NetCol8000-A In-room Air Cooled Smart Cooling Product Maintenance Guide Website:

http://support.huawei.com
Issue: 01 http://enterprise.huawei.com
Date: 2015-03-18 Copyright © Huawei Technologies Co., Ltd. 2015. All Rights Reserved.

Component Item Troubleshooting Monthly Quarterly Yearly


Filters Check whether the air filter is dust, damaged, and deformed. It is recommended that you replace the filter once every 6 months. ▽
Check the four compressor fixing screws are firm. Tighten the screws. ▽
If a large amount of foam comes out in a long time, the overheating degree is too small
Compressor Check that the oil sight glass has no many air bubbles and make sure watch the oil level. ◎
and needs to be increased. Contact Huawei technical support.
Check that the wiring terminals are secured. Tighten the terminals. ▽
Check that the sight glass is almost green, or not totally turns yellow. If the sight glass has turned yellow, refrigerant must be re-injected. ▽
If there are oil stains, check whether the air suction and exhaust pressure of the
Wear working gloves and touch the compressor angle valve, needle valve, and soldering points in the compressor is within the normal ranges (For the proper ranges of air suction and

cooling circuit to check whether there are oil stains. exhaust pressure, see section 4 Powering on the Equipment). If the water inlet pipe or
Pipeline drainpipe leaks, contact Huawei technical support.
Close the water inlet valve and service the leaking sections. If the thermal insulation
Check that no water exists under the water pipe or on the thermal insulation foam. ▽
foam is damaged or missing, rewrap the thermal insulation foam.
The thermal insulation foam is properly wrapped around the pipe. Replace the thermal insulation foam if it is damaged or missing. ▽
Check that the protective net cover is not deformed, and blades are intact. Replace the fans. ▽
Indoor fans
Check whether the fan generates abnormal noise, such as metal friction or harsh sound. Clean the foreign matters, and make sure that the fan is fixed properly. ▽
Check that T/H sensors in the smart cooling productand aisles are securely installed. Secure the sensors. ▽
T/H sensor If the temperature error is greater than 1ºC or humidity error is greater than 5%, the T/H
Use a precision T/H sensor to calibrate the T/H sensors inside and outside the cabinet. ●
sensor must be calibrated or replaced.
On the main screen, choose Start on the main menu, and choose Maint > Diagnostic Mode > Enter.
Electrical Start the electric heater. Measure the three phases of the electric heater circuit breaker by using a clamp ◎
Replace the electrical heaters.
heaters meter. Confirm that three-phase currents are present, and current deviation does not exceed 20%.
Check for corrosion on the heater surface. ◎
Water sensor Check that the water sensor is securely installed and its probe is appropriately located.
Replace the water sensor, secure the sensors. ◎
(optional)
Tap Common Functions > Status on the home screen to enter the Status screen, query operating status
Monitor of the smart cooling product system, including the compressor, indoor fan, outdoor fan, heater, infrared N/A ◎
humidifier, water supply valve, remote dry contact, and element management system (EMS).
On the main screen, choose Start on the main menu, and choose Maint > Diagnostic Mode > Enter.
1. Check that the water inlet valve is open.
Start the humidifier. Measure the three phases of the humidifier circuit breaker by using a clamp meter. ◎
2. Disconnect the humidifier water injection hose and dredge it.
Infrared Confirm that three-phase currents are present, and current deviation does not exceed 20%.
humidifier If water can only be injected to less than 1/3 of the humidifier, check whether there are
Check that water can be smoothly injected. ◎
blockages.
Check that the water pan drains water properly. Close the main humidifier water inlet. Clean the foreign matters in the water pan. ◎
Evaporator The evaporator fins are not pushed down. Use a fin brush to organize the fins that are pushed down. ●
Soldering point
Check that soldering points and needle valves do not leak using soapy water or check that they are free
and needle If leaking points are found, retrieve the refrigerant and weld the leaking points again. ●
from oil stains.
valve

Note:
If you have difficult in troubleshooting, contact Huawei technical support.
Compressor oil sight glass
Water sensor
You can view the chilled oil
If the two terminals of the water sensor are in contact with water or status from the oil sight glass
other conductive liquid, the two terminals are short-circuited, and of the compressor. Figure on
the main control board generates an alarm after detecting the the right show the normal and
signal. During the maintenance, check that the two detection plates abnormal chilled oil states.
are free from corrosion, foreign matter, and connection in between. (1) Water sensor detection plats