PART LOAD POINTS

Point Speed Torque Efficiency Motor loss Drive loss Relative Loss Absolute Loss

1 10 % 25 % 87.2 % 14 W 96 W 0.37 % 111 W

2 10 % 50 % 89.8 % 12 W 158 W 0.57 % 170 W

3 10 % 100 % 87.1 % 14 W 430 W 1.48 % 444 W

4 25 % 25 % 94.5 % 12 W 97 W 0.36 % 109 W

5 25 % 50 % 95.3 % 9W 175 W 0.61 % 184 W

6 25 % 100 % 94.2 % 11 W 451 W 1.54 % 462 W

7 50 % 25 % 97.2 % 10 W 99 W 0.36 % 109 W

8 50 % 50 % 97.3 % 7W 203 W 0.70 % 210 W

9 50 % 100 % 96.9 % 8W 477 W 1.61 % 484 W

10 90 % 25 % 98.3 % 12 W 102 W 0.38 % 114 W

Page 1/4
11 90 % 50 % 98.1 % 8W 247 W 0.85 % 256 W

12 90 % 100 % 97.6 % 6W 655 W 2.20 % 661 W

13 100 % 25 % 98.5 % 13 W 103 W 0.39 % 116 W

14 100 % 50 % 98.2 % 9W 259 W 0.89 % 268 W

15 100 % 100 % 97.5 % 6W 769 W 2.58 % 775 W

Relative Loss Absolute Loss

Standby loss 0.08 % 25 W

Page 2/4
Efficiency Summary
Motor
Designation: 225 RP4
Manufacturer: NORD
(for detailed efficiency information, contact motor manufacturer)
Drive
Series: VLT® HVAC Drive FC 102
Type code: FC-102P30KT2E20H2

System efficiency (PDS)


The system, also called the Power Drive System (PDS)
consist of a CDM (Complete Drive Module) and a motor.
The IES classification is determined by adding the losses
of the CDM and the losses of the motor at the operating
point 100% speed and 100% torque.

System efficiency determined according to EN 50598 - 2 and IEC


61800-9

Drive efficiency (CDM)


The complete drive module CDM IE classification is based
on drive losses. This includes EMC filters, braking
choppers etc. The loss determination is based on factory
setting with e.g default switching etc. The classification is
taken at 90% frequency and 100% current.

Drive efficiency determined according to EN 50598 - 2 and IEC 61800-9

Motor efficiency
The motor efficiency for direct on-line (DOL) motors is
calculated as defined in IEC 60034-30-1. The IE
classification for motors is defined in the operating point
at 100% speed and 100% torque.

Motor efficiency determined according to IEC 60034-30-1

Page 3/4
DRIVE DATA

Manufacturer Danfoss A/S, Nordborgvej 81, 6430 Nordborg, Denmark. CVR


20165715

Series VLT® HVAC Drive FC 102

Type code FC-102P30KT2E20H2

Apparent output power 41.4 kVA

Rated power 30 kW

Nominal current 115 A

Maximum operation temperature 45 °C

Nominal frequency 50 Hz

Voltage 3x 200 - 240 VAC

MOTOR DATA

Name NORD 225 RP/4 220/380V 60Hz 30 kW IE3

Manufacturer NORD

Designation 225 RP4

Technology IM

Efficiency class IE3

Apparent output power 30 kW

Nominal voltage 220 V

Nominal current 103.5 A

Nominal cos phi 0.81 phi

Nominal frequency 60 Hz

Nominal speed 1785 RPM

Poles 4

Motor loss 6.2 W

Motor part load efficiency based on standardized part load efficiency points

The compilation of information in this certificate (the "Information") relies upon the accuracy of the data entered by the user of MyDrive® ecoSmart™ and of the actual operating
and environmental conditions. Thus, the Information can be used as a guide for energy efficiency of a drive system only. The Information cannot substitute technical advice, are
not promises for energy savings and should not be relied on as accurate data or analyses. The Information is provided “AS IS” without warranty of any kind and does not
constitute a guarantee that the information is complete, current, or correct, and Danfoss accepts no responsibility for unsuitable or inaccurate material that may be
encountered. The use of this report does not relieve the user of any obligation or duty that might arise under any legislation covering the activities to which this document has
been or is to be applied.

Created on 20/8/2022 using MyDrive® ecoSmart™ © Copyright Danfoss Page 4/4