Customer: xxxxxx

xxxxxx
Project:

Station: xxxxx

Line Name: XXXX LINE-1

Sending End: XXXX

Receiving End: XXXX

Voltage Level: 132kV

Current Ratio of CT: = 800/1

XXXXX SUBSTATION
3 Phase Fault Level = 6000 MVA
X/R Ratio at above Voltage Level = 5.71

XXXXX SUBSTATION
3 Phase Fault Level = 6000 MVA
X/R Ratio at above Voltage Level = 5.71

Zone Timings for Z1, Z2, Z3: = Z1=0.0ms , Z2=0.35ms , Z3=0.5ms , Z4=0.8ms

Teleprotection type (PUTT/POTT) PUTT PUTT

Protected Line Parameters:

Line Length = 20.84 Km


Maximum transmittable power = 243.87 MVA
Positive sequence resistance (RL1) = 0.0697 ohm\km
Positive sequence reactance (XL1) = 0.398 ohm\km
Zero sequence resistance (RL0) = 0.281 ohm\km
Zero sequence reactance (XL0) = 1.29 ohm\km
Service capacitance of the line PU Length = XX nF/Km

In Case of Double Circuit Parameters:

Zero Sequence Mutual Impedance Data(Rom & Xom)


Rom=0.2810 , Xom= 0.8030

Shortest (Lowest impedence) adjacent line at XXXXXXX substation

Line Length = 7 Km
Positive sequence resistance (RL1) = 0.0697 ohm\km
Positive sequence reactance (XL1) = 0.398 ohm\km
Zero sequence resistance (RL0) = 0.281 ohm\km
Zero sequence reactance (XL0) = 1.29 ohm\km

Longest (Highest impedence) adjacent line at XXXXXXX substation

Line Length = 33 Km
Positive sequence resistance (RL1) = 0.0697 ohm\km
Positive sequence reactance (XL1) = 0.398 ohm\km
Zero sequence resistance (RL0) = 0.281 ohm\km
Zero sequence reactance (XL0) = 1.29 ohm\km

Remote End Transformer Data: Transformers at XXXXXXX substation

MVA rating = 160 MVA


Z,impedance (in pu) = 11.3% in pu
X/R ratio = 5.71
Number of Transfomers operating in parallel = 3 T1||T2

Tower Footing Resistance:

Tower footing resistence = 20

Over voltage protection timing:


Unrestricted
Setting for low set over voltage protection = 110 %
Time delay for low set over voltage protection = 5 msec
Setting for high set over voltage protection = 140 %
Time delay for high set over voltage protection = 0.1 msec

Unrestricted
Customer: xxxxxx

xxxxxx

Project:

Station: xxxxxx

FEEDER Name: XXXX TR-1

2. TRANSFORMER/REACTOR INPUT DETAILS

TRANSFORMER/REACTOR DETAILS

Transformer HV side Power MVA


Transformer LV side Power MVA
Transformer TV side Power MVA
Transformer % Impedance %
HV side voltage kV
LV side voltage kV
TV side voltage kV
HV side CT ratio A
LV side CT ratio A
TV side CT ratio A
HV NTRL CT Ratio A
LV NTRL CT Ratio A
TV NTRL CT Ratio A
HV NTRL CT Ratio A
LV NTRL CT Ratio A
TV NTRL CT Ratio A
VT Ratio V
Over Flux curve
Thermal curve
Vector Group
Tap changer Details
Total no of taps
Normal tap position
Tap changer Increasing %V
Tap changer decreasing %V

NER Value Ohm

(If Data sheet available please attache data sheet also)

FOR HIGH IMPEDANCE REF/DIFF/TEED


CT Details
Knee point Voltage of Phase CT
knee point Voltage of Neutral CT
Resistance Value of Phase CT
Resistance Value of Neutral CT
Length of cable from CT box to CRP (Phase side)
Length of cable from CT box to CRP (Neutral side)
Area of Cross section of the conductor
(For REF)
(For REF)
(For REF)
(For SEF)
(For SEF)
(For SEF)