HP9335 10-20KVA
High Frequency Online UPS
Indicates the UPS output voltage value, which could be displayed from
0 to 999VAC
Indicates the frequency value of the UPS output voltage, which could
be displayed from 0 to 99Hz.
Load Information
Indicates the load percent in watt or VA, only the maximum value of
them could be displayed from 0 to 199%.
Battery Information
Indicates the battery voltage value, which could be displayed from 0 to
999VDC
Indicates the battery capacitance percent, which could be displayed
from 0 to 199%
Indicates the battery is over charged, and the UPS would be switched
to Battery mode
Indicates the battery is weak, and the UPS would shut down soon
10
3-3. Audible Alarm
Description Buzzer status Muted
UPS status
Bypass mode Beeping once every 2 minutes
Battery mode Beeping once every 4 seconds Yes
Fault mode Beeping continuously
Warning
Overload Beeping twice every second
No
Others Beeping once every second
Fault
All Beeping continuously Yes
2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press the “ON” button to set up the power supply for the UPS, UPS will enter to power on mode.
After initialization UPS will enter to No Output mode, then Press and hold the “ON” button for 0.5s
to turn on the UPS, and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
8. Turn off the UPS without utility power supply in Battery mode
1) Turn off the UPS by pressing “OFF” button for at least 1s, and then the buzzer will beep once.
2) Then UPS will cut off power to output and there is no display shown on the display panel.
4. Parallel Operation
13
c) Turn on each UPS in turns. After a while, the UPSs will enter to AC mode synchronously and
then, the parallel system is completed.
3) Turn on the parallel system in Battery mode:
a) Turn on the battery breaker (only available in long-run model) and output breaker of each UPS.
NOTE: It’s not allowed to share one battery pack for long-run UPSs in parallel system. Each UPS
should be connected to its battery pack.
b) Turn on any UPS. A few seconds later, the UPS will enter to battery mode.
c) Then, turn on another UPS. A few seconds later, the UPS will enter to battery mode and add to
the parallel system.
d) If you have the third UPS, follow the same procedure of c). Then, the parallel system is
complete.
If more detailed information is needed, please contact supplier or service center for parallel
operation instruction.
14
5. Operating mode for models
Standby Mode
Bypass mode
15
Line mode
If output overloaded, the load percent is shown and alarm will keep twice every second. You should
get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than
90% of its nominal power capacity.
Note: Please follow the following steps to connect the generator. Activate the generator and wait until
the operation is stable before supplying power of the generator to the UPS (be sure that the UPS is in
idle mode). Then turn on the UPS according to the start-up procedure. After the UPS is turned on, then
the loads can be connected to the UPS one by one.
The power capacity of the AC generator should be at least twice of the UPS capacity.
Battery mode
Parallel mode
Fault mode
17
Warning mode
Fault code Fault event Icon Fault code Fault event Icon
01 Bus start failure None 26 Inverter A negative power None
fault
02 Bus over None 27 Inverter B negative power None
fault
03 Bus under None 28 Inverter C negative power None
fault
04 Bus unbalance None 33 Battery SCR short circuited None
06 Converter over current None 36 Inverter relay short circuited None
17 Inverter soft start failure None 48 Battery fuse broken in None
Battery mode
18 High inverter voltage None 49 Parallel communication None
failure
19 Low inverter voltage None 54 Parallel output current None
unbalance
20 Inverter A output(line to 65 Over temperature None
neutral) short circuited
21 Inverter B output(line to 66 DSP communication failure None
neutral) short circuited
22 Inverter C output(line to 67 Overload
neutral) short circuited
23 Inverter A-B output (line 70 Incorrect UPS setting None
to line) short circuited
24 Inverter B-C output (line 71 MCU communication failure None
to line) short circuited
25 Inverter C-A output (line
to line) short circuited
18
6-2. Warning Code
19
7. Storage and Maintenance
7-1. Storage
Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
7-2. Maintenance
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that
no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures
may replace batteries and supervise operations. Unauthorized persons must be kept well away from the
batteries.
Verify that no voltage between the battery terminals and the ground is present before maintenance
or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may
occur between the battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all
wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools
with insulated grips and handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The
batteries must be rightly deposed according to local regulation.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may
be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
20
7-3. Battery Maintenance
1)This series UPS only requires minimal maintenance. The battery used for standard models are value
regulated sealed lead-acid maintenance free battery. These models require minimal repairs. The only
requirement is to charge the UPS regularly in order to maximize the expected life of the UPS is turned
on or not, the UPS keeps charging the batteries and also offers the protective function of
overcharging and overcharging and over-discharging.
2)The UPS should be charged once every 4 to 6 months if it has not been used for a long time.
In the regions of hot climates, the battery should be charged and discharged every 2 months. The
standard charging time should be at least 12 hours.
3)Replace batteries with the same number and same type of batteries.
4)Do not replace the battery individually. All the batteries should be replaced at the same time following
the instructions of the battery supplier.
5)Normally, the batteries should be charged and discharged once every 4 to 6 months. Charging should
begin after the UPS shouts down automatically in the course of discharging, the standard charging
time for the standard UPS should be at least 12 hours.
1) Before disposing of batteries, remove conductive jewelry such as necklace, wrist watches and rings.
2)If it is necessary to replace any connection cables, please purchase the original materials from the
authorized distributors or service centers, so as to avoid overheat or spark resulting in fire due to
insufficient capacity.
3)Do not open or mutilate batteries or battery packs in a fire, they may explode.
4)Do not open or mutilate batteries, released electrolyte is highly poisonous and harmful to the skin and
eyes.
5)Do not short the positive and negative of the battery electrode, otherwise, it may result in electric
shock or fire.
6) Make sure that there is no voltage before touching the batteries. The battery circuit is not isolated
from the input potential circuit There may be hazardous voltage between the battery terminals and
the ground.
7)Even though the input breaker is disconnected, the components inside the UPS are still connected with
21
the batteries, and there are potential hazardous voltages. Therefore, before any maintenance and
repairs work is carried out, switch off the breaker of the battery pack or disconnect the jumper wire of
connecting between the batteries.
8)Batteries contain hazardous voltage and current. Battery maintenance such as the battery
replacement must be carried out by qualified personnel who are knowledgeable about batteries. No
other persons should handle the batteries.
22
8. Specifications
MODEL 10KT 10KT-XL 15KT 15KT-XL 20KT 20KT-XL
CAPACITY* 10000VA / 8000W 15000VA / 12000W 20000VA / 16000W
INPUT
110 VAC(Ph-N) ± 3 % at 50% Load
Low Line Loss
176 VAC(Ph-N) ± 3 % at 100% Load
Voltage
Low Line Comeback Low Line Loss Voltage + 10V
Range
High Line Loss 300 VAC(Ph-N) ± 3 %
High Line Comeback High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
Frequency Range
56Hz ~ 64 Hz @ 60Hz system
Phase Three phase with ground
Power Factor ≧ 0.99 at 100% Load
OUTPUT
Phase 3 Phase with Neutral
Output voltage 208/220/230/240VAC(Ph-N)
AC Voltage Regulation ± 1%
Frequency Range 46Hz ~ 54 Hz @ 50Hz system
(Synchronized Range) 56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 10min
AC mode 110%~130%: 1min
>130% : 1sec
Overload
100%~110%: 30sec
Battery mode 110%~130%: 10sec
>130% : 1sec
Current Crest Ratio 3:1 max
Harmonic Distortion ≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
Line Battery 0 ms
Transfer
Inverter Bypass 0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
Time
Inverter ECO <10 ms
EFFICIENCY
AC mode > 89% >89% >89%
Battery Mode > 86% >88% >87%
BATTERY
Type 12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah
Numbers 20(18-20 adjustable) 2 x 20(18-20 adjustable) 2 x 20(18-20 adjustable)
Standard
Recharge Time 9 hours recover to 90% capacity
Model
Charging Current 1.0 A ± 10% (max.) 2.0 A ± 10% (max.) 2.0 A ± 10% (max.)
Charging Voltage 273 VDC ± 1%
Type Depending on applications
Long-run Numbers 18 - 20
Model Charging Current 4.0 A ± 10% (max.) 4.0 A ± 10% (max.) 4.0 A ± 10% (max.)
Charging Voltage 273 VDC ± 1%
PHYSICAL
Dimension, D X W X H 782X248X 582X248X
782X248X890 582X248X767 782X248X890 582X248X767
Outline mm 890 767
Net Weight (kgs) 109 38 164 40 164 40
Dimension, D X W X H 915X412X 681X378X
915X412X1100 681X378X875 915X412X1100 681X378X875
Packaging mm 1100 875
Net Weight (kgs) 127 45 182 47 182 47
ENVIRONMENT
Operation Temperature 0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity <95 % and non-condensing
Operation Altitude** <1000m
Acoustic Noise Level Less than 58dB @ 1 Meter Less than 60dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
* Derate capacity to to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.