Professional Documents
Culture Documents
User’s manual
General contents
Installation 2/1
Use conditions 2/2
Identification of Sepam 2000 2/3
Equipment identification 2/4
Assembly and wiring 2/6
Connection schemes - Three-winding transformer 2/8
Connection schemes - Three-winding transformerwith 2 earthed neutral points 2/9
Connection schemes - Three-winding auto-transformer 2/10
Use and connection of current inputs to CTs 2/11
Use and connection of CSH 30 interposing ring CT 2/13
Connection of power supply and logic inputs and outputs 2/15
Connection of the Jbus/Modbus communication coupler 2/17
Testing 5/1
General information 5/2
Inhibition of outputs and test parameterization 5/3
Differential protection testing with simplified parameterization 5/4
Tripping value chart 5/5
Cabling testing by current injection 5/6
Restricted earth fault protection testing 5/8
Test sheet 5/10
SEPED306028EN - 01/2007 1
2
2 SEPED306028EN - 01/2007
Functions Contents
and characteristics
Introduction 1/2
Definitions and general parameters 1/3
Differential protection 1/4
ANSI 87T code 1/4
ANSI code 64 REF 1/5
Measurements 1/6
Disturbance recording 1/7
Control and monitoring 1/8
Operating mode 1/9
Program logic 1/10
Modbus communication 1/12
General characteristics 1/13
Functions
Functions Sepam 2000 D32
Protections ANSI code
Biased differential 87T b
Restricted earth fault (winding 2) 64REF b
Restricted earth fault (winding 3) 64REF b
Metering
Phase currents I (winding 1) b
Phase currents I’ (winding 2) b
Phase currents I’’ (winding 3) b
Phase shift between I and I’ b
Phase shift between I and I’’ b
Residual current Io b
Residual current Io’ b
Residual current Io’’ b
Differential currents: Id1, Id2, Id3 b
Through currents: It1, It2, It3 b
Tripping currents differential: trip Id1, trip Id2, trip Id3 b
through: trip It1, trip It2, trip It3 b
Disturbance recording b
Control and monitoring
Latching/acknowledgment 86 b
Annunciation 30 b
External tripping b
Detection of plugged connector (DPC) 74 b
Fault trip counter b
Disturbance recording triggering b
Sepam 2000 model
S36 CC
Number of ESTOR boards 2
Definitions
The terms winding 1 and winding 2 are used like that:
b winding 1 refers to the circuit that has the highest voltage Un; the corresponding
currents are connected to connectors 2A and 2B
b winding 2 refers to the circuit that has voltage Un’ less than or equal to Un;
the corresponding currents are connected to connectors 3A and 3B
b winding 3 refers to the circuit that has voltage Un’’ less than or equal to Un’;
the corresponding currents are connected to connectors 4A and 4B.
Example of Example of
three-winding three-winding
transformer: auto-transformer:
U = 132 kV, U = 20 kV,
U’ = 33 kV, U’ = 15 kV,
U’’ = 11 kV U’’ = 6 kV
The zone protected by Sepam 2000 D32 is the zone between the current sensors
connected to connectors 2A and 2B at one end, and the sensors connected to
connectors 3A, 3B, 4A and 4B at the other end.
Status menu
Parameters Selection Remote reading:
function code and
unit
Frequency Fn 50 or 60 Hz D5h - Hz
Phase CT ratio winding 1 In 10 to 6250 A D0h - A
Phase CT ratio winding 2 In’ 10 to 6250 A D9h - A
Phase CT ratio winding 3 In’’ 10 to 6250 A DAh - A
Type of residual current sensor winding 1 TC + CSH30 D2h - index (3)
Rated residual current winding 1 Ino 1 to 6250 A D2h - A
Type of residual current sensor winding 2 TC + CSH30 DBh - index (3)
Rated residual current winding 2 Ino’ 1 to 6250 A DBh - A
Type of residual current sensor winding 3 TC + CSH30 DFh - index (3)
Rated residual current winding 3 Ino" 1 to 6250 A DFh - A
Numerical index’ of vector group 0 to 11 (1) DEh
(winding 2 versus winding 1)
Numerical index" of vector group 0 to 11 (1) DEh
(winding 3 versus winding 1)
Rated power of the transformer S (2) 1 to 999 MVA DEh - MVA
Rated voltage winding 1 Un 220 V to 800 kV DEh - V
Rated voltage winding 2 Un’ 220 V to 800 kV DEh - V
Rated voltage winding 3 Un" 220 V to 800 kV DEh - V
(1) Whatever the star or delta connections of the windings.
(2) S refer to the rated power of the transformer in case of two-winding transformer.
S refer to the winding of highest power in case of three-winding transformer.
(3) Meaning of the index: 2 : CT + CSH30
other value : not used.
Id/Ib Operation
E61950
Id / It = 50 %
4 This protection adjusts the current phase and module of each winding according to
the parameterized transformer connection. It then compares the adjusted currents,
tripping
phase by phase. It is activated if the difference in currents Id for at least one phase
is greater than the operation set point.
3
The set point is defined by the operation characteristic below.
Protection stability with respect to external faults is also ensured by the biased
Id / It = 15 characteristic and by the 2nd and 5th harmonics neural network restraint which
2
analyzes the percentage as well as the differential and through currents.
2 setting zone This restraint prevents unwanted tripping when:
b the transformer is switched on
1
no tripping b an asymmetrical fault occurs outside the zone, causing saturation of
the current transformers
0,3 It/ b the transformer is supplied by excessive voltage (overfluxing).
0 2 4 6 8 10
Percentage operation characteristics
S Schematic diagram
= transformer rated current
3 Un
DE52923
I1’
I1
I1"
87T
→ → →
Id = Iadjusted -I’adjusted -I’’adjusted = differential current
→ → →
It = max ( Iadjusted , I’adjusted , I’’adjusted )
= through current
Characteristics
Function number F601
Bias characteristic Id/It
Setting 15 to 50%
Resolution 1%
Accuracy (1) ±1%
% drop-out (86 ±10)%
Mini. setting
Value 0.3 Ib
Accuracy (1) ±5%
% drop-out (90 ±3)%
Time characteristics
Operating time < 35 ms
Reset time < 35 ms
Outputs available for control logic
Phase 1 tripping F601/1
Phase 2 tripping F601/2
Phase 3 tripping F601/3
Phase 1, 2 or 3 tripping F601/4
Test mode F601/6
Remote reading, remote setting
Function n° 60 h
Parameter Id/It unit: %
(1) In reference conditions (IEC 60255-13).
Operation
E61953
Ido / ln
Restricted earth fault protection detects phase-to-earth faults in a winding of a
transformer, with an earthed neutral.
Ido
= 1,05 It offers the advantage of having greater sensitivity than differential protection.
Io
The function is based on a comparison of the residual current Io ( Io = I1 + I2 + I3 )
Iso and the neutral current Ineutral.
0.8
It picks up if the module of the difference Io-Ineutral is greater than the operating set
point. This set point is defined by, first, a minimum Iso set point and, secondly, by a
percentage type tripping characteristic with a slope of 1.05 and an Ino restraint
Iso setting zone
current characteristic in normal conditions (see curve).
lro = l1 + l2 + l3
2
The sensitivity of the protection is determined by the phase current sensors with a
minimum Iso set point of 5% In.
Io / ln The neutral current is measured by a CT (see determination of current sensors page
0.05
2/11).
Operation characteristics The protected zone is between the phase CTs and neutral CT.
In: phase CT rating
Schematic diagram
DE52924
E61952
Iro = I1 + I2 + I3
I1 + I2 + I3
external
Ineutral
fault Iro = 2* I1 + I2 + I3 +
3
détection
Characteristics
Function number F651-F661
Iso setting
Setting 0.05 In to 0.8 In if In u 20 A
0.1 In to 0.8 In if In < 20 A
Resolution 1 A ou 1 digit
Accuracy (1) ±5% or ±0.5% In
% drop-out (93 ±5) %
Min. reserve difference min. 0.4% In
Time characteristics
Fixed value 1.05
Accuracy (1) ±2%
Time characteristics
Operating time < 40 ms
Memory time < 25 ms
Fault recognition time < 25 ms
Reset time < 40 ms
Outputs available for control logic
Instantaneous tripping, 64 REF winding 2 F651/1
Instantaneous tripping, 64 REF winding 3 F661/1
Remote reading, remote setting
Function code F651 65 h
F661 66 h
Parameter Threshold Iso unit: 1A
Phase current
Measurement of current for each of the three phases of each winding.
Measurement of phase shift with respect to the primary current for each
of the phases.
Residual current
2 Measurement of Io current for each winding.
Tripping currents
Display of the value of the differential and through currents for each of the three
phases, which was stored when the differential protection gave the tripping order,
expressed in primary rms amps.
Characteristics
Measurements Ranges Accuracy (1)
Phase current 0 to 24 In ±0,5 % at In
Phase shift 0 to 359° ±3° at In
Residual current Io 0 to 10 Ino ±5 %
Differential currents Id1, Id2, Id3 0 to 24 In ±5 %
Through currents It1, It2, It3 0 to 24 In ±5 %
Tripping currents:
Differential: trip Id1, trip Id2, trip Id3 0 to 24 In ±5 %
Through: trip It1, trip It2, trip It3 0 to 24 In ±5 %
(1) In reference conditions (IEC 60255-13)
The measurements are available directly in the appropriate units (A, kA) on Sepam
via the console
Operation Principe
Used to record analog signal and logical states.
E61954
stored record
Record storage is triggered by a triggering event:
b tripping of differential protection
b tripping of restricted earth fault protection time
b local manual triggering
b remote manual triggering.
triggering event
The duration of the signal recorded before the
triggering event may be set using the pocket terminal
via the oscillography item in the status menu.
The date of record storage may also be accessed via
Characteristics 2
Record duration 86 periods
the pocket terminal in the oscillography item of the the duration before the triggering event may be set
status menu and via the communication link (refer to from 1 to 85 periods.
“Jbus/Modbus communication” document). This date Record content set-up file: date and channel characteristics
corresponds to the date of the triggering event. data file: 12 values per period/recorded signal
The stored event begins before the triggering event and Analog signals recorded all currents connected to the acquisition boards
continues afterwards. Logical states recorded tripping outputs O1, O2 and O21,
differential and restricted earth fault operation
The record includes of the following informations: digital inputs, I11 to I18
b values sampled from the different signals Number of records stored 2
b the date File format COMTRADE IEEE C37.111 - 1997
b the characteristics of the recorded channels. IEC 60255-24
The files are recorded in FIFO (First In First Out) type
shift storage: the oldest record is erased when a new
record is triggered.
Transfer Restitution
Files may be transferred locally or remotely: Record signals may be restituted using the SFT2826 software program.
b locally: using a PC which is connected to the console
E56443
Memorizes tripping orders (latching) and requires user action to be put back into
service (reset).
2 Fault detection
Differential b
Secondary restricted earth fault b
Tertiary restricted earth fault b
External tripping b
Inhibition of differential protection
Operating mode: test connection, inhibition of outputs b
External tripping
Input available to the Sepam to take into account a process fault detected by an other
device: tripping an indication.
protection
normal testing and commissioning operations.
tripping inhibited The change from one mode to the other is obtained by means of KP6 and KP9
parameter settings (1).
Normal
The protection functions operate on tripping and signalling contacts according
to the settings.
tripping protection
This mode is the normal operation mode.
2
inhibition testing and
tripping active Tripping inhibition
The protection functions operate on signalling contacts according to the settings.
The tripping output contacts are inhibited.
This mode is designed to test Sepam 2000 when the protected equipment is still
on duty.
Operation
Functions Control Indication
O1 O2 O21 O12 O13 O14 O22 Message
winding 1 winding 2 winding 3 winding 1 winding 2 winding 3
Differential b b b b b b b DIFF.
Restricted earth fault winding 2 b b b b b b b REF 2
Restricted earth fault winding 3 b b b b b b b REF 3
External tripping
Detection of plugged connectors
b v (1) v (1) b v (1) v (1) EXT. TRIP.
CONNECTOR 2
(1) According to parameter setting.
Parameter setting
Parameters KP can be set by means of the console
Functions Parameter
Tripping control
Winding 2 with shunt trip coil KP2 = 0
Winding 2 with undervoltage release coil KP2 = 1
Winding 3 with shunt trip coil KP3 = 0
Winding 3 with undervoltage release coil KP3 = 1
Operating functions
Input I2 activated if fault detected by auxiliary device (external tripping) normally closed contact KP7 = 0
normally open contact KP7 = 1
External tripping (I2) activates winding 1 (upstream) tripping External KP10 = 0
External tripping (I2) activates windings 1, 2 and 3 tripping External KP10 = 1
Latching of outputs associated with tripping O1 - O2 - O12 - O13 - O21 - O22 KP13 = 1
Operating mode
Switching to test mode KP6 = 1
Inhibition of differential and restricted earth fault tripping KP9 = 1
Counter
Resetting of fault trip counter KP20 = 1
Disturbance recording
Lock triggering KP50 = 1
Automatic unlock and triggering KP51 = 1
Manual unlock and triggering KP52 = 1
Remote setting
Remote setting enable KP38 = 0
Remote setting disable KP38 = 1
Electrical characteristics
Analog inputs
Current transformer 1 A CT < 0.001 VA
10 A to 6250 A ratings 5 A CT < 0.025 VA
Logic inputs
Voltage 24/30 Vdc 48/127 Vdc 220/250 Vdc
Consumption 4 mA 4 mA 3 mA
Auxiliary power supply
DC voltage
Typical consumption
24/30 Vdc
18 W
48/127 Vdc
19.5 W
220/250 Vdc
21 W
2
lLgic outputs (relays)
Voltage 24/30 Vdc 48 Vdc 125 Vdc 220/250 Vdc
Rated current 8A 8A 8A 8A
400 ms overload 15 A 15 A 15 A 15 A
Making capacity 15 A 15 A 15 A 15 A
Breaking capacity: DC with resistive load 8A 4A 0.8 A 0.3 A
DC with resistive load 6A 2A 0.4 A 0.15 A
DC at L/R = 40 ms 4A 1A 0.2 A 0.1 A
AC with resistive load 8A 8A 8A 8A
AC with p.f. = 0.3 5A 5A 5A 5A
Environmental characteristics
Electric insulation
Dielectric withstand IEC 60255-5 2 kV - 1 mn (1)
1.2/50 µs impulse wave withstand IEC 60255-5 5 kV (2)
Climatic withstand
Operation IEC 60068-2-1 and 2 - 5 °C to + 55 °C
IEC 60068-2-14 - 5 °C to + 55 °C
Storage IEC 60068-2 - 25 °C to + 70 °C
Damp heat IEC 60068-2-3 93% RH at 40 °C
56 days (storage)
10 days (operation)
Corrosion influence IEC 60654-4 class I
Mechanical robustness
Degree of protection IEC 60529 IP 51 front face
Vibrations IEC 60255-21-1 class I
Shocks / jolts IEC 60255-21-2 class I
Earthquakes IEC 60255-21-3 class I
Fire resistance IEC 60695-2-1 glow wire
Electromagnetic compatibility
Radiated fields IEC 60255-22-3 class X 30 V/m
IEC 61000-4-3 class III 10 V/m
Electrostatic discharge IEC 60255-22-2 class III
IEC 61000-4-2 class III
Damped 1 MHz wave IEC 60255-22-1 class III
5 ns electrical fast transients/burst IEC 60255-22-4 class IV
IEC 61000-4-4 class IV
1.2/50ms - 8/20ms surge immunity IEC 61000-4-5 class III 2 kV differential mode (42 Ω)
1 kV common mode (42 Ω)
Conducted disturbance emission EN 55022/CISPR22 class B with auxiliary power supply (3)
Radiated field emission EN 55022/CISPR22 class B (4)
" e" marking on our product guarantees their conformity to European directives.
(1) except for communication 1.4 kV dc and auxiliary power supply 2.8 kV dc.
(2) except for communication 3 kV common mode, 1 kV differential mode.
(3) EN 50081-1 generic standard.
(4) EN 50081-2 generic standard.
E61465
package.
2 We recommend that you follow the instructions given in
this document for quick, correct installation of your
Sepam 2000:
b equipment identification
b assembly 55
b connection of current and voltage inputs, probes
b microswitch setting normal use zone
40
b connection of power supply and earth
b checking prior to commissioning.
humidity (%)
35 65 93 95
There are five labels for identifying Sepam: Example of Sepam references:
2
b two labels on the right side panel which give the S36 Sepam 2036
product’s hardware features (1) CC Type
b a label on the front of the cartridge which gives the
D Differential
functional features (2)
32 2 windings
b a label on the left side of the cartridge which includes
its references (3) X no communication
b a label on the right side of the cartridge which may be 2 2 ESTOR boards
used to note the references of a non-standard control F French
logic scheme (4). T CT
B 48 - 125 V
N -5/+55 °C
DE52883
(1) Example of label on right side panel board name servicing dates
Identification
DE52884
E42463
of a non-standard
S36: standard Sepam program logic scheme
Sepam D32: type Sepam réf. : Date Version
D32: type
F: French (4) Label on the right side
A: revision index of the cartridge.
03143764FA-B0-01-9740208
Optional accessories
TSM 2001 pocket terminal
E61745
2
SFT 2801 / SFT 2821 kit
b The SFT 2801 software tool installed on a PC microcomputer may be used instead
MT10583
In the rest of the document, the term "pocket terminal" refers to both the TSM 2001
pocket terminal and the SFT 2801 kit.
37,5 31,5
26,5 429
482
E61098
87
Communication accessories
CCA 602 cable
3 m long cable with connectors supplied Sepam 2000 equiped with the
communication option.
E519789
Maximum thickness of mounting: 3 mm
2
20 300 338
352 332
Assembly (2)
b Insert Sepam 2000 through the front of the cut-out. (2)
E61731
E62000
(1)
Slot
8 7 6 5 4 3 2 1
S36 CC ESTOR ESTOR ESTOR ESB ECMD ECMD ECMD CE40
Connections
The Sepam 2000 connections are made on the 2
PE50740
removable connectors located on the rear of the device.
All the connectors are screw-lockable.
Wiring of screw connectors:
b Recommended wire fittings:
v Telemecanique DZ5CE0155 for 1.5 mm2
v DZ5CE0253 for 2.5 mm2.
Stripped length with fitting: 17 mm.
b Without fitting:
v stripped length: 10 to 12 mm
v maximum 2 wires per terminal.
The 21-pin connectors must be connected correctly by
hand before being locked by the 2 screws (top/bottom).
Terminal identification principle ESTOR ESTOR ESTOR ESB ECMD ECMD ECMD CE40
All the Sepam 2000 connection terminals are located
E48029
b slot (1 to 8)
14 14 14 14
13 13 13 13
b connector A or B 12 12 12 12 SW2 SW2 SW2
11 11 11 11
b terminal (1 to 21). 10 10 10 10 SW1 SW1 SW1
V-DC 24-30 48-125 220-250
b ESB: control interface INPUTS AND INPUTS AND INPUTS AND INPUTS AND CURRENT CURRENT CURRENT POWER SUPPLY
OUPUTS OUTPOUTS OUTPUTS OUTPUTS INPUTS INPUTS INPUTS
b ESTOR: control interface. ESTOR3 ESTOR2 ESTOR1 ESB WINDING 3 WINDING 2 WINDING 1
(1)
(1) In option.
MT10603.eps
L1 L2 L3
of the differential protection.
CE40 1B
1
2
3
1A 4
2 4
2B ECMD 87T ESB 5A 21
1
DPC 20
5
2 19
18
6 17
3 CDG
16
15
14
13
12
O2
11
10
9
8
O1
7
6
5
4
l2
3
2
l1
1
4 ESTOR 6A 21
3B ECMD
1
5
2
6
3
L1 L2 L3
1
ESTOR 7A 21
ESTOR 8A 21
4
4B ECMD
1
5
2
6
3
1
L1 L2 L3
MT1064.eps
L1 L2 L3
for restricted earth fault protections.
CE40 1B
1
2
3
1A 4
4
1
2B ECMD 87T ESB 5A 21
DPC 20
2
5
2 19
18
6 17
3 CDG
16
15
14
Connection of a 5 A 13
current transformer via a 12
CSH30 O2
11
interposing ring CT 10
9
8
O1
7
6
5
6 3A ECMD 64 4
5 DPC REF l2
2 3
4 2
3 30 A l1
1
1 2 2A
1 TC +
CSH30
ESTOR 6A 21
4
3B
1
5
2
6
3 1
L1 L2 L3
ESTOR 7A 21
Connection of a 5 A
current transformer via
a CSH30 interposing ring 6 4A ECMD 64
5 DPC REF
2 CT
4
3 30 A
1 2 2A
Connection of a 1 A current transformer via a CSH30 1 TC +
CSH30
interposing ring CT. 1
MT10612.eps
ESTOR 8A 21
3A ECMD 4
4B
6 1
5 DPC 5
2
4 2
3 30 A 6
2 3 1
1 2A
1 TC + CSH30
5 turns L1 L2 L3
MT10605.eps
L1 L2 L3
CE40 1B
1
2
3
1A 4
2 4
1
2B ECMD 87T ESB 5A 21
DPC 20
5
2 19
18
6 17
3 CDG
16
15
14
13
12
O2
11
10
9
8
O1
7
6
5
4
l2
3
2
l1
1
4 ESTOR 6A 21
4B ECMD
1
5
2
6
3
L1 L2 L3
1
ESTOR 7A 21
4
3B ECMD
1
5
2
6
3 1
ESTOR 8A 21
L1 L2 L3
S S
0.1 . y In y 2.5 . for winding 1
3 Un 3 Un
S S
0.1 . y In' y 2.5 . for winding 2
3 Un' 3 Un'
2
S S
0.1 . y In'' y 2.5 . for winding 3
3 Un'' 3 Un''
If the phase CT rated current In is sufficiently low (In y 300 A), the neutral current may
be measured by a CSH120 or CSH200 core balance CT.
If this is not the case (which happens most frequently), the neutral current is
measured by a CT. A CSH30 interposing ring CT is required between the 1 A or 5 A
secondary winding of the neutral CT and the Sepam 2000 residual current input.
1 A or 5 A CT connection diagram
ESTOR ESTOR ESTOR ESB ECMD ECMD ECMD CE40
The current transformer (1 A or 5 A) secondary circuits
E48029
are connected to the CCA 660 connector on the ECMD 21 21 21 21
module. 20 20 20 20
19 19 19 19
The connector contains 3 core balance CT primary- 18 18 18 18
(communicat
option)
throught adapters to ensure impedance matching and 17 17 17 17
16 16 16 16 B B B B
isolation between the 1 A or 5 A circuits and 15 15 15 15
Sepam 2000. 14 14 14 14
13 13 13 13
The connector may be disconnected with the power on 12 12 12 12 SW2 SW2 SW2
8 7 6 5 4 3 2 1
INPUTS AND INPUTS AND INPUTS AND INPUTS AND CURRENT CURRENT CURRENT POWER SUPPLY
OUPUTS OUTPOUTS OUTPUTS OUTPUTS INPUTS INPUTS INPUTS
ESTOR3 ESTOR2 ESTOR1 ESB WINDING 3 WINDING 2 WINDING 1
(1)
(1) In option.
1 2 3
E56490
ECM
DPC
B4
L1 B1
B5
L2 B2
B6
L3 B3
CCA660
E40488
terminals. The shields may be removed, if necessary, to
facilitate wiring. If removed, replace them after wiring.
b Remove the bridging strap if necessary.
The strap links teminals 1, 2 and 3.
b Connect the wires using 4 mm eye lugs.
The connector accommodates wires with cross
sections of 1.5 to 6 mm2 (AWG 16 to AWG 10).
b Close the side shields.
2
(1) Replaced by CCA660.
E61970
B 21
residual current is measured by a current transformer
8 4
with a secondary circuit (1 A or 5 A).
It acts as an adapter between the CT and the
Sepam 2000 residual current input.
It should be connected to the CT input of the øA F 16
Sepam 2000 and installed near the corresponding
E
Sepam input (max. 2 m). 5
2 Characteristics
D
2 ø 4,5
Assembly
The CSH 30 interposing ring CT is mounted on a
E44717
E40468
symmetrical DIN rail. It may also be mounted on a plate
through the mounting holes provided on its base.
E61733
E62001
ECMD 5 turns
A6
DPC
REF
calib. 30 A
A5
A4
A3
A2
2
calib. 2 A
A1
cb CT
CSH 30 1 A CT
interposing
DE52927
Please note:
Sepam 2036 models CR or CC have some inputs for connecting CTs. Remember to
set the micro-switches of all inputs.
SW2
E61432
CCA 604 4-point terminal block on the CE40 module 21 21 21 21
situated on the rear of the device. 20 20 20 20
19 19 19 19 (communication
The power supply input is protected against accidental 18 18 18 18 option)
17 17 17 17
polarity inversion. 16 16 16 16 B B B B
15 15 15 15
14 14 14 14
Safety: 13 13 13 13
SW2 SW2 SW2
The Sepam 2000 chassis must be earthed 12 12 12 12
Connection of logic inputs and outputs ESTOR ESTOR ESTOR ESB ECMD ECMD ECMD CE40
The logical data are connected to the CCA 621
E48029
8 7 6 5 4 3 2 1
INPUTS AND INPUTS AND INPUTS AND INPUTS AND CURRENT CURRENT CURRENT POWER SUPPLY
OUPUTS OUTPOUTS OUTPUTS OUTPUTS INPUTS INPUTS INPUTS
ESTOR3 ESTOR2 ESTOR1 ESB WINDING 3 WINDING 2 WINDING 1
(1)
(1) In option.
ESB board
Terminals Connected data
MT10606
ESTOR boards
ESTOR 1 board ESTOR 2 board
Terminals Connected data Connected data
MT10607
MT10608
ESTOR A ESTOR A 21
21 21 DPC detection of plugged connectors DPC detection of plugged connectors
DPC 20 DPC 20 20
19 19 19 I18 reserved I28 reserved
l18 l28
18 18 18 I17 reserved I27 reserved
l17 l27
17 17 17 I16 reserved I26 reserved
l16 l26
16 16 16 I15 reserved I25 reserved
l15 l25
15 15 15 I14 reserved I24 reserved
l14 l24
14 14 14 I13 reserved I23 reserved
l13 l23 13
13 13 reserved reserved
12 12 12 O14 transformer differential or O24 reserved
O14 O24 11 11 restricted earth fault indication
11
10 10 10 O13 indication of winding O23 reserved
O13 9 O23 9 9 2 tripping
8 8 8 O12 indication of winding O22 indication of winding 3 tripping
O12 O22 7 7 1 tripping
7
6 6 O11 reserved O21 winding 3 tripping
6
5
O11 5 O21 5
4 I12 remote control authorized I22 reserved
4 4
3
l12 3 l22 3
2 I11 reserved for communication I21 reserved
2 2 1 synchronization
l11 1 l21 1
E48029
ESTOR ESTOR ESTOR ESB ECMD ECMD ECMD CE40
21 21 21 21
20 20 20 20
19 19 19 19
(communication
18 18 18 18 option)
17 17 17 17
16 16 16 16 B B B B
15 15 15 15
14 14 14 14
13 13 13 13
12 12 12 12 SW2 SW2 SW2
11 11 11 11
10 10 10 10 SW1 SW1 SW1
V-DC 24-30 48-125 220-250
8 7 6 5 4 3 2 1
INPUTS AND INPUTS AND INPUTS AND INPUTS AND CURRENT CURRENT CURRENT POWER SUPPLY
OUPUTS OUTPOUTS OUTPUTS OUTPUTS INPUTS INPUTS INPUTS
ESTOR3 ESTOR2 ESTOR1 ESB WINDING 3 WINDING 2 WINDING 1
(1)
(1) In option.
b Status indicators 1
v green on indicator: lamp shows that Sepam 2000 is energized
v red trip indicator lamp: Sepam 2000 has tripped the circuit breaker after detecting
a fault. A related alarm message indicates the cause of tripping
1 2 5 v red : indicator: lamp shows internal Sepam faults. All the output relays are
E61746
2 b Display 2
The display unit indicates operating and maintenance messages.
status
indicators 1
displays 2
keys 3
The TSM 2001 pocket terminal and the SFT 2801 software for PC operate in the
same way.
E61745
The TSM 2001 pocket terminal provides access to all the Sepam 2000 data
such as:
b operating assistance messages
b protection settings.
The pocket terminal is supplied with power by Sepam 2000 and does not require any
1 4-line display
batteries; it can be connected with the power on.
The pocket terminal beeps when it is connected.
The main menu appears. If not check the brightness adjustment using the dial
The user may access the various items of information from three menu levels.
A menu may comprise several pages.
.
2
To access a menu, simply position the blinking cursor on the desired line and press
2 data entry keypad the enter key.
The first line of the menu contains the name of the current menu or function.
Indication of P/ at the top of the menu shows that the user has entered the password.
P/Select:
b The menu key is used to display the previous menu.
Protection
Program logic b The r and r keys are used to move the cursor one line up or down in a menu.
To move to the next screen of a menu, the user simply positions the cursor on the last
Add. reading line and presses the r key.
To move to the previous screen of a menu, the user simply positions the cursor on
the second line and presses the r key.
E48135
b The code key is used to enter and exit the parameter setting mode.
b The numeric and . keys are used to enter settings and the password.
b The units key is used to change setting unit multiplying factors (e.g. A, kA, …).
P/Select: b The data+ and data- keys are used to select setting values from a predefined
data table.
Status
b The clear key is used:
About Sepam v to clear error messages
v to call back a previous setting value during data input
v to reset tripping currents and maximum demand readings to zero.
Note: the first line always contains the name of the current b The enter key is used to confirm a menu selection or to confirm all the settings for
menu or function.
a function.
menu
E48136
enter
P/Select:
Protection
Program logic
Add. reading
enter
2 P/Select:
Status
About Sepam
P/PROGRAM LOGIC P/PHASE CT RATIO P/I PHASE P/LOGIC OUTPUT P/DIFF. TRANS
203 DFA CAT In = 500 A I1 = 123 A 01-02 = 10 Id/It = 15%
Transformer I2 = 125 A 011-014 = 0000
Differential I3 = 123 A 021-024 = 0000
MT10583
E48145
Enter your password
then
press enter key
2
Type the following on the keyboard 6543210 and then press enter.
This the password for standard Sepams. If your Sepam has been customized,
refer to the documentation provided by your OEM.
To exit from this mode, simply:
b press the code key
b wait 2 min after activating any key.
When the pocket terminal is in parameter setting mode, P\ appears on the top left
of the screen.
Modification of the password
b switch to parameter Setting mode and access "Password" in the "Status" menu.
v enter the old password and confirm by pressing "enter"
v enter the new password and confirm by pressing "enter"
v to check, enter the new password and confirm by pressing "enter"
v confirm again in the window which appears
E48146
P\Password
Validate settings
Yes = Enter No = Clear
E61747
2
Event counter
Annunciation
When an event is detected by Sepam 2000, an operating message appears on
the display.
The messages are stored in a list of 16 alarms and may be reviewed in chronological
order of appearance, starting with the most recent:
2
b on Sepam 2000, by pressing the alarm key
b on the pocket terminal, in the program logic menu.
Pressing the reset key will erase the alarms that can be consulted
on Sepam 2000. The alarms on the pocket terminal are not erased.
List of messages
Message (1) Typr Description
DIFF. P differential protection tripping, percentage setting
REF 2 P restricted earth fault protection tripping, winding 2
REF 3 P restricted earth fault protection tripping, winding 3
EXT TRIP C external tripping
TEST.COUPL T differential protection parameterized in test mode
INHIBIT. T inhibition of alarm and tripping outputs
INHIB.OPG T locking, disturbance recording tripping
CONNECTOR M connector unplugged
CARTBRIDGE M cartridge and Sepam not compatible
MAINTENANCE M internal Sepam fault
M.CARTRIDGE M internal cartridge fault
P = protection
C = control and monitoring
M = maintenance
T = test
(1) If your Sepam 2000 has been customized, other messages may appear. Please refer
to the information package supplied by your OEM.
Supply voltage
E61705
Ensure that the cubicle auxiliary supply voltage matches Sepam 2000's operating
voltage. It is indicated on the rear of the device, beside the power supply connector,
by a dot in the voltage box.
V-DC 24-30 48-125 220-250
Earthing
2 4
3 +
Check that the Sepam 2000 chassis is earthed by the grounding nut situated on the
Sepam side panel, on the power supply side. Check that the screw has been
tightened.
2
1
A
Cartridge
DE52887
Check that the cartridge is in its slot behind the front wicket door. To do so, open the
door by pulling on the notch situated on the left side panel. Sepam S36 has a shield
on the right, which resembles the memory cartridge door. This shield is not another
door; do not try to open it. Check, by hand, that the 2 threaded screws have been
tightened.
Do not plug in or unplug the cartridge while Sepam 2000 is energized.
The cartridge has an identification label on the front. The characters in the second
line of the label indicate the type of Sepam 2000. Ensure that the type matches the
Sepam 2000 model indicated on the side of Sepam 2000.
Example
CC on the cartridge label should match CC on the Sepam 2000 label.
B B
6 6
Connector
5 5 Check that all the connectors are correctly connected to the rear of the device and
4 4 4
3 3 3 +
screwed in.
2 2 2
1 1 1
A A A
Checking mode
2
All information may be accessed for checking purposes without the risk of changing
parameters and settings.
P\ CT ratio
E51985
protection setting
out of range
press clear
The user should then check and, if necessary, change the protection settings.
The PROTECTION line blinks until the settings have been corrected.
Settings out of range.
A protection value may be out of range when it is set.
Sepam 2000 detects this and indicates the permissible range of settings.
P\ DIFF.TRANS F601
E51984
(1) All parameters and settings must be based on a network discrimination study that is to be
carried out prior to commissioning.
(2) This mode is automatically cancelled if no keys are pressed for about 2 min. It may be
cancelled manually by pressing the Code key.
2 Io sensor sensor
winding 3
type of neutral point current
measurement winding 1
keys
data + and -
keys
10 A to 6250 A (3)
b sum of 3I
b 2 A core bal. CT
b 30 A core bal. CT
b CT + CSH30
b core bal. CT
+ ACE990 (7)
Ino CT rating in the case of numeric setting between
CT + CSH30 keys 1 A and 6250 A
Io’ sensor sensor type of neutral point current data + and - b sum of 3I
Io" sensor (5) measurement keys b 2 A core bal. CT
winding 2 (Io') b CT + CSH30
winding 3 (Io'') b core bal. CT
+ ACE990 (7)
Ino CT rating in the case of numeric setting between
CT + CSH30 keys 1 A and 6250 A (3)
Transformer sensor’ vector group of winding 2 numeric 0 to 11
reference winding 1 keys
sensor" vector group of winding 3 numeric 0 to 11
reference winding 1 keys
S rated power (2) numeric 1 MVA to 999 MVA
keys (4)
If the Sepam 2000 program logic is customized, the role of the parameters may be
different; please refer to the information package provided by the installer.
Parameter setting
Parameter Function
Tripping control
KP2 = 0 winding 2 breaker with shunt trip coil
KP2 = 1 winding 2 breaker with undervoltage release coil tripping
KP3 = 0 winding 3 breaker with shunt trip coil
KP3 = 1 winding 3 breaker with undervoltage release coil tripping
Parameterization of input
2 KP7 = 0
KP7 = 1
inputs I2 (external tripping) activated by N/O contact
inputs I2 (external tripping) activated by N/C contact
Parameterization of outputs
KP10 = 0 I2 (auxiliary 1) and I14 (auxiliary 2) trip winding 1 breaker (O2 and O13)
KP10 = 1 I2 (auxiliary 1) and I14 (auxiliary 2) trip winding 1, 2 and 3 breakers
(O1 and O2, O12, O13, O21 and O22)
KP13 = 0 Impulse outputs O1, O2, O12, O13, O21, O22 (tripping and indication)
(set by T1 and T2)
KP13 = 1 Impulse outputs O1, O2, O12, O13, O21, O22 (tripping and indication)
Remote setting
KP38 = 0 remote setting active
KP38 = 1 remote setting inactive
Maintenance and testing
KP6 = 1 change to test mode and inhibition of tripping outputs
KP9 = 1 inhibition of tripping outputs
KP20 = 1 reseting of fault trip counter
Disturbance recording
KP50 = 1 tripping (inhibition)
KP51 = 1 unlocking and automatic tripping
KP52 = 1 unlocking and manual tripping
Note: all other KP are not used.
Time delays
The time delays are factory - set by default to 0.2 s.
Time delay Function
T1 minimum duration of tripping order O1 and indication O12
T2 minimum duration of tripping order O2 and indication O13
Exploitation
Function Command Annunciation
O1 O2 O21 O12 O13 O22 O14 Message Indicator
winding 1 winding 2 winding 3 winding 1 winding 2 winding 3
Differential protection b b b b b b b DIFF. trip
Restricted earth fault b b b b b b b REF 2 trip
winding 2
Restricted earth fault b b b b b b b REF 3 trip
winding 3
External tripping
Trip output inhibition
b b (1) b (1) b b (1) b (1) EXT TRIP
INHIBIT.
trip
test
2
(fixed)
Test mode and trip COUPL. TEST test
output inhibition (fixed)
Test mode and trip COUPL. TEST test
output operative (blinking)
Sepam connector unplugged CONNTECTOR
Disturbance recording OPG INHIB.
triggering inhibition
(1) According to parameter setting.
2 Data recorded
All the analog inputs are recorded a,d the logical states recorded are as follow:
Function Name of logical state
Winding 1 tripping KFR1
Winding 2 tripping KFR2
Winding 3 tripping KFR6
Differential protection KFR3
Restricted earth fault protection, winding 2 KFR4
Restricted earth fault protection, winding 3 KFR5
b Configuration fault:
v red indicator lit up
v red lamp indicates CARTRIDGE
v no dialogue with the pocket terminal
v no dialogue with the communication link
v the watchdog is dropped out
v switching to fail-safe position
v Sepam 2000 is shut down: this is a major fault
.
Check whether the type of cartridge with the type of Sepam 2000.
(1) This may cause tripping with undervoltage control logic ("fail-safe" logic scheme).
2 Sepam 2000 is operating, however it has detected a transient fault or has failed
to pass self-testing.
Consult your maintenance department.
b red indicator lamp lit up and the recommendations given in the maintenance
chapter do not allow Sepam 2000 to be restarted.
Call in the maintenance department.
Tests
Lamp test: when the user presses the - lamp test - keys at the same time,
all the indicators on the front of the device light up, as well as the display
which alternately indicates 0.0.0.0.0.0.0.0.0.0.0 then ***********, then -----------.
Sepam replacement
When Sepam 2000 is replaced:
E61735
Characteristics 4/2
Output relays characteristics 4/3
Dependability 4/4
Autotests 4/5
Qualification tests 4/6
Electrical tests 4/7
Performance tests in reference conditions 4/8
Testing of output effects in rated domains 4/9
Effects of the environment on the equipment 4/10
Effects of the equipment on the environment 4/12
Reference documents 4/13
10 10
AC: resistive load
8 8
4
AC: cos ϕ = 0.3 6
4
AC: resistive load 2
DC: resistive load
50
0
2 2
DC : L = 0.04 s
W
DC : L = 0.02 s
25
25
0
0
1 R 1
W
W
0.8 0.8
DC : L = 0.02 s DC: resistive load
0.6 0.6 R
10
10
0
0.4 0.4
0
W
W
50
50
0.2 0.2
W
W
25
25
W
W
0.1 0.1
10 20 24 40 48 60 80 100 125 200 U(V) 10 20 24 40 48 60 80 100 125 200 V(V)
I(A) I(A)
E61466
10 10
AC : resistive load
8 8
6 AC : cos ϕ = 0.3 6
AC : resistive load
4 4
50
DC:
0
2 2
DC : L = 0.04 s resistive load
W
DC : L = 0.02 s
25
25
0
1 R 1
W
0.8 0.8
DC : L = 0.02 s DC : resistive load
0.6 0.6 R
10
10
0.4 0.4
0
W
W
50
50
0.2 0.2
W
W
25
25
W
0.1 0.1
10 20 24 40 48 60 80 100 125 200 U(V) 10 20 24 40 48 60 80 100 125 200 V(V)
This chapter presents the main definitions Consideration of dependability in Sepam 2000
of dependability and how it is taken into consideration By the same token as electromagnetic compatibility, dependability is taken into
in Sepam 2000, an analysis of the experience gained consideration right from the start of the development of Sepam 2000.
from feedback on the installed equipment base A Preliminary Risk Analysis (PRA) is used to list the unwanted events linked to the
and the maintenance of Sepam 2000. different functions performed by Sepam. Quantified dependability targets are set
in accordance with the main unwanted events revealed by the PRA.
Specialized dependability assessment and modeling techniques are used to
Definitions interpret the targets in terms of design requirements.
The definitions which follow are the main definitions b The predicted reliability analysis determines the failure rate of each Sepam 2000
2 of dependability applied to protective devices:
b The reliability of a protective device is its capability of
performing its function (or functions) over a given
component in use-related conditions. Compendiums of reliability data such as the
Military Handbook 217 (MIL HDBK 217) and the CNET RDF93 are used for this.
b The Failure Modes, Effects and Criticality Analysis (FMECA) analysis is used to
period of time in the operating conditions specified by analyze the effects of a simple component failure on the Sepam 2000 functions and
the manufacturer, i.e. mainly the capability of tripping to list the means available to detect them. The FMECA makes it possible to correct
when required and the capability of not tripping when certain risks of malfunctions and specify the self-monitoring functions.
unwanted. b The unwanted events are modeled to calculate the probability of their occurrence
b The availability of a protective device is its capability and to check that the dependability targets are being met.
of being in a state to perform its function (or functions) b A large share of the functions of digital protective equipment devices are
at a given point in time in the operating conditions performed by the software. It is therefore essential to master the quality of the
specified by the manufacturer. software in order to attain the overall dependability targets. Software quality is
These values do not necessarily have the same mastered by the implementation of a rigorous development method.
meanings, depending on whether they are considered b This method is derived from the recommendations set by the French (AFCIQ) and
from the viewpoint of the protective device or the international (IEEE) quality authorities. It stipulates:
electrical installation. v the breakdown of development into a series of phases
b The availability and maintainability of the protective v the use of design and encoding rules and methods aimed at achieving a high level
device contribute to the safety of people and of software structuring
equipment. The reliability of the protective device v the use of software configuration management tools which allow all the software
contributes to the uninterrupted availability of the power component parts to be managed.
supply.
E61468
internal Bus
current
acquisition
power supply display / keypad
2
CB control I/O processing communication
unit
cartridge
(EPROM)
program logic
logic I/O
This chapter presents the main specified It is divided into 5 sections, grouping together the different items involved in product
properties (mechanical, electrical, qualification by theme:
functional, etc...) that are verified during the Electrical tests
qualification tests carried out in the factory Tests related to the protection of people and equipment (grounding continuity,
("manufacturer" tests). insulation, fuses…).
It describes: Performance tests in reference conditions
b the content of each test Verification of special functional features (hardware and software) of the product
b the standards and reference documents when used in the "reference environment" (i.e. temperature, power supply…
2 b the expected results using strict tolerances).
Reference documents
In order to facilitate reading, only documents of prime importance are succinctly
referenced in each test description.
Aim
The aim of these tests is to test the special functional features (hardware and
software) of a device in its "reference environment", i.e. temperature, power supply,
etc., using strict tolerances.
2 For each type of input (sensors, process, etc.), minimum testing includes:
b dynamics and accuracy (examination of the rated domain)
b input impedance (examination of the rated domain)
b passband.
Logic input circuits
Composition of tests
For each type of input (static relay, etc.), minimum testing includes:
b input impedance (exploration of rated domain)
b thresholds (high, low, hysteresis)
b minimum set-up time (high and low levels).
Logic output circuits
Composition of tests
For static type outputs, minimum testing includes:
b output dynamics (I or V)
b output compliance (I or V)
b influence of load (transition time, over/undershoots)
b for datacom: protocol, frequency, gigue, etc.
For relay type outputs, minimum testing includes:
b breaking capacity (min.-max. I/V, load impedance)
b bounce time.
Miscellaneous
Initialization
Aim: to verify the efficiency of self-testing carried out by the device during start-up.
Downgraded operation
Aim: to verify the efficiency of self-testing carried out by the device while functioning.
Module interchangeability
Aim: to test maintenance capability.
Comments: the tests include:
b power source converter
b core-connector.
Aim
These tests test the level of interference (electrical, electromagnetic, etc.) generated
by the device.
DC power supply
Reference documents:
standards: IEC 61131-2
Power consumption
Aim: to check the conformity of the device to specifications.
2 Severity: the test is performed at the rated voltages of the two operational domains,
i.e. 48 V and 127 V.
Inrush current
Aim: to check the conformity of the device to specifications.
Acceptance criteria:
Time Inrush current maximum peak
50 µs y t < 1.5 ms 10 A
1.5 ms y t < 500 ms 10 A
500 ms y t 1.2* In (1)
(1) In = steady-state current.
Radiofrequency interference
Conducted interference
Aim: to check the interference voltage introduced by the device at the energy network
terminal posts.
Reference documents:
standards: CISPR 22
Acceptance criteria:
b maximum emission (virtually peak):
b 79 dB (µV) from 0.15 to 0.5 MHz
b 73 dB (µV) from 0.5 to 30 MHz.
Radiated interference
Aim: to test the electromagnetic field interference radiated by the device.
Reference documents:
standards: CISPR 22
Acceptance criteria:
maximum emission (virtually peak) at 10 m:
b 40 dB (µV/m) from 30 to 230 MHz
b 47 dB (µV/m) from 230 to 1000 MHz.
Standards
Title Reference Status
Vibration, shock, bump and seismic tests on measuring relays and protection IEC 60255-21-1 1988
equipment: vibration tests (sinusoidal).
Vibration, shock, bump and seismic tests on measuring relays and protection IEC 60255-21-2 1988
equipment: shock and bump tests.
Electrical disturbance for measuring relays and protection equipment: IEC 60255-22-1 1988
1 MHz burst disturbance tests.
Electrical disturbance for measuring relays and protection IEC 60255-22-2 1989-10
equipment: electrostatic discharge tests.
Electrical disturbance for measuring relays and protection IEC 60255-22-3 1989-10
2
equipment: radiated electromagnetic field disturbance tests.
Electrical disturbance for measuring relays and protection IEC 60255-22-4 1992
equipment: 1 MHz damped oscillating wave tests.
sensitivity to fast transient interference tests.
Electromagnetic compatibility (EMC) part 4-3: testing and measurement techniques IEC 61000-4-3 1998
immunity to electromagnetic fields radiated at radioelectric frequencies test
Electromagnetic compatibility (EMC) IEC 61000-4-5 1995
part 4: testing and measurement techniques impulse wave
Single input energising quantity measuring relays with dependent specified time IEC 60255-5 1977
Electrical relays: insulation tests IEC 60255-6 1988
Degrees of protection provided by enclosures (IP code) IEC 60529 1989
Programmable logic controllers: equipment characteristics IEC 61131-2 1992
Environmental testing: general and guidance IEC 60068-1 1988
Environmental testing: IEC 60068-2-1 1990-04
test A: cold
Basic environmental testing procedures: IEC 60068-2-14 1986
test N: change of temperature
Basic environmental testing procedures: IEC 60068-2-2 1974
test B: dry heat.
Basic environmental testing procedures: IEC 60068-2-3 1969
test Ca: damp heat, steady state
Basic environmental testing procedures: IEC 60068-2-52 1984
test Kb: salt mist, cyclic (sodium chloride solution)
Limits and methods of measurement of radio interference: IEC CISPR 22 1993
characteristics of information technology equipment
Test methods IEC 60695-2-1 1994
fire behaviour: glow wire test
Operating conditions for measurement and control equipment IEC 60654-4 1987
in industrial processes: effects of corrosion and erosion
Procedure
Set the parameters
(use the setting sheets which are included in the appendix to record the values)
b status
b control logic
b protection.
Perform testing
Different test methods are proposed:
b differential protection testing with simplified parameterization.
2 This parameterization may be used to check the protection characteristic using
two single-phase injection units. The outputs used for tripping and indication are
disabled, which makes it possible to carry out this test while the network is operating
normally.
b restricted earth fault protection test. It is recommanded that this test be performed
for each restricted earth fault used at the time of commissioning.
Equipment
b two 50 Hz (60 Hz) single-phase current generators
b 2 ammeters
b this document
b pocket terminal.
Depending on the settings of the KP6 and KP9 parameters, the protection is in one
E51995
KP6
protection of the following 4 operating modes:
normal KP6 and KP9 testing and tripping b normal
inhibited
b tripping inhibited
KP6 b protection testing and tripping inhibited
b protection testing and tripping active.
KP9 KP9 KP9 KP9
Test mode
The test mode is designed to simply current injection for the differential
protection test.
The test mode is obtained by using the KP6 parameter.
The changeover to test mode automatically parameterizes the differential protection.
b vector groups equal to 0
b Un, Un' and Un" values such that Un.In = Un'.In' = Un".In".
It disables switching of the tripping outputs. Upon the return to normal mode
(KP9 = 0), the initial parameter settings are recovered and the outputs become active
again.
Changeover from normal mode to test mode
KP6 0 → 1 protection test mode outputs inoperative according to chart
(whatever the and tripping inhibited "Test" indicator blinking
value of KP9) message: TEST COUPL.
Test mode:
KP9 0 → 1 → 0 protection test mode and Outputs: all operative
or tripping active "Test" indicator blinking
KP9 1 → 0 message: TEST COUPL.
(KP6 = 1)
Return to normal normal
KP6 1 → 0 no inhibition Outputs: all operative
(KP9 = 0) Indicator off
message: ------------
reset
KP6 1 → 0 inhibition outputs inoperative according to chart
(KP9 = 1) "Test" indicator blinking
message: INHIBIT
reset
MT10624
(setting pocket terminal) KP6 = 1. 2B 3B or 4B
SEPAM 2000
The test indicator is on. 6
3 ECM D ECM D 63
Caution 2 3 or 4
This operation should be carried out first since 5 5
it inhibits protection tripping. 2 2
4 4
1 1
b Wiring in accordance with the diagram opposite.
b Carry out two tests, one with the injection boxes 6 6
b Notation :
In: CT rated current for winding 1
I’n: CT rated current for winding 2
in: 1A or 5A
I1, I2, I3: phase current for winding 1
I’1, I’2, I’3: phase current for winding 2
iinj1, iinj2: injected currents
Id1, Id2, Id3: phase differential currents 1, 2, 3
It1, It2, It3: phase through currents 1, 2, 3.
curve B
curve A no tripping
tests
proposed:
The following chart gives an indication, according to the through current injected and
the Id/It setting, of the differential currrent (xin) value as of which the protection trips.
Id (xin) Id/It (setting of the protection)
It (xin) 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
0.0 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
0.5 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
1.0 0.300 0.300 0.300 0.300 0.350 0.400 0.450 0.500
1.5 0.300 0.300 0.375 0.450 0.525 0.600 0.675 0.750
2.0 0.300 0.400 0.500 0.600 0.700 0.800 0.900 1.000
2.5
3.0
0.375
0.450
0.500
0.600
0.625
0.750
0.750
0.900
0.875
1.050
1.000
1.200
1.125
1.350
1.250
1.500
2
3.5 0.525 0.700 0.875 1.050 1.225 1.400 1.575 1.750
4.0 0.600 0.800 1.000 1.200 1.400 1.600 1.800 2.000
4.5 0.675 0.900 1.125 1.350 1.575 1.800 2.025 2.250
5.0 0.750 1.000 1.250 1.500 1.750 2.000 2.250 2.500
5.5 0.825 1.100 1.375 1.650 1.925 2.200 2.475 2.750
6.0 1.032 1.200 1.500 1.800 2.100 2.400 2.700 3.000
6.5 1.344 1.344 1.625 1.950 2.275 2.600 2.925 3.250
7.0 1.656 1.656 1.750 2.100 2.450 2.800 3.150 3.500
7.5 2.016 2.016 2.016 2.250 2.625 3.000 3.375 3.750
8.0 2.376 2.376 2.376 2.400 2.800 3.200 3.600 4.000
8.5 2.736 2.736 2.736 2.736 2.975 3.400 3.825 4.250
9.0 3.144 3.144 3.144 3.144 3.150 3.600 4.050 4.500
9.5 3.552 3.552 3.552 3.552 3.552 3.800 4.275 4.750
10.0 4.008 4.008 4.008 4.008 4.008 4.008 4.500 5.000
10.5 4.488 4.488 4.488 4.488 4.488 4.488 4.725 5.250
11.0 4.992 4.992 4.992 4.992 4.992 4.992 4.992 5.500
11.5 5.544 5.544 5.544 5.544 5.544 5.544 5.544 5.750
12.0 6.120 6.120 6.120 6.120 6.120 6.120 6.120 6.120
12.5 6.720 6.720 6.720 6.720 6.720 6.720 6.720 6.720
13.0 7.320 7.320 7.320 7.320 7.320 7.320 7.320 7.320
13.5 7.920 7.920 7.920 7.920 7.920 7.920 7.920 7.920
14.0 8.496 8.496 8.496 8.496 8.496 8.496 8.496 8.496
14.5 9.048 9.048 9.048 9.048 9.048 9.048 9.048 9.048
15.0 9.576 9.576 9.576 9.576 9.576 9.576 9.576 9.576
15.5 10.032 10.032 10.032 10.032 10.032 10.032 10.032 10.032
16.0 10.488 10.488 10.488 10.488 10.488 10.488 10.488 10.488
16.5 10.896 10.896 10.896 10.896 10.896 10.896 10.896 10.896
17.0 11.280 11.280 11.280 11.280 11.280 11.280 11.280 11.280
17.5 11.640 11.640 11.640 11.640 11.640 11.640 11.640 11.640
18.0 12.000 12.000 12.000 12.000 12.000 12.000 12.000 12.000
18.5 12.336 12.336 12.336 12.336 12.336 12.336 12.336 12.336
19.0 12.648 12.648 12.648 12.648 12.648 12.648 12.648 12.648
19.5 12.960 12.960 12.960 12.960 12.960 12.960 12.960 12.960
20.0 13.248 13.248 13.248 13.248 13.248 13.248 13.248 13.248
20.5 13.560 13.560 13.560 13.560 13.560 13.560 13.560 13.560
21.0 13.848 13.848 13.848 13.848 13.848 13.848 13.848 13.848
21.5 14.136 14.136 14.136 14.136 14.136 14.136 14.136 14.136
22.0 14.424 14.424 14.424 14.424 14.424 14.424 14.424 14.424
22.5 14.712 14.712 14.712 14.712 14.712 14.712 14.712 14.712
23.0 14.976 14.976 14.976 14.976 14.976 14.976 14.976 14.976
23.5 15.264 15.264 15.264 15.264 15.264 15.264 15.264 15.264
24.0 15.552 15.552 15.552 15.552 15.552 15.552 15.552 15.552
in: CT secondary rated current; in = 1 A or 5 A.
Even couplings
0 4 8 6 10 2
E51989
SEPAM 2000
6 6 6 6 6 6
3 ECM D ECM D 63 3 3 3 3 3
2 3 or 4 5 5 5 5 5
5 5
2 2 2 2 2 2 2
4 4 4 4 4 4 4
1 1 1 1 1 1 1
6 6
5 5
A 4 4
3 3
2 2
1 1
I
Odd couplings
1 5 9 7 11 3
E51988
SEPAM 2000
6
3 ECM D ECM D 63 6
3
6
3
6
3
6
3
6
3
2 3 or 4
5 5 5 5 5 5 5
2 2 2 2 2 2 2
4 4 4 4 4 4 4
1
6
1
6
1 1 1 1 1
2
5 5
A 4 4
3 3
2 2
1 1
I
Id1 = 1 - k
3
. I .In/in
[ ]
It1 = max 1, k
3
. I .In/in
Id2 = 0 It2 = 0
Id3 = 1 - k
3
. I .In/in
[ ]
It3 = max 1, k
3
. I .In/in
b Parameterization of the protection for Test coupling (using the pocket terminal,
KP6 = 1).
The test indicator lights up.
Please note
This operation should be carried out first since it inhibits tripping of the protection.
Inject a current in the CSH 30 sensor associated with the neutral point current
measurement CT to check the value of the setting.
SEPAM 2000
E61718
6
3 ECM D ECM D 63 A
2 3
5 5
2 2
4 4
1 1
6 6
5 5
4 4
3 3
2 2 CSH 30
1 1
Inject a current into the CSH 30 sensor associated with the neutral point current CT
and into one of the phase current inputs to simulate a fault outside the zone.
Check the stability for a current of 2 In.
E61719
SEPAM 2000
6
3 ECM D ECM D 63 A
2 3
5 5
2 2
4 4
1 1
6 6
5 5
4 4
3 3
2 2 CSH 30
1 1
DE52925
2
To facilitate the test and calculations, set Ino to the same value as In.
Inject a current through the CSH30 interposing ring CT and a phase current in the
opposite direction.
The restraint current is equal to I1, the differential current is equal to I1 + I neutral.
When there is no I neutral, the slope is equal to 100%. Gradually inject Io until tripping
occurs. Record I neutral and I1 and calculate 100 x (I1 + I neutral)/I1 and compare to
105%.
DE52926
2 index" = ...............................
In = ...............................
k = ......................= .......................... test between windings 1 and 3
Un = ......................... Current injected: I = ............................
I’n = ............................... Un’ = .........................
I"n = ............................... Un" = .........................
Procedure:
b sed iinj2 to the value indicated in the chart
bgradualy increase iinj1 until the protection trips
b read the value of iinj1
b compare it to the theoretical value.
Test n° iinj2 Tripping current iinj1 iinj1 / iinj2 Tripping theorical value
a 0.5 in ....................................... A iinj1 = 0.3 in
in = 1 ou 5 A
Id/It : seuil à pourcentage, exprimé en %
by: ....................................................................................................
..........................................................................................................
Comments: ............................................................................................................................................................................
.................................................................................................................................................................................................
.................................................................................................................................................................................................
.................................................................................................................................................................................................
.................................................................................................................................................................................................
Ordering informations
Sepam type
D32 ........................................................................................................
Option
Communication ...................................................... without ..............................
................................................................................ Jbus/Modbus ....................
quantity
Accessories
Pocket terminal....................................................... TSM2001 .............
Jbus/Modbus communication
b 9-pin sub-D connector ......................................... CCA600-2 ...........
b 9-pin sub-D connector box .................................. CCA619 ...............
b Jbus/Modbus network connection box ................ CCA609 ...............
b Jbus/Modbus network connection box
(Sepam 2000 and Sepam series 20/40/80 compatible)CCA629 ...............
b RS 485 cable (length: 3 m)
with two 9-pin sub-D connectors ............................ CCA602 ...............
b interfaces box RS 485/RS 232 ........................... ACE909-2 ............
software or accessories.
SEPED306028EN 01-2007