You are on page 1of 1

DATE : 06-08-2022

MYCOM SCREW COMPRESSOR PERFORMANCE SINGLE STAGE (BOOSTER)

Title: Low stage compressor High stage compressor


MODEL : N250VM*-LB x2 MODEL : N200VS*-L MODEL : N200VL*-L
REFRIGERANT : AMMONIA REFRIGERANT : AMMONIA REFRIGERANT : AMMONIA
VFD
RECOMMENDED PORT : L RECOMMENDED PORT : L RECOMMENDED PORT : L

COMPRESSION RATIO : [-] 4.76 COMPRESSION RATIO : [-] 4.56 COMPRESSION RATIO : [-] 4.56

CAPACITY : [kW] 501.6 CAPACITY : [kW] 728.1 CAPACITY : [kW] 1108.0


CAPACITY : [TR] 142.6 CAPACITY : [TR] 207.0 CAPACITY : [TR] 315.0
ABSORBED POWER : [kW] 127.1 ABSORBED POWER : [kW] 198.3 ABSORBED POWER : [kW] 285.3

DRIVE SHAFT SPEED : [min-1] 3550 DRIVE SHAFT SPEED : [min-1] 3550 DRIVE SHAFT SPEED : [min-1] 3550
COMPRESSOR SPEED : [min-1] 3550 COMPRESSOR SPEED : [min-1] 3550 COMPRESSOR SPEED : [min-1] 3550
INDICATOR POSITION : [%] 100 INDICATOR POSITION : [%] 100 INDICATOR POSITION : [%] 100
CONDENSING TEMP. : [degC] -6.00 CONDENSING TEMP. : [degC] 40.0 CONDENSING TEMP. : [degC] 40.0
EVAPORATIVE TEMP. : [degC] -40.0 EVAPORATIVE TEMP. : [degC] -6.00 EVAPORATIVE TEMP. : [degC] -6.00
SUCTION SUPERHEAT : [degC] 5.00 SUCTION SUPERHEAT : [degC] 5.00 SUCTION SUPERHEAT : [degC] 5.00
LIQUID SUBCOOLING : [degC] 5.00 LIQUID SUBCOOLING : [degC] 5.00 LIQUID SUBCOOLING : [degC] 5.00
SUCTION TEMP. : [degC] -35.0 SUCTION TEMP. : [degC] -1.00 SUCTION TEMP. : [degC] -1.00
OIL SUPPLY TEMP. : [degC] 50.0 OIL SUPPLY TEMP. : [degC] 50.0 OIL SUPPLY TEMP. : [degC] 50.0
SUCTION PRESS. : [MPaA] 0.072 SUCTION PRESS. : [MPaA] 0.341 SUCTION PRESS. : [MPaA] 0.341
DISCHARGE PRESS. : [MPaA] 0.341 DISCHARGE PRESS. : [MPaA] 1.55 `` DISCHARGE PRESS. : [MPaA] 1.55
OIL SUPPLY PRESS. : [MPaA] 0.726 OIL SUPPLY PRESS. : [MPaA] 1.94 OIL SUPPLY PRESS. : [MPaA] 1.94
SUCTION PRES. DROP : [MPa] 0.000 SUCTION PRES. DROP : [MPa] 0.000 SUCTION PRES. DROP : [MPa] 0.000
DISCHARGE PRES. DROP : [MPa] 0.000 DISCHARGE PRES. DROP : [MPa] 0.000 DISCHARGE PRES. DROP : [MPa] 0.000

SWEPT VOLUME : [m3/h] 2380 SWEPT VOLUME : [m3/h] 975 SWEPT VOLUME : [m3/h] 1460
LOAD(SUCTION VOL. FLOW RATE) : [%] 100 LOAD(SUCTION VOL. FLOW RATE) : [%] 100 LOAD(SUCTION VOL. FLOW RATE) : [%] 100
DISCHARGE TEMP. : [degC] 61.5 DISCHARGE TEMP. : [degC] 79.4 DISCHARGE TEMP. : [degC] 85.2
REFRIG. FLOW RATE SUC. : [m3/h] 2280 REFRIG. FLOW RATE SUC. : [m3/h] 891 REFRIG. FLOW RATE SUC. : [m3/h] 1360
REFRIG. FLOW RATE DIS. : [m3/h] 676 REFRIG. FLOW RATE DIS. : [m3/h] 241 REFRIG. FLOW RATE DIS. : [m3/h] 376
REFRIG. FLOW RATE SUC. : [kg/h] 1435 REFRIG. FLOW RATE SUC. : [kg/h] 2408 REFRIG. FLOW RATE SUC. : [kg/h] 3665
REFRIG. FLOW RATE DIS. : [kg/h] 1435 REFRIG. FLOW RATE DIS. : [kg/h] 2408 REFRIG. FLOW RATE DIS. : [kg/h] 3665
INJECT. OIL FLOW RATE : [L/min] 70.2 INJECT. OIL FLOW RATE : [L/min] 55.8 INJECT. OIL FLOW RATE : [L/min] 55.8
LUB. OIL FLOW RATE : [L/min] 66.5 LUB. OIL FLOW RATE : [L/min] 60.4 LUB. OIL FLOW RATE : [L/min] 60.4
F.SIDE OIL FLOW RATE : [L/min] 12.2 F.SIDE OIL FLOW RATE : [L/min] 11.0 F.SIDE OIL FLOW RATE : [L/min] 11.0
*TOTAL* OIL FLOW RATE : [L/min] 149 *TOTAL* OIL FLOW RATE : [L/min] 127 *TOTAL* OIL FLOW RATE : [L/min] 127
OIL HEAT REJECTION : [kW] 48.3 OIL HEAT REJECTION : [kW] 105.7 OIL HEAT REJECTION : [kW] 126.6
OIL SPEC HT : [J/kgK] 1930 OIL SPEC HT : [J/kgK] 1930 OIL SPEC HT : [J/kgK] 1930
OIL DENSITY : [kg/m3] 880 OIL DENSITY : [kg/m3] 880 OIL DENSITY : [kg/m3] 880

COP : [-] 3.95 COP : [-] 3.67 COP : [-] 3.88

--- SUPER HEAT is NOT counted in refrigeration capacity --- --- SUPER HEAT is NOT counted in refrigeration capacity --- --- SUPER HEAT is NOT counted in refrigeration capacity ---

--- WITH THERMO-SIPHON OIL COOLER --- --- WITH THERMO-SIPHON OIL COOLER --- --- WITH THERMO-SIPHON OIL COOLER ---

--- Refrigeration oil is not soluble with refrigerant (mineral oil) --- --- Refrigeration oil is not soluble with refrigerant (mineral oil) --- --- Refrigeration oil is not soluble with refrigerant (mineral oil) ---

--- When choosing the motor set a safety factor of more than 10% for the brake power. --- --- When choosing the motor set a safety factor of more than 10% for the brake power. --- --- When choosing the motor set a safety factor of more than 10% for the brake power. ---

--- Please check carefully the operating range. --- --- Please check carefully the operating range. --- --- Please check carefully the operating range. ---
--- Reference temperature : Dew Point --- --- Reference temperature : Dew Point --- --- Reference temperature : Dew Point ---
! Can be used Unloader slide valve with the ditch type in this condition. ! Can be used Unloader slide valve with the ditch type in this condition. ! Can be used Unloader slide valve with the ditch type in this condition.
! All data herein is for reference only. ! All data herein is for reference only. ! All data herein is for reference only.
! Content is subject to change without notice. ! Content is subject to change without notice. ! Content is subject to change without notice.

*** MYCOMW26 compressor performance table is valid until the end of March, 2023. *** *** MYCOMW26 compressor performance table is valid until the end of March, 2023. *** *** MYCOMW26 compressor performance table is valid until the end of March, 2023. ***

SP
MYCOM SCREW COMPRESSOR PERFORMANCE 26
MAYEKAWA MFG. CO., LTD. * All data herein is for reference only.
MYCOMW 26EP * Content is subject to change without notice.

You might also like