You are on page 1of 152

ACCURA 2300S/2350-1P3FSC

Data Center Distribution Panel Digital Power Meter/


Single-Phase Three Feeder Power Measuring Module
Actually makes possible data center energy management

User Guide[English]
Revision 1.20 2019/02/15
Distribution Panel Digital Power Meter

Accura 2300S front view Accura 2300S rear view

Single-phase Three Feeder Power Measuring Module Special-Purpose Module

Accura 2350-1P3FSC-125A[Basic Module] Accura 2350-GAS Accura 2350-DO

Accura 2350-1P3FSC-125A-DIZCT[Option Module] Accura 2350-GW Accura 2350-IDC

Accura 2350-1P3FSC-60A[Basic Module] Accura 2350-TEMP Accura 2350-VDC

Accura 2350-1P3FSC-60A-DIZCT[Option Module] Accura 2350-DCM-50V-80A Accura 2350-DCM-500V-80A


Accura 2300S/2350-1P3FSC User Guide Notice

Notice

Symbol
Caution
Indicates the presence of dangerous voltage which can cause severe injury or death to persons
if proper precautions are not followed.

Warning
Alerts the user to the presence of hazards which can cause somewhat injury to persons,
damage to property or damage to the device itself, if proper precautions are not followed.

Note
Indicates the user’s attention to installation, operating and maintenance instructions.

Indicates alternative voltage or current.

Indicates direct voltage or current.

Installation Considerations
Installation and operation of Accura 2300S/2350 should be performed only by qualified, competent
personnel that have appropriate training and experience with high voltage and current devices.

Caution
Failure to observe the following instructions may result in severe injury or death.

 During normal operation of Accura 2300S/2350, hazardous voltages are present on its terminal strips of
voltages input and power.
 Standard safety precautions should be followed while performing any installation or service work[removing
PT fuses, shorting CT secondaries, etc.].
 Do not access to terminal strips of Accura 2300S/2350 after installation.

Warning
Observe the following instructions, or permanent damage to the meter may occur.

 Do not apply Accura 2300S/2350 to voltages and currents that exceed Input ratings of PT and CT

ⓒ 2015 Rootech Inc. All Rights Reserved Page 3


Notice Accura 2300S/2350-1P3FSC User Guide

 To use device in the other way than specified by manufacturer can cause severe damage.
 Connect ground terminal to the earth ground to protect device from noise and surge.
 Terminal screw torque is as follows.

- Barrier-type voltage terminal: 1.35Nm[1.00 ft-lbf] max.


- Barrier-type digital inputs/digital output terminal: 0.90Nm[0.66 ft-lbf] max.

About Manual
Rootech Inc. reserves the right to make changes in the device specifications shown in this User Guide without
notice. Rootech Inc. advises customers to obtain the latest specifications of device before giving orders to
confirm that the information being relied on by the customer is up to date.

In the absence of written agreement to the contrary, Rootech Inc. assumes no liability for Rootech Inc.
applications assistance, customer’s system design, or infringement of patents or copyrights of third parties by
or arising from the use of devices described herein.

The information contained in this document is believed to be accurate at the time of publication, however,
Rootech Inc. assumes no responsibility for any errors which may appear here and reserves the right to make
changes without notice.

Limitation of Liability
Where applicable law allows and does not prohibit or restrict such limitation, Rootech, Inc’s liability for
anything relating to this product shall be limited to the price paid for the product.

Page 4 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Warranty

Warranty
For products and software that are sold or licensed by Rootech Inc. during the period from the date of receipt
by you until the present, Rootech warrants only to the original purchaser.

The purchased products shall be substantially free from material defects in material and workmanship by
Rootech for two years from the date receipt by you.

The software itself is provided “as is” without any warranty of any kind.

In order for the original purchaser to make a claim under the warranties described above, the original
purchaser must promptly contact Rootech headquarter. After receiving such notice, Rootech may either in
Rootech’s sole discretion, examine the product at the original purchaser’s site or issue shipping instructions to
the original purchaser to return the relevant product to Rootech for examination at the original purchaser’s
expense, transportation charges prepaid.

If after examining the product Rootech reasonably confirms that such examined product does not meet the
warranties, then the original purchaser’s sole remedy and Rootech’s sole obligation or liability shall be, at
Rootech’s option, to repair, replace or refund the price paid for that product.

Limitation of Warranty
The Warranty does not apply to uninterrupted or error-free operation of the Product or cover normal wear and
tear of the product or costs caused by the removal, installation, or troubleshooting of the customer's electrical
systems.

The warranty claims for defects caused by any of the following factors are not covered.
 Improper use(alteration, accident, misuse, abuse) or Failure to act in accordance with installation,
operation or maintenance instructions
 Unauthorized modifications, changes or attempted repairs
 Failure to comply with applicable safety standards & regulations
 Damages when transporting or storing
 Damages by force majeure, examples are(not necessarily limited): fire, flood, earthquakes, storm damage,
overvoltage & lightning
 If the original identify markings(trade-mark, serial number, etc) have been defaced, altered, or removed

Rootech shall not be liable for any other claim than a claim solely for the breach of one of the above
warranties that is made in accordance with the above described procedures- made by the original purchaser,

ⓒ 2015 Rootech Inc. All Rights Reserved Page 5


Warranty Accura 2300S/2350-1P3FSC User Guide

its employees, agents, or contractors for any loss, damage, or expense incurred due to, caused by, or related
to any purchased product.

Any technical assistance provided by Rootech's personnel or representatives in system design shall be deemed
to be a proposal and not a recommendation. The responsibility for determining the feasibility of such
proposals lies with the original purchaser and should be tested by the original purchaser.

It is the original purchaser’s responsibility to determine the suitability of any product and associated
documentation for its purposes. The original purchaser acknowledges that 100% "up" time is not realizable
because of possible hardware or software defects. The original purchaser recognizes that such defects and
failures may cause inaccuracies or malfunctions.

Only the terms expressed in these limited Warranties shall apply and no distributor, corporation or other entity,
individual or employee of Rootech or any other entity is authorized to amend, modify or extend the Warranties
in any way.

Standard Compliance

Process Control Equipment

E324900

MSIP-REM-RTE-ACCURA 2300S

QMS-1347 KAB-QC-09

Page 6 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Warranty

Revision History
The following version of Accura 2300S/2350-1P3FSC User Guide has been released.

Revision Date Description


Revision 1.20 2019. 02. 15 Initial release

ⓒ 2015 Rootech Inc. All Rights Reserved Page 7


Contents Accura 2300S/2350-1P3FSC User Guide

Contents
Chapter 1 Introduction....................................................................................................................................... 14
Overview ......................................................................................................................................................... 14
Application ...................................................................................................................................................... 17
Device Lineup .................................................................................................................................................. 18
Data Center Distribution Panel Digital Power Meter/Single-phase Three Feeder Power Measuring Module ..... 18
Distribution Panel Digital Power Meter/General Power Measuring Module .................................................... 18
Special-Purpose Module ............................................................................................................................ 18
Installation Example................................................................................................................................... 19
Features .................................................................................................................................................... 21
Chapter 2 Installation ........................................................................................................................................ 24
Environmental Conditions ................................................................................................................................. 24
Before you begin .............................................................................................................................................. 25
Meter Overview ......................................................................................................................................... 25
Components ............................................................................................................................................. 26
Dimension ................................................................................................................................................ 27
Installation ................................................................................................................................................ 29
Step 1: Mounting.............................................................................................................................................. 31
Accura 2300S Mounting ............................................................................................................................ 31
Accura 2350-1P3FSC Power Measuring Module Panel Installation ............................................................... 32
Step 2: Accura 2300S Wiring ............................................................................................................................ 37
Accura 2300S Voltage Connection ............................................................................................................. 37
Accura 2300S Digital Input/Output Wiring ................................................................................................. 42
Step 3: Accura 2350-1P3FSC Through-hole Wiring ........................................................................................... 45
Step 4: Accura 2350-1P3FSC-DIZCT Wiring ...................................................................................................... 49
Step 5: Accura 2300S/2350 Combination of Communication ............................................................................ 52
Step 6: Accura 2300S External Communication ................................................................................................. 54
Ethernet Communication ........................................................................................................................... 54
RS-485 Communication ............................................................................................................................ 56
Step 7: Accura 2300S Power Supply and Ground............................................................................................... 57
Power Supply............................................................................................................................................. 57
Ground Terminal ....................................................................................................................................... 57
Chapter 3 Accura 2350-1P3FSC Operation/Setup ................................................................................................. 58
Operation Mode ....................................................................................................................................... 58
Button Operation....................................................................................................................................... 58
Display Mode ............................................................................................................................................ 59
Setup Mode............................................................................................................................................... 60
Chapter 4 Accura 2300S Operation/Setup .......................................................................................................... 68

Page 8 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Contents

Device Configuration........................................................................................................................................ 68
Operation Mode ....................................................................................................................................... 68
LED Display............................................................................................................................................... 68
Button Operation....................................................................................................................................... 68
Display Mode ................................................................................................................................................... 70
Front Display ............................................................................................................................................. 70
Module ID Selection................................................................................................................................... 72
Display Full Screen .................................................................................................................................... 73
Voltage/Current/Power [V∙I∙P]..................................................................................................................... 74
Voltage/Frequency [V∙FREQ] ...................................................................................................................... 74
Current [I] ................................................................................................................................................. 75
Power/Power Factor [P∙PF] .......................................................................................................................... 75
Demand [DEMAND] .................................................................................................................................. 76
Active Energy [ENERGY] ............................................................................................................................. 76
Leakage Current [MODULE] ...................................................................................................................... 76
Ethernet Information [INFO] ....................................................................................................................... 77
Temperature/Time [ETC] ............................................................................................................................ 78
Setup Mode ..................................................................................................................................................... 79
Setup Full Screen ....................................................................................................................................... 80
Measurement [METER] ............................................................................................................................... 81
Event [EVENT]............................................................................................................................................ 86
RS-485 Communication [COMM] .............................................................................................................. 96
Ethernet Communication [NETWORK] ........................................................................................................ 98
Reset [RESET] ........................................................................................................................................... 101
Display [DISPLAY] .................................................................................................................................... 102
Module ID [MODULE] .............................................................................................................................. 105
Information [INFO] .................................................................................................................................. 109
Digital Input/Output [ETC] ....................................................................................................................... 110
Event Log Mode ............................................................................................................................................. 115
Start Event and End Event ........................................................................................................................ 115
Start Event Alarm Generation ................................................................................................................... 115
Start Event Alarm Clearing ....................................................................................................................... 115
Button Function ....................................................................................................................................... 116
Event Log Number ................................................................................................................................... 117
Event Time-stamp .................................................................................................................................... 117
Dip Event Log .......................................................................................................................................... 118
Swell Event Log ....................................................................................................................................... 118
Fuse Fail Event Log .................................................................................................................................. 119
Temperature Evnt Log .............................................................................................................................. 119

ⓒ 2015 Rootech Inc. All Rights Reserved Page 9


Contents Accura 2300S/2350-1P3FSC User Guide

Current Event Log .................................................................................................................................... 120


Leakage Current Event Log ...................................................................................................................... 120
Demand Current Event Log ...................................................................................................................... 121
1P3FSC DI Event Log ............................................................................................................................... 121
No Event Log .......................................................................................................................................... 121
Required Setup Step ....................................................................................................................................... 122
Step 1: Accura 2300S Connection, PT Rating ............................................................................................ 122
Step 2: Accura 2350 Communication ID Auto-Assignment and Update ..................................................... 123
Step 3: Accura 2300S Ethernet Setup........................................................................................................ 126
Chapter 5 Measurement Description ................................................................................................................. 127
General Measurement .................................................................................................................................... 127
Measurement Event ........................................................................................................................................ 129
Measurement for Voltage Connection .............................................................................................................. 130
Three-phase 4-wire ................................................................................................................................. 130
Three-phase 3-wire ................................................................................................................................. 131
Single-phase 3-wire ................................................................................................................................. 133
Single-phase 2-wire ................................................................................................................................. 134
Dip[Sag]/Swell Measurement .......................................................................................................................... 135
Leakage Current Measurement ....................................................................................................................... 136
Residual Voltage Measurement ....................................................................................................................... 136
Phase Power Measurement ............................................................................................................................. 137
Power Factor(PF) Measurement........................................................................................................................ 138
PF Phase Angle Status Measurement ............................................................................................................... 138
Demand Measurement ................................................................................................................................... 139
Unbalance(NEMA MG1) ................................................................................................................................. 140
Sequence Unbalance...................................................................................................................................... 141
Aggregation ................................................................................................................................................... 142
APPENDIX A Specification................................................................................................................................. 144
APPENDIX B Standard Compliance ................................................................................................................... 147
APPENDIX C Accuracy/Reliability ....................................................................................................................... 148
Accuracy ................................................................................................................................................. 148
Reliability ................................................................................................................................................ 149
APPENDIX D Ordering Information ................................................................................................................... 150

Page 10 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Contents

Figures
Fig 1.1 Accura 2350-1P3FSC Dimension Compatibility for Each Rating of MCCB/ELB .................................. 16
Fig 1.2 Accura 2350-1P3FSC Power Measuring Module Installation ............................................................. 16
Fig 1.3 Accura 2300S/2350-1P3FSC Installation Example[Using external CT and Accura 2350-3P-CT5A
model incoming feeder] ............................................................................................................................. 19
Fig 1.4 Accura 2300S/2350-1P3FSC Installation Example[Using Accura 2350-1PSCSH model at incoming
feeder] ...................................................................................................................................................... 20
Fig 2.1 Accura 2300S Front ....................................................................................................................... 25
Fig 2.2 Accura 2300S Side ........................................................................................................................ 25
Fig 2.3 Accura 2300S Rear ........................................................................................................................ 25
Fig 2.4 Accura 2350-1P3FSC Power Measuring Module .............................................................................. 26
Fig 2.5 Accura 2300S Components ............................................................................................................ 26
Fig 2.6 Accura 2350-1P3FSC Power Measuring Module Components .......................................................... 26
Fig 2.7 Accura 2300S Front Dimension ...................................................................................................... 27
Fig 2.8 Accura 2300S Side Dimension ........................................................................................................ 27
Fig 2.9 Accura 2300S Rear Dimension ....................................................................................................... 27
Fig 2.10 Accura 2350-1P3FSC Power Measuring Module Dimension ........................................................... 28
Fig 2.11 Accura 2300S/2350-1P3FSC [Using 1PSCSH module at incoming feeder] ..................................... 29
Fig 2.12 Accura 2300S/2350-1P3FSC [Using 3P-CT5A module at incoming feeder]..................................... 30
Fig 2.13 Accura 2300S Mounting[ANSI 4”] ................................................................................................. 31
Fig 2.14 Accura 2300S Mounting[DIN96] ................................................................................................... 31
Fig 2.15 Accura 2350-1P3FSC Power Measuring Module Installation[Using mounting wing] ......................... 32
Fig 2.16 Accura 2350-1P3FSC Mounting Plate Cutout[Using mounting wing] ............................................... 33
Fig 2.17 Accura 2350-1P3FSC Mounting Plate [Using the lower part of power measuring module] ............... 34
Fig 2.18 Accura 2350-1P3FSC Remodelling Installation[Using Cable tie] ..................................................... 35
Fig 2.19 Accura 2350-1P3FSC Remodelling Installation[Using lower part of module] ................................... 36
Fig 2.20 Accura 2300S Voltage Connection ................................................................................................ 37
Fig 2.21 Three-phase 4-wire Direct Connection .......................................................................................... 38
Fig 2.22 Three-phase 4-wire 3PT Connection ............................................................................................. 38
Fig 2.23 Three-phase 3-wire Direct Connection .......................................................................................... 39
Fig 2.24 Three-phase 3-wire 2PT Connection ............................................................................................. 39
Fig 2.25 Single-phase 3-wire Direct Connection ......................................................................................... 40
Fig 2.26 Single-phase 3-wire 2PT Connection............................................................................................. 40
Fig 2.27 Single-phase 2-wire Direct Connection ......................................................................................... 41
Fig 2.28 Single-phase 2-wire 1PT Connection............................................................................................. 41
Fig 2.29 Accura 2300S Digital Input/Output Channel ................................................................................. 42
Fig 2.30 Digital Input................................................................................................................................. 42
Fig 2.31 DC Relay Application ................................................................................................................... 44

ⓒ 2015 Rootech Inc. All Rights Reserved Page 11


Contents Accura 2300S/2350-1P3FSC User Guide

Fig 2.32 AC Relay Application .................................................................................................................... 44


Fig 2.33 Accura 2350-1P3FSC Through-hole Installation Position ................................................................ 46
Fig 2.34 Accura 2350-1P3FSC Measurement Principle ................................................................................ 46
Fig 2.35 Three-phase 4-wire Through-hole Wiring ...................................................................................... 47
Fig 2.36 Three-phase 3-wire Through-hole Wiring ...................................................................................... 48
Fig 2.37 Digital Input 4 Channels of Option Module ................................................................................... 49
Fig 2.38 ZCT Input 3 Channels of Option Module ...................................................................................... 50
Fig 2.39 ZCT Wiring .................................................................................................................................. 50
Fig 2.40 Digital Input and ZCT Wiring of Option Module ............................................................................ 51
Fig 2.41 Accura 2300S/2350 Combination Example of Communication ..................................................... 52
Fig 2.42 Accura 2300S Ethernet Communication Port ................................................................................. 54
Fig 2.43 Accura 2300S Ethernet Communication ........................................................................................ 55
Fig 2.44 Accura 2300S RS-485 Communication ......................................................................................... 56
Fig 2.45 Accura 2300S RS-485 Communication Connection ....................................................................... 56
Fig 2.46 Accura 2300S Power Supply ......................................................................................................... 57
Fig 4.1 Accura 2300S Front ....................................................................................................................... 68
Fig 4.2 Screen of Display Mode.................................................................................................................. 69
Fig 4.3 Screen of Setup Mode .................................................................................................................... 69
Fig 4.4 Screen of Event Log Mode .............................................................................................................. 69
Fig 4.5 Accura 2300S Front Overview ........................................................................................................ 70
Fig 4.6 Accura 2300S Temperature Sensor ................................................................................................. 71
Fig 4.7 Accura 2350 Module ID Selection at Upper Part of LCD Screen ........................................................ 72
Fig 4.8 Line-to-neutral Voltage/Current/Power Display Screen ..................................................................... 74
Fig 4.9 Line-to-line Voltage/Current/Power Display Screen .......................................................................... 74
Fig 4.10 Line-to-line Voltage Display Screen ............................................................................................... 74
Fig 4.11 Current Display Screen ................................................................................................................. 75
Fig 4.12 Power Display Screen ................................................................................................................... 75
Fig 4.13 Demand Active Power Display Screen............................................................................................ 76
Fig 4.14 Net Energy Display Screen of Feeder 1.......................................................................................... 76
Fig 4.15 Leakage Current Display Screen ................................................................................................... 77
Fig 4.16 Ethernet Connection Display Screen .............................................................................................. 77
Fig 4.17 Accura 2300S Rear Surface Temperature Display Screen ................................................................ 78
Fig 4.18 3-phase 4-wire connection[3P4W]: PT Primary VAB , Secondary V12 ................................................. 81
Fig 4.19 3-phase 3-wire connection[3P3W]: PT Primary VAB , Secondary V12 ................................................. 82
Fig 4.20 1-phase 3-wire connection[1P3W]: PT Primary VL12 , Secondary V13................................................. 82
Fig 4.21 1-phase 2-wire connection[1P2W]: PT Primary VL12 , Secondary V1N ................................................ 82
Fig 4.22 Dip Event Setup[3-phase 4-wire] ................................................................................................... 87
Fig 4.23 Dip Event Setup[3-phase 3-wire] ................................................................................................... 87
Fig 4.24 Swell Event Setup[3-phase 4-wire]................................................................................................. 89

Page 12 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Contents

Fig 4.25 Swell Event Setup[3-phase 3-wire]................................................................................................. 89


Fig 4.26 Dip[Sag] Event Alarm Display ..................................................................................................... 115
Fig 4.27 Swell Event Alarm Display .......................................................................................................... 115
Fig 4.28 Event Log Number Example ........................................................................................................ 117
Fig 5.1 3PT 3P4W Connection ................................................................................................................. 130
Fig 5.2 2PT 3P3W Connection ................................................................................................................. 131
Fig 5.3 2PT 1P3W Connection ................................................................................................................. 133
Fig 5.4 1PT 1P2W Connection ................................................................................................................. 134
Fig 5.5 Half-cycle Refreshed 1-cycle RMS Calculation ................................................................................ 135
Fig 5.6 Voltage Dip[Sag] Detection ........................................................................................................... 135
Fig 5.7 Power Sign and PF Phase Angle Status .......................................................................................... 138
Fig 5.8 Demand Calculation .................................................................................................................... 139
Fig 5.9 Prediction Demand Calculation .................................................................................................... 139
Fig 5.10 Symmetrical Components ........................................................................................................... 141
Fig 5.11 Aggregation Process .................................................................................................................. 142

ⓒ 2015 Rootech Inc. All Rights Reserved Page 13


Chapter 1 Introduction Accura 2300S/2350-1P3FSC User Guide

Chapter 1 Introduction
Overview
Energy Management Paradigm Shift from Main Load to Branch Load
In the energy low-cost era, total energy management centered on switchgear panels such as main feeder
(from feeder to ABS) for stable power supply played an important role. However, there is an increasing
demand to manage the branch load electrical energy in manufacturing plants, IDC centers, and the
distribution boards of buildings when the energy costs rise sharply and the CO2 emission reduction policy is
implemented in 2015.

Limit of Applying the Switchgear Panel Digital Power Meter to Distribution Panel
To apply the digital power meter which is long used in the existing switchgear panel to distribution panel has
had the limit caused by narrow space, hazardous wiring of voltage and current, and high installation cost.
This fundamentally makes it difficult for energy management supervisor to access to the energy information of
branch loads in distribution panel.

Distribution Panel Digital Power Meter Specialized for Branch Load Management
Distribution panel digital power meter comprises both Accura 2300S[digital power meter] which is mounted
on front of distribution panel, and Accura 2350[power measuring module] which is mounted in branch loads
inside the panel. Accura 2300S collects power data from several Accura 2350s on RS-485 communication
and displays measurements of only one Accura 2350 selected on its LCD screen. This provides energy
management supervisor with the power quality information of branch loads which was impossible to identify.

Accura 2350-1P3FSC Single-phase Three Feeder Power Measuring Module, Suitable for Data Center
Distribution Panel Having Multiple Single-phase Feeders
Data center distribution panel has multiple single-phase feeders of the same current capacity. Accura 2350-
1P3FSC single-phase three feeder power measuring module measures three single-phase feeders of the same
current capacity at the same time. Installation time and cost can be drastically reduced comparing to
installment of Accura 2350-1P[1PSC] single-phase power measuring module.

Accura 2350-1P3FSC-DIZCT Single-phase Three Feeder Power Measuring Module[Option Module]


Supporting the Monitoring of Leakage Current for Each Single-phase Feeder, and MCCB Trip-status
Accura 2350-1P3FSC-DIZCT single-phase three feeder power measuring module[Option module] provides
the additional function to monitor both leakage current and MCCB trip-status of each single-phase feeder by
expanding the function of Accura 2350-1P3FSC single-phase three feeder power measuring module[Basic
module]. This makes it possible to do not only the energy management but also the safety management for
consistency of power supply.

Page 14 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 1 Introduction

Voltage ±0.2% RD Error/Current ±0.5% RD Error/IEC62053-22 Class 0.5S


Recently enterprise energy management system is essential for effective energy use and preventive
management to prepare CO2 emission management in data center, plant and building. The key factor to
determine reliability of the energy management is measuring accuracy. Accura 2300S/2350 supports
1
precision measurement of ±0.2% reading error of voltage and ±0.5% reading error of current, and
conforms to IEC62053-22 class 0.5S for power and energy. This makes it possible to precisely analyze and
diagnose various problems with energy management and power facilities.

1. Single-phase three feeder power measuring module can increase the error of up to ± 1% reading value depending on
the penetration position of power cable.

Dip[Sag]/Swell[IEC61000-4-30], Power Quality


Accura 2300S provides a variety of power quality information, including dip[sag], swell and harmonic
information[up to 31th], crest factor, K-factor, and unbalance ratio. This enables the energy manager to easily
identify power quality changes in various power distribution systems in the power plant, thus realistic power
quality management is possible. Power quality information conforms to IEC61000-4-30.

Maximum/Minimum/Average during Aggregation Interval


Accura 2300S calculates average at every 0.5 second interval from measurements at cycle time, providing
maximum/minimum/average at 1 second, 5 second, 1 minute, 5 minute, 1 hour and 6 hour intervals from
average at every 0.5 second interval. The measuring interval which is more than 0.5 second interval is called
aggregation interval.
Accura 2300S provides both of maximum/minimum/average at each aggregation interval and time
information[time stamp] at the time of generation, as well as average at 0.5 second interval about various
measuring parameters such as voltage, current, power, and etc on communication. This includes information
of the measuring parameters fluctuating instantaneously, which makes it possible to precisely analyze the
trend of quality of voltage, current, and power.

CE/UL Safety and Reliablity


The internal and external structures of Accura 2300S [instrument design, circuit design, and electrical fire]
meet the safety and reliability standards of CE[EN61326-1, EN61326-2-1, EN61010-1] and UL[UL61010-1].

All-in-one Installation with MCCB/ELB Having the Same Current Rating


Accura 2350-1P3FSC single-phase three feeder power measuring module is installed all-in-one with the
existing MCCB because the distance between through-holes of the module on two kinds of current rating, 60A
and 125A is compatible with that between terminals of MCCB/ELB.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 15


Chapter 1 Introduction Accura 2300S/2350-1P3FSC User Guide

Fig 1.1 Accura 2350-1P3FSC Dimension Compatibility for Each Rating of MCCB/ELB

Split-core Structure Possible to Install on Live Wire


Accura 2350-1P3FSC single-phase three feeders power measuring module makes it possible to install without
power interruption by split-core structure.

Fig 1.2 Accura 2350-1P3FSC Power Measuring Module Installation

Page 16 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 1 Introduction

Application

Enterprise Energy Management


Providing energy information of branch loads in distribution panel, Accura 2300S/2350 together with Accura
3300S/3500S/3550S/3700/7500 mounted in switchgear panels truly makes it possible to realize enterprise
energy management system.

Data Center Energy Management on Each Server


Accura 2350-1P3FSC single-phase three feeder power measuring module is optimized for server distribution
panel with multiple single feeders of the same current capacity, measuring three single feeders per one
module. In addition, Accura 2350-1P3FSC-DIZCT single-phase three feeder power measuring module[option
module] supports safety management by monitoring both leakage current of each feeder and MCCB trip-
status.

CO2 Emission Management by Reduction of High Energy Cost


Accura 2300S/2350 provides various power quality information which enables management of energy use,
power facility operation and high efficiency device analysis. This can be an essential infrastructure for
management of CO2 emission, presenting the exact analytic criterion on energy usage status to energy
management supervisor.

Energy Efficiency Verification of High Efficiency Device


Accura 2300S/2350 provides high accuracy energy information to determine the efficiency of high efficiency
device such as LED, lighting, motor, and power facility.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 17


Chapter 1 Introduction Accura 2300S/2350-1P3FSC User Guide

Device Lineup
Data Center Distribution Panel Digital Power Meter/Single-phase Three Feeder Power
Measuring Module
Data center distribution panel digital power meter comprises Accura 2300S [digital power meter] which is
mounted at the front of distribution panel, and Accura 2350-1P3FSC which is mounted per 3 feeders inside
the panel. Accura 2300S collects and display data from the large number of Accura 2350-1P3FSC using the
6C telephone line 1.
Device Model Description Weight
Distribution panel digital Accura 2300S Collects data from all Accura 2350s 487 g
power meter
2
Selectively displays one Accura 2350
Ethernet[or RS-485] communication
Temperature of Accura 2300S rear side 3
Single-phase three feeder Accura 2350-1P3FSC-125A Current measurement rating 125A 457 g
Power measuring module
Accura 2350-1P3FSC-125A-DIZCT Current measurement rating 125A, 468 g
option[connects DI, ZCT]
Accura 2350-1P3FSC-60A Current measurement rating 60A 393 g
Accura 2350-1P3FSC-60A-DIZCT Current measurement rating 60A, 404 g
option[connects DI, ZCT]
1. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG]. Distance from the
power line should be 5mm or more so that communication interference caused by the noisy power line will not occur.
2. Accura 2300S displays only measurements of one Accura 2350 selected. Refer to “Chapter 4>Display Mode>Module ID
Selection”.
3. It is not for firewatching, but for reference only. A temperature sensor is mounted on the rear of Accura 2300S.

Distribution Panel Digital Power Meter/General Power Measuring Module


Refer to “Accura 2300S/2350 User Guide” for details of distribution panel digital power meter except for the
Accrua 2350-1P3FSC which measures the three single-phase feeder at the same time.

Special-Purpose Module
Accura 2350 module for special purpose in addition to measuring module is as follows. Refer to “Accura
2300S/2350 User Guide” for more details about these special-purpose modules.

Module Model Description


GAS Accura 2350-GAS Gas concentration of the surroundings
GW[Gateway] Accura 2350-GW Collects data of device that supports RS-485 commuinication.
TEMP[Temperature] Accura 2350-TEMP Simultaneous measurement of inside and outside termperature
DO[Digital Output] Accura 2350-DO Provides digital output which is able to be controlled in remote and
from Accura 2300S.
IDC[DC Current Input] Accura 2350-IDC Analog current input [-20mA to 20mA]
VDC[DC Voltage Input] Accura 2350-VDC Analog voltage input [-50V to 50V]
DCM Accura 2350-DCM -50V-80A Measurement up to DC 50V and 80A
[DC voltage/current] -500V--80A Measurement up to DC 500V and 80A

Page 18 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 1 Introduction

Installation Example
Accura 2300S/2350-1P3FSC Installation Example[Accura 2350-3P-CT5A using external CT is used at
the incoming feeder]
The following is the installation example of single-phase three feeder power measuring module optimized for
distribution panel branching single-phase power line of the same current capacity. However, as the incoming
feeder has large current capacity and three-phase power line, it can not be measured by Accura 2350-
1P3FSC. In this case, Accura 2350-3P-CT5A using external CT is installed in Fig 1.3 or Accura 2350-1PSCSH
installed in Fig 1.4. Refer to “Accura 2300S/2350 User Guide” for the details about Accura 2350-3P-CT5A-75
and Accura 2350-1PSCSH.

Fig 1.3 Accura 2300S/2350-1P3FSC Installation Example[Using external CT and Accura 2350-3P-
CT5A model incoming feeder]

Installation
Front panel Accura 2300S Distribution panel digital meter
1
Incoming feeder Accura 2350-3P-CT5A-75 Three-phase power measuring module
Branch load Accura 2350-1P3FSC-125 Single-phase three feeder power
Accura 2350-1P3FSC-60 measuring module

Internal 6C telephone line 2


communication
External Ethernet 3
communication

1. If through-hole current exceeds 250A, Accura 2350-3P-CT5A-75 using external CT should be chosen.
Refer to “Accura 2300S/2350 User Guide” for details about Accura 2350-3P-CT5A-75.
2. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG], and is recommended
as the distance more than 5mm with power line which creates a lot of noise not to cause communiation interferences.
3. Only for communication with host program.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 19


Chapter 1 Introduction Accura 2300S/2350-1P3FSC User Guide

Accura 2300S/2350-1P3FSC Installation Example [Using Accura 2350-1PSCSH model at incoming


feeder]

Fig 1.4 Accura 2300S/2350-1P3FSC Installation Example[Using Accura 2350-1PSCSH model at


incoming feeder]

[Three-phase 3-wire 2 modules]

[Three-phase 4-wire 3 modules]

Installation
Front panel Accura 2300S Distribution panel digital meter
1
Incoming feeder Accura 2350-1PSCSH Single-phase single hole power
measuring module
Branch load Accura 2350-1P3FSC-125 Single-phase three feeder power
Accura 2350-1P3FSC-60 measuring module

Internal 6C telephone line 2


communication
External Ethernet 3
communication

1. For three-phase measurement, three split-core single-phase single hole power measuring modules are needed, one
module for each phase[A, B, C]. However in three-phase 3-wire, only two modules are needed.
2. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG], and is recommended
as the distance more than 5mm with power line which creates a lot of noise not to cause communiation interferences.
3. Only for communication with host program.

Note

Accura 2350-1PSCSH power measuring module is recommended in the following cases.


- Measures current exceeds 250A.
- Through-hole connection of 3P/1P module is difficult because of a large gap between bus bars[or cables].

Page 20 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 1 Introduction

Features
Accura 2300S Distribution Panel Digital Power Meter
Accura 2300S collects and display data from the large number of Accura 2350-1P3FSC using the 6C
telephone line 1.

Accura 2300S Function


Combination with Accura 2350s for internal communication
Collects data from the large number of Accura 2350s.
Display[Measurement information of the selected module is displayed: Accura 2350-1P3FSC
Single-phase Three Feeder Power Measuring Module]
Display
2
LCD display of measurements of Accura 2350
General
Sampling/cycle for harmonic analysis 64
Sampling/cycle for RMS and power calculation 32
Measurement frequency range 50/60Hz, 42-69Hz
Voltage ±0.2% RD

Current ±0.5% RD 15

Power, Power factor IEC62053-22 Class 0.5S


4, 5
Demand, Peak demand, Predicted demand
Maximum, Minimum after user reset
Maximum 5, Minimum 5, Average 5 in aggregation interval 14

Energy
kWh/kVarh received, kWh/kVarh delivered IEC62053-22 Class 0.5S
kWh/kVarh net[kWh/kVarh received - kWh/kVarh delivered]
kWh/kVarh sum[kWh/kVarh received+kWh/kVarh delivered]
Power Quality
Voltage/Current THD 11, Current TDD 11 Up to 31st harmonic
Crest factor 12, 5, K-factor 13, 5
Dip[Sag], Swell IEC61000-4-30
5
Voltage Unbalance NEMA MG1
Voltage/Current symmetrical unbalance[zero, negative] 5 IEC61000-4-30
5
Vector diagram
Oscilloscope 5
Measuring Event
Dip[Sag], Swell event Half-cycle refreshed 1-cycle RMS measurement
Phase open event
Fuse fail event
Over leakage current event
Over current event
Over demand current event
Over temperature event
Over power event
Number of event logs Maximum 100
Digital Input/Output of Accura 2300S
Digital Input 2 channels, dry contact

ⓒ 2015 Rootech Inc. All Rights Reserved Page 21


Chapter 1 Introduction Accura 2300S/2350-1P3FSC User Guide

Digital output 1 channel, Form A relay


Temperature of Accura 2300S
Temperature of Accura 2300S rear 3 1 sensor
Communication
External Ethernet[100Mbps/Full Duplex, Ethernet switching9, 2 ports[Ethernet1, Ethernet2]
RSTP10, Modbus TCP protocol]
RS-485[1,200 to 115,200bps, Modbus RTU protocol] 1 port[Ta, Tb]
6
Internal RS-485 2 ports[RJ12-1, RJ12-2]
Combination
Number of Accura 2350s connected to Accura 2300S Maximum 15/port 7
1 8
6C telephone line extension length Maximum 6m/port
General
UL certification UL61010-1
CE certification EN61326-1, EN61326-2-1, EN61010-1
AC power AC 85 - 265V
DC power DC 100 - 300V
1. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG], and is recommended
as the distance more than 5mm with power line which creates a lot of noise not to cause communiation interferences.
2. Accura 2300S displays only measurements of one Accura 2350 selected. Refer to “Chapter 4>Display Mode>Accura
2350 Module ID Selection”.
3. It is not for firewatching, but for reference only. A temperature sensor is mounted on the rear of Accura 2300S.
4. Predicted demand is calculated by assuming that the current power is maintained at the value of the current time during
the demanded sub-interval remaining in the demanded sub-interval.
5. Not displayed on LCD screen of Accura 2300S. It is available only by communication.
6. Only for dedicated communication with all Accura 2350s connected by 6C telephone line.
7. Accura 2300S can connect up to 15 power measuring modules per port[RJ12-1, RJ12-2]. When connecting the special-
purpose modules other than the power measuring module, refer to the individual manual of the special-purpose module.
8. Maximum extension length of 6C telephone line from one port of Accura 2300S to the last Accura 2350 module
connected.
9. Accura 2300S has Ethernet switch function so network connection is available among Accura 2300Ss without external
switch.
10. Refer to RSTP[Rapid Spanning Tree Protocol], IEEE 802.1D-2004.
√∑31 2
𝑘=2 𝑉𝑘 √∑31 2
𝑘=2 𝐼𝑘
11. THD[Total Harmonic Distortion], Voltage THD: , Current THD:
𝑉1 𝐼1
√∑31 2
𝑘=2 𝐼𝑘
TDD[Total Demand Distortion]:
𝐼𝐿
Where 𝐼𝐿 can be current rating chosen only by communication between current rating[default] and peak demand current.
𝑉𝑝𝑒𝑎𝑘
12. Crest factor:
𝑉𝑟𝑚𝑠

∑31
𝑘=1(𝑘 𝐼𝑘 )
2
13. K-factor: 31 2
∑𝑘=1 𝐼𝑘
14. Accura 2300S provides statistic information (maximum, minimum, average) of voltage, current and power through
communication. This includes the information of measuring parameter which often changes so this makes it possible to
accurate trend-analyzing about voltage, current and power.
15. An error of up to ± 1% can be increased depending on the penetration position of the power cable

Page 22 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 1 Introduction

Accura 2350-1P3FSC Single-phase Three Feeder Power Measuring Module


Accura 2350-1P3FSC is single-phase three feeder power measuring module installed for three single-phase
feeders in the distribution panel which measures the current, power and energy totally.

Device Function
Single-phase Model Pickup Measuring Range
Three Feeder [Accuracy guaranteed]
Power Measuring Module Accura 2350-1P3FSC-125A 0.83A 1.25A - 150A
Accura 2350-1P3FSC-125A-DIZCT 0.83A 1.25A - 150A
Accura 2350-1P3FSC-60A 0.40A 0.60A - 72A
Accura 2350-1P3FSC-60A-DIZCT 0.40A 0.60A - 72A
Measurement
Sampling/cycle for harmonic analysis 64
Sampling/cycle for RMS and power calculation 32
Measurement Frequency Range 50/60Hz, 42-69Hz
Current ±0.5% RD 6

[Basic module] Power, Energy IEC62053-22 Class 0.5S


5
Leakage Current Input/Digital Input[Optional Items ]
Leakage current input 5 3 channels for three single-phase
feeders
Digital input 5 4 channels, dry contact
Communication
1
RS-485 2 ports[RJ12A, RJ12B] 2
Combination
6C telephone line connection with Accura 2300S[or 2350]3, 4
General
UL certification UL61010-1
[Option module]
CE certification EN61326-1, EN61326-2-1, EN61010-1
Power supply Supplied from Accura 2300S
1. Only for dedicated communication with Accura 2300S[or 2350] connected by 6C telephone line.
2. No functional difference between RJ12A and RJ12B.
3. Accura 2300S can connect up to 15 power measuring modules per port[RJ12-1, RJ12-2]. When connecting special-
purpose modules other than the power measuring module, refer to the individual manual of the special-purpose module.
4. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG], and is recommended
as the distance more than 5mm with power line which creates a lot of noise not to cause communiation interferences.
5. Supported only at the optional module, Accura 2350-1P3FSC-DIZCT. When ordering ZCT, please contact ROOTECH Inc..
6. An error of up to ± 1% can be increased depending on the penetration position of the power cable

ⓒ 2015 Rootech Inc. All Rights Reserved Page 23


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Chapter 2 Installation
Environmental Conditions
Accura 2300S/2350 should be mounted in a dry, dirt free location away from heat sources and very high
electric fields. To operate properly and effectively, environmental conditions should range within the following
guidelines.

Item Acceptable Range


Position Indoor use
Operating temperature -20 to 70C[-4℉ to 158℉]
1
Safety temperature -20 to 65C[-4℉ to 149℉]

Storage temperature -40 to 85C[-40℉ to 185℉]

Operating humidity non-condensing 5% - 95%


1. Conforms to UL61010-1.

Warning

- The meter should be mounted in a distribution cabinet or similar enclosure to ensure the terminal strips on
the meter are not user-accessible after the installation.

- Mount the meter in a dry location free from dirt and corrosive vapors. Once installed, no cleaning of the
device is necessary.

Page 24 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Before you begin


Before installing the meter, observe the instructions and safety precautions presented in this guide.

Caution
Power up after the voltage and current wiring is completed.

Meter Overview

Fig 2.1 Accura 2300S Front Fig 2.2 Accura 2300S Side

Fig 2.3 Accura 2300S Rear

ⓒ 2015 Rootech Inc. All Rights Reserved Page 25


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Fig 2.4 Accura 2350-1P3FSC Power Measuring Module

Single-phase Three Feeder Power Measuring Module Single-phase Three Feeder Power Measuring Module
Accura 2350-1P3FSC [Basic module] Accura 2350-1P3FSC-DIZCT [Option module]

Components

Fig 2.5 Accura 2300S Components

Accura 2300S Connector Two nuts, two bolts Telephone line: 3m x2, 75cm x1

Fig 2.6 Accura 2350-1P3FSC Power Measuring Module Components

Accura 2350-1P3FSC Mounting wings Two screws Telephone line: 20cm x1

Page 26 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Dimension

Fig 2.7 Accura 2300S Front Dimension Fig 2.8 Accura 2300S Side Dimension

Fig 2.9 Accura 2300S Rear Dimension

ⓒ 2015 Rootech Inc. All Rights Reserved Page 27


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Fig 2.10 Accura 2350-1P3FSC Power Measuring Module Dimension

Accura 2350-1P3FSC-125A Accura 2350-1P3FSC-125A-DIZCT

Accura 2350-1P3FSC-60A Accura 2350-1P3FSC-60A-DIZCT

Dimension
Device Model Dimension
Distribution panel digital power meter Accura 2300S 126.3W x 114.1H x 82.2D
Single-phase three feeder power Accura 2350-1P3FSC-125A 53.0W x 120.0H x 85.0D
measuring module Accura 2350-1P3FSC-125A-DIZCT (except for mounting wings)
Accura 2350-1P3FSC-60A 53.0W x 100.0H x 85.0D
Accura 2350-1P3FSC-60A-DIZCT (except for mounting wings)

Page 28 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Installation
Accura 2300S/ 2350-1P3FSC [1PSCSH module is used at incoming feeder]
Split-core power measuring module makes it possible to install without power interruption by split-core
structure.

Fig 2.11 Accura 2300S/2350-1P3FSC [Using 1PSCSH module at incoming feeder]

[Three-phase 3-wire 2 modules]

[Three-phase 4-wire 3 modules]

Transformer needed
@ exceeding AC
265V

Installation
Front panel Accura 2300S Distribution panel digital power meter
1
Incoming feeder Accura 2350-1PSCSH Split-core single-phase single hole power
measuring module
Branch load Accura 2350-1P3FSC Single-phase three feeder power
measuring module

Communication 6C Telephone Line 2 6C Telephone line

1. For three-phase 4-wire measurement, three split-core single-phase single hole power measuring modules are needed, one
module for each phase[A, B, C]. However in three-phase 3-wire, two modules are used. Refer to “Accura 2300S/2350 User
Guide” for details.
2. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG], and is recommended as
the distance more than 5mm with power line which creates a lot of noise not to cause communiation interferences.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 29


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Accura 2300S/ 2350-1P3FSC [3P-CT5A module is used at incoming feeder]


Split-core power measuring module makes it possible to install without power interruption by split-core
structure.

Fig 2.12 Accura 2300S/2350-1P3FSC [Using 3P-CT5A module at incoming feeder]

Transformer needed
@ exceeding AC
265V

Installation
Front panel Accura 2300S Distribution panel digital power meter
1
Incoming feeder Accura 2350-3P-CT5A-75 Three-phase Power Measuring Module
Branch load Accura 2350-1P3FSC Single-phase three feeder power
measuring module

Communication 6C Telephone Line 2 6C Telephone line

1. Refer to “Accura 2300S/2350 User Guide”.


2. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG], and is recommended
as the distance more than 5mm with power line which creates a lot of noise not to cause communiation interferences.

Page 30 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Step 1: Mounting
Accura 2300S Mounting
Accura 2300S is mounted on front of distribution panel.

① Fit Accura 2300S into the cutout [ANSI 4”, DIN96 supported].
② Combine connector to the right side of Accura 2300S.
③ Fix Accura 2300S to panel using nuts. Particularly, in case of conforming to DIN96 compliance,
hole-punching is not required and can be more easily mounted using washers with nuts.

Fig 2.13 Accura 2300S Mounting[ANSI 4”]

Fig 2.14 Accura 2300S Mounting[DIN96]

ⓒ 2015 Rootech Inc. All Rights Reserved Page 31


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Accura 2350-1P3FSC Power Measuring Module Panel Installation

New Installation[Using mounting wing]

① After combining the mounting wing to the side of the module, fit the holes of mounting at the
designated position.

② Fasten with screws.

Fig 2.15 Accura 2350-1P3FSC Power Measuring Module Installation[Using mounting wing]

Keep tolerance 0.5mm

Page 32 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Fig 2.16 Accura 2350-1P3FSC Mounting Plate Cutout[Using mounting wing]

Application Model
Accura 2350-1P3FSC-125A

Accura 2350-1P3FSC-125A-DIZCT

Application Model
Accura 2350-1P3FSC-60A

Accura 2350-1P3FSC-60A-DIZCT

ⓒ 2015 Rootech Inc. All Rights Reserved Page 33


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

New Installation[Using the lower part of Power Measuring Module].


① Separate the split core measurement module vertically and align the bottom hole with the specified
position.

② Fasten the screws to fix the bottom of the split core measurement module to the panel.
③ Attach the top of the split core measurement module to the bottom by tightening the screws.

Fig 2.17 Accura 2350-1P3FSC Mounting Plate [Using the lower part of power measuring module]

Application Model
Accura 2350-1P3FSC-125A

Accura 2350-1P3FSC-125A-DIZCT

Application Model
Accura 2350-1P3FSC-60A

Accura 2350-1P3FSC-60A-DIZCT

Page 34 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Remodelling Installation[Cable tie fixing]

① Combine the upper part of Accura 2350-1P3FSC single-phase three feeder power measuring
module with the lower part fitting the power line of the corresponding phase to the through-hole.

② Secure the upper part and lower part using the screws on the upper part.
③ Secure the module using cable tie[200x4.8mm].

Fig 2.18 Accura 2350-1P3FSC Remodelling Installation[Using Cable tie]

200mmx4.8mm cable tie

ⓒ 2015 Rootech Inc. All Rights Reserved Page 35


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Remodelling Installation[Using the lower part of power measuring module]

① Fit the hole of lower part of Accura 2350-1P3FSC single-phase three feeder power measuring
module at the designated location fitting the power line of the corresponding phase to the through-
hole.

② Secure the lower part of Accura 2350-1P3FSC single-phase three feeder Power Measuring Module
to the panel.

③ Combine the upper part of Accura 2350-1P3FSC single-phase three feeder power measuring
module with the lower part fitting the power line of the corresponding phase to the through-hole.

Fig 2.19 Accura 2350-1P3FSC Remodelling Installation[Using lower part of module]

Keep tolerance 0.5mm

Page 36 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Step 2: Accura 2300S Wiring


Accura 2300S Voltage Connection

Fig 2.20 Accura 2300S Voltage Connection

Voltage Input
Item Description
Connector name V1, V2, V3, VN
Connector type Terminal block
Wire specification 2.1 to 3.5 mm2[14 to 12 AWG]
Measuring range AC 60 - 600V direct L-L[Line-to-line]
[Accuracy guaranteed]
1
Minimum measurement AC 5V direct L-N[Line-to-neutral]
1
Maximum measurement AC 660V direct L-L[Line-to-line]
Frequency range 50/60Hz, 42-69Hz
Voltage connection Three-phase 4-wire/3-wire, Single-phase 3-wire/2-wire
Burden 0.02VA/phase @ 220V
Withstand voltage AC 2,000V RMS, 60Hz for 1minute
Impedance 3MΩ/phase
Compliance Category Ⅲ

1. When using an external PT, the primary voltage is the product of the PT ratio.

Note
Accuracy may be affected if the voltage input is out of measurement range. External PT[Potential Transformer]
should be used in case of higher voltage than the voltage of input specifications.

Warning
If an external PT is used, a fuse should be installed on the secondary side.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 37


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Three-phase 4-wire Connection

Fig 2.21 Three-phase 4-wire Direct Connection

Note

Select 3P4W in “Voltage Connection” menu screen.

Fig 2.22 Three-phase 4-wire 3PT Connection

Note

Select 3P4W in “Voltage Connection” menu screen.

Page 38 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Three-phase 3-wire Connection

Fig 2.23 Three-phase 3-wire Direct Connection

Note

Select 3P3W in “Voltage Connection” menu screen.

Fig 2.24 Three-phase 3-wire 2PT Connection

Note

Select 3P3W in “Voltage Connection” menu screen.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 39


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Single-phase 3-wire Connection

Fig 2.25 Single-phase 3-wire Direct Connection

Note
Select 1P3W in “Voltage Connection” menu screen. Be sure to use V1, V3, VN terminals.
Neutral line is the center point between line1 and line2 and should be connected to V N.

Fig 2.26 Single-phase 3-wire 2PT Connection

Note

Select 1P3W in “Voltage Connection” menu screen. Be sure to use V1, V3, VN terminals.
Neutral line is the center point between line1 and line2 and should be connected to V N.

Page 40 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Single-phase 2-wire Connection

Fig 2.27 Single-phase 2-wire Direct Connection

Note

Select 1P2W in “Voltage Connection” menu screen. Be sure to use V1, VN terminals.
Line-neutral voltage or line1-line2 voltage connection is possible

Fig 2.28 Single-phase 2-wire 1PT Connection

Note

Select 1P2W in “Voltage Connection” menu screen. Be sure to use V1, VN terminals.
Line-neutral voltage or line1-line2 voltage connection is possible

ⓒ 2015 Rootech Inc. All Rights Reserved Page 41


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Accura 2300S Digital Input/Output Wiring

Fig 2.29 Accura 2300S Digital Input/Output Channel

Digital Input 2 Channels


Channel 1 Channel 2
Connector name DI1 DI2
1
Ground DIG DIG
1. DIG is common inside.

Item Description
Connector type Terminal block
Input type 2-Channel, Dry contact (Common Ground)

Wire specification 1.5 to 3.5 mm2[16 to 12 AWG]


Rating voltage DC 5V[Self excitation]
Isolation voltage Maximum 300V
Minimun pulse width 1sec

Fig 2.30 Digital Input

Warning
Applying external power supply to digital input channel causes damage to meter because of internal DC 5V.

Page 42 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Digital Output 1 Channel


Channel 1
Terminal name DO
Ground DOG

Item Description
Connector type Terminal block
Wire specification 1.5 to 3.5 mm2[16 to 12 AWG]
Output contact 1-Channel, Form A relay
Output type 1 Latch, single pulse 2, periodic pulse 2
Turn-on time Maximum 6msec
Turn-off time Maximum 3msec
Isolation voltage AC 2,000V 1 minute
Maximum rating AC 250V 5A, DC 110V 0.3A, DC 30V 5A
1. Operation of digital output is as follows.
Output Type Command Operation 3
Latch Command “1” Closed contact maintains.
Command “0” Open contact maintains.
Single pulse[uncountable] Command “1” Single pulse outputs. Additional generations of
“Closed” command within pulse period are
ignored.
Command “0” Not available (Command “1” is self-cleared)
Single pulse[countable] Command “1” Single pulse outputs. Additional generations of
“Closed” command within pulse period are
counted, which generates additional pulses.
Command “0” Not available (Command “1” is self-cleared)
Periodic pulse Command “1” Configured periodic pulse consistently outputs
Command “0” After periodic pulse during period configured
outputs, periodic pulse stops.
2. One cycle of pulse is defined as pulse period and pulse on time.
3. This is the case that the output polarity configuration is “Normal”. If the configuration is “Reverse”, the “Closed” output
and “Open” output are reserved.

Note

Refer to “Chapter 4>Setup Mode>Digital Input/Output>Digital Output Type” setup menu for latch or pulse
type selection.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 43


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Fig 2.31 DC Relay Application

Fig 2.32 AC Relay Application

Note

Use Clamp Diode or Varistor in order not to apply more than voltage rating to digital output.

Page 44 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Step 3: Accura 2350-1P3FSC Through-hole Wiring

Accura 2350-1P3FSC Power Measuring Module Current Through-hole Input


Item Description
Connector type Through-hole
Wire specification Selection according to through-hole size
Measuring range Model Minimum Measuring Range
Measurement [Accuracy guaranteed1]
Accura 2350-1P3FSC-125A 0.83A 1.25A - 150A
Accura 2350-1P3FSC-125A-DIZCT 0.83A 1.25A - 150A
Accura 2350-1P3FSC-60A 0.40A 0.60A - 72A
Accura 2350-1P3FSC-60A-DIZCT 0.40A 0.60A - 72A
Impedance Not applicable because of through-hole structure
Frequency range 50/60Hz, 42-69Hz
Through-hole size Model Size
Accura 2350-1P3FSC-125A 16.6(W) x 21.8(H) mm
Accura 2350-1P3FSC-125A-DIZCT 16.6(W) x 21.8(H) mm
Accura 2350-1P3FSC-60A 11.8(W) x 21.8(H) mm
Accura 2350-1P3FSC-60A-DIZCT 11.8(W) x 21.8(H) mm
Weight Model Weight
Accura 2350-1P3FSC-125A 457 g (except for mounting wing)
Accura 2350-1P3FSC-125A-DIZCT 468 g (except for mounting wing)
Accura 2350-1P3FSC-60A 393 g (except for mounting wing)
Accura 2350-1P3FSC-60A-DIZCT 404 g (except for mounting wing)
Mounting Wing 4g
1. Current accuracy meets ± 0.5% reading error, power/energy meets IEC62053-22 Class 0.5S, and maximum ± 1% error
can be increased depending on the penetration position of the power cable.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 45


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Accura 2350-1P3FSC Through-hole Installation Position


Accura 2350-1P3FSC single-phase three feeder power measuring module measures three single-phase feeders of

the same current capacity at the same time. 4 power lines that are inside among the 6 power lines for the connected
three feeders should be installed through the hole of power measuring module.

Fig 2.33 Accura 2350-1P3FSC Through-hole Installation Position

[Correct through-hole installation]

[Wrong through-hole installation]

Accura 2350-1P3FSC Measurement Principle


Current measurement of the first feeder measures the reverse direction current that returns from the load and the

current of the second and third feeder measures the normal direction current that flows to the load.

Fig 2.34 Accura 2350-1P3FSC Measurement Principle

[Reverse direction]
[Normal direction]

[Normal direction]

Page 46 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Three-phase 4-wire Through-hole Wiring

Fig 2.35 Three-phase 4-wire Through-hole Wiring

Application Model

Single-phase Three Feeder Power Measuring Module

Accura 2350-1P3FSC-125A
Accura 2350-1P3FSC-125A-DIZCT

Accura 2350-1P3FSC-60A
Accura 2350-1P3FSC-60A-DIZCT

Note

The figure is an example of the representative three-phase 4-wire through-hole wiring. Only 4 power lines
that are inside among the 6 power lines of three feeders should be installed through the hole of Accura
2350-1P3FSC. Installation can be done regardless of the phase or direction of the through-hole. Refer to
“Chapter 3>Setup Mode>Connection/Load Direction” and “Chapter 3>Setup Mode>Feeder Phase” for the
configuration of load direction and phase.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 47


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Three-phase 3-wire Through-hole Wiring

Fig 2.36 Three-phase 3-wire Through-hole Wiring

Application Model

Single-phase Three Feeder Power Measuring Module

Accura 2350-1P3FSC-125A
Accura 2350-1P3FSC-125A-DIZCT

Accura 2350-1P3FSC-60A
Accura 2350-1P3FSC-60A-DIZCT

Note

The figure is an example of the representative three-phase 3-wire through-hole wiring. Only 4 power lines
that are inside among the 6 power lines of three feeders should be installed through the hole of Accura
2350-1P3FSC. Installation can be done regardless of the phase or direction of the through-hole. Refer to
“Chapter 3>Setup Mode>Connection/Load Direction” and “Chapter 3>Setup Mode>Feeder Phase” for the
configuration of load direction and phase.

Page 48 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Step 4: Accura 2350-1P3FSC-DIZCT Wiring


Accura 2350-1P3FSC-DIZCT single-phase three feeder power measuring module[Option module] provides
the additional function to monitor both leakage current and MCCB trip-status of each single-phase feeder by
expanding the function of Accura 2350-1P3FSC single-phase three feeder power measuring module[Basic
module].

Digital Input 4 Channels


Total 4 channels of digital input are supported including the 3 channels for monitoring MCCB trip-status of
each feeder and 1 channel for surplus portion.

Fig 2.37 Digital Input 4 Channels of Option Module

Channel 1 Channel 2 Channel 3 Channel 4


Terminal name DI1 DI2 DI3 DI4
Ground 1 DIG DIG DIG DIG
1. DIG is connected inside.

Item Description
Connector type Terminal Block
Pitch 5 mm
Wire specification 0.21 to 2.1 mm2[24 to 14 AWG]
Contact specification Dry contact
Isolation between channels Non-isolation
Minimum pulse width 0.5 sec

ⓒ 2015 Rootech Inc. All Rights Reserved Page 49


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

ZCT Input 3 Channels


Three channels of ZCT input are supported for monitoring the leakage current of each feeder.

Fig 2.38 ZCT Input 3 Channels of Option Module

Channel 1 Channel 2 Channel 3


Connector Name Z1 Z2 Z3
Ground 1 Z1G Z2G Z3G
1. Z1G, Z2G and Z3G are connected inside.

Item Description
Connector type Terminal Block
Pitch 5 mm
Wire specification 0.21 to 2.1 mm2[24 to 14 AWG]
Leakage current input Voltage-output ZCT 200mA/100mV @ 1.2kΩ Burden 1

Accuracy ±0.5% Full Scale 2

1. When ordering ZCT, please contact ROOTECH Inc..


2. Full scale of ZCT leakge current measurement is 2 Arms and this is accuracy for the case that the external ZCT error is 0.

Fig 2.39 ZCT Wiring

Page 50 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Fig 2.40 Digital Input and ZCT Wiring of Option Module

ⓒ 2015 Rootech Inc. All Rights Reserved Page 51


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Step 5: Accura 2300S/2350 Combination of Communication


Accura 2300S collects and display data from the large number of Accura 2350s using the 6C telephone line
communication.

Fig 2.41 Accura 2300S/2350 Combination Example of Communication

Installation
Front panel Accura 2300S Distribution panel digital power meter
1
Incoming feeder Accura 2350-3P-CT5A-75 Three-phase power measuring module
Branch load Accura 2350-1P3FSC Single-phase three feeder power
measuring module
2
Communication 6C Telephone Line 6C Telephone Line

Do not make Ring Connection

Number of Accura 2350s connected to Accura 2300S Maximum 15/port 3


6C telephone line extension length between Accura Maximum 6m/port 4
2300S and 2350s

Page 52 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Dedicated Communication
Number of Accura 2350s connected to Accura 2300S Maximum 15 modules/port 3
6C telephone line extension length Maximum 6m/port 4
Connector type RJ12
Communication port Accura 2300S 2 ports [RJ12-1, RJ12-2] 5
Accura 2350 2 ports [RJ12A, RJ12B] 6
1. If through-hole current exceeds 250A, Accura 2350-3P-CT5A-75 using external CT should be chosen.
2. Packaged with device. Core conductor of telephone line should be minimum 0.128mm2[26 AWG], and is recommended
as the distance more than 5mm with power line which creates a lot of noise not to cause communiation interferences.
3. Accura 2300S can connect up to 15 power measuring modules per port[RJ12-1, RJ12-2]. When connecting the special-
purpose modules other than the power measuring module, refer to the individual manual of the special-purpose module.
4. Maximum extension length of 6C telephone line from one port of Accura 2300S to the last Accura 2350 module
connected.
5. RJ12-1 and RJ12-2 are placed on the side of the upper part of Accura 2300S.
6. No functional difference between type A and B of RJ12A and RJ12B.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 53


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

Step 6: Accura 2300S External Communication

Ethernet Communication
Accura 2300S provides Ethernet communication for high speed transmission of data collected from many
Accura 2350s. Inside of Accura 2300S, Ethernet switch built in so using 2 Ethernet ports Ethernet connection is
available among Accura 2300Ss without another external switch. Up to 20 Accura 2300Ss can be connected
and Star, Daisy Chain and Ring connection modes are available. To transmit the measured data, Accura
2300S supports the standard protocol Modbus TCP.

Supporting RSTP[Rapid Spanning Tree Protocol], ring connection mode is available. Ring connection can
minimize the data loss when the one side of wire is cut by restarting communication through the opposite way
within quick time.

Note

For fast recovery with ring connection, use ring connection of Ethernet switch, RSTP[Rapid Spanning Tree
Protocol] supported and adjusting the order of priority of configured route for corresponding switch.

Fig 2.42 Accura 2300S Ethernet Communication Port

Page 54 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Fig 2.43 Accura 2300S Ethernet Communication

For fast recovery with ring connection, recommend


ring connection of Ethernet switch, RSTP[Rapid
Spanning Tree Protocol] supported and adjusting the
order of priority of configured route for
corresponding switch.

Ethernet cable maximum 100m

Maximum 20 Accura 2300S can be connected

Ethernet 2 Ports
Item Description
Port name Ethernet1, Ethernet2
Feature Ethernet Switching, RSTP[Rapid Spanning Tree Protocol]
Ethernet cable STP[Shielded Twisted Pair]/SFTP[Screened Foiled Twisted Pair] CAT5e
Protocol Modbus TCP
Type 100Base-TX[100 Mbps/Full Duplex]
Connection Star, Daisy-Chain, Ring

Warning
Use STP[Shielded Twisted Pair] or SFTP[Screened Foiled Twisted Pair] cable because power line creates a lot of
electromagnetic waves which causes severe interferences with Ethernet communication in distribution panel.
Refer to “Chapter 4>Setup Mode>Ethernet Communication” setup screen.

Note

For fast recovery with ring connection, use ring connection of Ethernet switch, RSTP[Rapid Spanning Tree
Protocol] supported and adjusting the order of priority of configured route for corresponding switch.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 55


Chapter 2 Installation Accura 2300S/2350-1P3FSC User Guide

RS-485 Communication
Accura 2300S provides 1 port of RS-485 communication along with Ethernet communication.

Fig 2.44 Accura 2300S RS-485 Communication

RS-485 1 Port
Item Description
Port name Ta[TRX+], Tb[TRX-]
Connector type Screw pluggable
Protocol Modbus RTU
Baud rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Wire 0.21 to 3.5 mm2[24 to 12 AWG], Shielded twisted pair 1

Maximum cable length 1219m[4000ft]


Maximum devices 32/bus
1. Connect shield line to G terminal.

Fig 2.45 Accura 2300S RS-485 Communication Connection

Page 56 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 2 Installation

Step 7: Accura 2300S Power Supply and Ground

Fig 2.46 Accura 2300S Power Supply

Power Supply
Item Description
Connector name L+, N-
Connector type Screw pluggable
Wire specification 2.1 to 3.5 mm2[14 to 12 AWG]
Operating voltage AC 85 - 265V 50/60Hz, DC 100 - 300V
Withstand voltage AC 2,000V RMS, 60Hz for 1 minute
Compliance Pollution degree 2
Power comsumption Maximum 20VA Depends on the number of Accura 2350 connected
1
Inrush current Peak 25A, duration 2msec under (AC 220V)
1. If a fuse is installed at the input terminal, a fuse of more than 2A / 500V is recommended due to inrush current.

Ground Terminal
Item Description
Connector name
Connector type Screw pluggable
Wire 2.1 to 3.5 mm2[14 to 12 AWG]

Note

Wire Accura 2300S’s ground terminal to the earth ground of distribution panel.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 57


Chapter 3 Accura 2350 Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Chapter 3 Accura 2350-1P3FSC Operation/Setup


Operation Mode
The front of Accura 2350 consists of an LCD and one SET button showing the measured values and setup
information. The LCD screen consists of two operation modes as shown below.

Mode Function
Display Mode Display the measured values[current, power, amount of power, etc.] automatically including
Module ID. Accura 2300S setup allows you to specify the auto-cycling display of all Accura 2350
modules as a specific measurement value screen.
Setup Mode Setup of Module ID, Connection/Load direction, and so on.
If there is no button input for 10 seconds, it automatically switches to the display mode.

Button Operation

Button Description

[Display Mode] Automatically displays measured values sequentially.

Short press 1 Enter setup mode.

[Setup Mode]
Short press Each time you press the button, the next menu item is sequentially selected
[select the menu item to change].

Long press 2 Enter setup change mode.


Make the setup value changeable[blinking].

Short press Select setup value.


[Each time you press it increases the setup value one by one]

Long press Return to setup mode


Saves the selected setup value[Blinking Stop].
[Move to next digit setup or next setup menu]

1. Press and release immediately.


2. Press and hold for 1 sec, and release button.

Note
If there is no button operation for 10 seconds in setup mode, it automatically returns to display mode.
If there is no button operation for 25 seconds in setup change mode, it automatically returns to display mode

Page 58 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 3 Accura 2350 Operation/Setup

Display Mode
Front Display
Symbol
◄◄ Load direction Installed at the left side of the distribution
panel
►► Load direction Installed at the right side of the
distribution panel
ID Accura 2350 ID 1
ZCT ZCT Leakage
SET Setup Mode

1. Module ID is divided as follows. All Accura 2350s are factory-assigned as Standby ID by default.
Module ID ID Description
Communication ID ID 0 - 39 Able to communicate with Accura 2300S.
Conflict ID ID duplication Two or more IDs are the same Module ID, unable to communicate.
Standby ID ID 255 Module ID for connection status recognition, unable to communicate.

Auto-Display
Accura 2350-1P3FSC single-phase three feeder power measuring module is auto-displayed in the following
order. Short pressing SET button enters setup mode.

ID Feeder 1 Feeder 2 Feeder 3 Leakage Digital


Current/ Current/ Current/ Current 1,2 Input 1
Power Power Power

[2 sec] 3 [2 sec] 4 [2 sec] 4 [2 sec] 4 [2 sec] [2 sec]

[Auto-Display]
1. Measurement screen is supported only by Accura 2350-1P3FSC-DIZCT option module.
2. Leakage current is displayed when the leakage current threshold is set in ZCT leakage current threshold setting screen.
If "oFF" is set in the leakage current threshold setting, the leakage current is not measured and is displayed as "oFF".
3. Measurement screen is displayed for 4 seconds at Accura 2350-1P3FSC-DIZCT.
4. Measurement screen is displayed twice at Accura 2350-1P3FSC basic module.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 59


Chapter 3 Accura 2350 Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Setup Mode
Setup Menu
Each time SET button is pressed briefly, the setup menu is selected in the following sequence.
ID Connection/ Feeder Feeder1-3 Feeder1-3 Leakage DI DI
Load Phase Current Leakage Current Polarity 1
Event 1
Direction Sequence Rating Current 1 Event 1
Threshold

1. Setup screen is supported only at Accura 2350-1P3FSC-DIZCT option module.

Note
If there is no button operation for 10 seconds in setup mode, it automatically returns to display mode.
If there is no button operation for 25 seconds in setup change mode, it automatically returns to display mode

Module ID
Item Range Description
1
ID [d][d] Module ID 2 Setup
0 - 39[default 255]

1. d  decimal number.
2. Module ID is divided as follows. All Accura 2350s are factory-assigned as Standby ID by default.
Module ID ID Description
Communication ID ID 0 - 39 Able to communicate with Accura 2300S.
Conflict ID ID duplication Two or more IDs are the same Module ID, unable to communicate.
Standby ID ID 255 Module ID for connection status recognition, unable to communicate.

Note
You can manually assign Accura 2350's Module ID with SET button, but you can automatically assign the Module ID to all
Accura 2350s connected to Accura 2300S by using "Module ID Auto Assignment" setup on Accura 2300S.

Page 60 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 3 Accura 2350 Operation/Setup

Connection/Load Direction

Item Description
Ld ►►: Load Connection Load direction: right side of distribution panel
ULN : Line-to-Neutral Voltage Line-to-neutral voltage load wiring

Ld ►►: Load Connection Load direction: right side of distribution panel


ULL : Line-to-Line Voltage Line-to-line voltage load wiring

Ld ◄◄ : Load Connection Load direction: left side of distribution panel


ULN : Line-to-Neutral Voltage Line-to-neutral voltage load wiring

Ld ◄◄ : Load Connection Load direction: left side of distribution panel


ULL : Line-to-Line Voltage Line-to-line voltage load wiring

ⓒ 2015 Rootech Inc. All Rights Reserved Page 61


Chapter 3 Accura 2350 Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Feeder Phase
In “Connection/Load Direction”, this configures the phase among A,B,C,N in case of “VLN” line-to-neutral
voltage connection, and two phases among A,B,C in case of “VLL” line-to-line voltage connection.

The following configuration screen is the case of “VLN” line-to-neutral voltage connection.

Item Description
Fd.1[Feeder 1] Phase sequence configuration for feeder 1
an[AN, default] A-N line-to-neutral voltage load connection

Fd.2[Feeder 2] Phase sequence configuration for feeder 2


bn[BN, default] B-N line-to-neutral voltage load connection

Fd.3[Feeder 3] Phase sequence configuration for feeder 3


cn[CN, default] C-N line-to-neutral voltage load connection

Page 62 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 3 Accura 2350 Operation/Setup

The following configuration screen is the case of “VLL” line-to-line voltage connection.

Item Description
Fd.1[Feeder 1] Phase sequence configuration for feeder 1
ab[AB, default] A-B line-to-line voltage load connection

Fd.2[Feeder 2] Phase sequence configuration for feeder 2


bc[BC, default] B-C line-to-line voltage load connection

Fd.3[Feeder 3] Phase sequence configuration for feeder 3


ca[CA, default] C-A line-to-line voltage load connection

ⓒ 2015 Rootech Inc. All Rights Reserved Page 63


Chapter 3 Accura 2350 Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Feeder 1 Rating Current


Item Description
Fd.1 : Feeder 1 Rating current is used as the reference value
A: A-N Load connection 1 of TDD index and bar graph.

Rating Current[default rating current] 2 Rating current can be only configured for the
smaller value than the default rating current.

1. In case of line-to-neutral voltage connection, it is displayed as the one of phase A, B, C and in case of line-to-line
voltage connection, it is displayed as one line-to-line among AB, BC, CA.
2. The rating current for each Accura 2350 single-phase three feeder power measuring module is as follows.

Model Rating Current


Accura 2350-1P3FSC-125A 125A
Accura 2350-1P3FSC-125A-DIZCT
Accura 2350-1P3FSC-60A 60A
Accura 2350-1P3FSC-60A-DIZCT

Feeder 2 Rating Current


Item Description
Fd.2: Feeder 2 Rating current is used as the reference value
B 1: B-N Load connection of TDD index and bar graph.

Rating Current[default rating current] Rating current can be only configured for the
smaller value than the default rating current.

1. It is the case that line-to-neutral connection is set to B phase.

Feeder 3 Rating Current


Item Description
Fd.3: Feeder 3 Rating current is used as the reference value
C 1: C-N Load connection of TDD index and bar graph.

Rating Current[default rating current] Rating current can be only configured for the
smaller value than the default rating current.

1. It is the case that line-to-neutral connection is set to C phase.

Page 64 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 3 Accura 2350 Operation/Setup

Feeder 1 Leakage Current Measurement


Leakage current measurement is supported only at Accura 2350-1P3FSC-DIZCT option module.
If leakage current threshold value is configured, measured ZCT leakage current is displayed. Also detecting if
the measured value exceeds the threshold value according to the leakage current event configuration, the
value is processed as leakage current event log in Accura 2300S.
Leakage current threshold value can be configured on Accura 2300S LCD screen or communication.
Threshold value configuration with Accura 2300S is commonly applied to all Accura 2350s which are
connected to Accura 2300S. In order to configure the threshold value differently for each Accura 2350,
individual configuration is needed using SET button of Accura 2350.

Item Description
1
A : ZCT through A-N Load

oFF - 999 mA[default 200] oFF : Measurement deactivated


Digit : Threshold value [mA]

1. It is the case that line-to-neutral connection is set to A phase.

Feeder 2 Leakage Current Measurement


Item Description
1
B : ZCT through B-N Load

oFF - 999 mA[default 200] oFF : Measurement deactivated


Digit : Threshold value [mA]

1. It is the case that line-to-neutral connection is set to B phase.

Feeder 3 Leakage Current Measurement


Item Description
1
C : ZCT through C-N Load

oFF - 999 mA[default 200] oFF : Measurement deactivated


Digit : Threshold value [mA]

1. It is the case that line-to-neutral connection is set to C phase.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 65


Chapter 3 Accura 2350 Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Leakage Current Event


Leakage current measurement is supported only at Accura 2350-1P3FSC-DIZCT option module.
Event configuration is possible at leakage current measurement activated. If leakage current measurement is
configured as “oFF”, leakage current event configuration is invalid. If leakage current measurement is
configured as on, in case measured ZCT leakage current value exceeds the threshold value, the value is
performed as event logs in Accura 2300S. Event configuration is commonly applied for all ZCT from feeder 1
to feeder 3.
Leakage current event setup threshold value can be configured with Accura 2300S LCD screen or
communication. Event configuration with Accura 2300S is commonly applied to all Accura 2350s which are
connected to Accura 2300S. To configure the leakage current differently for each Accura 2350, individual
configuration is needed using SET button of Accura 2350.

Item Description
oFF[default] Event disabled

on Event enabled

Digital Input Polarity


Digital input is supported only at Accura 2350-1P3FSC-DIZCT option module.
Logic value for digital input is configured. In case of Normal configuration, “Closed” input is configured as
logic value 1 and in case of Reverse configuration, “Open” input is configured as logic value 1. However, the
display symbol at the LCD screen is expressed as “Closed” is displayed “ㅁ” and “Open” is displayed “_”
regardless of the polarity configuration.

Item Description
nrП: Normal[default] “Closed” : Logic value 1, status “ㅁ”
“Open” : Logic value 0, status ”_”

rEu: Reverse “Closed” : Logic value 0, status “ㅁ”


“Open” : Logic value 1, status ”_”

Page 66 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 3 Accura 2350 Operation/Setup

Digital Input Event


Digital input is supported only at Accura 2350-1P3FSC-DIZCT option module.
The event processing for the digital input is configured. Configuration for the event processing is processed
corresponding to the configured status of contact point regardless of polarity configuration.

Item Description
oFF[default] Event disabled

CLS[Closed] “Closed” contacet event

oPN[Open] “Open” output event

bth[Both] “Closed/Open” output event

ⓒ 2015 Rootech Inc. All Rights Reserved Page 67


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Chapter 4 Accura 2300S Operation/Setup


Front of Accura 2300S comprises 4.7” LCD, which displays measurement information and setup, 4 LEDs
which display power supply and communication status and 4 buttons for selection of all operation states.

Device Configuration
Fig 4.1 Accura 2300S Front

Operation Mode
Accura 2300S operates in 3 modes as follows.
Mode Function
Display mode 1 Selectively displays measurements of the selected Accura 2350 Module ID.
1
Setup mode Confirms and changes the configured value of measurement and operation[connection, PT, event,
Ethernet communication, RS-485 communication, etc.].
Event log mode Displays event logs of power quality such as dip and swell event logs. Event segment on the top
bar lights up to indicate event log mode.
1. Screen column is displayed at the bottom of the LCD so you can easily check the current column position. The display of
column position is displayed differently in the display[DISPLAY] mode and in the setting[SETUP] mode.

LED Display
4 LEDs placed at the lower-left part display the operation states of Accura 2300S.
LED Name Color Function
POWER GREEN On, when the status of inner power supply of Accura 2300S is normal.
EVENT RED Blink, when start event such as Dip/Swell generates.
ETHERNET YELLOW Blink, during Ethernet communication.
MODULE YELLOW Blink, during RS-485 communication with Accura 2350.

Button Operation
Front buttons comprise 4 buttons, Left[<]/ESC, Up[^]/SETUP, Down[v]/EVENT, and Right[>]/ENTER. In case
of short press, Left[<], Up[^], Down[v], and Right[>] buttons operate as direction moving function. In case
of long press, pressing the buttons for more than 1 second, buttons operate as special functions, ESC, SETUP,
EVENT, and ENTER.
In display mode which displays the measured value, using dirction buttons, Left[<], Up[^], Down[v], and

Page 68 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Right[>], enables moving to all measurement display screen. At this time, display[DISPLAY] menu is displayed
on the screen column position display at the bottom of the LCD, so that it is easy to see which column position
the current display screen is located.

Fig 4.2 Screen of Display Mode

In order to setup and confirm the connection of Accura 2300S, PT, event, Ethernet communication and RS-485
communication, long pressing the SETUP button enables LCD screen to move to setup mode. In setup mode,
using Left[<], Up[^], Down[v], Right[>], ESC, ENTER buttons enables confirmation of the information and
modification. At this time, setup[SETUP] menu is displayed on the screen column position display at the bottom
of the LCD, so that it is easy to see which column position the current setup screen is located.

Fig 4.3 Screen of Setup Mode

If start event such as Dip[Sag]/Swell, Fuse Fail and etc. generates, EVENT LED and the LCD backlight blink to
easily recognize the occurrence of the start event. Long pressing EVENT button and entering event log mode,
start event alarm generated is cleared and event logs can be confirmed. Also in case that the event does not
generate, long pressing EVENT button enables to view event logs. In event log mode, Event segment at upper
bar is turned on.

Fig 4.4 Screen of Event Log Mode

ⓒ 2015 Rootech Inc. All Rights Reserved Page 69


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Display Mode
Front Display

Fig 4.5 Accura 2300S Front Overview


A
V Voltage
I Current
P Active Power
Q Reactive Power
S Apparent Power
E Energy
PF Power Factor
B
L-N Line-to-neutral
L-L Line-to-line
3
THD Total Harmonic Distortion[%]
FUND Fundamental
D : Upper Bar RMS True RMS[Root Mean Square]
1 1 4
Module [d][d] Accura 2350 Module ID TDD Total Demand Distortion
Event Event log display C
Leakage ZCT Leakage display A Phase A
Dip[Sag] Blinks when Dip[Sag] start event occurs B Phase B
Swell Blinks when Swell start event occurs C Phase C
MAX Maximum AB Line-to-line AB
MIN Minimum BC Line-to-line BC
DMD Demand CA Line-to-line CA
TIME Time Year/Month/Day/Hour/Min/Sec LEAD Lead phase
E : Left- Lower LED LAG Lag phase
POWER Power[LED on] AVG Three-phase average
EVENT Event[LED blinks] TOT Three-phase total
ETHERNET Ethernet[LED blinks]
2
MODULE RS-485 communication with Accura 2350
module[LED blinks]
1. d  decimal, ten digits can be up to 3. Display the module ID to display the measured information among many Accura
2350 modules connected to Accura 2300S.
2. MODULE LED blinks only by communication between Accura 2300S and Accura 2350s.

√∑31 2
𝑘=2 𝑉𝑘 √∑31 2
𝑘=2 𝐼𝑘
3. THD[Total Harmonic Distortion], Voltage THD : , Current THD :
𝑉1 𝐼1

√∑31 2
𝑘=2 𝐼𝑘
4. TDD[Total Demand Distortion]:
𝐼𝐿
Where 𝐼𝐿 can be selected on communication between current rating[default] and peak demand current.

Page 70 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

1
F: Screen Column Position Display
Display Mode Setup Mode
V·I·P·E Display of voltage, current, power and energy METER Setting Measurement Related Elements
V·FREQ Voltage, Frequency Details EVENT Setting Event-Related Elements
I Current Details COMM RS-485 communication related setting
P·PF Power and power factor details NETWORK Setting Ethernet-related elements
DEMAND Demand power, demand current information RESET Setting reset related elements
ENERGY Energy Details DISPLAY Setting LCD Display Details
2
MODULE Leakage current and special module information MODULE Setting Module ID
INFO Ethernet connection information MODULE Group device configuration using 1P module
ETC Temperature, time information INFO Serial number, version information, etc.
ETC Digital input display
Digital output setting / control / display
1. Screen column is displayed at the bottom of the LCD so you can easily check the current column position. The display of
column position is displayed differently in the display[DISPLAY] mode and in the setting[SETUP] mode.
2. Accura 2350 Module ID is used as communication ID when communicating with Accura 2300S.

Start-up Time
Accura 2300S needs about 1-minute for start-up time. During the time, measurement values are not
displayed on LCD screen.

Temperature Sensor
Accura 2300S measures the temperature of Accura 2300S which is not for firewatching, but for reference only.

Fig 4.6 Accura 2300S Temperature Sensor

ⓒ 2015 Rootech Inc. All Rights Reserved Page 71


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Module ID Selection
Accura 2300S selects Module ID of Accura 2350 to display measurement values on LCD among many Accura
2350s which are communicating with Accura 2300S. In display mode, by long press of ENTER button, Module
ID on the upper left will blink at 0.4 second intervals, and Module ID can be changed by Up[^]/Down[v]
button. If you want to assign the Module ID to the changed value, press ENTER button long again. Accura
2350 Module ID is used as the communication ID for RS-485 communications with Accura 2300S.

Fig 4.7 Accura 2350 Module ID Selection at Upper Part of LCD Screen

Button Operation
Button Description

[Display Mode]
Press 1 Select display screen.

[Module ID Selection Mode]


Long press 2 Make the Module ID possible to be changed[blink].

Press Select Module ID to display 3.

Long press Set the changed Module ID and move to display mode[blink
or press stops].

1. When the button is pressed, "Beep" sounds.


2. Press for more than 1 sec. After one second, "Beep" sounds.
3. Each time Module ID is changed, measurements of Accura 2350 of the Module ID are displayed on LCD screen.

Note
Module ID blinks when:

① 1.2 second interval: In case that Accura 2300S cannot communicate with Accura 2350.
- disconnection of 6C telephone line
- changing of Module ID
- conflicting ID with Module ID

② 0.4 second interval: In case that Module ID is possible to be changed.

Page 72 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Display Full Screen


Accura 2300S displays measurements of one Accura 2350 Module ID.

Column

Summary

V·I·P·E
or

Frequency
Voltage/

V·FREQ
Current

I
Power Factor
Power/

P·PF
DEMAND
Active Energy
Rec Del Tot
Consecutively

ENERGY
Screen

MODULE
Current
Leakage
1
Port 2 INFO

Information
Ethernet

INFO
Temperature/
Date

ETC

1. Leakage current and digital input are only supported by Accura 2350-1P3FSC-DIZCT option module.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 73


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Voltage/Current/Power [V∙I∙P]

On the first screen of display screen, voltage, current and active power of feeder 1 is dipslayed[V·I·P].
In case that the load connection is line-to-netural voltage connection, it is displayed as line-to-neutral voltage.
If the load connection is line-to-line voltage connection, it is displayed as line-to-line voltage.

Fig 4.8 Line-to-neutral Voltage/Current/Power Display Screen

Fig 4.9 Line-to-line Voltage/Current/Power Display Screen

By pressing Down[v] button at the first screen, voltage, current and power of feeder 2 are displayed. By
additionally pressing the Down[v] button, the measurement of feeder 3 can be confirmed. These are
sequently displayed in the reverse order by pressing Up[ v ] button.

Voltage/Frequency [V∙FREQ]

Detailed information for voltage is displayed by pressing Right[>] button at default screen. First screen of
voltage display column displays each line-to-line voltage and average. Line-to-neutral voltage, maximum and
minimum of line-to-line voltage, maximum and minimum of line-to-neutral voltage, voltage THD, frequency
by pressing Down[v] button. These are sequently displayed in the reverse order by pressing Up[ v ] button.

Fig 4.10 Line-to-line Voltage Display Screen

Page 74 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Current [I]
Detailed information for current is displayed by repressing Right[>] button at VOLTAGE column display screen.
First screen of current display column displays rms currents for three feeders. And fundamental current,
maximum and minimum of current, current THD, current TDD of three feeders are sequently displayed by
pressing Down[ v ] button. These are sequently displayed in the reverse order by pressing Up[ v ] button.

Fig 4.11 Current Display Screen

Power/Power Factor [P∙PF]

Detailed information for power and power factor is displayed by repressing Right[>] button at CURRENT
column display screen. First screen of power display column displays active power of three feeder[P]. And
reactive power[Q], apparent power[S], maximum and minimum of active power, maximum of reactive power,
maximum of apparent power, power factor are sequently displayed by pressing Down[ v ] button. These are
sequently displayed in the reverse order by pressing Up[ v ] button.

Fig 4.12 Power Display Screen

ⓒ 2015 Rootech Inc. All Rights Reserved Page 75


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Demand [DEMAND]
Detailed information for demand power and demand current of three feeder is displayed by repressing
Right[>] button at POWER column display screen. First screen of demand display column displays demand
active power of three feeder, and demand current, maximum of demand active power and maximum of active
current are sequently displayed by pressing Down[ v ] button. These are sequently displayed in the reverse
order by pressing Up[ v ] button.

Fig 4.13 Demand Active Power Display Screen

Active Energy [ENERGY]


Detailed information for energy is displayed by repressing Right[>] button at DEMAND column display screen.
First screen of energy display column displays net energy of feeder 1 and net energy of feeder 2 and feeder 3
are sequently displayed by pressing Down[ v ] button. Then, received energy, delivered energy, total energy
are sequently displayed. These are sequently displayed in the reverse order by pressing Up[ v ] button. Net
energy is the value that subtracts delivered energy from received energy. Total energy is the value that adds
received energy and delivered energy.

Fig 4.14 Net Energy Display Screen of Feeder 1

Leakage Current [MODULE]


Leakage current input and digital input are supported only at Accura 2350-1P3FSC-DIZCT option module.
Leakage current measurement of 3 ZCT channels and contact status of 4 digita input[DI] are displayed by
repressing the Right[>] button at the ENERGY display screen. Module ID of the uppe bar is one of the module
ID of single-phase three feeder power measuring module with ZCT measurement function.
In case that ZCT measurement function is not activated, the leakage current value is displayed as “oFF”. ZCT
measurement function is activated by configuring the threshold value on the module LCD screen for the value

Page 76 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

that is not 0. Digital status is displayed on the fourth row as the contact status from channel 1 to channel 4
starting from left to right. “Closed” is displayed as “ㅁ” and, “Open” is “_”. In case that there is no single-
phase three feeder power measuring module with ZCT measurement function, the screen moves to INFO
menu screen immediately.

Fig 4.15 Leakage Current Display Screen

Ethernet Information [INFO]


The screen moves to product information[INFO] menu screen by repressing Right[>] button at MODULE
column display screen. At INFO screen, Ethernet connection information can be recognized.
First screen displays Ethernet connection status for two Ethernet ports. And corresponding device information
that is connected to Ethernet port 1, IP address and MAC address are sequently displayed by pressing
Down[ v ] button. Then, device information that is connected to Ethernet port 2, IP address and MAC address
are sequently displayed. These are sequently displayed in the reverse order by pressing Up[ v ] button.
In case RSTP configuration of Ethernet communication configuration is OFF, only the Ethernet connection
status information for the port is displayed. Corresponding IP address and MAC address information for the
port is not displayed. Also, IP information is displayed only in case that the corresponding device is Accura
device.

Fig 4.16 Ethernet Connection Display Screen

Connection status for each port and RSTP roles for each port are displayed. At second row, the status of
Ethernet port 1 is displayed. At third row, the status of Ethernet port 2 is displayed. The status descriptions are
as follows.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 77


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Port Status Term Port Status 1 Desciption


rt Root port Route for RSTP Root Node
dg Designated port Route for RSTP Leaf Node
bu Backup port Alternative route for same LAN
at Alternative port Alternative route for same RSTP Root Node
Cn Connecting Port connected. Determining RSTP roles
__ No connection Port disconnected.
1. Refer to RSTP[Rapid Spanning Tree Protocol], IEEE 802.1D-2004 for detailed description for terms.

At fourth row, etherent connection status is displayed. Descriptions are as follows.

Ethernet Status Term Ethernet Status Description


Star Star connection Ethernet loop including this Accura 2300 is not formed. In
Daisy-Chain connection this case as there is no alternative route, if connected port is
disconnected, network disconnection occurs with adjacent
Accura 2300.
rIng Ring connection Ethernet loop including this Accura 2300 is formed. In this
case, even if connected port is disconnected, network
disconnection does not occur as for automatically finding
alternative route.
No.Cn No connection Both ports are disconnected.

Temperature/Time [ETC]
The screen enters ETC menu screen by repressing Right[>] button at INFO column display screen. At ETC
screen, measured temperature and current time can be recognized by temperature sensor at Accura 2300S
rear side.

Fig 4.17 Accura 2300S Rear Surface Temperature Display Screen

Page 78 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Setup Mode
Move to setup mode by long pressing SETUP button to confirm and configure connection, PT, event, Ethernet
communication, RS-485 communication of Accura 2300S. Values can be confirmed and modified by using
Left[<], Up[^], Down[v], Right[>], ESC, and ENTER buttons. At this time, setup[SETUP] menu is displayed
on the screen column position display at the bottom of LCD to display the current column position.

Button Description

[Display Mode] Description

Press 1 Select display screen.

[Setup Mode]

Long press 2 Enter setup mode.

Press Select setup menu screen.

Long press Make the value to status[blink] that the value is changeable.

Press Select the configuration value

Or

Press Move to the next[left or right] digit value

Long press Save the changed value[blink stops].

Or

Long press Do not save the changed value[blink stops].

Long press Exit setup mode and move to display mode.

1. When the button is pressed, "Beep" sounds.


2. Press for more than 1 sec. After one second, "Beep" sounds.

Note

If there is no button operation for 10 minutes in setup mode, it automatically returns to display mode.
If there is no button operation for 1 minute while modifying set value, it automatically returns to setup mode.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 79


Accura 2300S/2350-1P3FSC User Guide

ⓒ 2015 Rootech Inc. All Rights Reserved


Column METER EVENT COMM NETWORK RESET DISPLAY MODULE MODULE INFO ETC
Start leakage 3CT group
Connection Dip event Fuse Fail event current Speed IP Demand reset Energy type ID Update assignment Serial number DI status
Dip start Temperature Leakage A2350 Hardware
PT rating voltage event current time Parity beat Subnet mask Max/min reset display ID Setup 2CT group version DO output type
Reference Dip Start Demand LCD display Additional Software
voltage end voltage temperature current event Stop beat Gateway Energy reset time assignment version DO polarity
Demand End Start demand
sub-interval Swell event temperature current Address Mac address All reset Event B/L Time Pulse period
Number of Swell start
sub-interval voltage Current event Power event RS-485 map NTP sync Event LED Time Pulse on time
Swell end LCD B/L
Phase Power voltage Start current Start power NTP server Brightness DO interlock
Chapter 4 Accura 2300S Operation/Setup

Event Blink Energy


Total Power End current End power TCP timeout Period per pulse
Event Blink DI Channel 1 Energy
PF sign Current time Power time RSTP On-time Event Module ID
Setup Full Screen

Leakage current Storm DI Channel 2 DO output


No load PF Energy Unit event 1P3F DI event DHCP Blocking Demo Event control

Page 80
Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Measurement [METER]
Voltage Connection
Setup range Description
3P4U [default] 3-Phase 4-wire [3P4W]
3P3U 3-Phase 3-wire [3P3W]
1P3U Single-phase 3-wire [1P3W]
1P2U Single-phase 2-wire [1P2W]
1
3P3O 3-Phase 3-wire Open-Delta [3P3O]

1. “3P3O” is setup menu for some older Accura 2300 that is not supported for 3P3W voltage connection in Accura 2300
for 3-phase 3-wire voltage connection. It works as 3P3W connection even if it is set to 3P3O connection.

PT Rating
Ratio of primary and secondary line-to-line voltage ratio is used as conversion ratio for primary voltage.
Regardless of voltage connection for measurement, always PT primary and secondary line-to-line voltage
should be input.

Setup range Description


1
Pr[d][d][d][d][d][d] PT primary line-to-line voltage rating
000001 – 999999 1 - 999999
[default 380]
Sc[d][d][d] 1 PT secondary line-to-line voltage rating
001 – 999 1 - 999
[default 380]

1. d  decimal

Primary and secondary line-to-line voltage for each connection method is as follows. In case of direct
connection without using PT, primary and secondary line-to-line voltage should be input as the same value.

Fig 4.18 3-phase 4-wire connection[3P4W]: PT Primary VAB , Secondary V12

ⓒ 2015 Rootech Inc. All Rights Reserved Page 81


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Fig 4.19 3-phase 3-wire connection[3P3W]: PT Primary VAB , Secondary V12

Fig 4.20 1-phase 3-wire connection[1P3W]: PT Primary VL12 , Secondary V13

Neutral-line is the center point between Line1 and Line2, and must be connected to V1, V3, VN terminals.

Fig 4.21 1-phase 2-wire connection[1P2W]: PT Primary VL12 , Secondary V1N

Line1-Line2, line-to-line or line-to-neutral voltage connection is possible.


Line1-Line2, line-to-line or line-to-neutral voltage can be wired, and must be connected to V1, VN terminals.

Page 82 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Reference Voltage
This reference voltage is referred as the reference voltage value for Dip[Sag]/Swell detection. Reference
voltage should be primary voltage value, does not have to be the same value with the rating voltage and the
value that is the real reference may be input. In case of 3P4W or 1P3W setup, primary line-to-line voltage or
line-to-neutral voltage can be selectively input.

Setup range Description


1
VL-L / VL-N Primary line-to-line voltage or line-to-neutral
[d][d][d][d][d][d] 2 000001 ~ 999999

1. It can be selected only for 3P4W and 1P3W connection, but it is fixed to line-to-line voltage in other connection.
2. d  decimal number.

In each voltage connection, the reference voltage is determined as follows.

Voltage Connection Setup Type Description


3-phase 4-wire[3P4W] Line-to-line voltage setup Line-to-neutral reference voltage
= 1⁄√3 * Line-to-line voltage setup value
Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
3-phase 3-wire[3P3W] Line-to-line voltage setup Line-to-line reference voltage
= 1* Line-to-line voltage setup value
1-phase 3-wire[1P3W] Line-to-line voltage setup Line-to-neutral reference voltage
= 1⁄2 * Line-to-line voltage setup value
Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
1-phase 2-wire[1P2W] Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value

Demand Sub-interval
Accura 2300S uses sliding window demand power calculation method.
Demand time[minute]= Demand sub-interval x Number of demand sub-interval
ex] For the case with 15-minute demand time, demand sub-interval is 15-minute and number of demand
sub-interval is 1. Refer to “Chapter 5>Demand Measurement” for details.

Setup range Description


1 - 60 minutes[default 15] Demand sub-interval time

ⓒ 2015 Rootech Inc. All Rights Reserved Page 83


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Number of Demand Sub-interval

Setup range Description


1 - 12[default 1] Number of demand sub-interval

Phase Power Calculation Method


Accura 2300S supports two methods for calculation of reactive power[Q] and apparent power[S] for each
phase. One is to calculate the power based on fundamental voltage and current, and the other is to calculate
the power based on RMS voltage and RMS current considering harmonic components. Refer to “Chapter
5>Phase Power Measurement” for details.

Setup range Description


Fund[default] Fundamental component calculation
HarM Harmonic component calculation

Total Power Calculation Method


Accura 2300S supports two methods for calculation of total power from phase power. One is to calculate the
total power based on vector-sum of 3-phase apparent power vectors. And the other is that to calculate the
total power based on only arithmetic sum of magnitudes of 3-phase apparent power vectors. Refer to
“Chapter 5>Three-Phase Total Power Measurement” for details. Three-phase total power is not applicable to
Accura 2350-1P3FSC single-phase three feeder power measuring module.

Setup range Description


UEct[default] Vector-sum calculation
SCaLa Arithmetic sum calculation

Page 84 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Power Factor Sign


Power factor is basically determined by the sign of active power. The sign of power factor makes it possible to
know whether the direction of power flow is a received state or a delivered state. In case of displaying the
power factor only for absolute value, configure the sign as “OFF”.

Setup range Description


on[default] Real power factor with sign
oFF Absolute power factor
without sign

Power Factor Display at No Load


In case that apparent power is 0(no load state), power factor is not deterministic by formula. Configure power
factor display for this case. For details, refer to "Chapter 5>Power Factor Measurement".

Setup range Description


1.0 [default] 1.0 display
0.0 0.0 display

Energy Scale
The unit of accumulated energy can be set to kWh or Wh. When converting from kWh to Wh, multiply the
accumulated energy by 1000, and conversely, when converting from Wh to kWh, It is converted into an
integer value after dividing by 1000.

Setup range Description


1 kWh[default] Energy is accumulated in 1 kWh scale.
1000 Wh Energy is accumulated in 1 Wh scale.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 85


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Event [EVENT]
Dip Event
In case of configuring Dip event as “on”, the screen that configures Dip start voltage and end voltage are
displayed. In case of configuring Dip event as “oFF”, the screen immediately moves to Swell event setup
screen.

Setup range Description


oFF[default] Event off
on Event on

Dip Start Voltage


Dip start voltage is configured as a percentage to reference voltage. Dip start event is generated when the
measured voltage goes below the start voltage.

Setup range Description


1.0 - 98.0% [default 90.0%] Percentage of Dip reference voltage

Dip start voltage display


VL-N [Line-to-neutral] 3P4W/1P3W/1P2W connection
VL-L[Line-to-line] 3P3W connection
[d][d][d].[d] V/kV Dip reference voltage * Percentage

In each voltage connection, dip/swell reference voltage is determined as follows.

Voltage Connection Setup Type Description


3-phase 4-wire[3P4W] Line-to-line voltage setup Line-to-neutral reference voltage
= 1⁄√3 * Line-to-line voltage setup value
Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
3-phase 3-wire[3P3W] Line-to-line voltage setup Line-to-line reference voltage
= 1* Line-to-line voltage setup value
1-phase 3-wire[1P3W] Line-to-line voltage setup Line-to-neutral reference voltage
= 1⁄2 * Line-to-line voltage setup value
Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
1-phase 2-wire[1P2W] Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value

Page 86 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Dip End Voltage


Dip end voltage is configured as percentage to reference voltage. Dip end event is generated when measured
voltage returns above the end voltage. Hysteresis voltage exists between start voltage and end voltage to
prevent a large number of short events and minimum Hysteresis is 1%. In other words, end voltage can be
configured at least 1% higher than start voltage. If start voltage is configured higher than end voltage, end
voltage is automatically reconfigured 1% higher than start voltage.

Setup range Description


2.0 - 99.0% [default 92.0%] Percentage of Dip reference voltage

Dip end voltage display


VL-N [Line-to-neutral] 3P4W/1P3W/1P2W connection
VL-L[Line-to-line] 3P3W connection
[d][d][d].[d] V/kV Dip reference voltage * Percentage

Fig 4.22 Dip Event Setup[3-phase 4-wire]

Reference voltage: Line-to-line voltage


380V setting

Fig 4.23 Dip Event Setup[3-phase 3-wire]

Reference voltage: Line-to-line voltage


380V setting

ⓒ 2015 Rootech Inc. All Rights Reserved Page 87


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Swell Event
In case of configuring Swell event as “on”, the screen that configures Swell start voltage and Swell end voltage
are displayed. In case of configuring Swell event as “oFF”, the screen immediately moves to reference voltage
percentage setup screen.

Setup range Description


oFF[default] Event off
on Event on

Swell Start Voltage


Swell start voltage is configured as a percentage to reference voltage. Swell start event is generated when the
measured voltage goes above start voltage.

Setup range Description


102.0 - 999.0% [default 110.0%] Percentage of Swell reference voltage

Swell start voltage display


VL-N [Line-to-neutral] 3P4W/1P3W/1P2W connection
VL-L[Line-to-line] 3P3W connection
[d][d][d].[d] V/kV Swell reference voltage * Percentage

In each voltage connection, dip/swell reference voltage is determined as follows.

Voltage Connection Setup Type Description


3-phase 4-wire[3P4W] Line-to-line voltage setup Line-to-neutral reference voltage
= 1⁄√3 * Line-to-line voltage setup value
Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
3-phase 3-wire[3P3W] Line-to-line voltage setup Line-to-line reference voltage
= 1* Line-to-line voltage setup value
1-phase 3-wire[1P3W] Line-to-line voltage setup Line-to-neutral reference voltage
= 1⁄2 * Line-to-line voltage setup value
Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
1-phase 2-wire[1P2W] Line-to-neutral voltage setup Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value

Page 88 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Swell End Voltage


Swell end voltage is configured as percentage to reference voltage. Swell end event is generated when
measured voltage returns below the end voltage. Hysteresis voltage exists between start voltage and end
voltage to prevent a large number of short events and minimum Hysteresis is 1%. In other words, end voltage
can be configured at least 1% lower than start voltage. If start voltage is configured lower than end voltage,
end voltage is automatically reconfigured 1% lower than start voltage.

Setup range Description


101.0 - 998.0% [default 108.0%] Percentage of Swell reference voltage

Swell end voltage display


VL-N [Line-to-neutral] 3P4W/1P3W/1P2W connection
VL-L[Line-to-line] 3P3W connection
[d][d][d].[d] V/kV Swell reference voltage * Percentage

Fig 4.24 Swell Event Setup[3-phase 4-wire]

Reference voltage: Line-to-line voltage


380V setting

Fig 4.25 Swell Event Setup[3-phase 3-wire]

Reference voltage: Line-to-line voltage


380V setting

ⓒ 2015 Rootech Inc. All Rights Reserved Page 89


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Fuse Fail Event


When the voltage is measured as 0 in each phase and the current is measured as a non-zero value, it is
judged that the fuse of the corresponding phase is Fuse Fail. Fuse Fail start event is generated when it is
judged as Fuse Fail, and Fuse Fail end event is generated when it is restored to normal.

Setup range Description


oFF[default] Event off
on Event on

Temperature Event
Temperature of Accura 2300S side temperature sensor is different from the actual temperature in the
distribution panel due to temperature difference of the measured value depending on the number of Accura
2350 connected to Accura 2300S, so caution is required when setting the temperature event. When the
temperature event is set to on, a screen for setting the start temperature and end temperature are displayed. If
the temperature event is set to off, setup screen moves to current event setup screen directly.

Setup range Description


oFF[default] Event off
on Event on

Start Temperature
Temperature start event is generated when measured temperature goes above start temperature.

Setup range Description


20 - 9999 ℃ [default 50 ℃] Start temperature

Page 90 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

End Temperature
Temperature end event is generated when measured temperature returns below the end temperature.
Hysteresis exists between start temperature and end temperature to prevent a large number of short events
and minimum Hysteresis is 1%. In other words, end temperature can be configured at least 1% lower than
start temperature. If start temperature is configured lower than end voltage, end temperature is automatically
reconfigured 1% lower than start temperature.

Setup range Description


0 - 9998 ℃ [default 48 ℃] End temperature

Current Event
When the current event is set to on, the screens that configure start current, end current and current delay time
are displayed. If the current event is set to off, setup screen moves to leakage current event setup screen.

Setup range Description


oFF[default] Event off
on Event on
Commonly applied to all Accura 2350s.

Start Current
Current start event is generated when measured current goes above start current and maintains upward status
for exceeding current delay time.

Setup range Description


5.0 - 999.0 % [default 100.0%] Start current percentage
Reference current for percentage is rating current for each Accura 2350.
Commonly applied to all Accura 2350s.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 91


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

End Current
Current end event is generated when the measured current returns below the end current. Hysteresis exists
between start current and end current to prevent a large number of short events and minimum Hysteresis is
1%. In other words, end current can be configured at least 1% lower than the start current. If start current is
configured lower than end voltage, end current is automatically reconfigured 1% lower than start current.

Setup range Description


0.0 - 998.0 % [default 98.0%] End current percentage
Reference current for percentage is rating current for each Accura 2350.
Commonly applied to all Accura 2350s.

Current Delay Time


Current start event is generated when the measured current goes above start current and maintains upward
status for exceeding current delay time.

Setup range Description


0, 1 - 999 sec [default 1 sec] Current delay time[sec]

0 setup: Current delay time is 0.5-second.


Commonly applied to all Accura 2350s.

Leakage Current Event


When the leakage current event is set to on, the screens that configure start leakage current and leakage
current delay time are displayed. If the leakage current event is set to off, setup screen moves to demand
current event setup screen.

Setup range Description


All.oFF[default] Event off
All.on Event on
no.SEL Exit change mode to previous setup mode.
Commonly applied to all Accura 2350s.
Individual setup for each module can be done in each Accura 2350 module.

Start Leakage Current


Leakage current start event is generated when the measured leakage current goes above start leakage current
and maintains upward status for exceeding leakage current delay time.

Page 92 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Setup range Description


0.02 - 1.00 A [default 0.20 A] Start leakage current
Commonly applied to leakage current measurements of all Accura 2350s.
Individual setup for each module can be done in each Accura 2350 module.

Leakage Current Delay Time


Leakage current start event is generated when measured leakage current goes above start leakage current
and maintains upward status for exceeding leakage current delay time.

Setup range Description


0 - 999 sec [default 1sec] Leakage current delay time[second]
0 setup: Leakage current delay time is 0.5-second.
Commonly applied to all Accura 2350s.
Individual setup for each module can be done in each Accura 2350 module.

Demand Current Event


When the demand current event is set to on, the screen that configures start demand current is displayed. If
the demand current event is set to off, setup screen moves to power event setup screen.

Setup range Description


oFF[default] Event off
on Event on
Commonly applied to all Accura 2350s.

Start Demand Current


Demand current start event is generated when the measured demand current goes above start demand
current.

Setup range Description


5.0 - 999.0 % [default 70.0%] Start demand current percentage
Reference current for percentage is rating current for each Accura 2350.
Commonly applied to all Accura 2350s.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 93


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Power Event
Selects and activates power event for total or each phase for the power event. In case of each phase, the event
for the all each phase is detected, and in case of total, the event only for the total power is detected.

Setup range Description


oFF[default] No event
Pha.on Each phase power event
tot.on Total power event

Start Power
Power start event is generated if the measured power goes above the start power and maintains upward status
for exceeding power delay time. Start power level can be configured as percentage or power value.

Setup range Description


1
5.0 - 999.0 % [default 100.0%] Percentage of reference power
Reference power for percentage is obtained by multiplying rating voltage by
rating current for each Accura 2350.
Commonly applied to all Accura 2350s.

1. Reference power is as follows.


Voltage connection Reference voltage Phase reference power Total reference power
1 3
3P4W VLL 𝑉𝐿𝐿 / √3 ∗ 𝐼𝑟𝑎𝑡 √3 ∗ 𝑉𝐿𝐿 ∗ 𝐼𝑟𝑎𝑡
VLN 2 𝑉𝐿𝑁 ∗ 𝐼𝑟𝑎𝑡 3 ∗ 𝑉𝐿𝑁 ∗ 𝐼𝑟𝑎𝑡
3P3W VLL 𝑉𝐿𝐿 / √3 ∗ 𝐼𝑟𝑎𝑡 √3 ∗ 𝑉𝐿𝐿 ∗ 𝐼𝑟𝑎𝑡
1P3W VLL 𝑉𝐿𝐿 / 2 ∗ 𝐼𝑟𝑎𝑡 𝑉𝐿𝐿 ∗ 𝐼𝑟𝑎𝑡
VLN 𝑉𝐿𝑁 ∗ 𝐼𝑟𝑎𝑡 2 ∗ 𝑉𝐿𝑁 ∗ 𝐼𝑟𝑎𝑡
1P2W VLL 𝑉𝐿𝐿 ∗ 𝐼𝑟𝑎𝑡 𝑉𝐿𝐿 ∗ 𝐼𝑟𝑎𝑡
1. VLL means primary line-to-line voltage.
2. VLN means primary line-to- neutral voltage.
3. Irat means rating current for each module.

End Power
Power end event is generated if the measured power goes below end power. Hysteresis exists between start
power and end power to prevent short and several event generations. So, the end power should be
configured at least 1% lower than the start power. If the start power is configured lower than the end power,
end power is automatically reconfigured 1% lower than the start power. End power level can be configured as
percentage or power value.

Page 94 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Setup range Description


1
0.0 - 998.0 % [default 98.0%] Percentage of reference power
Reference power for percentage is obtained by multiplying rating voltage by
rating current for each Accura 2350.
Commonly applied to all Accura 2350s.

1. Reference power is the same as that shown in the start power.

Power Delay Time


Power start event is generated if the measured power goes above the start power and maintains upward status
for exceeding power delay time. Delay time can be configured as the second unit up to 9 seconds including
the 0.5-second. Since the default time unit for calculating the power is 0.5-second, the maximum time error
for the delay time caused by this is 0.5-second.

Setup range Description


0, 1 - 9 sec [default 0] Power delay time[sec]
0 setup: Power delay time is 0.5-second.
Commonly applied to all Accura 2350s.

1P3FSC DI Event
There are 4 digital input[DI] at Accura 2350-1P3FSC-DIZCT option module and the event configuration for
this contact input is possible. The configuration through Accura 2300S is commonly applied to all connected
Accura 2350-1P3FSC-DIZCT option module and DI event for each option module is possible through the
communication or option module.

Setup range Description


All.oFF[default] No event
All.cLS[All Closed] “Closed” output event
All.oPn[All Open] “Open” output event
All.bth[All Both] “Closed/Open” output event
no.SEL Exit change mode and keep previous setting
This setup is commonly applied to all Accura 2350-1P3F-DIZCT option modules
connected to Accura 2300S.
On/off individual configuration for each module is possible at Accura 2350-
1P3FSC-DIZCT option module.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 95


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

RS-485 Communication [COMM]

Baud rate
Setup range Description
1200 1200 bps
2400 2400 bps
4800 4800 bps
9600 [default] 9600 bps
19200 19200 bps
38400 38400 bps
57600 57600 bps
11520 115200 bps

Parity bit
Setup range Description
EuEn [default] Even Parity
nonE None Parity
odd Odd Parity

Stop bit
Setup range Description
1 [default] 1-bit stop
2 2-bit stop

Device address
Setup range Description
1
[d][d][d] [default 0] 0, 1 - 247
In order to read Accura 2300S measurement values by RS-485 communication,
the device address must be set to a valid value other than 0.

1. d  decimal number.

Page 96 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

RS-485 Communication map


Setup range Description
a2300 [default] Accura 2300 Map
r050 RTM050 Map
If RS-485 communication map is set to r050, it is possible to communicate with
the same map as RTM050 map.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 97


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Ethernet Communication [NETWORK]


IP address
Setup range Description
000.000.000.000 - 255.255.255.255 IP address
[default 010.010.010.100]

Subnet Mask
Setup range Description
255.255.000.000 - 255.255.255.252 Subnet mask
[default 255.255.255.000]

Gateway
Setup range Description
000.000.000.000 - 255.255.255.255 Gate way
[default 010.010.010.001]

Mac. Address
Setup range Description
1
[h][h].[h][h] MAC address
[h][h].[h][h]
[h][h].[h][h]

1. h  hexadecimal number.

Page 98 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

NTP Time Synchronization


Setup range Description
Sync Synchronize the time of Accura 2300S
with NTP server.
Press and hold ENTER button to make Sync blink, then press and hold ENTER
button again to stop Sync blinking. Time Sync is complete.

NTP Server
Enter NTP[Network Time Protocol] server IP address for time synchronization of Accura 2300S
Setup range Description
000.000.000.000 - 255.255.255.255 IP address of NTP server
[default 010.010.010.001]

Modbus-TCP timeout
Setup range Description
5 - 600 sec [default 600 sec] Timeout for no request of Modbus-
TCP communication.

RSTP
Setup range Description
oFF [default] RSTP disable
on RSTP enable

ⓒ 2015 Rootech Inc. All Rights Reserved Page 99


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

DHCP
Setup range Description
oFF [default] DHCP disable
on DHCP enable

Storm Blocking
Setup range Description
oFF [default] Storm blocking disable
on Storm blocking enable

Page 100 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Reset [RESET]
Demand Reset
Setup range Description
dMd rESEt Demand reset

Maximum/Minimum Reset
Setup range Description
Max Min rESEt Maximum/Minimum reset
Peak Demand is also reset.

Energy Reset
Setup range Description
Enrg rESEt Energy[kWh, kVARh, kVAh] reset

All Reset
Setup range Description
ALL rESEt All[Demand, Maximum/Minimum,
Energy] reset

ⓒ 2015 Rootech Inc. All Rights Reserved Page 101


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Display [DISPLAY]
Energy Type
Energy type is configured to select value of energy in voltage/current/power/energy display screen of display
mode.

Setup range Description


nEt[default] Net[kWh received – kWh delivered]
rEc kWh received
dEL kWh delivered
tot Sum[kWh received + kWh delivered]

Accura 2350 Display Control


Configuration terms are written in case of Accura 2350-3P three-phase measuring module. The
coreresponding operations for Accura 2350-1P3FSC-DIZCT option module are as follows.

Setup range Description


rot[Rotation, default] Rotation display
[IDPhase current/powerThree-phase
current average/powerThree-phase energy]
Id[ID] ID display[ID]
Ph_a[Phase A] Feeder 1 current display[Phase A]
Ph_b[Phase B] Feeder 2 current display[Phase B]
Ph_c[Phase C] Feeder 3 current display[Phase C]
abc[ABC] Feeder 1-3 ZCT leakage current display 1
Enrg[Energy] Digital Input[DI] 4-channel display 2
PSEq[Phase Sequence] Connection/Load direction display
Ctr[CT ratio] CT ratio display
Irat[I rating] Rating current display
1. Display screen of Accura 2350-1P3FSC-DIZCT option module, and it is display screen for feeder1 at the basic module.
2. Display screen of Accura 2350-1P3FSC-DIZCT option module, and it is display screen for feeder 2 at the basic module.

LCD Backlight Time


Setup range Description
10 - 300 sec [default 60sec] LCD backlight time setup
When the LCD backlight time elapses from the last button, the 'LCD brightness' is
changed to the low setting value to reduce power consumption.

Page 102 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Event LCD Time


Setup range Description
Пo.OFF, 0 - 9999 min Setup of LCD backlight blink time when an
[default 0] event occurs
Пo.OFF: blink time ∞
0: blink time 5sec
[d][d][d][d]: blink time 1 - 9999 min
When the start event occurs, the LCD backlight blinks for this setup time. When
No.OFF is set, LCD backlight blinking disappears by checking the event log.

Event LED Time


Setup range Description
Пo.OFF, 0 - 9999 min Setup of EVENT LED blink time when an event
[default Пo.OFF] occurs
Пo.OFF: blink time ∞
0: blink time 5sec
[d][d][d][d]: blink time 1 - 9999 min
When the start event occurs, the EVENT LED blinks for this setup time. When
No.OFF is set, EVENT LED blinking disappears by checking the event log.

LCD Brightness
Setup range Description
H 0 - 99 % [default 90%] The highest brightness
M 0 - 99 % [default 40%] The middle brightness
L 0 - 99 % [default 0%] The lowest brightness
The LCD backlight blink is periodically alternating between the highest brightness
and middle brightness.

Event LCD Blink Period


Setup range Description
0.1- 10.0 sec [default 1.0 sec] Setup of LCD blink period

ⓒ 2015 Rootech Inc. All Rights Reserved Page 103


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Event LCD Blink On-time


Setup range Description
0.1- 10.0 sec [default 0.5-sec] Setup of LCD blink on-time

Demo
Setup range Description
oFF[default] Demo off
baL 3-phase Balance demo on
UnbaL 3-phase Unbalance demo on
dIP.S Short Dip demo on
dIP.L Long Dip demo on
SUL.S Short Swell demo on
SUL.L Long Swell demo on

Page 104 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Module ID [MODULE]

Module ID Update

Module ID Status
cn[Communication] 1,4 Number of communicable IDs(automatic recognition)
cF[Conflict] 2,4 Number of conflict/standby IDs(automatic recognition)
to[Total] 3,4 Total number of Module IDs (automatic recognition)
Update of Communicable Module ID Information for module management
IduP[ID Update] 5 Long Press Right[>] button to update module ID
information

1. cn[Communication]: Accura 2300S communicates with Accura 2350 in real time using communicable module ID
information.
2. cF[Conflict]: Number of Accura 2350 modules with duplicate ID[ID collision] or Standby ID. These Accura 2350s cannot
communicate with Accura 2300S.
3. to[Total]: Number of Accura 2350 modules that are physically connected.
4. When Accura 2300S and 2350 are physically connected, they are automatically recognized and displayed.
5. Execute ID update after resolving cF[Conflict] module, then UNIT segment at the upper left will also stop blinking and
stay on. If there is a change in the connected modules after this, the change is indicated by blinking UNIT segment again.

Module ID ID Description
Communication ID ID 0 - 39 Able to communicate with Accura 2300S.
Conflict ID ID Duplication Two or more IDs are the same Module ID, unable to communicate.
1
Standby ID ID 255 Module ID for connection status recognition, unable to communicate.
1. All Accura 2350s are factory-assigned as standby IDs by default.

Note
cF number is nonzero and blinks[Two or more Accura 2350s with duplicate IDs are recognized, or Accura 2350 modules

with Standby IDs exist].

① Assign conflict IDs of Accura 2350 with another communicable ID.

② After eliminating all collisions , execute IduP[Id Update] to update the information of communicable Accura 2350s.

Module ID Auto Assignment


The communicable Module ID 1 of Accura 2350 can be automatically assigned in the following 4 ways.
Setup range
RJ-1 Inc2 Module ID is increased by 2 from RJ-1. Refer to page 106.
RJ-1 Inc2 Module ID is increased by 2 from RJ-2. Refer to page 106.
RJ-1 Inc1 Module ID is increased by 1 from RJ-1. Refer to page 107.
RJ-1 Inc1 Module ID is increased by 1 from RJ-2. Refer to page 107.
StbY All modules are initialized to standby ID. Refer to page 108.

1. Communicable Module ID: 0 - 39.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 105


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Setup range Description


RJ-1 Inc2 Auto-assign 1 Module ID with standby ID 2 by 2-increment [0, 2, 4, …] in order of connection to RJ12-1 port.
Auto-assign Module ID with standby ID by 2-increment [1, 3, 5, …] in order of connection to RJ12-2 port.

[Assigned standby ID] [Auto-assigned module ID]

RJ-2 Inc2 Auto-assign 1 Module ID with standby ID 2 by 2-increment [0, 2, 4, …] in order of connection to RJ12-2 port.
Auto-assign Module ID with standby ID by 2-increment [1, 3, 5, …] in order of connection to RJ12-1 port.

[Assigned standby ID] [Auto-assigned module ID]

1. If a module is already assigned to a specific communicable ID, it is excluded from automatic assignment.
2. All Accura 2350s are factory-assigned as standby IDs by default.

Page 106 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Setup range Description


RJ-1 Inc1 Auto-assign 1 Module ID with standby ID 2 by 1-increment [0,1,2,.. N] in order of connection to RJ12-1 port.
Auto-assign Module ID with standby ID by 1-increment [N+1,N+2…] in order of connection to RJ12-2 port.

[Assigned standby ID] [Auto-assigned Module ID]

RJ-2 Inc1 Auto-assign 1 Module ID with standby ID 2 by 1-increment [0,1,2,.. N] in order of connection to RJ12-2 port.
Auto-assign Module ID with standby ID by 1-increment [N+1,N+2…] in order of connection to RJ12-1 port.

[Assigned standby ID] [Auto-assigned Module ID]

1. If a module is already assigned to a specific communicable ID, it is excluded from automatic assignment.
2. All Accura 2350s are factory-assigned as standby IDs by default.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 107


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

StbY [Standby] Assign all Accura 2350s as standby ID 1.

[Assigned specific Module ID] [Assigned standby ID]

1. All Accura 2350s are factory-assigned as standby IDs by default.

Page 108 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Information [INFO]
These information setups are items to be configured in manufacturing steps, and the user can only confirm it.

Serial Number
Display Description
Sn Product serial number
1
[d][d]
[d][d][d][d]
[d][d][d][d]

1. d  decimal number.

Hardware Version
Display Description
1
[d].[d][d] Hardware version
_[d][d] Hardware revision number

1. d  decimal number.

Software Version
Display Description
1
a[d].[d][d] Application version
F[d].[d][d] Firmware version

1. d  decimal number.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 109


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Digital Input/Output [ETC]

Digital Input Status


Setup range Description
“_” Open contact display
“ㅁ” Closed contact display
Simultaneously display the status of channel 1 and channel 2 from the left.

Digital Output Type


Setup range Description
1
Latch[default] Latch type
PuLS.U 1 Uncountable pulse type 2

PuLS.C 1 Countable pulse type 2

1 2
P.PuLS Periodic pulse type

1. The operation for digital output type is as follows.


2. Pulse is defined as a pulse period and a pulse on time.
Output type Command Operation 3
Latch 1 Maintain Closed contact.
0 Maintain open contact.
Uncountable pulse 1 Pulse generation of single closed contact. After the pulse is generated, the
command is automatically cleared.
Additional commands entered within the pulse period are ignored.
0 Not used(Command is auto-cleared)
Countable pulse 1 Pulse generation of single closed contact. After the pulse is generated, the
command is automatically cleared.
Additional commands entered within the pulse period are generated an
additional number of times after the end of the pulse period.
0 Not used(Command is auto-cleared)
Periodic pulse 1 Pulse of closed contact is generated continuously while the command is 1.
0 Pulse generation of closed contact is stopped after completion of the
pulse.
3. Explanation of the case where the output polarity setup is "normal". If "Reverse" is selected, the operation of the
closed contact and the open contact is reversed.

Page 110 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Output Polarity
Setup range Description
nor∩ [default] Normal:
Closed contact when command "1"
Open contact when command is "0"
rEu Reverse:
Open contact when command "1"
Closed contact when command is "0"

Pulse Period
This menu screen is displayed only in the case that uncountable pulse/countable pulse/periodic pulse type is
selected in “Digital Output Type” menu screen.

Setup range Description


1
[d][d].[d][d] Period of pulse
0.01 - 34.45 sec[default 0.2 sec]
If pulse period is configured shorter than pulse on time, pulse on time is
automatically changed equally as pulse period.
In periodic pulse mode, if pulse period and pulse on time are the same, ON state
is maintained.

1. d  decimal number.

Pulse On time
This menu screen is displayed only in the case that uncountable pulse/countable pulse/periodic pulse type is
selected in “Digital Output Type” menu screen.

Setup range Description


1
[d][d].[d][d] On time of pulse
0.01 - 34.45 sec[default 0.1 sec]
It can be set only to a value less than or equal to the pulse period.
In periodic pulse mode, if pulse period and pulse on time are the same, ON state
is maintained.

1. d  decimal number.

The following setup screens differ depending on the setup of digital output type.
When the digital output type is set to latch[Latch], periodic pulse[P.PULS], and uncountable pulse[PuLS.U], the
setup screen moves to the parameter setup screen to select event for interlocking with DO output. If the digital
output type is set to countable pulse[PuLS.C], it moves to the parameter setup screen to select the accumulated
energy for interlocking with DO output.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 111


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Event Parameter at Latch/Periodic Pulse/Uncountable Pulse Mode


This setup screen is displayed in case that digital output type is configured as latch/periodic pulse/uncountable
pulse mode. If a start event is selected to interlock as DO output, when this selected start event is generated
DO output operates in configured type corresponding to DO output type setup. DO output operates when the
start event of selected event is generated and is cleared by long pressing EVENT button, entering to event log
mode and confirming the event.
Possible start event to select is as follows.

Setup range Description


no[No, default] No selection
dIP[Dip] Dip start event interlocking
SueLL[Swell] Swell start event interlocking
F.FaIL[Fuse Fail] Fuse Fail start event interlocking
Ph.oPn[Phase Open] Phase open start event interlocking
Leaㅏ[Leakage Current] Leakage current start event interlocking
curnt[Current] Current start event interlocking
dMd.c[Demand Current] Demand current start event interlocking
teMp[Temperature] Accura 2300S temperature start event
interlocking
M.tMP[Module TEMP] TEMP temperature start event interlocking
GAS[Module GAS] GAS start event interlocking
Udc[Module VDC] VDC voltage start event interlocking
Idc[Module IDC] IDC current start event interlocking
PoW[Power] Power start event interlocking
Eu.LEd[Event LED] For all the events mentioned above, the "Event
LED" is interlocked with the OR logic.
Therefore, if "Event LED" is selected in event
selection for DO output, any event among
several events will be interlocked with DO
output.

Page 112 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Event Parameter at Countable Pulse Mode


This setup screen is displayed in case that digital output type is configured as countable pulse mode. If the
accumulated energy for interlocking with DO output is selected and the accumulated energy scale is set per
unit pulse, DO output pulse is automatically generated every time the accumulated power per unit pulse is
increased.
The selectable energy parameters are as follows.

Setup range Description


no[No Parameter, default] No selection
rㅏWh Received active energy interlocking
dㅏWh Delivered active energy interlocking
rㅏUrh Received reactive energy interlocking
dㅏUrh Delivered reactive energy interlocking

Accumulated Energy Scale Per Unit Pulse


DO output pulse is automatically generated every time the corresponding energy is increased by the amount
per unit pulse.

Setup range Description


1
[d][d].[d][d] [default 0.35] 0.01 - 99.99 Unit: kWh, kVarh

1. d  decimal number.

Module ID to Interlock Accumulated Energy


Set Accura 2350 Module ID of the accumulated power for DO output pulse.

Setup range Description


[d][d] 1 [default 0] Module ID 0 - 39

1. d  decimal number.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 113


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

DO Direct Control
This is a screen for directly controlling the digital output. Control command “0” and “1” is reversely
performed corresponding to DO polarity setup. The actual status of the contact is displayed at the rightmost
segment of the fourth line. The actual status display of the contact is independent of the output polarity setup.

Setup range Description


When DO polarity is Normal
0 Open contact operation
1 Closed contact operation
When DO polarity is Reverse
0 Closed contact operation

1 Open contact operation

DI Channel 1 Event
Accura 2300S supports 2 channel digital inputs. Event setup of DI channel 1 is as follows.

Setup range Description


oFF [default] No event
cLoSE Closed contact event enabled
oPEn Open contact event enabled
both Closed/Open contact event enabled

DI Channel 2 Event
Accura 2300S supports 2 channel digital inputs. Event setup of DI channel 2 is as follows.

Setup range Description


oFF [default] No event
cLoSE Closed contact event enabled
oPEn Open contact event enabled
both Closed/Open contact event enabled

Page 114 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Event Log Mode


Start Event and End Event
Accura 2300S generates a start event when the event condition is satisfied when the power quality event such
as Dip[Sag], Swell, Fuse Fail is set, and generates the end event when the event is restored to the normal state.
All events except digital input [DI] event are always composed of start event and end event.

Start Event Alarm Generation


When the start event and the DI event occur, the event log is processed and a start event alarm is generated.
When start event alarm occurs, LCD backlight and the EVENT LED on the lower left blink. When the dip/swell
start event occurs, the Dip/Swell segment on the top bar blinks.
When the end event occurs, only the event log is processed and no alarm is generated.
The maximum 100 event logs are displayed.

Note

- Event LCD backlight illumination time can be set to clear the LCD backlight blinking, which indicates the
start event generation, to be cleared when the event log is confirmed, or to be maintained until 9999
minutes.

- It is possible to eliminate the EVENT LED blinking that notifies the generation of the start event by the
setting of the event LED illumination time when the event log is confirmed, or to maintain it until 9999
minutes.

Fig 4.26 Dip[Sag] Event Alarm Display

Fig 4.27 Swell Event Alarm Display

Start Event Alarm Clearing


When an alarm occurs, the long press of EVENT button to enter the event log mode clears the event alarm. In
the event log mode, you can check the recent 100 event logs in detail. In the event log mode, Event segment
on the top bar lights up to indicate event log mode.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 115


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Button Function

Button Function

[Display Mode]

Press 1 Select display screen.

[Event Log Mode]

Long Press 2 Enter event log mode[the newest event log is first displayed].

Press Select the event log.

or

Long Press Move to the newest event log.

Long Press Exit event log mode and move to display mode.

1. When the button is pressed, "Beep" sounds.


2. Press for more than 1 sec. After one second, "Beep" sounds.

Note
If there is no button operation for 10 minutes in event log mode, it automatically returns to the display mode.

Page 116 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Event Log Number


Event log number is assigned from E000 to E999 in the order of event generation. If event log number is
assigned E999, next event log number is recursively assigned E000. Up to 100 event logs can be stored.

Fig 4.28 Event Log Number Example

The following shows that a new event log is generated in the existing event logs assigned from E777 to E678.

Event Log[E678 ~ E777] Event Log[E679 ~ E778]

E000 Start number of event log E000 Start number of event log

E001 E001

E677 E677
1
E678 Event log N-99 ↑ E678

E679 Event log N-98  E679 Event log N-99 1 ↑


100 logs
E680 Event log N-98
100 logs
1
E777 Event log N ↓

E778 E778 Event log N 1 ↓

E779

E998

E999 End number of event log E999 End number of event log

1. Event log number that are stored.


Event log N-99 The oldest event log
Event log N The newest event log

Event Time-stamp
Pressing Down[v] button while selecting an event log screen by Left[<]/Right[>] button shows the time-
stamp of the selected event.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 117


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Dip Event Log


Dip Start Event Log
Display Description
E[d][d][d] Event log number 000 - 999
1
A dIP.S Dip start event generation in phase A
[d][d][d][d] V Voltage at start event [V]

1. Phase or line-to-line in which the event occurred: Phase[A, B, C] in 3P4W, Line-to-line[AB, BC, CA] in 3P3W wiring.

Dip End Event Log


Display Description
E[d][d][d] Event log number 000 - 999
1
A dIP.E Dip end event generation in phase A
[d][d][d][d] V Minimum voltage in the dip duration [V]
[d][d][d][d][d] Dip event duration time [msec]

1. Phase or line-to-line in which the event occurred: Phase[A, B, C] in 3P4W, Line-to-line[AB, BC, CA] in 3P3W wiring.

Swell Event Log


Swell Start Event Log
Display Description
E[d][d][d] Event log number 000 - 999
1
A SuL.S Swell start event generation in phase B
[d][d][d][d] V Voltage at start event [V]

1. Phase or line-to-line in which the event occurred: Phase[A, B, C] in 3P4W, Line-to-line[AB, BC, CA] in 3P3W wiring.

Swell End Event Log


Display Description
E[d][d][d] Event log number 000 - 999
1
A SuL.E Swell end event generation in phase A
[d][d][d][d] V Maximum voltage in the swell duration [V]
[d][d][d][d][d] Swell event duration time [msec]

1. Phase or line-to-line in which the event occurred: Phase[A, B, C] in 3P4W, Line-to-line[AB, BC, CA] in 3P3W wiring.

Page 118 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Fuse Fail Event Log


Fuse Fail Start Event Log
Display Description
E[d][d][d] Event log number 000 - 999
1
A FuSE Fuse fail start event generation in phase A
Strt Start event

1. Phase in which the event occurred.

Fuse Fail End Event Log


Display Description
E[d][d][d] Event log number 000 - 999
1
A FuSE Fuse fail end event generation in phase A
End End event
[d][d][d][d][d] Fuse fail event duration time [msec]

1. Phase in which the event occurred.

Temperature Evnt Log


Temperature Start Event Log
Display Description
E[d][d][d] Event log number 000 - 999
tMP.S Temperature start event generation
[d][d][d][d] ℃ Temperature at start event [℃]

Temperature End Event Log


Display Description
E[d][d][d] Event log number 000 - 999
tMP.E Temperature start event generation
[d][d][d][d] ℃ Maximum temperature in event duration [℃]
[d][d][d][d][d] Temperature event duration time [msec]

ⓒ 2015 Rootech Inc. All Rights Reserved Page 119


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Current Event Log


Current Start Event Log

Display Description
Module [d][d] Module ID of Accura 2350 where the event
occurred.
E[d][d][d] Event number 000 - 999
A 1.Cr.S Feeder1 Current start event [Phase A 1]
[d][d][d][d] A Current at the time of event [A]

1. Among the single-phase three feeder, feeder[1,2,3] and phase[A,B,C] where the event occurred are displayed.

Current End Event Log

Display Description
Module [d][d] Module ID of Accura 2350 where the event
occurred.
E[d][d][d] Event number 000 - 999
A 1.Cr.E Feeder1 Current end event [Phase A 1]
[d][d][d][d] A Maximum current during the event [A]
[d][d][d][d][d] ms Event duration time[sec]

1. Among the single-phase three feeder, feeder[1,2,3] and phase[A,B,C] where the event occured are displayed.

Leakage Current Event Log


Leakage current measurement is supported only at Accura 2350-1P3FSC-DIZCT option module.
Leakage Current Start Event Log

Display Description
Module [d][d] Module ID of Accura 2350 where the event
occurred.
E[d][d][d] Event number 000 - 999
2.Lㅏ.S Feeder2 1 leakage current start event
[d][d][d][d] A Leakage current at the time of event [A]

1. Among the single-phase three feeder, feeder[1,2,3] where the event generated is displayed.

Leakage Current End Event Log

Display Description
Module [d][d] Module ID of Accura 2350 where the event
occurred.
E[d][d][d] Event number 000 - 999
2.Lㅏ.E Feeder2 leakage current end event
[d][d][d][d] A Maximum current during the event [A]
[d][d][d][d][d] ms Event duration time [msec]

1. Among the single-phase three feeder, feeder[1,2,3] where the event generated is displayed.

Page 120 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Demand Current Event Log


Demand Current Start Event Log

Display Description
Module [d][d] Module ID of Accura 2350 where the event occurred.
E[d][d][d] Event number 000 - 999
C 3.dП.S Feeder3[Phase C] 1 demand current start event
[d][d][d][d] A Demand current at the time of event [A]

1. Among the single-phase three feeder, feeder[1,2,3] and phase[A,B,C] where the event generated are displayed.

Demand Current End Event Log

Display Description
Module [d][d] Module ID of Accura 2350 where the event occurred.
E[d][d][d] Event number 000 - 999
C 3.dП.E Feeder3[Phase C] 1 demand current end event
[d][d][d][d] A Maximum current during the event [A]
[d][d][d][d][d] Event duration time[min]

1. Among the single-phase three feeder, feeder[1,2,3] and phase[A,B,C] that the event generated are displayed.

1P3FSC DI Event Log


Digital input is supported only at Accura 2350-1P3FSC-DIZCT option module. Specific information for the
generated digital input event is displayed.

Display Description
Module [d][d] Module ID of Accura 2350-1P3FSC-DIZCT option
module where the event occurred.
E[d][d][d] Event number 000 - 999
3F.dI DI event display of DIZCT option module
Ch. 1 DI channel 1 1 where the event is generated
cLoSE “Closed” output event
oPEn “Open” output event
1. Among the 4 DI 4 channels, the channel[1,2,3,4] the the event generated is displayed.

No Event Log
The information of no event log generated is displayed.

Display Description
Пo No event log
Eunt

ⓒ 2015 Rootech Inc. All Rights Reserved Page 121


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Required Setup Step


The following settings are required for Accura 2300S to operate properly.

Step 1: Accura 2300S Connection, PT Rating


Set voltage connection and PT rating[When using external PT]. If an external PT is not used, input the same
line-to-line voltage to the primary voltage and the secondary voltage.

Connection

In the case of 3-phase 4-wire[default], the following step[2, 3, 4, 5] is skipped.

① Long press 1 SETUP button  Go to setup mode.


② Press Left [<] or Right [>] button to move to "Measurement" column. "Measurement" is
the first column of SETUP mode, and the first screen of "Measurement" is the voltage

connection[Conn] setup.

③ Long press ENTER button 3P4W blinks.


④ Select the setting element from 3P4W to 3P3W by Up[^] or Down[v] button.
⑤ Long press ENTER button Setting element stops blinking when it is set to 3-phase 3-
wire.

PT Rating

① In the voltage connection[Conn] setup screen, press Down[v] button to move to the "PT
rating[Pt]" setup screen.

A. Pr[Primary]PT primary line-to-line voltage rating.

B. Sc[Secondary] PT secondary line-to-line voltage rating.

The ratio of the primary and secondary line-to-line voltage input values is used as the

conversion ratio for the primary voltage. Regardless of the voltage connection, the PT

rating should always be input as PT primary / secondary line-to-line voltage.

② Long press ENTER button Only the numbers that can be set are blinking.
③ Use Up[^] or Down[v] buttons to select a number.
④ Press Left[<] and Right[>] buttons to move to the next digit to be selected. Continue
Right[>] button to move to the Sc[Secondary] setting element.

⑤ Repeat steps ③ and ④ until all digits are selected.


⑥ Long press ENTER button All digit settings are completed and saved.
⑦ Long press ESC button Exit setup mode and move to display mode.
1. Press for more than 1 sec. When the button is pressed, "Beep" sounds. And after one second, "Beep" sounds again.

Page 122 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Step 2: Accura 2350 Communication ID Auto-Assignment and Update


Accura 2300S can automatically assign module IDs of all connected Accura 2350s as shown in the following
steps. Refer to "Chapter 4>Setup Mode>Accura 2350 Module ID Setup" for the auto assignment method.

Step 2-1 Auto assignment to Accura 2350 Standby ID


If all connected Accura 2350s are already assigned Standby ID 1, skip to Step 2-2.

Module ID Auto Assignment

① Long press 2 SETUP button  Go to setup mode.


② Press Left[<] or Right[>] button to move to "Accura 2350 Module ID Setup" column.
Press Down[v] button to move to the "Module ID auto assignment[IdSt]" screen.

③ Long press ENTER button  RJ-1[RJ12-1]/Inc2[Increment 2] blinks.


④ Up[^] or Down[v] to select the setting element from RJ-1[RJ12-1]/Inc2[Increment 2] to
Stby[Standby].

⑤ Long press ENTER button  set Stby[Standby] and blink stops auto-assign all of
Accura 2350s with Standby ID.

⑥ Long press ESC button  Exit setup mode and move to display mode.

1. All Accura 2350s are factory-assigned as Standby ID by default.


2. Press for more than 1 sec. When the button is pressed, "Beep" sounds. And after one second, "Beep" sounds again.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 123


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Step 2-2 Sequential auto-assignment of Accura 2350 Module IDs

Module ID Auto Assignment

① Long press 1 SETUP button  Go to setup mode.


② Press Left[<] or Right[>] button to move to "Accura 2350 Module ID Setup" column.
Press Down[v] button to move to the "Module ID auto assignment[IdSt]" screen.

③ Long press ENTER button  Stby[Standby] blinks.


④ Up[^] or Down[v] to select the setting element from Stby[Standby] to RJ-2[RJ12-
2]/Inc2[Increment 2].

⑤ Long press ENTER button  set RJ-2[RJ12-2]/Inc2[Increment 2] and blink stops auto-
assign all of Accura 2350s with module ID.

⑥ Long press ESC button  Exit setup mode and move to display mode.

1. Press for more than 1 sec. When the button is pressed, "Beep" sounds. And after one second, "Beep" sounds again.

Note
If step 2-2 is performed without performing step 2-1[Auto assignment to Accura 2350 Standby ID], the
module IDs are sequentially and automatically assigned only to Accura 2350 assigned as a Standby ID,
except for Accura 2350 already assigned to a specific module ID.

Page 124 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 4 Accura 2300S Operation/Setup

Step 2-3 Accura 2350 Module ID Information Update


The following example illustrates updating the information of Accura 2350 11 module IDs that are
automatically assigned sequentially in step 2-2 for communication between Accura 2300S and 2350.

Module ID Information Update[cn  Communication, cF  Conflict, to  Total]

① Long press 1 SETUP button  Go to setup mode.

② Press Left[<] or Right[>] button to move to "Accura 2350 Module ID Setup" column.

③ Identify current Accura 2350 Module ID status.


- cn 11 2, 5  Number of Communication ID is 11.

- cF 00 3, 5  Number of Conflict/Standby ID is 0.

- to 11 4, 5  Total number of Accura 2350 modules is 11.

④ Long press ENTER button IduP[Id Update] blinks.

⑤ Long press ENTER button IduP[Id Update] 6 blink stops Update the communicable
Module ID information of all connected Accura 2350s.

⑥ Long press ESC button Exit setup mode and move to display mode.
1. Press for more than 1 sec. When the button is pressed, "Beep" sounds. And after one second, "Beep" sounds again.
2. cn[Communication]: Accura 2300S communicates with Accura 2350 in real time using communicable module ID
information.
3. cF[Conflict]: Number of modules with duplicate ID[ID collision] or Standby ID. These Accura 2350s cannot communicate
with Accura 2300S.
4. to[Total]: Number of Accura 2350 modules that are physically connected.
5. When Accura 2300S and 2350 are physically connected, they are automatically recognized and displayed.
6. Execute ID update after resolving cF[Conflict] module, then UNIT segment at the upper left will also stop blinking and
stay on. If there is a change in the connected modules after this, the change is indicated by blinking UNIT segment again.

Module ID ID Description
Communication ID ID 0 - 39 Able to communicate with Accura 2300S.
Conflict ID ID Duplication Two or more IDs are the same Module ID, unable to communicate.
1
Standby ID ID 255 Module ID for connection status recognition, unable to communicate.
1. All Accura 2350s are factory-assigned as standby IDs by default.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 125


Chapter 4 Accura 2300S Operation/Setup Accura 2300S/2350-1P3FSC User Guide

Step 3: Accura 2300S Ethernet Setup

Step 3-1 Accura 2300S IP, Subnet Mask, Gateway

IP

① Long press 1 SETUP button Go to setup mode.

② Press Left[<] or Right[>] button to move to "Ethernet Communication Setup" column.

③ Long press ENTER button the value that is possible to be changed blinks.

④ Increase or decrease the value of the menu screen by using Up[^] or Down[v] button.

⑤ Move to the next[left or right] digit of the value of the menu screen by using Left[<] and
Right[>] button.

⑥ Repeat sub-step[4, 5] until changing the value is complete.

⑦ Long press ENTER button save the changed value and blink stops.

⑧ Press Down[v] button move to “Subnet Mask[Sbnt]” menu screen.


Subnet Mask

① Search “Subnet Mask[Sbnt]” menu screen.

② Long press ENTER button the value that is possible to be changed blinks.

③ Increase or decrease the value of the menu screen by using Up[^] or Down[v] button.

④ Move to the next[left or right] digit of the value of the menu screen by using Left[<] and
Right[>] button.

⑤ Repeat sub-step[3, 4] until changing the value is complete.

⑥ Long press ENTER button save the changed value and blink stops.

⑦ Press Down[v] button move to “Gateway[gatE]” menu screen.


Gateway

① Search “Gateway[gatE]” menu screen.

② Long press ENTER button the value that is possible to be changed blinks.
③ Increase or decrease the value of the menu screen by using Up[^] or Down[v] button.

④ Move to the next[left or right] digit of the value of the menu screen by using Left[<] and
Right[>] button.

⑤ Repeat sub-step[3, 4] until changing the value is complete.

⑥ Long press ENTER button save the changed value and blink stops.

⑦ Long press ESC button exit setup mode and move to display mode.

1. Press for more than 1 sec. When the button is pressed, "Beep" sounds. And after one second, "Beep" sounds again.

Page 126 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Chapter 5 Measurement Description


General Measurement
The general measurement parameters are shown in the following table. Some of the parameters are provided
for communications only.
Accura 2300S front LCD display provides measurement value of 2 seconds aggregation interval based on the
basic measurement value of 0.5-second frame. It is also provided by communication. Additionally, the
measured values provided for communication are values for 0.5-second, 1-second, 5-second, 1-minute, 5-
minute, 1-hour, and 6-hour aggregation intervals, and the default aggregation interval is 1-second.
Since the maximum and minimum values after the reset provided by Accura 2300S are stored in the
nonvolatile memory, they are preserved even when Accura 2300S is turned off and then turned on. The peak
demand is initialized to zero by a maximum/minimum reset, not a demand reset.

▣ Accura 2300S Display & Communication support ▲ Only for Communication support
Measurement Parameter Phase Average Aggregation Interval After Reset Unit
/ Total Avg. Max Min Max Min
Voltage Line-to-neutral ▣ ▣ ▲ ▲ ▲ ▣ ▣ V
Line-to-line ▣ ▣ ▲ ▲ ▲ ▣ ▣ V
6
Fundamental ▲ ▲ ▲ ▲ ▲ V
1, 6
THD ▣ ▲ ▲ ▲ %
6
Phasor ▲ ▲ ▲ ▲ V
Line-to-neutral Unbalance (NEMA MG1) ▲ ▲ ▲ ▲ %
Line-to-line Unbalance (NEMA MG1) ▲ ▲ ▲ ▲ %
6
Zero-sequence Unbalance ▲ ▲ ▲ ▲ %
6
Negative-sequence Unbalance ▲ ▲ ▲ ▲ %
Frequency ▣ ▲ ▲ ▲ Hz
o
Ambient Temperature ▣ ▲ ▲ ▲ C
3
Residual Voltage ▲ ▲ ▲ ▲ V
Current Current ▣ ▲ ▲ ▲ ▣ ▣ A
Fundamental ▣ ▲ ▲ ▲ A
THD 1 / TDD 2 ▣ ▲ ▲ ▲ %
Phasor ▲ ▲ ▲ ▲ A
4
Crest Factor ▲ ▲ ▲ ▲ -
K-Factor 5 ▲ ▲ ▲ ▲ -
Leakage Current ▣ ▲ ▲ ▲ A
Power Active Power ▣ ▲ ▲ ▲ ▣ ▣ kW
Reactive Power ▣ ▲ ▲ ▲ ▣ kVAR
Apparent Power ▣ ▲ ▲ ▲ ▣ kVA
Power Factor Power Factor ▣ ▲ ▲ ▲ -
Phase Angle of Power Factor ▣ ▲ ▲ ▲ -
Energy Received Active ▣ kWh
Received Active ▣ kWh

ⓒ 2015 Rootech Inc. All Rights Reserved Page 127


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Sum Active ▣ kWh


Net Active ▣ kWh
Received Reactive ▲ kVARh
Delivered Reactive ▲ kVARh
Sum Reactive ▲ kVARh
Net Reactive ▲ kVARh
Apparent ▲ kVAh
Demand Demand/Peak Demand Current ▣ ▣ A
Prediction Demand Current ▲ A
Demand/Peak Demand Power ▣ ▣ kW
Prediction Demand Power ▲ kW
Harmonic Voltage harmonic magn.(DC,1st, 2nd~31th) ▲ V
st nd th
Current harmonic magn.(DC,1 , 2 ~31 ) ▲ A
RMS Voltage Half-cycle refreshed 1-cycle RMS voltage ▲ V
Instantaneous 2-cycle voltage waveform ▲ V
Waveform (32-sample/cycle)
2-cycle current waveform ▲ A
(32-sample/cycle)

√∑31 2
𝑘=2 𝑉𝑘 √∑31 2
𝑘=2 𝐼𝑘
1. THD(Total Harmonic Distortion), Voltage THD: , Current THD :
𝑉1 𝐼1

√∑31 2
𝑘=2 𝐼𝑘
2. TDD(Total Demand Distortion):
𝐼𝐿
Where 𝐼𝐿 can be configured only by communication between current rating[default] and peak demand current.
3. Residual voltage is the RMS voltage calculated by adding the three-phase voltage.
𝑉𝑝𝑒𝑎𝑘
4. Crest factor:
𝑉𝑟𝑚𝑠

∑31
𝑘=1(𝑘 𝐼𝑘 )
2
5. K-factor:
∑31 2
𝑘=1 𝐼𝑘
6. Values for phase voltages in three-phase 4-wire connection, and values for line-to-line voltages in three-phase 3-wire
connection.

Page 128 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Measurement Event
The following table shows the measurement events provided by Accura 2300S. Accura 2300S event log
provides a detailed view of the last 100 event logs. In the event log mode, Event segment on the top bar lights
up to indicate event log mode.

▣ Accura 2300S Display & Communication ▲ Only for Communication


Event Item Phase/ Total Start Event End Event
Channel Measured Measured Peak Value Duration
Value Value
Events of Accura 2300S and 2350-3P/1P/1P3FSC
Dip ▣ ▣ ▲ ▣ ▣

Swell ▣ ▣ ▲ ▣ ▣

Phase Open ▣ - - - -

Fuse Fail ▣ - - - -

Over Current ▣ ▣ - ▣ ▣

Over Demand Current ▣ ▣ - ▣ ▣

Over Leakage Current ▣ 1


▣ - ▣ ▣

Over Temperature ▣ ▣ - ▣ ▣

Over Power ▣ ▣ - ▣ ▣

DI Event ▣ 2
- - - -

Events of Accura 2350 Special Modules


Over Temperature of TEMP Module ▣ ▣ - ▣ ▲

Over Gas of GAS Module ▣ ▣ - ▣ ▲

Over Analog Input of VDC/IDC Module ▣ ▣ ▲ ▣ ▲

Under Analog Input of VDC/IDC Module ▣ ▣ ▲ ▣ ▲

Over Voltage/Current of DCM Module ▣ ▣ ▲ ▣ ▲

Under Voltage/Current of DCM Module ▣ ▣ ▲ ▣ ▲

1. Three channels of ZCT leakage current input are supported at Accura 2350-1P3FSC-DIZCT option module.
2. Four channels of DI contact point event are supported at Accura 2350-1P3FSC-DIZCT option module.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 129


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Measurement for Voltage Connection


Voltage, current, and power measurements for the voltage connections are as follows.

Three-phase 4-wire

Voltage connection

Fig 5.1 3PT 3P4W Connection

Voltage Measurement

Vector Diagram Item Description


Line-to-neutral voltage ▶Line-to-neutral voltage[V1, V2, V3] sensing based
sensing on connected N terminal voltage (real line-to-
V3
neutral voltage)
VA = V1
VB = V2
V1 VC = V3

Line-to-line voltage VAB = VA – VB = V1 – V2


VN : N terminal voltage calculation VBC = VB – VC = V2 – V3
VCA = VC – VA = V3 – V1
V2

Measured values provided

Item Line-to-neutral voltage[rms] Line-to-line voltage[rms] Current[rms] Active Power


Phase A VA VAB IA (I1) PA = VA * IA * PFA
Phase B VB VBC IB (I2) PB = VB * IB * PFB
Phase C VC VCA IC (I3) PC = VC * IC * PFC

Page 130 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Three-phase 3-wire

Voltage connection
The use of 2PT or 3PT for three-phase 3-wire voltage connection is the same for Accura 2300S, only the
installation cost is different.

Fig 5.2 2PT 3P3W Connection

Voltage Measurement

Vector Diagram Item Description


Line-to-neutral voltage ▶Line-to-neutral voltage[V1, V2, V3] sensing
sensing based on N terminal voltage
V3
Vo = V1 + V2 +V3 Zero voltage calculation ▶ From sensed line-to-neutral voltage
Vo = V1 + V2 + V3
Virtual neutral voltage ▶ Configuring zero voltage in 1/3,
V1
Vn = V o / 3 calculation Vn = Vo/3 (Virtual neutral voltage)
▶ Newly calculated neutral voltage is the center
VN : N terminal voltage of mass of the triangle that comprises input V1, V2
and V3.

V2

ⓒ 2015 Rootech Inc. All Rights Reserved Page 131


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Virtual line-to-neutral ▶ Calculate virtual line-to-neutral voltage based


VA = V 1 – V n voltage calculation on virtual neutral voltage.
VC
VB = V2 – V n VA = V1 – Vn
V C = V3 – V n VB = V2 – Vn
Vn : Virtual neutral voltage VC = V3 – Vn
V3
VA
Zero voltage of virtual line-to-neutral voltage is 0.

V1 Line-to-line voltage VAB = VA – VB = V1 – V2


calculation VBC = VB – VC = V2 – V3
VN : N terminal voltage
VCA = VC – VA = V3 – V1

VB V2

Measured values provided

Item Line-to-neutral voltage[rms] Line-to-line voltage[rms] Current[rms] Active Power


Phase A VA VAB IA (I1) PA = VA * IA * PFA
Phase B VB VBC IB (I2) PB = VB * IB * PFB
Phase C VC VCA IC (I3) PC = VC * IC * PFC

Since there is no actual neutral point in the 3-phase 3-wire voltage connection, only the line-to-line voltage
and the total power can be known, and the actual voltage and the electric power for each phase cannot be
known. However, it is possible to obtain the virtual center point at which the residual voltage of the 3-phase
voltage becomes zero, and regard it as the neutral point, thereby obtaining the voltage per phase and the
power per phase.

Page 132 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Single-phase 3-wire

Voltage connection

Fig 5.3 2PT 1P3W Connection

Voltage Measurement

Vector Diagram Item Description


Line-to-neutral ▶ Line-to-neutral voltage[V1, V3] sensing based on
V3 VN V1 voltage sensing N terminal voltage
VA = V1
VN : N terminal voltage
VB = 0 (processed as 0 by 1P3W configuration)
VC = V3
Line-to-line voltage VAB = 0 (processed as 0 by 1P3W configuration)
calculation VBC = 0 (processed as 0 by 1P3W configuration)
VCA = VC – VA = V3 – V1

Measured values provided

Item Line-to-neutral voltage[rms] Line-to-line voltage[rms] Current[rms] Active Power


Phase A VA 0 IA (I1) PA = VA * IA * PFA
Phase B 0 0 0 0
Phase C VC VCA IC (I3) PC = VC * IC * PFC

ⓒ 2015 Rootech Inc. All Rights Reserved Page 133


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Single-phase 2-wire

Voltage connection

Fig 5.4 1PT 1P2W Connection

Voltage Measurement

Vector Diagram Item Description


Line-to-neutral ▶ Line-to-neutral voltage[V1] sensing based on N
V3 VN V1 voltage sensing terminal voltage
VA = V1
VN: N terminal voltage
VB = 0 (processed as 0 by 1P2W configuration)
VC = 0 (processed as 0 by 1P2W configuration)
Line-to-line voltage VAB = VA
calculation VBC = 0 (processed as 0 by 1P2W configuration)
VCA = 0 (processed as 0 by 1P2W configuration)

Measured values provided

Item Line-to-neutral voltage[rms] Line-to-line voltage[rms] Current[rms] Active Power


Phase A VA VA IA (I1) PA = VA * IA * PFA
Phase B 0 0 0 0
Phase C 0 0 0 0

Page 134 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Dip[Sag]/Swell Measurement

Half-cycle Refreshed 1-cycle RMS


RMS value for 1-cycle is measured by sliding in half-cycle interval. Time resolution of this 1-cycle RMS value is
half-cycle. By monitoring this 1-cycle RMS value, Dip[Sag]/Swell event is detected.

Fig 5.5 Half-cycle Refreshed 1-cycle RMS Calculation

220.0 173.8 110.0 110.0 110.0 173.8 220.0 220.0

Half-cycle refreshed 1-cycle RMS

Dip[Sag]/Swell Detection
As it is defined in IEC 61000-4-30, Dip[Sag]/Swell of voltage is detected by monitoring the half-cycle
refreshed 1-cycle RMS value. Time resolution of Dip[Sag]/Swell is half-cycle.

Fig 5.6 Voltage Dip[Sag] Detection

Dip theshold = 180.0

Dip duration
Dip start time Dip end time

1-cycle RMS 220.0 220.0 173.8 110.0 110.0 110.0 173.8 220.0 220.0

Dip start voltage Dip end voltage


Dip peak voltage (Max. Residual Voltage)

ⓒ 2015 Rootech Inc. All Rights Reserved Page 135


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Leakage Current Measurement


Leakage current measurement is supported by installing an external ZCT[voltage-type] and connecting the
ZCT output voltage to the ZCT input terminal of Accura 2350 module.
Depending on the setting, the leakage current measurement can be done in two ways: "Half-cycle RMS" and
"1-cycle Fundamental RMS".

Half-cycle RMS Method[Default]


Calculates the half-cycle RMS value for every half-cycle and provides the maximum value of these RMS values
[60 @ 60 Hz] for every 0.5-second frame as the leakage current measurement value.

1-cycle Fundamental RMS Method


Calculates the 1-cycle fundamental RMS value for every 1-cycle and provides the maximum value of these
RMS values [30 @ 60 Hz] for every 0.5-second frame as the leakage current measurement value.

Residual Voltage Measurement


The residual voltage(Vrsd) is the RMS value calculated by summing the 3-phase voltages obtained by
sampling. This residual voltage includes the residual voltage for the harmonic component.

𝑉𝑟𝑠𝑑 = ∑ 𝑉𝑎,𝑏,𝑐

Page 136 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Phase Power Measurement


Two methods are available for calculating reactive power(Q) and apparent power(S) for each phase.
1) Fundamental calculation: calculation of reactive power based on fundamental voltage/current.
2) Harmonic calculation: calculation of reactive power based on RMS voltage/current
Depending on how the reactive power is calculated, reactive power and apparent power can vary. As the
apparent power varies, the power factor(PF) also varies.

Fundamental Calculation Method


Active power for each phase is calculated by multiplying voltage and current.
1 𝑇
𝑃𝑘 = 𝑇 ∫0 𝑣𝑘 (𝑡) 𝑖𝑘 (𝑡)𝑑𝑡 where k=a,b,c,

The reactive power for each phase is calculated by delaying the phase of the voltage by 90 degrees with
respect to the fundamental frequency.
1 𝑇
𝑄𝑘 = ∫0 𝑣𝑘 (𝑡 − 𝑇4) 𝑖𝑘 (𝑡)𝑑𝑡 where k=a,b,c,
𝑇

The apparent power for each phase is calculated by the magnitude of the vector sum of the active power and
the reactive power.

𝑆𝑘 = √𝑃𝑘2 + 𝑄𝑘2 where k=a,b,c,

Harmonic Calculation Method


Active power for each phase is calculated by multiplying voltage and current.
1 𝑇
𝑃𝑘 = 𝑇 ∫0 𝑣𝑘 (𝑡) 𝑖𝑘 (𝑡)𝑑𝑡 where k=a,b,c,

Calculate the apparent power for each phase by multiplying the RMS voltage by the RMS current. The RMS
values of voltage and current contain harmonic components.

1 𝑇 1 𝑇
𝑉𝑘,𝑟𝑚𝑠 = √𝑇 ∫0 𝑣𝑘2 (𝑡) 𝑑𝑡 , 𝐼𝑘,𝑟𝑚𝑠 = √𝑇 ∫0 𝑖𝑘2 (𝑡) 𝑑𝑡 where k=a,b,c

𝑆𝑘 = 𝑉𝑘,𝑟𝑚𝑠 ∙ 𝐼𝑘,𝑟𝑚𝑠 where k=a,b,c

The magnitude of the vector difference between the apparent power and the active power is calculated to
obtaine the magnitude of the reactive power for each phase. The sign of the reactive power is the sign of the
reactive power calculated by the fundamental calculation method mentioned above.

𝑄𝑘 = ±√𝑆𝑘2 − 𝑃𝑘2 where k=a,b,c

ⓒ 2015 Rootech Inc. All Rights Reserved Page 137


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Power Factor(PF) Measurement


Power factor is calculated as the ratio of the effective power to the apparent power. The sign of the power
factor is a positive or negative value depending on the sign of the active power. If it is positive, it shows the
power receiving state. If it is negative, it shows the power delivering state.
If the apparent power is zero, the power factor cannot be calculated normally. In this case, it can be set to 1.0
or 0.0 display, and is set to default to 1.0 display.

𝑃𝑎 𝑃𝑏 𝑃𝑐
𝑃𝐹𝑎 = , 𝑃𝐹𝑏 = , 𝑃𝐹𝑐 =
𝑆𝑎 𝑆𝑏 𝑆𝑐

Sign of power factor can be removed by setting. In this case, the power receiving/delivering state cannot be
known only by the power factor value. The power factor when removing the sign is as follows.

𝑃𝑎 𝑃𝑏 𝑃𝑐
𝑃𝐹𝑎 = | |, 𝑃𝐹𝑏 = | |, 𝑃𝐹𝑐 = | |
𝑆𝑎 𝑆𝑏 𝑆𝑐

PF Phase Angle Status Measurement


The relationship between the power sign and the PF phase angle status(LEAD/LAG) is shown in the following
figure for the 4-quadrant voltage and current. When the reactive power(Q) is 0, it is neither a LEAD state nor
a LAG state.

Fig 5.7 Power Sign and PF Phase Angle Status

Q
-0.0 +0.0

PF(-) PF(+)

LEAD LAG
-1.0 +1.0
LAG LEAD P

PF(-) PF(+)

-0.0 +0.0

Note
If the current phase for voltage phase is phase leading or lagging, PF phase angle status is displayed as
LEAD or LAG status on the front display screen of Accura 2300S. If the reactive power is zero, PF phase
angle status is not displayed.

Page 138 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Demand Measurement
Demand
Demand time(Tdmd) is determined by the product of “Demand Sub-Interval(Tsub)” and “Number of Sub-
Interval(Nsub)”. A demand value is calculated by processing an average value for a demand time(Tdmd)
while sliding at demand sub-interval time(Tsub). Peak demand is the maximum value among the demand
values after the max/min reset, and it is initialized by max/min reset.
Demand time(Tdmd) [min] = Demand Sub-Interval(Tsub) * Number of Sub-Interval(Nsub)
Ex) In Korea[demand time=15 minute], demand sub-interval is 15-minute and number of sub-interval is 1.

Fig 5.8 Demand Calculation


source
input Demand Sub-Interval [Tsub] (in this case, 5 min)

Number of Sub-Interval [Nsub] (in this case, 3)


Demand time [Tdmd]
(in this case, 15 min)

Avg 2.6 Avg 3.0 Avg 4.0 Avg 4.8 Avg 4.3 Avg 2.5

1:15 1:20 1:25 1:30 1:35 1:40 1:45 time


(4.8+2.6+3.0)/3 (2.6+3.0+4.0)/3 (3.0+4.0+4.8)/3 (4.0+4.8+4.3)/3 (4.8+4.3+2.5)/3

demand output 3.47 3.20 3.93 4.37 3.87

Prediction Demand
Prediction demand is calculated from the predicted average of on-going demand sub-interval which is
calculated at every second by assuming that the present value is maintained during the remaining time of on-
going demand sub-interval.

Fig 5.9 Prediction Demand Calculation


source
Demand time [Tdmd]
input
(in this case, 5*3 min)

prediction
Avg 2.6 Avg 3.0 Avg 4.0
Avg 4.4

1:15 1:20 1:25 1:30 1:35 time


(4.8+2.6+3.0)/3 (2.6+3.0+4.0)/3

demand output 3.47 3.20


(3.0+4.0+4.4)/3

prediction demand output 3.80

ⓒ 2015 Rootech Inc. All Rights Reserved Page 139


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Unbalance(NEMA MG1)
Line-to-neutral Voltage Unbalance
It represents the degree of voltage that deviates most from the average voltage of the three-phase voltage.
The phase voltage unbalance index is 0 even when the phase voltages are equal in magnitude and the
phases are unbalanced.

𝑀𝑎𝑥(𝛥𝑉𝑝ℎ)
𝑃ℎ𝑎𝑠𝑒 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑈𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 = × 100 [%]
𝑉𝑝ℎ, 𝑎𝑣𝑔

Vph,avg: Average of line-to-neutral voltages of 3-phase.


Max(ΔVph): Difference voltage most deviating from the average of line-to-neutral voltages.

Line-to-line Voltage Unbalance


It indicates the degree of line-to-line voltage that deviates most from the average voltage of the three-phase
line-to-line voltage. If the magnitude of the phase voltage is the same and the phase is unbalanced, the
phase voltage unbalance index is zero, but the line-to-line voltage unbalance index is not zero.

𝑀𝑎𝑥(𝛥𝑉𝐿𝐿)
𝐿𝑖𝑛𝑒 − 𝑡𝑜 − 𝑙𝑖𝑛𝑒 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑈𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 = × 100 [%]
𝑉𝐿𝐿, 𝑎𝑣𝑔

VLL,avg: Average of line-to-line voltages of 3-phase.


Max(ΔVLL): Difference voltage most deviating from the average of line-to-line voltages.

Page 140 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Sequence Unbalance
The fundamental signals of 3-phase voltage can be decomposed into the symmetrical components which are
positive-sequence, negative-sequence and zero-sequence component.

Fig 5.10 Symmetrical Components


Vc1 Vb2
Va0
Vb0
Va1
Vc0
Va2
Vb1 Vc2 Va0=Vb0=Vc0

positive-sequence negative-sequence zero-sequence

Zero-sequence component(U0): Same component


Positive-sequence component(U1):Symmetrical component for phase sequence A-B-C
Negative-sequence component(U2):Symmetrical component for phase sequence A-C-B

Symmetrical zero-sequence, positive-sequence, and negative-sequence are determined as follows.

𝑈0 1 1 1 1 𝑈𝑎 2𝜋
𝑗∙
[𝑈1 ] = ∙ [1 𝑎 𝑎2 ] ∙ [𝑈𝑏 ] , 𝑤ℎ𝑒𝑟𝑒 𝑎 = 𝑒 3
3
𝑈2 1 𝑎2 𝑎 𝑈𝑐

Negative-Sequence Unbalance Ratio


This is the ratio of negative-sequence component based on positive-sequence component.

𝑈2
𝑁𝑒𝑔𝑎𝑡𝑖𝑣𝑒 − 𝑠𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝑢𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 𝑟𝑎𝑡𝑖𝑜 = × 100 [%]
𝑈1

Zero-Sequence Unbalance Ratio


This is the ratio of zero-sequence component based on positive-sequence component.

𝑈0
𝑍𝑒𝑟𝑜 − 𝑠𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝑢𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 𝑟𝑎𝑡𝑖𝑜 = × 100 [%]
𝑈1

ⓒ 2015 Rootech Inc. All Rights Reserved Page 141


Chapter 5 Measurement Description Accura 2300S/2350-1P3FSC User Guide

Aggregation
Accura 2300S/2350 samples and processes voltage/current every 0.5-seconds and provides basic
measurement data every 0.5-second for a 0.5-second interval. Using the basic 0.5-second data, the
aggregation for longer than 0.5-second is calculated as shown in the figure below. This figure shows the
aggregation for 1-second and 5-second intervals.
Aggregation consists of a average value, a maximum/minimum value, and a time-stamp for maximum/
minimum. Average, maximum/minimum, and time-stamp are generated for each aggregation. The average
value is the average of 0.5-second data during the aggregation interval. The maximum value/minimum value
is the maximum value/minimum value among the 0.5-second data during the aggregation interval.
The time-stamp for the maximum/minimum is the difference time between the start time of the aggregation
and the occurrence time of maximum/minimum value. Therefore, the actual time for maximum/minimum can
be obtained by adding the aggregation start time and the difference time of the time-stamp.

Fig 5.11 Aggregation Process

Fixed aggregation
Accura 2300S provides six aggregations from aggregation 1 through 6 with fixed aggregation interval[1-
second, 5-second, 1-minute, 5-minute, 1-hour, 6-hour]. In fixed aggregation, the offset time for the beginning
of the aggregation interval is fixed to zero. That is, the start of the aggregation interval is fixed to start at 0
hour 0 minute 0 second. To set the offset time to a non-zero value, you should use customed aggregation.
The measurement values displayed on Accura 2300S LCD screen are 2-second aggregation values updated
every 0.5-second, and these are provided by communication through aggregation 201 setup.
Also, the Max/Min value after the user-reset displayed on Accura 2300S LCD screen is the Max/Min values
among the 0.5-second measurement values, and these are provided by communication through aggregation
202 setup.

Aggregation name Aggregation interval Buffer length Buffering time Circular index
Aggregation 0 0.5-second (base) 120 60 seconds 0-9999
Aggregation 1 1-second 32 32 seconds 0-9999
Aggregation 2 5-second 12 60 seconds 0-9999
Aggregation 3 1-minute 12 12 minutes 0-9999
Aggregation 4 5-minute 10 50 minutes 0-9999
Aggregation 5 1-hour 10 10 hours 0-9999

Page 142 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide Chapter 5 Measurement Description

Aggregation 6 6-hour 10 60 hours 0-9999


1
Aggregation 201 2-second - - -
2
Aggregation 202 - - - -
1. Measurement values that are displayed at Accura 2300S LCD screen: 2-second aggregation measurement value
updated every 0.5-second.
2. Max/Min measurement values that are displayed at Accura 2300S LCD screen: Max/Min values among the 0.5-second
measurement values after the user-reset.

Customed aggregation
Accura 2300S provides 5 customized aggregations 11 to 15 that allow the user to arbitrarily set the offset
time for the aggregation interval and the interval start.
If the offset setting is 0, the start of the aggregation interval corresponds to 0: 0: 0: 0. For example, if you
want to collect average data at 1 hour intervals at 10 minutes of each hour, you can select one of
aggregations 11 to 15, set the aggregation interval for this aggregation to 3600 seconds, and set the
aggregation offset time to 600 seconds.

Aggregation name Aggregation interval Buffer length Buffering time Circular index
Aggregation 11 default 3-second 22 66 seconds 0-9999
Aggregation 12 default 15-minute 12 180 minutes 0-9999
Aggregation 13 default 2-hour 10 20 hours 0-9999
Aggregation 14 default 12-hour 10 120 hours 0-9999
Aggregation 15 default 1-day 10 10 days 0-9999

Event aggregation
If activated event is detected, measurement data during 3-frame[at the time of generation/before 0.5-
second/after 0.5-second] is indexed and stored separately into “Aggregation 200” space. By collecting the
stored event aggregation data[measurement data/1-cycle RMS voltage], detailed analysis of situation
before/after the time of event generation can be done.

Aggregation name Aggregation interval Buffer length Buffering time Circular index
1
Aggregation 200 1.5-seconds 100 - 0-999
1. If activated event is detected, measurement data during 3-frame[at the time of generation/before 0.5-second/after 0.5-
second] is stored at circular buffer.

Aggregation Data Collection


If you select one aggregation, the selected aggregation data is collected through Modbus map. Because the
aggregated data is stored in the circular buffer of Accura 2300S for a certain period of time, aggregation
measurement values can be acquired more flexibly in time.
As shown in the tables above, the recent index of the aggregation can be easily found because the index is
rotated in the range of 0-9999 or 0-999, which is larger than the circular buffer size.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 143


APPENDIX A Specification Accura 2300S/2350-1P3FSC User Guide

APPENDIX A Specification
Accura 2300S Distribution Panel Digital Power Meter
Voltage Input
Connector type Terminal block (V1, V2, V3, VN )
Wire 2.1 to 3.5 mm2[14 to 12 AWG]
1
Measurement range AC 60 - 600V direct L-L[Line-to-Line]
[Accuracy guaranteed 2]
1
Minimum measurement AC 5V direct L-N[Line-to-Neutral]
1
Maximum measurement AC 660V direct L-L[Line-to-Line]
Frequency range 50/60Hz, 42 - 69Hz
Voltage connection Three-phase 4-wire/3-wire, Single-phase 3-wire/2-wire
Burden 0.02VA/phase @ 220V
Withstand voltage AC 2,000V RMS, 60Hz for 1minute
Impedance 3MΩ/phase
Compliance Category Ⅲ
Digital Input
Connector type Terminal block(DI1, DI2, DIG)
Input type 2-Channel, Dry contact (Common Ground)

Wire 1.5 to 3.5 mm2[16 to 12 AWG]


Rating DC 5V[Self excitation]
Isolation Maximum 300V
Min. Pulse Width 1sec
Digital Output
Connector type Terminal block(DO, DOG)
Wire 1.5 to 2.5 mm2[16 to 12 AWG]
Output contact 1-Channel, Form A relay
Output type Latch, Uncountable/Countable single pulse 3, Periodic pulse 3
Isolation AC 2,000V for 1 minute
Maximum rating AC 250V 5A, DC 110V 0.3A, DC 30V 5A
Ethernet Communication
Connector type/Port RJ45, 2-Port(Ethernet1, Ethernet2)
Ethernet cable STP[Shielded Twisted Pair]/SFTP[Screened Foiled Twisted Pair] CAT5e
Protocol Modbus TCP
Type 100Base-TX[100 Mbps/Full Duplex]
Connection Star, Daisy-Chain, Ring connection
RS-485 Communication
Port name Ta[TRX+], Tb[TRX-], G[Ground]
Connector type Screw-type terminal[Pluggable]
Protocol Modbus RTU
Baud rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Wire 0.21 to 3.5 mm2[24 to 12 AWG], Shielded twisted pair 4

Max. cable length 1219m[4000ft]


Max. connection devices 32 devices / bus
Accura 2350 Internal Communication

Page 144 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide APPENDIX A Specification

Connector type/Port RJ12 5, 2-Port(RJ12-1, RJ12-2)


Protocol RS-485, internal dedicated protocol
Modules/Port Max. 15 modules of Accura 2350 per port 6
Length/Port Max. 6m per port 7
Power supply
Connector type Terminal block(L+, N-, G)
Wire 2.1 to 3.5 mm2[14 to 12 AWG]
Operating voltage AC 85 - 265V 50/60Hz, DC 100 - 300V
Withstand voltage AC 2,500V RMS, 60Hz for 1 minute
Compliance Pollution degree 2
Power Consumption Maximum 20VA Depends on number of Accura 2350 connected
Inrush current Peak 25A, duration 2msec or less (AC 220V) 8
General
Weight 487g
1. Because of input voltage level of the device, when using an external PT, the primary voltage is the product of the PT ratio.
2. Voltage accuracy meets ± 0.2% reading error.
3. Pulse is defined as pulse period and pulse on time.
4. Connect shield wire to G terminal.
5. Packaged with device. Core conductor of cable should be minimum 0.128mm2[26 AWG]. It is recommended that
distance from power line is 5mm or more so that interference caused by noisy power line will not occur.
6. Accura 2300S can connect up to 15 Accura 2350 power measuring modules per port[RJ12-1, RJ12-2]. When connecting
special modules other than the power measuring module, refer to the individual manual of the special module.
7. Maximum length of cable from one port of Accura 2300S to the last Accura 2350 module connected.
8. If a fuse is installed at the input terminal, it is recommended to fuse more than 2A/500V due to inrush current.

ⓒ 2015 Rootech Inc. All Rights Reserved Page 145


APPENDIX A Specification Accura 2300S/2350-1P3FSC User Guide

Accura 2350-1P3FSC Single-phase Three Feeder Power Measuring Module

Item Description
Connector type Through-hole
Wire specification Select according to through-hole size
Measuring range Model Minimum Measuring Range
measurement [Accuracy guaranteed 1]
Accura 2350-1P3FSC-125A 0.83A 1.25A - 150A
Accura 2350-1P3FSC-125A-DIZCT 0.83A 1.25A - 150A
Accura 2350-1P3FSC-60A 0.40A 0.60A - 72A
Accura 2350-1P3FSC-60A-DIZCT 0.40A 0.60A - 72A
Impedance Not applicable because of through-hole structure
Frequency range 50/60Hz, 42 - 69Hz
Through-hole size Model Size
Accura 2350-1P3FSC-125A 16.6(W) x 21.8(H) mm
Accura 2350-1P3FSC-125A-DIZCT 16.6(W) x 21.8(H) mm
Accura 2350-1P3FSC-60A 11.8(W) x 21.8(H) mm
Accura 2350-1P3FSC-60A-DIZCT 11.8(W) x 21.8(H) mm
Weight Model Weight
Accura 2350-1P3FSC-125A 457 g (except for mounting wing)
Accura 2350-1P3FSC-125A-DIZCT 468 g (except for mounting wing)
Accura 2350-1P3FSC-60A 393 g (except for mounting wing)
Accura 2350-1P3FSC-60A-DIZCT 404 g (except for mounting wing)
Mounting wing 4g
1. Current accuracy meets ± 0.5% reading error, power/energy meets IEC62053-22 Class 0.5S, and maximum ± 1% error
can be increased depending on the penetration position of the power cable.

Accura 2300S/2350 Common

Item Description
Operating temperature -20 to 70℃ [-4 to 158℉]

Safety temp 1 -20 to 65℃ [-4 to 149℉]

Storage temp -40 to 85℃ [-40 to 185℉]

Operating humidity No condensation, 5% - 95%


1. Conforms to UL61010-1.

Page 146 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide APPENDIX B Standard Compliance

APPENDIX B Standard Compliance


Accuracy
IEC62053-22 Static meters for active energy
Power Quality
IEC61000-4-30 Power quality measurement methods
Safety
UL61010-1 Safety requirements for electrical equipment for measurement, control and
laboratory use
EMC
IEC61000-4-2 Electrostatic discharge[ESD] immunity
IEC61000-4-3 Radiated, radio-frequency, electromagnetic field immunity
IEC61000-4-4 Electrical fast transient/burst immunity
IEC61000-4-5 Surge immunity
IEC61000-4-6 Immunity to conducted disturbances, induced by radio-frequency fields
IEC61000-4-8 Power frequency magnetic field immunity
IEC61000-4-11 Voltage dips, short interruptions and voltage variations immunity
Certification
UL61010-1 UL
EN61326-1, EN61326-2-1, EN61010-1 CE
KN22, KN24 KC
ISO 9001:2015[QMS-1347] ISO
General
Warranty 2 years

ⓒ 2015 Rootech Inc. All Rights Reserved Page 147


APPENDIX C Accuracy/Reliability Accura 2300S/2350-1P3FSC User Guide

APPENDIX C Accuracy/Reliability
Accuracy
Accura 2300S/2350-1P3FSC
Item Display Range Accuracy
Voltage line-to-neutral Va, Vb, Vc 0.000 - 9999V, kV ±0.2% RD

Vrsd 0.000 - 9999V, kV ±0.2% RD 1

Voltage line-to-line Vab, Vbc, Vca 0.000 - 9999V, kV ±0.2% RD

Current Ia, Ib, Ic 0.000 - 9999A, kA ±0.5% RD 2

Power Active 0.000 - ±9999kW IEC62053-22 Class 0.5S 2

Reactive 0.000 - ±9999kVar

Apparent 0.000 - 9999kVA


Energy Active 0 - ±999,999,999kWh IEC62053-22 Class 0.5S 2

Reactive 3 0 - ±999,999,999kVarh

Apparent 3 0 - 999,999,999kVAh
Demand Power 0.000 - ±9999kW IEC62053-22 Class 0.5S 2

Current 0.000 - 9999A, kA ±0.5% RD 2

Frequency 42 - 69Hz ±10mHz

Power factor 0.000 - 1.000 LEAD/LAG ±0.5% FS

THD Voltage 0.0 - 999.9% ±0.5% FS

Current 0.0 - 999.9% ±0.5% FS

TDD Current 0.0 - 999.9% ±0.5% FS

Crest factor 3 0.0 - 999.9 ±0.5% FS

K-factor 3
0.0 - 999.9 ±0.5% FS

1. It is the % reading error for the maximum phase voltage in the three phases because it is the residual voltage calculated
from the phase voltage.
2. Single-phase three feeder power measuring modules meet ±0.5% reading error for current accuracy. And these split-
core modules can increase the maximum ± 1% reading error depending on the penetration position of power cable.
3. Not displayed on Accura 2300S LCD screen and provided only by communication.

Power Quality
Parameter Standard Condition Accuracy
Voltage Dip[Sag]/Swell IEC61000-4-30 Half-cycle refreshed ± 0.5% FS
1-cycle RMS measurement
Voltage/Current THD IEC61000-4-7 up to 31st harmonics ± 0.5% FS
Current TDD IEC61000-4-7 up to 31st harmonics ± 0.5% FS
Voltage/Current Unbalance IEC61000-4-30, NEMA MG1 ± 0.5% FS
Vector diagram ± 0.5% FS

Page 148 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/2350-1P3FSC User Guide APPENDIX C Accuracy/Reliability

IEC62053-22, Electricity metering equipment: Active energy Class 0.5S

Current Range Power Factor Percentage error limits for Class 0.5S
0.01 In - 0.05 In 1 ± 1.0%
0.05 In - Imax 1 1 ± 0.5%
0.02 In - 0.1 In 0.5 inductive ± 1.0%
0.8 capacitive ± 1.0%
0.1 In - Imax 0.5 inductive ± 0.6%
0.8 capacitive ± 0.6%
0.25 inductive ± 1.0%
0.5 capacitive ± 1.0%
1. Maximun current Imax =1.2 In, where rated current In= 60A, 125A.

Reliability
IEC61326, Electrical Equipment for Measurement, Control, and Laboratory- EMC

Standard Condition Accura 2300S/2350


IEC61000-4-2 Electrostatic discharge[ESD] immunity 4kV/8kV contact/air 12kV/20kV
IEC61000-4-3 Radiated, radio-frequency, electromagnetic 10V/m, 80M - 2700MHz 10V/m,
field immunity 80M - 2700MHz
IEC61000-4-4 Electrical fast transient/burst immunity 2kV 4kV
IEC61000-4-5 Surge immunity 1kV/2kV, 2kV/4kV
line-to-line/line to earth
IEC61000-4-6 Immunity to conducted disturbances, 10V 10V
induced by radio-frequency fields
IEC61000-4-8 Power frequency magnetic field immunity 30A/m 30A/m
IEC61000-4-11 Voltage dips, short interruptions and 0.5 cycle, 0.5 cycle,
voltage variations immunity each polarity 100% each polarity 100%

ⓒ 2015 Rootech Inc. All Rights Reserved Page 149


APPENDIX D Ordering Information Accura 2300S/2350-1P3FSC User Guide

APPENDIX D Ordering Information


Accura 2300S Distribution Panel Digital Power Meter
Accura 2300S
Accura 2300S

Accura 2350-1P3FSC Single-phase Three Feeder Power Measuring Module

Accura 2350 - Type - Rating - Option


Accura 2350 - 1P3FSC - 125A
Accura 2350 - 1P3FSC - 125A - DIZCT 1
Accura 2350 - 1P3FSC - 60A
Accura 2350 - 1P3FSC - 60A - DIZCT 1
1. When ordering ZCT, please contact ROOTECH Inc..

Special- Purpose Modules


Accura 2350 - Type Range Description
Accura 2350 - GAS GAS Module
Accura 2350 - GW GW[Gateway] Module
Accura 2350 - TEMP Temperature Module
Accura 2350 - DO DO[Digital Output] Module
Accura 2350 - IDC IDC[DC Current Input] Module
Accura 2350 - VDC - 50V VDC[DC Voltage Input] Module
Accura 2350 - DCM - 50V - 80A DCM Module[DC 50V/80A]
Accura 2350 - DCM - 500V - 80A DCM Module[DC 500V/80A]

Page 150 ⓒ 2015 Rootech Inc. All Rights Reserved


Accura 2300S/Accura 2350-1P3FSC

User Guide

Data Center Distribution Panel Digital Power Meter/


Single-phase Three Feeder Power Measuring Module

Rootech
102-611 Digital Empire2, Sinwon-ro 88
Yeongtong-gu, Suwon, Gyeonggi-do, Korea

Tel. +82 31-695-7350


Fax. +82 31-695-7399

www.rootech.com
supervisor@rootech.com

ⓒ 2015 Rootech Inc. All Rights Reserved

Accura EMeter, Accura 2300S/2350, Accura 2300S/2350-1P3FSC, Accura 3000, Accura 3300E, Accura 3300S/3300,
Accura 3500S/3500, Accura 3550S/3550, Accura 3700, Accura 5500, Accura 7500 are trademarks of Rootech Inc.
Contact rootech for detailed specifications and order information.