You are on page 1of 8

OPTIMAL CONTROL FOR CENTRAL COOLING PLANTS

B.C. Ahn, Ph. D.


Kyungwon University, Kyunggi-Do, 461-701, Korea
J.W. Mitchell, Ph.D., P.E.
University of Wisconsin, Madison, Wisconsin, U.S.A.

ABSTRACT
The optimal supervisory control strategy for a central Pape et al.[1991] developed an overall empirical cost
chilled water facility has been determined. A function of the optimal control for the total power
quadratic linear regression relation for the total consumption of the cooling plant. In his paper, the
system power in terms of the controlled and cost function with respect to two control variables
uncontrolled variables was developed using such as supply air temperature and chilled water
simulated data. The supply air, chilled water, and temperature, and uncontrolled variables. However,
condenser water temperatures that minimize energy The optimal strategy for cooling tower associated
consumption are determined as functions of load, with the condenser water set temperature is not
ambient wet bulb temperature, and sensible heat considered. Ulleberg[1993] developed a building
ratio. The use of the quadratic expression to energy management system (BEMS) controller. The
determine optimal control is demonstrated. controller, which learns the behavior of the air
conditioning system with the passage of time and
attempts to control the system based on an optimal
INTRODUCTION set point control such as supply air and chilled water
In a cooling plant, There are many control variables temperatures, was tested on an emulator.
that may be controlled to minimize building energy
consumption. Global optimal control methods for the The object of this paper is to illustrate the optimal
cooling plants have been studied by Sud[1984], control in which, for a given building load and
Lau[1985], and Johnson[1985]. Their studies showed ambient conditions, the overall system energy
significant savings associated with the use of optimal consumption was minimized while maintaining
control method as compared with traditional control comfort conditions in the building. The optimal set
one. However, they did not develop general temperatures for supply air, chilled water, and
algorithms suitable for on-line control. condenser water, are selected such that energy
consumption is minimized under a range of
Braun[1988] developed a methodology for uncontrolled variable, which are load, ambient wet
determining the optimal control strategy for an bulb temperature, and sensible heat ratio. The chilled
HVAC system and showed that saving of 10 to 20 % water loop pump and cooling tower fan speeds were
are possible by applying optimal control to the controlled by the PID controller such that the supply
system. He showed that the power consumption of a air and condenser water set temperatures reach the
cooling plant may adequately be represented as a set points designated by the optimal supervisory
quadratic function of continuous control variable and controller. Then, the effects of the controlled
uncontrolled variables. In addition, he showed that variables on the total system and component power
the power consumption of a chiller may also be consumption were compared.
adequately represented as a quadratic function of the
load and the temperature difference between leaving
condenser and evaporator water temperatures. He OPTIMAL CONTROL ALGORITHM
also demonstrated that the power of pumps and fans An optimization process is able to find the minimum
may be represented with a quadratic function of of the sum of the operating costs J as a function of
control variables and flow rates. His study provides the forcing functions f with respect to the discrete
the basis for the method used in this paper.

-1-
control variables M and the continuous control 2 N ( N − 1) 2
variables u . Expressed mathematically N coeff = N u − u u + Nu + N f
2
N f ( N f − 1) (4)
J = J ( f , u, M ) (1) − + N f + N f Nu +1
2
The forcing function f is a vector containing all where N u is the number of continuous control
uncontrolled variables, such as load, ambient wet variables and N f is the number of uncontrolled
bulb temperature, and sensible heat ratio. The variables. In this study there are three controlled
continuous control variables u are those such as variables and three uncontrolled variables, thus 28
supply air temperature, chilled water temperature, coefficients need to be determined by regression
and condenser water temperature that can varied techniques.he exact model of the quadratic formula
continuously over the control range. The discrete has the form
control variables M are those controls that have
y = B0 + B1 x1 + B2 x 2 + ⋅ ⋅ ⋅ + Bn +1 x1 + ⋅ ⋅ ⋅
discrete settings, such as high and low fan speed, the 2

number of operating chillers, and the number of (5)


+ B2 n +1 x1 x 2 + ⋅ ⋅ ⋅ + e
operating fans or pumps.
A simple function for which an optimum exists that
can be determined analytically is a quadratic where y are the responses, xi are the predictors, Bi
function. Braun et al[1988] have shown that power are the regression coefficients, n is the number of
requirements for chillers, fans, and pumps can be variables in the equation ( n = 6 in the considered
adequately expressed as quadratic relationships. case), and e is an error term with a normal
Similarly, they have shown that the cost of energy for distribution with a mean of zero and a standard
an entire cooling plant can also be represented as a deviation . A second order least squares linear
quadratic function. Their process for optimization regression estimates the Bi with bi and predicts
will be reviewed here. Therefore, the cost function

represented by equation(1) can be written to
y = b0 + b1 x1 + b2 x 2 + ⋅ ⋅ ⋅ + bn +1 x1 + ⋅ ⋅ ⋅
2
represent the entire system (6)
+ b2 n +1 x1 x 2 + ⋅ ⋅ ⋅
J ( f , M , u ) = u T Au + b T u + f T Cf + d T f
+ f T Eu + g (2) where y is the fitted or predicted value. The two
outputs, standard deviation (S) and the coefficient of
where A is a symmetric matrix , C , and E are determination (R2), from the regression can be used
coefficient matrices, b and d are coefficient vector, to judge the quality of fit between predicted and
and g is a scalar. The optimal control is determined observed values. The coefficient of determination is
by equating the first derivative of the power with the fraction of the variation in y that is explained by
respect to each control variable to zero ( ∂J ∂u = 0 ). the fitted equation. These two parameters have to be
Solving for the optimal values of continuous control improved as far as possible to obtain a good fit. As it
variables yields linear relations between the control may be anticipated from equation (6), the values of
variables and the forcing function. the coefficients depend strongly on the number of
data sets (sets of predictors and corresponding
1 −1 1 −1 response) used in the regression.
u=− A b − A Ef (3)
2 2
This formulation and resulting linear control laws are APPLICATION TO THE COOLING
the result of unconstrained optimization. And the PLANT
control laws results in a minimum power Figure 1 shows a schematic of the typical variable air
consumption only if the Hermitian of the cost volume(VAV) air-conditioning system used in this
function is a positive definite matrix[Ogata(1967)]. study. It is a centralized chilled water facility, with
The coefficients in equation (2), which depend on the chilled water distributed to a set of air-handling units.
discrete control variables, i.e., the various operating The HVAC system meets the air conditioning
modes, need to be determined empirically. To requirements of the building zones through control of
complete this task a least square linear regression the supply fan speed, cooling tower fan speed, chilled
technique was employed. The total number of water and condenser water pump speed, supply air
possible coefficients of equation (2) in terms of the temperature setting, chilled water temperature
controlled and uncontrolled variables in the quadratic setting, and condenser water temperature setting. The
equation for each feasible set of discrete control system has three control variables: the chilled water
modes is set temperature, the supply air set temperature, and
condenser water set temperature. The significant

-2-
Pfan,ct

Cooling
Tower
Ppump,ct
Tcond.set

Condenser

Expansion Pchiller
Valve Chiller
Compressor
Tchw.set
Evaporator

Main Water Loop Ppump,mw

Cooling Coil
Filter Supply Fan
Tspa.set
Ventilation
Air
Mixing Pfan,s
Damper VAV Other
Unit 1-1 Zones
AHU 1 - 6
Exhaust Zone 1-1
Air

Ptot = Pchiller + Pfan,ct + Ppump,ct + Ppump,mw + Pfan,s

Figure 1 Schematic of a conventional air conditioning system

uncontrolled variables are the cooling load, the reaches the set point designated by the supervisory
ambient wet bulb temperature, and sensible heat controller. The feedback controller uses the typical
ratio. The ambient dry bulb temperature as a ambient PID control algorithm to return the control variable
condition has almost no effect on the total power to set point. The PID controller for the pump speed
consumption of cooling system (Braun 1988). was designed to control the supply air set
The cooling coil requires feedback control to temperature. The controller in the frequency domain
provide the supply air temperature set by supervisory has a transfer function
control system. The control signal for the chilled
M ( s) K
water main loop pump modulating cooling coil water = Gc ( s) = K p + i + K d s (7)
flow rate is updated until the control variable, which E (s ) s
is the supply air set temperature, reaches the set point
designated by the supervisory controller. The cooling Where M (s), E(s), Gc (s), K p , Ki , Kd , and s are conti-
tower fan speed is also controlled by the feedback nuous data controller output, error, controller transfer
control such that the condenser water set temperature functions, proportional, integral, derivative control

-3-
gains, and Laplace variable. The integral K i / s can The total system power is not exactly a quadratic
be approximated by the z-transform on the polygonal function of the controlled and uncontrolled variables.
integration (Kuo [1977]). However, near the optimum, the behavior of the
system power can be very well approximated with a
M ( z) K T ( z + 1) K d ( z − 1) quadratic function. Therefore, to obtain an accurate
= D( z ) = K p + i +
E ( z) 2( z − 1) Tz equation, data near the optimum is needed. Thus, it is
important that the region in which the data is taken
K iT K d includes the optimal conditions. After collecting
K1 = K p + + enough data near optimal conditions, a regression
2 T
(8) was performed to obtain the quadratic correlation for
K iT 2 K d
K 2 = −K p + − the power. In this study, the MINITAB regression
2 T program package release 11 was used to obtain the
K
K3 = d coefficients of the quadratic equation.
T The quadratic cost function for the total system of
where T is sampling time. The following difference cooling plant can be presented as
equation was obtained from equation (8), which is
easy to implement in a digital controller. P = P(Tchw.set, Tspa.set, Tcond .set ,
Load , Twb, SHR) (11)
m(k ) = m(k − 1) + K 1e(k ) + K 2 e(k − 1) + K 3 e(k − 2)
e( k ) = r − c( k ) (9) All the coefficients of equation (2) were determined
empirically using linear least squares regression
where m(k ), e(k ) , r ,and c (k ) are the kth controller techniques. In the system which was considered in
output, the kth error, required set-point, and this paper, only one set of discrete control variables
measured control value, respectively. exits, and thus one formula for system power was
The supply air flow rate was evaluated using the developed.
room and supply air set temperatures and the sensible The Hermitian matrix A in the quadratic cost
load. The cooling tower fan speed was controlled by function of equation (2) must be positive definite in
the feedback control such that the condenser water order to obtain the minimum power. Since A is a real
set temperature reached the set point designated by symmetric matrix, the Sylvester criterion (a
the supervisory controller. A PID speed control necessary and sufficient condition in order that the
algorithm was also used as the feedback controller. quadratic form, where A is real symmetric matrix, be
The water flow rate in cooling coil or air flow rate in positive definite is that the determinant of A be
cooling tower under a PID controller was determined positive and the successive principal minors of the
by the following control law determinant of A be positive) can be used to check if
Hermitian matrix A is positive definite or not. After
⋅ ⋅
the regression technique was applied to the example
m = m MAX − m(k ) (10)
⋅ ⋅ ⋅ ⋅ system, matrix manipulation and rearranging yielded
if m > m MAX then m = m MAX the coefficients, controlled variables, and
⋅ ⋅ uncontrolled variables for its quadratic cost function
where m, m MAX , and m(k ) are water or air flow rate, (equation (2)) as follows:
maximum water or air flow rate, and PID controller
output, respectively. The pump in the cooling tower
was assumed to operate at constant speed. Optimal  1.124 − 1.145 0.013 
 
set point temperatures for condenser water A − 1.145 2.025 − 0.028
=
temperature, chilled water temperature, and supply  0.013 − 0.028 0.511 
air temperature were such that energy consumption
was minimized under variation of load, ambient wet  0.002 − 0.035 − 0.795 
 
bulb temperature, and sensible heat ratio as C =  − 0.035 0.039 − 13.259  (12)
uncontrolled variables.  − 0.795 − 13.259 70.58 
The simulation study was done by using the
TRNSYS Ver. 14.2 (Klein et al. 1996) program. The 0.007 0.011 − 0.006
system model studied in the paper is based on the E = 0.168 − 0.111 − 0.665
system used by Pape[1992] and the models of 1.246 21.695 − 0.732
Braun[1988] included in TRNSYS program were
used as system components. Modular programs of b = [− 1.800 − 42.264 − 9.373]T
the TRNSYS were modified for the control of each d = [− 0.469 10.998 − 192.670]
T

component and additionally some control programs g = 317.69


such as supervisory control were developed.

-4-
u = [Tchw.set Tspa.set Tcond.set ]T while the optimal condenser set temperature is also
f = [Load Twb SHR]T
affected by the optimal supply air and chilled water
set temperatures.
The predicted power obtained from the quadratic
Then, the successive principal minors of the regression equation is presented as a function of the
determinant of A and the determinant of A are solved simulated power in Figure 2. The standard deviation
analytically to determine if the Sylvester criterion was S = 3.166 (about 2%) and the coefficient of
was satisfied in the quadratic cost function to obtain determination was R2 = 99.4%. The quality of fit
the minimum power,: between predicted and observed system power is a
straight line occurs which characterizes a good fit.
a11 = 1.124 > 0 Only very few points are off the line, and these points
represent conditions which are far away from the
a11 a12 optimal control.
= 1.147 > 0
a 21 a 22 (13) In this study, the three set points temperatures are
constrained to avoid problems with components
a11 a12 a13 operation. The chilled water temperature is
a 21 a 22 a 23 = 0.586 > 0 constrained between 11oC and 3oC to provide
sufficient dehumidification and to prevent freezing in
a 31 a 32 a 33

500
Once the empirical coefficients in equation (2) were

Predicted System Power (kW)


known, the derivatives with respect to the controlled 400
variables were taken to yield linear control laws. In
300
this paper, derivatives were taken with respect to the
supply air temperature (Tspa.set) , chilled water 200

temperature (Tchw.set ) , and condenser water temp- 100


erature (Tcond .set) . The following three equations
0
were solved analytically for the optimal set point 0 100 200 300 400 500
temperatures: Simulated System Power (kW)

∂P
=0
∂Tchw.set
∂P Figure 2 Predicted versus simulated total
=0 (14) system powers
∂Tcond .set
∂P
=0 the evaporator tubes. The supply air temperature is
∂Tspa.set
constrained between 15oC and 8oC to avoid
overcooling or becoming too humid in the
According to equation (3), the resulting equations for
conditioned spaces. The condenser water temperature
three set point temperatures are linear relation with
is also constrained to be greater than 19oC to avoid
respect to uncontrolled variables or ambient
the possibility of compressor lubrication problem and
conditions such as building load, ambient wet bulb
surging.
temperature, and sensible heat ratio:
The set point temperatures are linear functions of the
forcing functions due to the assumption of quadratic
Tchw.set.optimal = G1 ( Load , Twb, SHR) dependence of power to the variables. The linear
Tspa.set.optimal = G2 ( Load , Twb, SHR, control laws are shown in Figure 3 to 5.
Tchw.set.optimal ) The optimal set point temperatures (Tspa.set.optimal,
(15)
Tchw.set.optimal, and Tcond.set.optimal) and the
Tcond .set.optimal = G3 ( Load , Twb , SHR,
total system power are presented as functions of the
Tchw.set.optimal, Tspa.set.optimal) building load in Figure 3, as functions of the ambient
wet bulb temperature in Figure 4, and as functions of
These three unbounded optimal set point
sensible heat ratio in Figure 5, respectively. In
temperatures are linear functions of the forcing func-
Figure 3, the ambient wet bulb temperature (18oC)
tions due to the assumption of the quadratic
and sensible heat ratio (0.8) are fixed. The optimal
dependence of power on these variables.
supply air and chilled water set temperatures
In equation (15), the optimal supply air set point
decrease with increasing load, while the optimal
temperature is affected by the chilled water set
condenser water set temperature increases with
temperature selected from optimal control algorithm,
increasing load. The temperature difference between

-5-
the optimal supply air and chilled water set point (0.8) are fixed. The optimal chilled water set
temperatures increases with load. In the predicted temperature decreases a little with increasing ambient
total system power consumption, the increase of the wet bulb temperature, while the ambient wet bulb
power at higher loads is greater than at lower loads. temperature has very a little influence on the optimal
If the load is less than 100 ton or greater than 450 supply air set temperature because it influences on
ton, the optimal set temperatures may reach the the very small amount of ventilation load. Thus, the
constraints. However, it is really not important and temperature difference between the optimal supply
the figure does not show it. air and chilled water set point temperatures increases
with ambient wet bulb temperature more than with
load. The optimal condenser water set temperature
increases with ambient wet bulb temperature. The
Tcond.set Tspa.set Tchw.set Power
influence of the ambient wet bulb temperature on the
30 400

Predicted System Power


optimal condenser water set temperature is relatively
Temperature ( oC)

25
300 very high. The predicted total system power
20
increases linearly with increasing ambient wet bulb

(kW)
15 200
10 temperature.
100
5 In Figure 5, the load (300 ton) and ambient wet bulb
0 0 temperature (18oC) are fixed. The optimal chilled
0 100 200 300 400 500
water and supply air set temperatures decrease with
Load (ton)
increasing sensible heat ratio. The temperature
difference between the optimal supply air and chilled
Figure 3 Optimal setpoint temperatures and water set point temperatures is held constant.
predicted system power for varying However, the sensible heat ratio has very a little
load effect on the optimal condenser water set
temperature. The predicted total system power
increases linearly with sensible heat ratio.
In Figure 6 to 8, the simulated and predicted total
Tcond.set Tspa.set Tchw.set Power system power, the chiller power, the cooling tower
35 350
fan power, the main water pump power, and air
Predicted System Power

30 300
Temperature ( oC)

25 250
handling unit fan power are presented as functions of
the supply air set temperatures (Figure 6), as
(kW)

20 200
15 150
functions of the chilled water set temperature (Figure
10 100
5 50
7), and as functions of the condenser water set
0 0 temperature (Figure 8), respectively. The power
10 15 20 25 30
o
consumption of the cooling tower pump are constant
Wet Bulb Temperature, Twb ( C)
for all conditions and are therefore not shown. In this
air conditioning system, there are 6 supply fans
Figure 4 Optimal setpoint temperatures and (AHU 1-6). The figures show the power for one
predicted system for varying ambient supply fan. However, the total power included 6
wet bulb temperature supply fan powers. The figures are valid for a fixed
set of forcing function (Load = 300 ton, Twb = 18oC,

Tcond.set Tspa.set Tchw.set Power

25 250 300 30
Predicted System Power

Total & Chiller Power (kW)

Ptot,sim
Component Power (kW)
Temperature ( oC)

20 200 250 Ptot,pred


15 150 Pchiller
200 20
(kW)

Pfan,ct
10 100 150 Ppump,mw
5 50 Pfan,s
100 10
0 0 50
0.5 0.6 0.7 0.8 0.9 1
0 0
Sensible Heat Ratio, SHR
0 4 8 12 16
o
Supply Air Set Temperature ( C)
Figure 5 Optimal setpoint temperatures and
predicted system power for varying
ambient wet bulb temperature Figure 6 Predicted, simulated total system, and
component powers for varying supply
In Figure 4, the load (300 ton) and sensible heat ratio air set temperature

-6-
water set temperature. The supply air and condenser
250
Ptot,sim
25
water set temperatures are fixed at 11oC and 26oC,

Total & Chiller Power (kW)


respectively. The predicted total system power

Component Power (kW)


Ptot,pred
200 20
Pchiller
Pfan,ct
consumption is a good fit to the simulated power. As
150 15
Ppump,mw the chilled water set temperature increases, the chiller
100 Pfan,s
10 power decreases while the main water loop pump
power increases. The influences of the chilled water
50 5
set temperature on the cooling tower fan and supply
0 0 air fan power are relatively very small. Through the
0 4 8 12 16 trade-off between the main water loop pump power
o
Chilled Water Set Temperature ( C) and chiller power, the total system power use in both
simulated and predicted system are minimized at a
supply air set temperature of 7oC. However, the only
Figure 7 Predicted, simulated total system, and
slight difference of the total system powers between
component powers for varying chilled
7oC and 9oC in higher chilled water set temperatures
water set temperature
is occurred.
Figure 8 shows that the total system and component
power consumption vary with changes in the
250 30 condenser water set temperature. The supply air and
Total & Chiller Power (kW)

Ptot,sim
chilled water set temperatures are fixed at 11oC and
Component Power (kW)

200 Ptot,pred 25
Pchiller 7oC, respectively. As the condenser water set
20
150 Pfan,ct temperature increase, the cooling tower fan power
Ppump,mw
Pfan,s
15 decreases while the chiller power increases. The
100
10 changes of the condenser water set temperature does
50 5 not have effects on the main water loop pump and
supply air fan powers. Through the trade-off between
0 0
24 26 28 30 32 34
cooling tower fan power and chiller power, the total
o
system power use in both simulated and predicted
Condenser Water Set Temperature ( C)
system are minimized at a supply air set temperature
of 26oC. However, the difference of the total system
Figure 8 Predicted, simulated total system, and powers between 25oC and 26oC in lower condenser
component powers for varying cond- water set temperatures is very small.
denser water set temperature

CONCLUSION
SHR = 0.8). The total system and chiller power are The optimal control strategy in which, for a given
shown on left y axis and other component powers are building load and ambient condition, the total system
on right y axis. operation cost is minimized is applied to the cooling
Figure 6 shows that the total system and component plant. A quadratic least square regression technique
power consumption vary with changing supply air set is used for predicting the total system power in terms
temperature. The chilled water and condenser water of the forcing function and control variables. The
set temperatures are fixed at 7oC and 26oC, optimal values of set temperatures such as supply air,
respectively. The predicted total system power is a chilled water, and condenser water temperature, are
good fit to that simulated. The supply air fan power selected that energy consumption is minimized with
increases with the supply air set temperature because varying load, ambient wet bulb temperature, and
the flow rate has to be increased to meet the load, sensible heat ratio as uncontrolled variables.
while the main water loop pump power decrease fast A quadratic regression equation for predicting the
with increasing supply air set temperature because total cooling system power in terms of the forcing
less water has to be provided for a fixed chilled water function and control variables is fit to the data
temperature. Through the trade-off between supply collected under different values of controlled and
air fan power and the main water loop pump power, uncontrolled variables. The standard deviation and
the total system power use in both simulated and the coefficient of determination shows that the fit is
predicted system are minimized at a supply air set good. As the Hermitian matrix of the system
temperature of 11oC. The change of the supply air set quadratic cost function turned out to be positive
temperature does not have an effect on the chiller and definite, the optimal minimum power was able to be
cooling tower fan powers. obtained. The optimal control is determined by
Figure 7 shows that the total system and component equating the first derivative of the power with respect
power consumption vary with changes in the chilled to each control variable to zero. The resulting set of

-7-
equations determine the optimal values of the 1991, Optimal control and Fault Detection in
controlled variables. Heating, Ventilating, and Air-conditioning Sys-
The influence of the load and sensible heat ratio on tems, ASHRAE Transactions 97(1):729-745.
the optimal supply air and chilled water set Sud, I., 1984, Control Strategies for Minimum
temperatures are relatively high, while ambient wet Energy Usage, ASHRAE Transactions, Vol.90,
bulb temperature have slight effects on them. In Part 2: 247-277.
contrast to that result, the ambient wet bulb Ulleberg, O., 1993, Emulation and Control of Heat-
temperature have much influences on the optimal ing, Ventilation, and Air-conditioning Systems,
condenser water set temperature, while the load has Master thesis, University of Wisconsin-Madison.
less and the sensible heat ratio has no influence on it.
The trade-off among the component power
consumption results in that the total system power NOMENCLATURE
use in both simulated and predicted system are A− 1 inverse matrix
minimized at lower supply air, higher chilled water, b coefficient vector
and lower condenser water set temperature bi regression coefficients
conditions. However, the total system powers varies C coefficient matrix
slightly in near that set temperature conditions. c (k ) the measured control variable
The quadratic cost function approach is good for d coefficient vector
optimal control and is a algorithm suitable for on-line D (z ) controller z-transfer function
control. This study will be a basis for fault detection e error with normal distribution
and diagnosis researched in the next time. E coefficient matrix
e(k ) the kth control error
e( k − 1) the ( k − 1)th control error
REFERENCE e(k − 2) the (k − 2)th control error
Braun, J.E., 1988, Methodologies for Design and E (s) error s-transfer function
Control of Central Cooling Plants, PhD. E (z ) error z-transfer function
Dissertation, Department of Mechanical Engin- f forcing function (uncontrolled
eering, University of Wisconsin-Madison. variables)
Braun, J.E., S.A. Klein, W.A. Beckman, and J.W. g scalar
Mitchell, 1989, Methodologies for Optimal G1 , G2 , andG3 functions
Control of Chilled Water Systems without J operating cost function
Storage, ASHRAE Transactions, Vol. 95, Part 1: Kp proportional control gain
652-662. Ki integral control gain
Box, G.E.P., W.G. Hunter, and J.S. Hunter, 1979, Kd derivative control gain
Statistics for Experimenters, An Introduction to Load cooling load
Design, Data Analysis, and Model Building, John M⋅
discrete control variables
Wiley & Sons, New York. m MAX maximum mass flow rate
Draper, N.R. and H. Smith, 1981, Applied m(k ) the kth controller output
Regression Analysis, Second Edition, John Wiley m( k − 1) the (k − 1)th controller output
& Sons, New York M (s ) controller output s-transfer function
Klein, S.A., et al., TRNSYS: a Transient System M (z ) controller output z-transfer function
Simulation Program Version 14.2, Solar Energy n the number of variables
Laboratory, University of Wisconsin-Madison. N coeff total number of coefficients
Kuo, B.C., 1977, "Digital Control System", SRL Nf the number of continuous uncon-
Publishing Company. trolled variables
Lau, A.S., W.A. Beckman, and J.W. Mitchell, 1985, Nu the number of continuous control
Development of computer control routines for a variables
large chilled water plant, ASHRAE Transactions, P power
Vol. 91, Part 1: 766-780. r the required set point
Minitab Inc. , 1996, MINITAB User’s Guide R2 the coefficient of determinition
Release 11 S standard deviation
Johnson, G.A., 1985, Optimization Techniques for s Laplace variable
a centrifugal chiller plant using a programmable SHR sensible heat ratio
controller, ASHRAE Transactions, Vol. 91, Part 2: T sampling time
835-847. Twb ambient wet bulb temperature
Ogata, K. 1967, State Space Analysis of Control u continuous control variables
Systems, Prentice Hall E-Series. xi predictors
Ts
Pape, F.L.F., J.W. Mitchell, and W.A. Beckman, z variable ( z = e )

-8-

You might also like