Air-to-water heat pumps designed to produce hot water up to 60°C,

with air temp. up to 50°C and corrosive atmosphere.


Main components:
- multiple scroll compressors R410A with vapour injection
- high efficiency BPHE condenser
- electronic expansion valve with MOP
RAK.E/PC-B/ST/SP 180C6 - evaporating control through variable fans speed

SERIES RAK.E/PC-B/ST/SP
MODEL 180C6 R410A 400/3/50
Operating conditions Design Extreme
HEATING CAPACITY - rated gross value [kW] 264 346
Total engaged electrical power [kW] 87.7 84.3 (400-3-50)
Compressors engaged power [kW] 84.8 82.3
Fans engaged power [kW] 6.3 1.9
Engaged current [A] 176 166 (PF=0.90)
Condenser
Medium water
Fluid temperature IN [°C] 55.0 53.4
Fluid temperature OUT [°C] 60.0 60.0
Water flow [m3/h] 45.4 45.4
Pressure drop [kPa] 22 22
Fouling factor [m2°C/kW] 0.0180
Evaporating coils
Air DB temperature [°C] 20.0 50.0
RH [%] 80% 60%
Air flow [m3/h] 80000 24000
Coefficient Of Performances: Gross [kW/kW] 3.02 4.17
SOUND LEVELS
Sound pressure level Lp(A) 1m / 10m (1) [dB(A)] 72.0 59.0
Sound pressure spectrum 1m [Hz] 63 125 250 500
- octave band [dB(A)] 33.4 44.3 57.2 63.2
[Hz] 1000 2000 4000 8000
[dB(A)] 65.1 63.4 65.6 66.1
Sound power level Lw(A) - ISO 9614 [dB(A)] 92.0
Sound power spectrum [Hz] 63 125 250 500
- octave band [dB(A)] 51.1 64.2 77.2 83.2
[Hz] 1000 2000 4000 8000
[dB(A)] 85.1 83.4 85.6 86.1
DIMENSIONS
Length x Width x Height [mm] 3900 x 2000 x 1946
WEIGHT [kg] Shipping 2040 Operating 2245
WATER CONNECTIONS - condenser IN/OUT DN80

Compressor's envelope & main working conditions

X-axys <-> SST


(Saturated Suction Temp [°C])

Y-axys <-> SDT


(Saturated Discharge Temp [°C])

Operating onditions:
x: design
o: extreme

Commercial offer ref. FC9199 VIDA YACHT CLUB _ rev.2


List of selected options:
MC01 A/V spring mounts
Air-to-water heat pumps designed to produce hot water up to 60°C,
with air temp. up to 50°C and corrosive atmosphere.
Main components:
- multiple scroll compressors R410A with vapour injection
- high efficiency BPHE condenser
- electronic expansion valve with MOP
RAK.E/PC-B/ST/SP 180C6 - evaporating control through variable fans speed

SERIES RAK.E/PC-B/ST/SP
MODEL 180C6 R410A 400/3/50
COMPRESSOR Scroll compressors, optimized for use with R410A with vapour injection,
in even trio configuration

Quantity / Model [] 2x3 ZHI46K1P-TWD 183110


FLA / LRA (each compressor) / Start method [A] 37 168 DOL
Capacity control: Six steps (16-33-50-66-83-100%)
Suction service valve Common suction valve (1 per circuit)
Discharge shut-off valve Yes
Discharge check valve Built-in low-pressure drop
Soundproofing box Integral box for compressors
CONDENSER High efficiency brazed plate heat exchanger

Materials Plates: AISI 316 Brazing: Copper


Dimensions [mm] 739 x 322 x 664
Water box No (optional)
Design pressure: fluid (tubes side) / refr. (shell side) [barg] 32.0 32.0
Water side volume [dm3] 59
Insulation PEN/PEAL 19mm (l≤0.038W/m/K)
AIR COILS & FANS Tube & fins air coils Cu-Al (Blue fins).
AC axial fans with phase-cut speed regulator for evaporating pressure
control at high ambient temp.

No.coils / No.of rows / Fin spacing [ ] / [ ] / [mm] 2 3 2.1


No.of fans / Diameter [ ] / [mm] 4 800
Air volume [m3/h] 80000
Extreme operating air conditions: air DB temp. / RH [°C] / [%] 50 60%
FLA (each fan) [A] 3.9
REFRIGERANT EQUIPMENT & INSTRUMENTS R410A 2 circuits 33 kg
Lamination device(s) type Electronic expansion valve
Refrigerant flow control loop Superheat PID controller with MOP function
Drier filter(s) Yes
Pressure switches w/manual reset HP: Yes LP: Yes
Pressure gauges HP: Yes LP: Yes
Pressure transducers HP: 4-20mA LP: 4-20mA
Temperature probes (NTC 10kOhm_25°C) Air: Yes Cond: IN & OUT Liq.refr.: No
Relief valves HP: Double LP: Double
Mechanical flow switch Optional
ELECTRICAL DATA
Electrical panel IP54
Power supply [V-Ph-Hz] 400-3-60
Unit max operating current MOC [A] 242
Unit max starting current [A] 373
Aux voltage levels (internal trafo) [V] 230 / 24Vac
Main switch Manual switch disconnector 400A
Compressor protecting device Switch-disconnector with fuses
Air-to-water heat pumps designed to produce hot water up to 60°C,
with air temp. up to 50°C and corrosive atmosphere.
Main components:
- multiple scroll compressors R410A with vapour injection
- high efficiency BPHE condenser
- electronic expansion valve with MOP
RAK.E/PC-B/ST/SP 180C6 - evaporating control through variable fans speed

SERIES RAK.E/PC-B/ST/SP
MODEL 180C6 R410A 400/3/50