The effect of temperature and pressure on calcareous deposit properties was put into
evidence and was useful to explain the different established pseudo polarization
curves.
For carbon steel: the results are broadly in a good agreement with DNV RPB 401 and
ISO 15589-2 standards. For stainless steel: the initial current was independent of the
location; the steady state current demand at -600 mV/Ag.AgCl depends strongly on the
environment; the current demands tent to decrease with time in tropical and arctic
zones, but increase in sub-tropical area and the current demand at -950 mV/Ag.AgCl
does not depend on the location.
Key words: Cathodic Protection; in situ data collection; deep sea; calcareous deposit;
carbon steel; Stainless steel
33
RÉSUMÉ
Le travail présenté a été réalisé avec les objectifs de fournir aux concepteurs de
protection cathodique des données relevées in situ, c'est-à-dire dans l'environnement
réel où la structure est installée. Des Capteurs ont été déployés sur six sites différents
à entre 35 m et 900 m de profondeur. Les mesures sont réalisées à l’aide d’un capteur
CPC qui enregistre le potentiel de la cathode et le courant de couplage entre une
cathode et une anode
L'effet de la température et de la pression sur les propriétés du dépôt calcaire a été mis
en évidence et a été utile pour expliquer les différentes courbes de pseudo polarisation
établies.
Pour un acier au carbone: les résultats sont globalement en bon accord avec les
standards DNV RPB 401 et ISO 15589-2. Pour l'acier inoxydable: le courant initial est
indépendant de la localisation, le courant en régime permanent à -600 mV / Ag.AgCl
dépend fortement de l'environnement; la demande en courant tend à décroître en
fonction dutemps dans les zones tropicales et arctiques, mais augmente en Afrique
subtropicale et la demande en courant à -950 mV / Ag.AgCl ne dépend pas de la
localisation.
Mots clés: protection cathodique; relevé de données in-situ mer profonde; dépôt
calco-magnésien; acier ; acier inoxydable
32
RÉSUMÉ
ABSTRACT
Florent BATISSE
RÉSUMÉ
Nous préconisons depuis plusieurs années la mise en place de revêtement de type « bande
paraffinique » au niveau des accessoires des réseaux d’eau potable afin d’augmenter la valeur
d’isolement globale des ouvrages.
Les donneurs d’ordre réclament des données techniques pour valider l'utilisation et
l'application de ces produits sur leurs installations.
Même si par expérience il est admis que le produit apporte satisfaction depuis de nombreuses
années, il n'existe que très peu d’études, si ce n’est dans certains laboratoires comme Gaz de
France, mais la diffusion de ces documents est restreinte.
Florent BATISSE
ABSTRACT
We have been recommending for several years the development of coatings based on wax
tapes on pieces of equipment of drinking water systems for increasing the overall insulation
value of the structures.
The end users require technical data to validate the use and application of these products on
their facilities.
Even if experience shows this material provides satisfaction for many years, there are very
few studies, except in some laboratories such as those of Gaz de France, but diffusion of these
documents is restricted.
The objective of our tests was to characterize the performance of the material, to verify its
compatibility with the application of cathodic polarization and to demonstrate the
improvement that it can give to the operation of a cathodic protection system.
- Making a laboratory study in collaboration with the University Paul Sabatier in Toulouse
and the University of La Rochelle on:
1. the material composition and the guaranty of the absence of any toxic compound,
2. the behavior of the coating in a corrosive electrolyte,
3. the compatibility of this coating with the application of cathodic protection.
- verifying in situ, with the technical assistance of a leasing company and the Port Autonome
de Nantes-Saint Nazaire, the improvement from the application of this coating on the
operation of cathodic protection, and whether this benefit persists in the time.
RÉSUMÉ
ABSTRACT
Our paper is a bibliography review on this subject with the aim of supplying
additional information to the experimental standard XP A 05-674 (August 2007)
"Cathodic protection of the underwater part of ships".
The use of calibrated coupons is necessary to address the current density value needed
for cathodic protection.
29
RÉSUMÉ
Ces essais ont été menés pendant une durée de 3 mois suivant les procédures décrites
en annexes B et C du DNV RP B401de janvier 2005
ABSTRACT
There are however other applications in the industry that deal with higher
temperatures. The electrochemical properties of the alloy, especially its current
capacity (Ah / kg), are then changed. This has a major impact on the design of
cathodic protection.
These tests were conducted for a period of three months according to the procedures
described in Appendices B and C of DNV RP B401( January 2005).
TRAITEMENT DE REALCALINISATION
DU PONT CAMILLE DE HOGUES
Carl REDON
RÉSUMÉ
Après le montage d’un échafaudage adapté à la géométrie du pont, les épaufrures sont
purgées. Des raccords électriques (cathodes) sont positionnés sur les armatures. Un
treillis métallique est ensuite attaché à la surface du béton et connecté électriquement
(anodes). Des fibres sont projetées sur ce treillis de manière à former un cataplasme
qui est imbibé par une solution électrolytique alcaline. Le traitement proprement dit
débute : la mise sous tension pendant une quinzaine de jours enclenche le processus de
réalcalinisation décrit ci-avant.
Carl REDON
ABSTRACT
After mounting a scaffold adapted to the geometry of the bridge, spalls are purged.
Electrical fittings (cathode) are positioned on the reinforcements. A metallic mesh is
then attached to the concrete surface and electrically connected (anodes). Fibers are
projected onto the mesh to form a poultice that is soaked with an alkaline electrolytic
solution. The actual treatment begins: the power energizing for a fortnight starts the
realkalization process described above.
Cores were taken to ensure that the effective recovery of pH occurred in accordance
with the normative document FD CEN / TS 14038-1. After treatment, the poultice
anode was deposited to follow up on the finishing (coatings, washes ...) based on
samples previously approved by Mr. Jeanneau, Chief Architect of Historical
Monuments.
RÉSUMÉ
Au fur et à mesure des années, la protection cathodique a évolué, les mesures sont
devenues de plus en plus précises, notamment pour la réalisation de la mesure du
potentiel « OFF ».
Nous constatons que les mesures « OFF » sont effectuées sur des témoins métalliques
de taille et de formes différentes. Paradoxalement, l’évolution du témoin, ne s’est pas
accompagnée par la même évolution de l’électrode de mesure depuis les années 80.
Pour cela nous avons effectué plusieurs essais afin de mettre en évidence les solutions
et les problématiques générées par l’utilisation de ces équipements.
ABSTRACT
As to the years, cathodic protection has evolved; the measures have become
increasingly accurate, especially for the realization of the“OFF” potential
measurement.
We note that the measurements are carried off on metallic coupons of various sizes
and shapes. Paradoxically, the measuring electrode has known little or no change
since the 80s.
This study is aimed at verifying the relevance and interaction of equipment used to
achieve the ON / OFF potential measurements and at optimizing them.
It reveals three major research areas: the coupon, the reference electrode and the
coupon and electrode interactions.
To do this, we performed several tests in order to highlight the solutions and problems
caused by the use of such equipment.
Jean VITTONATOa
a
TOTAL TDO/TEC/COR
Tour Coupole, 2 place Jean Millier, 92078 Paris La Défense Cedex
Jean.vittonato@total.com
RÉSUMÉ
La protection cathodique des pipelines immergés en eau de mer est réalisée dans la
quasi-totalité des cas par anodes galvaniques. Un des points clés du dimensionnement
de cette protection réside dans la détermination de l’espacement maximum requis entre
les anodes afin d’assurer l’efficacité de la protection sur toute la distance inter-anodes.
Des formules analytiques sont disponibles dans les standards internationaux ou dans
d’autres documents de référence. L’objet de l’article est d’étudier une configuration
d’installation d’anodes et de comparer les résultats obtenus avec d’une part ces
standards ou documents de référence, et d’autre part avec une modélisation numérique.
Une analyse critique des formules analytiques est proposée ainsi qu’une
recommandation pratique.
Jean VITTONATO
ABSTRACT
Cathodic protection of pipelines submerged in sea water is carried in almost all cases
by galvanic anodes. One of the key points of the design of this protection lies in
determining the maximum spacing required between the anodes in order to ensure
effective protection over the entire distance between anodes. Analytical formulas are
available in international standards or other reference materials. The purpose of this
paper is to study an installation configuration of anodes and compare the results with
one hand these standards or reference materials, and also with numerical modeling.
A critical analysis of analytical formulas is proposed as well as a practical
recommendation.
RÉSUMÉ
ABSTRACT
Marcel ROCHEa
Président de la Commission PCRA du CEFRACOR
a
Total Technology Specialists, Le Mesnil-le-Roi, France, marcel.roche@orange.fr
RÉSUMÉ
Les réunions plénières sont consacrées à l’échange des connaissances et à leur consolidation dans
les domaines où des progrès sont nécessaires, et notamment à valider les productions de groupes de
travail créés en fonction des besoins. Les nouvelles techniques et méthodes de contrôle ainsi que les
activités des compagnies spécialisées sont également présentées. Les comptes rendus des réunions
plénières récentes et certaines de leurs annexes sont placés après validation dans la partie « Espace
Adhérents » du site web du CEFRACOR (http://www.cefracor.org/).
Pour les sujets nécessitant la rédaction de documents complémentaires des normes françaises,
européennes ou internationales et des guides professionnels, le fruit des travaux est mis à la
disposition de tous les utilisateurs potentiels en français et en anglais sur le site Web sous la forme
de « Recommandations PCRA » (à ce jour 9 ont été publiées).
Marcel ROCHEa
President of the PCRA CEFRACOR Commission
a
Total Technology Specialists, Le Mesnil-le-Roi, France, marcel.roche@orange.fr
ABSTRACT
The plenary meetings are devoted to the exchange of knowledge and its consolidation in the
areas where improvement is needed, especially to validate the products of working groups
launched as needed. New techniques and measurement methods as well as activities of
specialized companies are also presented. The recent minutes of plenary meetings and some
of their annexes are placed after validation in the "Members Area" of the CEFRACOR
website (http://www.cefracor.org/).
For topics that require writing documents additional to French, European or international
standards and professional guidelines, the fruit of the work is made available to all
potential users in French and English on the website in the form of "Recommandations
PCRA” (so far 9 have been published).
Pierre FRANCE
RÉSUMÉ
Pierre FRANCE
ABSTRACT
RÉSUMÉ
ABSTRACT
RÉSUMÉ
ABSTRACT
Most studies of the electrochemical corrosion behavior carried out on aluminum have
been carried out in chloride media and inhibitors used to fight against this
phenomenon are typically chromates, harmful to health and the environment. We
proposed to study the corrosion inhibition effect on aluminum of two non-polluting
products, which are sodium molybdate and silicate. The test environment is distilled
water, environment specific to certain closed cooling circuits such as those used in
car engines. To this end, we used a series alloy 4000 and another 5000 series on
which we performed comparative electrochemical tests with both types of inhibitor
(polarization curves and impedance diagrams) followed by MEB observations. The
thermodynamic parameters considered are those of the service conditions:
concentration, temperature and agitation of the solution.
The agitation improves the efficiency of both inhibitors for the alloy series 5000 (up
99.88%) but did not affect the silicate for inhibition in the case of alloy Series 4000.
This reveals a selective influence of hydrodynamic factors on the effectiveness of
both inhibitors in relation to the nature of the substrate. These results are confirmed
by the impedance spectra performed at the corrosion potential and MEB
observations of surface states of the two alloys.
RÉSUMÉ
Les propriétés intrinsèques de ces anodes telles que la densité de courant, la durée de
vie et le potentiel anodique seront des notions abordées dans cette communication afin
de présenter la technologie des anodes Ti/MMO.
Ces anodes sont constituées d'un substrat de titane revêtu d'une couche
électrocatalytique d'oxydes mixtes métalliques (Ir, Ru, Ta). Les performances des
anodes Lida® sont en corrélation directe avec la nature et les caractéristiques de ce
revêtement.
La polyvalence de ces anodes permet de les utiliser non seulement pour la protection
cathodique de l’acier dans les sols, l’eau douce ou l’eau de mer, mais aussi des
armatures du béton aérien, enterré ou immergé. Tous ces paramètres font de l'anode
Lida® une anode de choix pour la protection cathodique à courant imposé.
ABSTRACT
The objective of this communication is to present the Lida® TiMMO anode technology
and its use in impressed current cathodic protection. The De Nora Group's Lida®
anodes have clearly demonstrated their use and efficiency since they first appeared in
the market place in the 1970's.
This communication will present the TiMMO anode technology, focusing on its
intrinsic properties such as: durability, high output and rugged performance.
The anodes comprise an insoluble mixed-metal oxide (Ir, Ru, Ta) coating bonded to a
titanium substrate. The performance of Lida® anodes is directly linked to the nature
and characteristics of this coating.
The properties of these anodes are such that they are used, not only for the cathodic
protection of steel structures underground and in salt or fresh water, but also for steel
reinforcement in atmospheric, underground and submerged concrete structures.
Together, these properties make Lida® anodes the anode of choice for impressed
current cathodic protection.
Center for Safety and Durability of Structures and Materials, CISDEM (IETcc) CSIC-
UPM, Madrid, Spain, andrade@ietcc.csic.es
ABSTRACT
The corrosion of reinforcement in concrete leads into cracking and spalling of the
concrete cover and into the decrease of the load-bearing capacity of the structures.
The on-site measurement of the corrosion rate enables to predict the future evolution of
the process and serves for quantifying the time to repair.
In the Project APPLET two corrosion rate meters and a standard potentiostat have been
used for studying their ability to detect the damage and its quantification.
The corrosion rate meters have different manners to measure the Polarization Resistance:
1) the standard potentiostat was employed with a simple prismatic counter electrode,
2) the “Gecorr” applies the current with a circular counter electrode surrounded by a
guard ring whose current is modulated to be sure that it is confined in the predetermined
area,
3) the “Galvapulse” uses also a guard ring but without the modulation of the external
current.
In the present paper, numerical calculations are presented to show the distribution and
quantification of the current lines between the counter electrode and the reinforcement.
The results show that when no confinement is used (case of standard potentiostat) the
current lines reach a certain distance far away of the border of the counter electrode and
then the area polarized is larger than the size of the counter. In the case of Gecorr the
modulation of the confinement is efficient and confines the current lines in the area pre-
selected while in the case of Galvapulse, the lines also spray far beyond the border of the
central counter electrode and the guard ring is not able to confine the current below the
pre-selected area.
19
Centre pour la sécurité et la durabilité des structures et des matériaux, CISDEM (IETcc)
CSIC-UPM, Madrid, Espagne, andrade@ietcc.csic.es
RÉSUMÉ
* Center for Safety and Durability of Structures and Materials, CISDEM (IETcc) CSIC-
UPM, Madrid, Spain, andrade@ietcc.csic.es
** Conservación y Explotación de Carreteras, Xunta de Galicia, Spain
*** Galaicontrol, Spain
**** Escuela de Ingenieros Tecnicos de Obras Publicas, La Coruña, Spain.
ABSTRACT
Corrosion of reinforcement and other damages were detected in a bridge, more than 25
years old, linking inland to a small island in the sea.
Two kinds of the cathodic protection systems were recommended: for the deck where only
small zones are affected, discrete anodes of zinc embedded in the patch repairs, and for
the piles also zinc anodes that are placed in holes made intruding the concrete in the
zones above sea level and zinc jackets surrounding the submerged zones of the piles.
For the control of the efficiency of the cathodic protection, CP, systems it has been
decided the use of the measurement of the instantaneous potential-off value and after
several hours of depolarization as well as the “Passivation Verification Technique”,
PVT, which can measure the efficiency of the anodes without switching off the current.
In the present paper, results are reported on the corrosion rates of the reinforcement
before the application of the CP and the results of the PVT just after energizing the
system and after several months of working.
18
RÉSUMÉ
La corrosion des armatures et d’autres dommages ont été détectés dans un pont, âgé de
plus de 25 ans, reliant le continent à une petite île en mer.
Deux types de systèmes de protection cathodique ont été recommandés: pour le tablier du
pont, où seules de petites zones sont touchées, des anodes de zinc ponctuelles intégrées
dans le patch de réparation, et pour les piles aussi des anodes en zinc qui sont placées
dans des trous forés dans le béton dans les zones au-dessus du niveau de la mer, ainsi que
des manchons en zinc entourant les zones immergées des piles.
Dans le présent document, les résultats sont présentés sur le taux de corrosion de
l'armature avant l'application de la PC et les résultats de la technique PVT juste après
mise sous tension du système ainsi qu’après plusieurs mois en service.
17
RÉSUMÉ
Dans un souci d’efficacité, les règles d’éloignement des anodes à courant imposé de
toute structure métallique sont de 50 m pour les courants imposés inférieurs à 10 A et
100 m pour les courants imposés supérieurs à 10 A.
Les déversoirs horizontaux ou verticaux tels qu’ils sont utilisés aujourd’hui respectent
ces règles d’installation énoncées, en éloignant la tête de puits verticale ou le champ
d’anodes horizontales de 50 m ou 100 m de tous réseaux acier.
La technique proposée permet d’installer un poste de soutirage sur tous les réseaux
urbains ou à espace restreint et ceci en respectant les règles de mise en œuvre.
17
ABSTRACT
For the sake of efficiency, the rules for the remoteness of impressed current anodes
from any metallic structure are 50 m for impressed currents less than 10 A and 100 m
for impressed currents exceeding 10 A.
Horizontal or vertical groundbeds which are used today respect the former
installation requirements, by the separation of the wellhead vertical or horizontal
anodes groundbeds 50 m or 100 m from all steel networks.
RÉSUMÉ
ABSTRACT
The presence of internal stresses in organic coatings is a common phenomenon that can
cause loss of adhesion of the coating system. In the case of external coatings used to protect
pipelines against corrosion during a long term, this parameter must be taken into account to
quantify the lifetime of these systems. Two types of coatings are frequently applied: a
monolayer and a trilayer, each with advantages and disadvantages.
The application of these pipeline coatings is carried out in a semi-continuous way when the
steel cylinder is heated above 200°C. The protective coating is achieved by spraying (epoxy)
or extrusion (polyethylene). The system is then rapidly cooled down by quenching through
water shower to stiffen the material.
A withdrawal of several inches is observed on the coatings derived from the application
process. It is due to differential dilatation encountered with these systems. Indeed, the
contraction of the steel cylinder on the temperature range 200°C-20 C is much lower (α =
16.10-6 K-1) than those of the epoxy (K α = 45.10-6 1) and polyethylene (α = 100.10-6 K-1).
This is accentuated by the crystallization of polyethylene on cooling. During storage,
spontaneous disbonding was also observed at the ends of pipeline trilayers at the interface
adhesive / epoxy. Therefore, it appears that the internal stresses developed during the coating
application are nearby (higher in the case of damage) the strength of the interface.
This work considers the calculation of internal stresses generated during the application
process. Numerical models were performed using Abaqus (EF Commercial Code) with the
ultimate goal of having a reliable model (quantitatively) and requiring a minimum number of
input parameters (simple behavior law). Direct confrontation of results from numerical
calculations and those observed experimentally on site (withdrawal, cooling time ...) were
used to validate numerical models for the displacement and temperature fields set by the
process. In contrast, the values of internal stresses calculated showed the need to use in the
model laws of "dissipative" behavior (plasticity or viscoelasticity) to limit the overestimation
of stress levels.
Key words: Coating; internal stress, thermo-mechanical, finite elements method.
15
SUMMARY
RÉSUMÉ
La protection cathodique (PC) de l'acier dans le béton est une technique bien acceptée
pour la prévention de la corrosion et les moyens de réhabilitation, lorsque des ouvrages
en béton armé sont touchés par la carbonatation, la pénétration de chlorures ou les
deux. Ces dernières années, la PC est devenue de plus en plus reconnue en Allemagne
pour la réhabilitation des parkings de voitures de plusieurs étages. La plupart des
systèmes de PC actuellement installés sont des systèmes dits à courant imposé (PCCI)
avec systèmes de télécommande et surveillance intégrés, qui répondent aux exigences
de la norme EN 12696. Jusqu'à présent, l'utilisation d'anodes galvaniques dans ce
domaine d'application est limité à un petit nombre d'applications d‘essai.
À l'été 2008 un projet de recherche a été lancé afin d'obtenir des données plus fiables
sur les performances et l'applicabilité de l'anode de zinc pulvérisée thermiquement
recouverte d‘une couche bitumineuse sur des parkings de voitures de plusieurs étages.
Pour ce faire, deux zones d'essai avec un total de sept domaines de surveillance et
deux systèmes différents de surveillance et de contrôle, répondant tous les deux aux
exigences de la norme EN 12696, ont été installés. Les données enregistrées ont été, en
plus des courants débités par les anodes galvaniques dans les domaines de
surveillance, le développement de la polarisation, le potentiel instantané en circuit
ouvert à la coupure, ainsi que les impédances du béton. Les résultats obtenus dans les
premiers mois du temps d'enregistrement donnent quelques éléments démontrant une
performance relativement bonne de l'anode de zinc. Bien que les courants galvaniques
soient à peine supérieurs à 2 mA/m², la dépolarisation de l'armature est supérieure à 80
mV.
14
CERTIFICATION OF CP PERSONNEL:
THE GERMAN EXPERIENCE WITH EN 15257
ABSTRACT
___________________________________________________________________________
14
RÉSUMÉ
Daniel COPIN
RÉSUMÉ
Après avoir fait un rapide tour d’horizon des certifications dans les principaux pays de
notre continent, l’auteur propose d’établir un système permettant une reconnaissance
mutuelle des différentes certifications européennes, avec l’aide de la Fédération
Européenne de Corrosion (EFC) et du CEOCOR. Le but final pourrait être l’attribution
d’une marque de qualité du type "European Cathodic Protection Certification" avec un
logo commun.
Cette marque, prolongeant l’accréditation des systèmes opérés dans chacun des pays
européens (délivrée en France par le COFRAC), mettrait ainsi l’Europe à un haut
niveau mondial dans le domaine de la certification de la compétence des personnes en
protection cathodique.
Daniel COPIN
ABSTRACT
Certificates of competency issued by the CEFRACOR are all under the label
"AFNOR Competence / Cathodic Protection" or its equivalent "CEFRACOR
Competence / Cathodic Protection".
After a quick overview of certification schemes in the main countries of our continent,
the author proposes to establish a system of mutual recognition of the different
European certifications, with the assistance of the European Federation of Corrosion
(EFC) and the CEOCOR. The ultimate goal would be the attribution of a quality mark
such as "European Cathodic Protection Certification” with a common logo.
This mark, in the continuation of the accreditation of the systems operated in each of
the European countries ( delivered in France by COFRAC), would put Europe at a
high level in the field of certification of competence of persons in cathodic protection
in the world.
The national accreditation bodies will demonstrate that the different certification
systems work well under the terms defined by EN ISO/CEI 17024 and EN 15257
standards.
12
ABSTRACT
References:
[1] J. Bonastre, P. Garcés, F. Huerta, C. Quijada, L.G. Andión, F. Cases, Corros. Sci.
48 (2006) 1122-1136.
[2] J. Bonastre, R. Lapuente, P. Garcés, F. Cases, Synth. Metals 159 (2009) 1723-
1730.
[3] J. Bonastre, P. Garcés, J.C. Galván, F. Cases, Prog. Org. Coat. 66 (2009) 235-
241.
12
RÉSUMÉ
Références:
[1] J. Bonastre, P. Garcés, F. Huerta, Quijada C., LG Andión, F. cas, Corros. Sci. 48
(2006) 1122-1136.
[2] J. Bonastre, R. Lapuente, P. Garcés, F. cas, Synth. Métaux 159 (2009) 1723-
1730.
[3] J. Bonastre, P. Garcés, J.C. Galván, F. Cases, Prog. Org. Coat. 66 (2009) 235-241.
11
ABSTRACT
Galvanic anodes have been used in patch repairs and as part of global corrosion
control of steel reinforcement in concrete for over ten years. Field results have shown
good performance in extending the service life of the structure or structural
components which have allowed the further development of galvanic anodes. New
improved galvanic anodes are now being assessed in their ability to stop existing
corrosion by applying a minimum charge to the steel reinforcement.
This paper looks at the principles involved in controlling or arresting steel
reinforcement corrosion and presents results, both from field and laboratory studies,
which support the principles.
RESUME
Les anodes galvaniques ont été utilisées dans les réparations localisées et dans le cadre
du contrôle de la corrosion globale des armatures dans le béton depuis plus de dix ans.
Les résultats de terrain ont montré de bonnes performances dans l'augmentation de la
durée de vie de structure ou d’éléments structurels, qui ont permis la poursuite du
développement des anodes galvaniques. De nouvelles améliorations des anodes
galvaniques sont actuellement évaluées dans leur capacité à arrêter la corrosion
existante en appliquant une charge minimum à l'armature d'acier.
Cet article examine les principes impliqués dans le contrôle ou l'arrêt de la corrosion
d'armature en acier, et présente les résultats, à la fois sur des études de terrain et de
laboratoire, confirmant les principes évoqués.
RÉSUMÉ
Références bibliographiques :
« Stray Currents from Electric Railways » Carl MICHALKE, 1904.
« Guide for Measurement of Interference Caused by Cathodic Protection and Railway
Drainage Systems » New South Wales Electrolysis Committee (Australie), Edition de
1990, révisée en 1998.
10
SUMMARY
In 2006, TRAPIL decided to restart a project which has been dropped a few years ago.
It concerns the replacement of the drainage lamps by an electronic module.
The principle for regulation of the drainage system was expressed at the end of 2006.
The prototype of the programmable electronic bridge controller HBC was realized in
2007 and allowed to eliminate definitively the lamps on the TRAPIL drainage stations.
The results are the following ones:
- very significant reduction of the drained currents and decrease of the ground electric
pollution of soils;
- detection of the influence of conventional drainage stations in the vicinity;
- in the surveys, the pipe potentials are stabilized, more particularly at the level of the
insulating joints. The recordings become a simple routine check.
These devices, after a functioning for more than three year, show a good reliability
and efficiency.
The drainage TRAPIL / a2s2 has been presented to EUROCORR‘2008.
In the present communication, we develop the principle and applications of this
device. It is a particular configuration of the Wheatstone bridge, which makes that this
system of mitigation of stray currents constitutes a scientific approach and not just an
empirical technique.
Keywords: stray currents, influences, drainage, mitigation
Bibliographical references:
« Stray Currents from Electric Railways » Carl MICHALKE, 1904.
« Guide for Measurement of Interference Caused by Cathodic Protection and Railway
Drainage Systems » New South Wales Electrolysis Committee (Australia) Published
october 1990, revised october 1998.
09
RÉSUMÉ
ABSTRACT
Cathodic protection is a widely used method for ensuring the durability of metallic
harbor structures. The design of this protection system is usually calculated
empirically, in the absence of any documented experimentation, although
environmental factors are sometimes very variable in time and space. This is
especially true for sites submitted to tidal effects, either marine or estuarine. A study
conducted on multiple harbor sites succeeded establishing both electrochemical and
environmental data versus water level, and defining a simulation of the polarization
behavior of metallic materials according to the zones of exposure. The results open
perspectives in terms of identifying influent factors to assess the real current demand
and thus to optimize the design of cathodic protection in harbor sites.
RÉSUMÉ
Références:
[1]- ASTM G 31-72, Standard Practice for Laboratory Immersion Corrosion Testing of
Metal (1999).
[2]- AMAL AL-BORNO. Coatings for damp pipe surfaces. Corrosion 2003, N°
03011, NACE (Houston, Texas), p. 1-7.
[3]- C. GABRIELLI, Méthodes électrochimiques, mesures d’impédances. Technique
d’Ingénieur, traité, analyse et caractérisation, 2002, vol. PE 2210, p.1-21.
08
ABSTRACT
Two primers are subject to investigation in this study, a conventional zinc phosphate
primer manufactured by the Algerian National Company of Paintings (ENAP) which
serves as a reference, and a primer based on polypyrrole developed in this study .
The study of corrosion behavior and evolution of the protective power of these primers
were conducted by an immersion test [1], and by stationary electrochemical
techniques [2] (polarization curves) and non-stationary techniques (spectroscopy
Electrochemical impedance, cathodic delamination test) [3]. These methods highlight
on one hand the influence of the nature of anti-corrosive fillers used in the
formulations of the primers on the protection performance of carbon steel against
corrosion in saline environment (NaCl 3.5 %), and, secondly, the solubility of the anti-
corrosion filler in the solvent system chosen (dimethylformamide, xylene).
References:
[1] - ASTM G 31-72, Standard Practice for Laboratory Immersion Corrosion Testing
of Metal (1999).
[2] - Amal Al-Borno. Pipe coatings for damp surfaces. Corrosion 2003, No. 03011,
NACE (Houston, Texas), p. 1-7.
[3] - C. GABRIELLI, electrochemical methods, impedance measurement, Technical
Engineer, processed, analysis and characterization, 2002, Vol. PE 2210, p.1-21.
07
François CASTILLON
RÉSUMÉ
TIGF exploite un réseau de 5.000 km de canalisations de transport de gaz naturel
comportant des revêtements de tout type selon l’âge de construction. Ce réseau est réparti
sur 15 départements du Sud-Ouest de la France, et une partie a plus de 50 ans d'âge (réseaux
RAP et GSO).
L’acier du réseau est protégé de la corrosion depuis l'origine par l’application de la
protection cathodique, avec des appareillages électriques composant les soutirages et des
méthodes de contrôle des potentiels qui ont évolué au fil des ans.
Les pratiques classiques de comparaison annuelle des potentiels « ON », complétées
éventuellement de mesures « OFF » par interruption du débit des soutirages, fournissaient
des valeurs suspectées de fournir une image faussement sûre de la bonne application de la
protection cathodique en tout point du réseau.
Une première phase expérimentale a permis de mettre au point une procédure de mesure
« universelle », simple, fiable, économique, permettant l’acquisition de valeurs cohérentes
utilisables pour garantir la protection du réseau.
C’est en 2003 que l'entreprise a introduit la méthode de mesure de potentiel à courant coupé
sur la liaison canalisation coupon (MCCLCC), d’abord sur un échantillon de 700 prises de
potentiel, puis généralisée sur la totalité du réseau en 2004. 2400 témoins de mesures
(coupons en acier reliés au pipe) ont été positionnés sous forme de puits de mesure sur la
totalité des prises de potentiels du réseau TIGF, avec des surfaces de 50 cm² pour les
canalisations récentes revêtues de polyéthylène ou polypropylène, et de 100 cm² pour les
canalisations comportant des revêtements anciens dont la porosité est la principale
caractéristique.
Cette technique permet de mesurer simultanément le potentiel ON (potentiel témoin sol,
liaison canalisation-coupon établie), le potentiel OFF (potentiel témoin sol, liaison
canalisation-coupon ouverte) et le courant qui circule entre le sol et le coupon liaison avec la
conduite fermée. Sur chaque point de mesure du réseau de TIGF, un enregistrement de ces
trois valeurs est réalisé chaque année sur une durée de 15 minutes ou 24 heures selon la
qualification respective de la prise de potentiel, «ordinaire » ou « spéciale ».
Cet exposé qui s’appuie sur un historique de 7 ans de mesures, aborde intrinsèquement les
différences des valeurs liées à l’environnement géologique, à l’environnement électrique,
qu’il soit maîtrisé (courants de protection cathodique) ou pas (courants vagabonds continus
ou alternatifs).
Ce travail expose les principales interprétations permettant d’expliquer les influences des
paramètres cités ci-dessus. Les différentes conclusions reposent sur des expertises de
témoins effectuées sur site et en laboratoire.
Mots-clés : Témoin, coupon, potentiel, protection cathodique
07
François CASTILLON
ABSTRACT
RÉSUMÉ
Les canalisations enterrées de transport de gaz sont protégées de la corrosion externe par un
revêtement hydrocarboné de polyéthylène. Une protection active, la protection cathodique (PC),
agit sur les défauts ou les manques de ce revêtement. Elle consiste à abaisser le potentiel de l’acier
par rapport à son potentiel naturel pour assurer une vitesse de corrosion négligeable. Pour atteindre
ce but, la norme NF EN ISO 12954 : 2001 recommande des valeurs de référence des potentiels de
protection à appliquer en fonction des conditions de sol. Cependant certains types de sol ne sont pas
pris en compte, comme les sols argileux ou limoneux de forte résistivité.
De plus, dans certains sols, les potentiels de protection sont surestimés. Dans d’autres cas, pour des
sols très résistifs par exemple, il n’est pas possible d’appliquer les potentiels de protection
préconisés aux canalisations. Mais le non respect du critère n’est pas forcément synonyme de
dommage sur la canalisation.
Afin d’affiner ces recommandations, GDF SUEZ et TOTAL ont engagé une étude en laboratoire
destinée à développer des outils et des méthodes pour évaluer la corrosivité d’un sol, et à confirmer
les conditions « nécessaires et suffisantes » de protection pour garantir une vitesse de corrosion
résiduelle négligeable. Le but final est d’optimiser la gestion de la protection cathodique des
canalisations enterrées.
Des essais de perte de masse à moyen terme ont donc été effectués sur des coupons d’acier enterrés
en situation de corrosion libre ou de protection cathodique. Ces coupons ont été enterrés dans des
boîtes remplies de sol « homogénéisé » provenant du terrain. La corrosivité des sols a été évaluée en
mesurant régulièrement les paramètres physico-chimiques et électrochimiques suivants : teneur en
eau, résistivité du sol, potentiel redox, pH et potentiel d’abandon. De plus des mesures d’impédance
électrochimique en mode de perturbation linéaire et périodiquement des tracés de courbes de
polarisation, , ont été réalisés sur ces coupons.
L’interprétation des courbes de polarisation a permis de déterminer des vitesses d’attaque dans le
cas d’un coupon en corrosion libre, et de corrosion résiduelle dans le cas d’un coupon placé sous
PC. La confrontation, pour les différents types de sol, entre les vitesses théoriques obtenues avec les
courbes de polarisation et les vitesses pratiques obtenues par perte de masse a permis d’apprécier
l’aptitude des modèles électrochimiques à prédire la vitesse de corrosion réelle, en fonction des
types de sol.
a
GDF SUEZ, CRIGEN,
b
LEMMA, EA 3167, Université de La Rochelle, Bâtiment Marie Curie,
c
GRT Gaz/DRE/PNE, 5 rue Ferdinand de Lesseps, 60200 Compiègne
d
TOTAL, EP/TDO/TEC/COR
e
TIGF, 49 avenue Dufau, BP 5222, 64022 Pau
ABSTRACT
Buried gas transmission lines are protected against external corrosion by polyethylene
organic coatings. Cathodic protection (CP) is designed and operated with the aim to
mitigate corrosion, where coating is faulty. Basically, pipe potential is lowered, at least to a
value, the protection potential, such that residual corrosion rate is practically negligible.
The NF EN ISO 12954: 2001 standard specifies reference values of the protection
potentials, according to soil conditions. However, some kind of soils, like silt and clay with
high resistivity, are not considered by this standard.
Moreover, in some kind of soils, protection potentials recommended by the ISO standard
are overestimated. In other cases, where soil resistivity is very high, recommended
protection potentials cannot be applied on pipelines. However, such noncompliance does
not necessarily generate damage on the pipes.
In order to refine these recommendations, a laboratory study has been initiated by GDF
SUEZ and TOTAL, with the general aim to improve guidance on cathodic protection
criteria by developing tools and methods to estimate soil corrosivity and identifying the
“necessary and sufficient” conditions to guaranty a negligible corrosion rate.
Some mid-term weight loss tests were made on steel samples, buried in soil boxes, freely
exposed to corrosion or under PC. The soil boxes were filled with soil media from the field.
Soil corrosivity was assessed by regular measurements of physico-chemical and
electrochemical parameters: pH, soil conductivity, humidity level, redox potential and free
corrosion potential. Electrochemical impedance and polarization curves, at different terms
during tests, were made on these samples.
By polarization curves interpretation, it has been possible to determine attack rate if the
sample was in free corrosion conditions or residual corrosion rate in case the sample was
under CP. Comparison, for different kind of soils, between theoretical and weight loss
corrosion rate allows appreciating electrochemical models aptitude to predict actual
corrosion rate.
Cet exposé a pour objet de décrire le document rédigé par le groupe de travail créé au sein
de la commission Construction Bâtiment du CEFRACOR, intitulé "Anodes galvaniques
pour la protection et la réparation du béton armé". Ces procédés, qui visent essentiellement
à agir directement sur les processus de corrosion des armatures, utilisent le zinc,
l’aluminium et leurs alliages pour réaliser ces anodes :
- Surfaciques : par projection, en treillis ou en bandes,
- Sous forme d’anodes discrètes, isolées ou en réseau (avec ou sans courant imposé
préalable).
Ce document est destiné aux principaux acteurs dans le domaine de la réparation des
ouvrages : propriétaires et gestionnaires d’ouvrages, maitres d’œuvre et prescripteurs,
ingénieurs des entreprises, fournisseurs de procédés, laboratoires d’étude et de contrôle.
A but essentiellement pratique, il a pour objectifs de donner des éléments de compréhension
du fonctionnement de ces anodes, de servir de recommandations pour l’utilisation de cette
technique (principe, modes de conception et de calcul, contrôles, domaines d’applications),
et de donner des éléments pouvant servir à l’élaboration de cahiers des charges, sachant que
globalement, ces systèmes ont des « avantages » revendiqués, mais aussi des « limites »
reconnues.
Les méthodes de dimensionnement « traditionnelles » des anodes galvaniques (sol, milieu
marin) ne peuvent s’appliquer directement, et des méthodes simplifiées ont été adaptées
pour chaque système. En général, on utilise des hypothèses déduites de l’expérience.
Pour contrôler soit la bonne mise en route du système, soit son fonctionnement sur la durée
(pour notamment mieux évaluer la fin de vie des anodes), des mesures sur le terrain sont
indispensables, sur des surfaces de référence représentatives spécifiquement aménagées. Il
est probable que les valeurs de la norme NF EN 12696 ne puissent pas être atteintes, en tous
cas à chaque moment de l’exploitation des anodes. Cela nécessite la mise en place de
systèmes adaptés, sur des zones caractéristiques de l’ensemble de l’installation. Plusieurs
paramètres peuvent être mesurés, et on doit attirer l’attention sur l’importance de
l’enregistrement de ces paramètres, compte tenu de leur grande variabilité. Ces paramètres
sont : l’intensité du courant (ramenée à la surface d’armatures concernée), les potentiels
« on » et « off », la dépolarisation, le courant de corrosion calculé et estimé, etc.
Par ailleurs, il convient de distinguer les contrôles à la réception, qui sont obligatoires et
doivent permettre de rendre compte au donneur d’ordre de la bonne mise en route du
procédé, de son fonctionnement puis de valider le dimensionnement, et les contrôles de
suivi (optionnels) nécessaires entre autre pour évaluer en cours de fonctionnement la
durabilité du système.
Les domaines d’emploi, la durabilité, et les garanties relatifs à ces procédés applicables dans
le Bâtiment, le Génie Civil, les Ouvrages d’art, les Ouvrages portuaires, sont également
décrits.
05
GALVANIC ANODES FOR PROTECTION
AND REPAIR OF REINFORCED CONCRETE
ABSTRACT
This paper aims at describing the document prepared by the working group established
within the Building Construction Committee CEFRACOR, entitled "Galvanic anodes for the
protection and repair of reinforced concrete." These methods, designed primarily to act
directly on the reinforcement corrosion process, use zinc, aluminum and their alloys to
constitute these anodes:
- Surface anodes: sprayed, grid or strips,
- In the form of discrete anodes, isolated or networked (with or without impressed current
first).
This document is intended to major players in the field of repair works: Owners and
operation managers of structures, contractors and specifiers, engineers, suppliers of
processes, laboratory for study and control.
With a very practical purpose, it aims at providing elements of understanding of how these
anodes, at providing recommendations for the use of this technique (principle methods of
design and calculation, control, application areas) and at providing elements that can be
used to develop specifications, knowing that together these systems have claimed "benefits",
but recognized "limitations".
The "traditional" design methods for galvanic anodes (ground, seawater) are not directly
applicable, and simplified methods have been adapted for each system. In general,
assumptions derived from experience are used.
To check whether the correct commissionning of the system or its functioning over time
(especially to better assess the end of life of anodes), the field measurements are essential,
on representative reference surfaces specifically arranged. It is likely that the values of the
standard EN 12696 cannot be achieved in some case at all stages of the operation of the
anodes. This requires the establishment of appropriate systems, on typical areas
representative of the entire system. Several parameters can be measured, and attention
should be drawn to the importance of recording these parameters, given their great
variability. These parameters are: the current (reported to the surface of the rebars
involved), the "on" and "off" potentials, the depolarization, the corrosion current calculated
and assessed, etc.
Moreover, it is necessary to distinguish the checks at the reception, which are mandatory
and must be able to reflect for the end user the good start-up of the process, the operation
and validate the design and monitoring controls (optional) necessary to evaluate, among
other, during current operation the system sustainability.
Areas of application, sustainability, and guarantees related to these procedures applicable
in the building, civil engineering, land structures, harbor structures, are also described.
04
Avant la mise en place d’un système de protection cathodique sur un ouvrage en béton
armé, par un système à courant imposé ou à anodes galvaniques, l’évaluation de la
corrosion passe par l’utilisation de méthodes de diagnostic basées sur des observations
visuelles, des prélèvements suivis d’analyses (profondeur de carbonatation, profils en
chlorures, etc.), et des méthodes instrumentales, dont certaines à principe
électrochimiques : mesures de potentiel, de résistivité, de vitesse de corrosion. Ces
dernières peuvent être d’un appui intéressant quant au choix du système à adopter et à
son dimensionnement.
Leur principe est connu et largement décrit : l’application d’une faible variation de
tension entre le parement du béton (sur lequel une ou plusieurs électrodes sont posées)
conduit à un courant de polarisation. Une autre méthode consiste à envoyer une
impulsion de courant, et à mesurer l’évolution de la polarisation. Des relations
simplifiées conduisent ensuite à la vitesse de corrosion, en termes de densité de
courant, transformées en perte d’épaisseur.
Toutefois, la pratique montre que les choses ne sont pas si simples. Les dispositifs
expérimentaux sont parfois complexes et les appareils commercialisés, des « boites
noires » donnant des résultats délicats à interpréter. La surface d’armatures en regard
des électrodes, variable en fonction de paramètres pas toujours connus. Il est
également important de noter que la vitesse de corrosion n’est pas constante dans le
temps, car elle dépend du mécanisme de corrosion (carbonatation, chlorures), et
surtout des conditions à l’interface acier béton (dont la chimie de la solution
interstitielle, la diffusions des espèces, dont l’oxygène, la température, etc.). D’autres
méthodes indirectes issues de l’expérience de la protection cathodique peuvent être
utilisées : la mesure de la dépolarisation d’armatures sous protection cathodique (avec
courant imposé ou anodes galvaniques), combinée avec le courant correspondant.
ABSTRACT
Before setting up any cathodic protection system (by impressed current or galvanic
anodes) on a reinforced concrete structure, its condition should be assessed. The
diagnostic methods are based on visual observations, sampling for analysis (depth of
carbonation, chloride profiles, etc..), and instrumental methods among which some
electrochemical methods: potential, resistivity and corrosion rate measurements.
These methods may be of interest to support the choice of the cathodic protection
system and its design.
Their principle is known and widely described: the application of a low voltage
lowering between the surface of concrete (on which one or more electrodes are set)
leads to a polarization current. Another method is to send a current pulse, and to
measure changes in polarization. Simplified relationships then lead to the corrosion
rate in terms of current density easily transformed into thickness loss.
However, practice shows that things are not so simple. The experimental devices are
often complex and the commercial devices are nothing but "black boxes" giving results
almost impossible to interpret. Rebar surface facing the electrodes varies according to
parameters not always known. It is also important to note that the corrosion rate is not
constant in course of time because it depends on the mechanism of corrosion
(carbonation, chloride), and especially conditions at the steel concrete interface
(including solution chemistry interstitial diffusion of species, including oxygen,
temperature, etc.). Other indirect methods derived from experience of cathodic
protection, can be used such as the degree of depolarization of the rebar under
cathodic protection (impressed current or with galvanic anodes), combined with the
corresponding current.
The purpose of this paper is to highlight the problems associated with these
determinations, and in particular to show how changes in environmental conditions
(temperature, humidity, ...), concrete characteristics are important parameters, and
thus provide elements of understanding in measures assessment.
03
ABSTRACT
The periodical check of the integrity of hydrocarbon pipelines and reservoirs (gas, oil
etc.) is essential for safety, environmental and economical aspects. Water pipelines
and reservoirs can also be affected during operation by leaks which can be expensive
and even dangerous in the long run. Pipeline companies, especially Gas and Oil
Companies deserve a high level of attention and lots of human and economic
resources to safeguard the integrity of their structures (visual inspections by
manpower or helicopters, development and application of safety plans, coating fault
surveys, periodical maintenance measurements etc.). All these efforts can be thwarted
in case of accidents; liquid or gas leakages due to mechanical impacts by third parties
are typical incidents quite hard to prevent.
A sudden impact can result in an immediate release of substances. Less severe impacts
or corrosions, nevertheless, can damage the pipeline/reservoir, without an immediate
awareness. These could also be mechanical scratches or dents which, together with
the application of cathodic protection, can develop the so-called hydrogen-induced
delayed fracture.
The integrity of special vessels such as LPG or water buried tanks, or modern gas and
water pipelines can be kept under control by means of automatic devices and
electronic software applications, provided that their coating resistance is sufficiently
high. A short circuit at an insulating joint on a pipeline can be easily and immediately
detected if such a system is installed.
The paper is aimed at reviewing some laboratory tests and field applications to verify
the limits and the practicability in the real field of such methods.
03
RÉSUMÉ
RÉSUMÉ
Le système GRILLO-KKS-BETON est une anode galvanique qui permet de protéger les
armatures du béton armé contre la corrosion. Il s’agit d’une anode de zinc qui est appliquée
par métallisation à l’arc électrique. Pour finir, on applique un revêtement organique sur
l’anode afin de la protéger contre la corrosion due aux influences environnementales.
On peut installer des fenêtres de test pour contrôler le bon fonctionnement du système. On
enregistre alors les potentiels, les courants et les températures. Grâce à ces mesures, on peut
vérifier le fonctionnement d’un système de protection cathodique. Parmi les critères utilisés,
les plus importants sont : le critère 100 mV, la valeur du potentiel de l’armature 24 h après
la déconnexion, l’évolution du potentiel de l’armature, la valeur du courant de protection.
Le système GRILLO-KKS-BETON existe depuis environ 15 ans. Au début, il n'y avait que
des résultats de recherches effectuées par la société GRILLO. À cet effet, des échantillons
de béton armé ont été fabriqués sur lesquels nous avons appliqué notre système de
protection. Ces échantillons ont été analysés afin de vérifier la conformité aux critères. Il
s'est finalement avéré qu’une anode de zinc pure combinée à un revêtement organique
adapté remplissait les critères. Cela signifie que la dépolarisation révélait une augmentation
de plus de 100 mV en 24 h. L’évolution du potentiel de l’armature témoigne d'une
croissance constante de sorte que le potentiel de l'armature a atteint une valeur au niveau
duquel la corrosion n'a plus lieu.
Par la suite, des instituts indépendants comme l’Université de Sciences Appliquées de
Würzburg ou le CSTC en Belgique, ont aussi effectué leurs propres recherches. Ces instituts
ont également pu confirmer le bon fonctionnement du système. En outre, les examens du
CSTC ont été réalisés avec un béton à haute résistivité (CEM IIIA + cendre volante ; béton
carbonaté jusqu’au niveau des armatures). Même dans ces conditions difficiles pour une
anode galvanique, le bon fonctionnement a été confirmé.
Entre-temps, de nombreuses structures ont été assainies à l'aide de ce système. Il existe des
enregistrements détaillés qui montrent que la dépolarisation remplit le critère de 100 mV
pour toutes les structures réalisées. En outre, le courant de protection mesuré est toujours
suffisant. L’évolution des potentiels indique une bonne performance du système, car le
potentiel augmente avec le temps pour atteindre une valeur au niveau de laquelle la
corrosion n’a plus lieu.
À l’aide des valeurs de courant de protection enregistrées, on peut calculer la durée de vie
du système, qui s’élève au moins à 30 ans.
ABSTRACT
A. CHTAINI
Equipe d’Electrochimie et des Matériaux Inorganiques, Université Sultan Moulay Slimane,
Faculté des Sciences et Techniques, BP 523, Beni-Mellal, Maroc.
chtainia@yahoo.fr
ABSTRACT
A. CHTAINI
Equipe d’Electrochimie et des Matériaux Inorganiques, Université Sultan Moulay Slimane,
Faculté des Sciences et Techniques, BP 523, Beni-Mellal, Maroc.
chtainia@yahoo.fr
RESUME