You are on page 1of 1

GENERATOR ROOM VENTILATION CALCULATION

Diesel Generator capacity = 750 KVA

H
Ventilating air (cu.m/min.) = + Engine Combustion Air
D x SH x Dt

Where :- input
H = Total Heat Radiation in (KW) (for engine + generator) calculated
H = 125.5 KW (from material submittal)
V = Ventilating air (cu.m/min.)
D = Density of air (kg/m3)
= 1.07 At 54 deg. C
SH = Specific heat of air ( kw.min/Kg.C)
= 0.017
dT= Temp. Rise inside engine room ( deg.C)
= 10 deg.C
ECA = Engine Combustion Air (Exhaust gas flow )
= 120 cu.m/min (from material submittal)
7,182 cu.m/hr.

THEN :-

125.5
Ventilating air (V) = + 120
1.07 x 0.017 x 10

V = 810 cu.m/min

V = 28,564 cu.ft/min.