You are on page 1of 3

Co nfig PLC Co m 2 a s Mo d b us-RT U ,9600,8,N ,1

Se t DT M d ip switch to co nfig Mo d b us-R T U ,9600,8,N ,1


d ip 1: ON , d ip 2: OFF, d ip 3: OFF, d ip 4: ON , d ip 5: ON, d ip 6: OFF, d ip 7: ON , d ip 8: OFF

0 M1002
MOV H81 D1120

ON only fo COM2(RS-48
r 1 scan a 5) Communi
fter RUN. cation pro
Initial pu tocol

SET M1120

COM2(RS-48
5) Communi
cation pro
tocol hold

SET M1143

1.COM2(RS-
485) ASCII
/ RTU mode
selections
Co nfig D T M Sta tio n N um b e r to PLC, fro m 2~ 11
Se t DT M kno b switch fro m 2~ B

8 M1002
SET M1356

ON only fo Enable sta


r 1 scan a tion numbe
fter RUN. r selectio
Initial pu n function

RST M1353

Enable 32
slave unit
s linkage
and up to

MOV K2 D1900

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K3 D1901

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K4 D1902

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K5 D1903

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K6 D1904

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K7 D1905

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K8 D1906

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K9 D1907

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati

MOV K10 D1908

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati
MOV K11 D1909

SLAVE ID#
14 PLC LIN
K reads. C
ommunicati
D T MR 04 Ad d re ss Se tting s
R e a d fro m Ad d re ss H x268(PV va lue , unit: 0.1) , Le ng th = 4
D T M1 PV va lue = D 1480~ 1483
D T M2 PV va lue = D 1512~ 1515
D T M3 PV va lue = D 1544~ 1547
D T M4 PV va lue = D 1576~ 1579
D T M5 PV va lue = D 1608~ 1611
D T M6 PV va lue = D 1640~ 1643
D T M7 PV va lue = D 1672~ 1675
D T M8 PV va lue = D 1704~ 1707
D T M9 PV va lue = D 1736~ 1739

D T M10 PV va lue = D 1768~ 1771


//////////////////////////////////////////////////////////////

W rite fro m Ad d re ss H x000 (SV va lue , unit: 0.1), Le ng th = 4


D T M1 SV va lue = D 1496~ 1499
D T M2 SV va lue = D 1528~ 1531
D T M3 SV va lue = D 1560~ 1563
D T M4 SV va lue = D 1592~ 1595
D T M5 SV va lue = D 1624~ 1627
D T M6 SV va lue = D 1656~ 1659
D T M7 SV va lue = D 1688~ 1691

D T M8 SV va lue = D 1720~ 1723


D T M9 SV va lue = D 1752~ 1755
D T M10 SV va lue = D 1784~ 1787
//////////////////////////////////////////////////////////////

63 M1002
FMOV H268 D1355 K10

ON only fo Starting r
r 1 scan a eference f
fter RUN. or Master
Initial pu to read fr

FMOV K4 D1434 K10

Data lengt
h to be re
ad on Salv
e ID# 1

FMOV H0 D1415 K10

Starting r
eference f
or Master
to write i

FMOV K4 D1450 K10

Data lengt
h to be wr
itten on S
lave ID# 1
Ena b le / D isa b le the Sla ve ID #
fo r e xa mp le , if M1360 = OFF, ID 1 is D isa b le d

92 M1002
SET M1355

ON only fo Selecting
r 1 scan a Slave link
fter RUN. ing mode i
Initial pu n EASY PLC

SET M1360

Slave ID# 1
status on
PLC Link
network

SET M1361

Slave ID# 2
status on
PLC Link
network

SET M1362

Slave ID# 3
status on
PLC Link
network

SET M1363

Slave ID# 4
status on
PLC Link
network
SET M1364

Slave ID# 5
status on
PLC Link
network

SET M1365

Slave ID# 6
status on
PLC Link
network

SET M1366

Slave ID# 7
status on
PLC Link
network

SET M1367

Slave ID# 8
status on
PLC Link
network

SET M1368

Slave ID# 9
status on
PLC Link
network

SET M1369

Slave ID# 1
0 status o
n PLC Link
network
Sta rt Mo d b us Link
For Mo nito ring
M1392= Erro r Fla g fo r ID 1(ON = Erro r, OFF = N o rma l)

104 M1002
SET M1351

ON only fo Enable aut


r 1 scan a o mode on
fter RUN. PLC Link
Initial pu

SET M1350

Enable the
function
of PLC Lin
k
107

END