EST Catalog  Intelligent Initiating Devices

Intelligent Heat
Detector
SIGA-HRD

S853

Overview Standard Features


The SIGA-HRD is an intelligent fixed temperature/rate-of-rise fire Note: Some features described here may not be supported by
detector. It monitors the temperature of the surrounding air and all control systems. Check your control panel’s Installation and
analyzes the data from the sensor to determine whether to initiate Operation Guide for details.
an alarm. The rate-of-rise heat function quickly detects a fast,
• Next Generation Heat Sensing Technology
flaming fire. The fixed-temperature heat function detects fire when
the air temperature near the detector exceeds the alarm point. • 15 °F (9 °C) per minute rate-of-rise alarm point
The SIGA-HRD brings advanced sensing technology to a practi- • 135 °F (57 °C) fixed temperature alarm point
cal design that increases efficiency, saves installation time, cuts • Uses existing wiring
costs, and extends property protection capabilities. Continuous
self-diagnostics ensures reliability over the long-haul, while the lat- • Automatic device mapping
est thermister technology makes these detectors ideal whereever • Ground fault detection by module
dependable heat detection is required.
• Up to 250 devices per loop
• Non-volatile memory
• Electronic addressing
• Bicolor (green/red) status LED
• Standard, relay, fault isolator, and audible mounting bases
• 50 foot (15.2 meter) spacing

Page 1 of 4 D ATA S H E E T 85001-0647


Not to be used for installation purposes. Issue 1
Application Accessories
The SIGA-HRD combination fixed temperature/rate-of-rise heat Detector mounting bases have wiring terminals that are acces-
sible from the “room-side” after mounting the base to the electrical
detector provides a 15 °F (9 °C) per minute rate-of-rise heat
box. The bases mount to North American 1-gang boxes and to
sensor for the detection of fast-developing fires, as well as a
3½ inch or 4 inch octagon boxes, 1½ inches (38 mm) deep. They
135°F (57°C) fixed temperature sensor for slow building-fires. The also mount to European BESA and 1-gang boxes with 60.3 mm
heat sensor monitors the temperature of the air and determines fixing centers. The SIGA-SB4, SIGA-RB4, and SIGA-IB4 mount to
whether an alarm should be initiated. North American 4 inch sq. electrical boxes in addition to the above
boxes. They include the SIGA-TS4 Trim Skirt, which is used to
cover the “mounting ears” on the base. The SIGA-AB4G mounts
to a 4 inch square box only.
Compatibility
The SIGA-HRD detector is compatible only with the Signature
Loop Controller.

SIGA-AB4G/T SIGA-SB SIGA-IB SIGA-RB SIGA-LED


Installation Audible Base Standard Base Isolator Base Relay Base Remote LED

Signature Series detectors mount Remote LED SIGA-LED - The remote LED connects to the
to North American 1-gang boxes, SIGA-SB or SIGA-SB4 Standard Base only. It features a North
3-1/2 inch or 4 inch octagon American size 1-gang plastic faceplate with a white finish and red
boxes, and to 4 inch square elec- Self-locking tab
alarm LED.
trical boxes 1-1/2 inches (38 mm) SIGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also
deep. They mount to European be ordered separately to use with the other bases to help hide
BESA and 1-gang boxes with 60.3 surface imperfections not covered by the smaller bases.
mm fixing centers. See mounting LED Indicator
Sounder Bases - Signature Series sounder bases are designed
base installation and wiring for
for use where localized or group alarm signaling is required.
more information.
• SIGA-AB4G bases provide sounder capability to Signature
Series to heat and smoke detectors. They are not intended
for use with combination carbon monoxide detectors in Fire-
Sensing and reporting technology plus-CO mode.
The microprocessor in each detector provides additional benefits - • SIGA-AB4GT bases provide sounder capability to Signature
Self-diagnostics and History Log, Automatic Device Mapping, and Series smoke and heat detectors, as well as carbon monox-
Fast, Stable Communication. ide detectors when used with a SIGA-TCDR Temporal Pattern
Generator.
Self-diagnostics and History Log - Each Signature Series • SIGA-AB4G-LF bases provide 520 Hz low frequency
detector constantly runs self-checks to provide important mainte- sounder capability to Signature Series smoke and heat detec-
nance information. The results of the self-check are automatically tors, as well as carbon monoxide detectors when used with a
updated and permanently stored in the detector’s non-volatile SIGA-TCDR Temporal Pattern Generator. The SIGA-AB4G-LF
memory. is suitable for applications requiring low frequency audible
tones.
Automatic Device Mapping - The loop controller learns where
each device’s serial number address is installed relative to other
devices on the circuit. The mapping feature provides supervision
of each device’s installed location to prevent a detector from being Warnings & Cautions
reinstalled (after cleaning etc.) in a different location from where it • This detector does not operate without electrical power. As
was originally. fires frequently cause power interruption, discuss further safe-
Fast Stable Communication - On-board intelligence means less guards with the local fire protection specialist.
information needs to be sent between the detector and the loop • This detector does not sense fires in areas where heat cannot
controller. Other than regular supervisory polling response, the reach the detector. Heat from fires in walls, roofs, or on the
detector only needs to communicate with the loop controller when opposite side of closed doors may not reach the detector.
it has something new to report. • This heat detector by itself does not provide life safety protec-
tion Use this detector with ionization and/or photoelectric
smoke detectors.
• This detector does not detect oxygen levels, smoke, toxic
gases, or flames. Use this device as part of a broad-based
life safety program which includes a variety of information
sources pertaining to heat and smoke levels, extinguishment
systems, visual and audible devices, and other safety mea-
sures.
• Independent studies indicate that heat detectors should only
be used when property protection alone is involved. Never
rely on heat detectors as the sole means of fire protection.

Page 2 of 4 D ATA S H E E T 85001-0647


Not to be used for installation purposes. Issue 1
Typical Wiring
The detector mounting bases accept #18 AWG (0.75mm2), #16 Relay Detector Base, SIGA-RB, SIGA-RB4
(1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm²) wire sizes. This base includes a relay. Nor-
Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred mally Open or Normally Closed
for ease of installation. operation is selected during in-
stallation. The dry contact is rated
for 1 amp (pilot duty) @ 30 Vdc.
Standard Detector Base, SIGA-SB, SIGA-SB4
The relay’s position is supervised
This is the basic mounting base Remote LED to avoid accidentally jarring it out
for EDWARDS Signature Series Max resistance of position. The SIGA-RB can be
detectors. The SIGA-LED Re- per wire
must not exceed
operated as a control relay if pro-
mote LED is supported by this 10 Ohms grammed to do so at the control
Base. panel. The relay base does not
Term Description
Term
1
Description
Not Used
support the SIGA-LED Remote 1 Normally Open
2 DATA IN/OUT (+) LED. CONTACT RATING 2 DATA IN/OUT (+)
1.0 Amp @ 30 VDC 3 Common
3 Not Used
(Pilot Duty) 4 DATA IN (-)
4 DATA IN (-)
DATA IN (-) 5 Not Used
4 Remote LED (-) DATA OUT (-)
6 Normally-Closed
5 Remote LED (+)
7 DATA OUT (-)
6 Not Used
7 DATA OUT (-) DATA IN (+) DATA OUT (+)
From Signature Controller To Next Device
or Previous Device

Audible Sounder Bases, Fire Mode


Isolator Detector Base, SIGA-IB, SIGA-IB4 AB4GT, AB4G, AB4G-LF sounder bases
This base includes a built-in line fault isolator for use on Class A
circuits. A detector must be installed for it to operate. The isolator
base does not support the SIGA-LED Remote LED. SIGA-AB4GT, SIGA-AB4G-LF:
SIGA-AB4G, Output Mode
The isolator operates as follows: SIGA-AB4G-LF: Jumper cuts Default = Fire
Volume Setting Cut/remove jumper for
- a short on the line causes all iso- Default = High Fire plus CO
lators to open within 23 msec Cut/remove
jumper for SIGA-AB4G:
- at 10 msec intervals, low dB Tone Setting
beginning on one side DATA- DATA- DATA+
Default = Temporal
of the Class A SIG+ SIG- OUT IN IN/OUT Cut/remove jumper for
Steady
circuit nearest the loop
controller, the isolators SIGA-AB4GT:
close to provide the Not Used
next isolator down the
line with power Term Description
1 Not Used 24 Vdc in
- - 24 Vdc out
- when the isolator next 2 DATA IN/OUT (+) From power supply
3 DATA IN (-) or previous base + + To next base or EOL relay
to the short closes, it reopens within 10 4 Not Used
msec. 5 Not Used -
6 DATA OUT (-) Data in - Data out
The process repeats beginning on the 7 Not Used From Signature Controller
+
to next Signature device
or previous device +
other side of the loop controller.

Page 3 of 4 D ATA S H E E T 85001-0647


Not to be used for installation purposes. Issue 1
Specifications
Operating voltage 15.20 to 19.95 VDC
Normal operating current 32 µA
Alarm current 32 µA
Contact us... Vibration level 10 to 35 Hz, with an amplitude of 0.01 in.
Email: edwards.fire@fs.utc.com Rate-of-rise rating 15°F/min (8°C/min)
Web: www.est-fire.com Fixed temperature rating 135°F (57.2°C). Actual alarm point 129 to 141°F (53.9 to 60.6°C).
EST is an EDWARDS brand. Maximum spacing 50 ft. (15.2 m) centers
1016 Corporate Park Drive
Compatible bases See Ordering Information
Mebane, NC 27302 Compatible detector testers Testifire 1000, Testifire 2000
Operating environment 32 to 100°F (0 to 38°C), 0 to 93% RH, noncondensing
In Canada, contact Chubb Edwards...
Email: inquiries@chubbedwards.com Storage temperature -4 to 140°F (-20 to 60°C)
Web: www.chubbedwards.com Agency Listings CAN/ULC-S530, UL 521
© 2016 UTC Fire & Security Americas
Corporation, Inc. All rights reserved.
Specifications subject to change
Ordering Information
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
Catalog Ship Wt.
Description
United Technologies Corporation. Number lbs (kg)
SIGA-HRD Intelligent fixed temperature/Rate-of-rise heat detector 0.4 (0.16)

Compatible Bases
SIGA-SB Detector Mounting Base - Standard
SIGA-SB4 4-inch Detector Mounting Base c/w Trim Skirt
SIGA-RB Detector Mounting Base w/Relay
SIGA-RB4 4-inch Detector Mounting Base w/Relay, c/w Trim Skirt 0.2 (.09)
SIGA-IB Detector Mounting Base w/Fault Isolator
SIGA-IB4 4-inch Detector Mounting Base w/ Fault Isolator, c/w Trim Skirt
SIGA-LED Remote Alarm LED (not for EN54 applications)
SIGA-AB4G Audible (Sounder) Base for Fire Detectors 0.3 (0.15)
SIGA-AB4G-LF Low Frequency Audible (Sounder) Base for CO and Fire Detectors 0.3 (0.15)
SIGA-AB4GT Audible (Sounder) Base for CO and Fire Detectors 0.3 (0.15)
SIGA-TS4 Trim Skirt (supplied with 4-inch bases) 0.1 (.04)
SIGA-DMP Detector Mounting Plate 3.0 (1.4)
SIGA-RTA Detector Removal Tool
SIGA-VA Detector Cleaning Tool

06-03-16

Page 4 of 4 D ATA S H E E T 85001-0647


Not to be used for installation purposes. Issue 1
UQGS.S1122 - Heat-automatic Fire Detectors Page 1 of 2

UQGS.S1122
Heat-automatic Fire Detectors
Page Bottom

Heat-automatic Fire Detectors

See General Information for Heat-automatic Fire Detectors

EDWARDS, A DIV OF UTC FIRE & SECURITY AMERICAS CORPORATION, INC. S1122
8985 TOWN CENTER PKWY
BRADENTON, FL 34202 USA

Heat/Carbon Monoxide detector, addressable intelligent type, Model(s) SIGA-HCD

Heat detectors, Model(s) Rated 135 F Model 73340, Rated 135F Model 73342, Rated 194 F Model 73341, Rated 194 F Model 73343,
ZC20FTU-3,SC20FTU-3,MC20FTU-3

Spacing (Ft)

Model Compatibility Contact Temp Smooth to Wall or


No. Type Restrictions Arrangement Range (°F) Ceiling Partition

GSA-HFS, SIGA-HFS FT D5 - 135 70 35

GSA-HRS, SIGA-HRS FT/ROR D5 - 135 70 35

GSA-HRSIC, SIGA-HRSIC, JTY-ZOM-SIGAHRSI

FT/ROR D5 - 135 70 35

JTW-ZDM-S2HFSI FT D5 - 135 50 25

JTW-ZOM-S2HRSI FT/ROR D5 - 135 50 25

SIGA-DHI, JTW-ZDM-SIGA-DHC

FT/ROR D5 - 135 50 25

SIGA-HFD FT D5 - 135 50 25

SIGA-HRD FT/ROR D5 - 135 50 25

SIGA2-HCOS FT/ROR D5 - 135 50 25

SIGA2-HFS FT D5 - 135 50 25

SIGA2-HRS FT/ROR D5 - 135 50 25

SIGA2-PHCOS, SIGA2-HCOS

FT D5 - 135 50 25

ZC20RRU-3,SC20RRU-3,MC20RRU-3

FT/ROR None - - - -

D5 - For use only with Listed control units with which compatibility was determined by test.

FT - Fixed temperature

FT/ROR - Fixed temperature/rate of rise combination

Trademark and/or Tradename: ""E" in a Shield" , "Dukane" , "ESL" , "Edwards Co Inc" , "Edwards Company Inc." , "Edwards System
Technology" , "FAST" , "Fire Alarm Systems Technology" , "FireworX" , "G.S. Building Systems Corp." , "GE Security" , "GE Security Inc" , "GS" ,

"GSBS" , "Interlogix Inc" , "KIDDE" , "Mirtone" , "Sentrol" , "Vigilant" , "Walter Kidde Portable Equipment INC." , "Ziton" , ,

, , , , ,

Last Updated on 2016-04-29

Questions? Print this page Terms of Use Page Top

© 2016 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name... 22/9/2016
UQGS.S1122 - Heat-automatic Fire Detectors Page 2 of 2

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2016 UL LLC".