ELECTRONIC COUNTER
INSTALLATION MANUAL
CODE : MA/260/00/EN/22
REVISION : 12/2014
CAUTIONS
This equipment, if not installed and used in accordance with this instruction manual, may cause interference to radio communications and also can be noised
from them.
VEGA II must be powered by fail-safe backup equipment to prevent accidental runaway delivery of products due to power supply variation and disturbances.
Use an external power isolator to switch on/off the electronic power supply.
Use separated different power supply lines for electronics and for external devices (AC solenoids, etc.)
STATIC PRECAUTIONS
Some parts of the instruments (such as circuit boards) may be damaged by static electricity. Therefore, when carrying out any work that involves the risk of
static damage to the instrument you must wear an earthed wrist strap at all times to protect the instrument against static shock.
SAFETY INFORMATION
Electricity is dangerous and you risk injury or death if you do not disconnect the power supplies before to open the housing of the instrument.
2 WARRANTY
Instruments are guaranteed for twelve months for the date of delivery.
Warranty cover only defective parts and faulty workmanship and doesn't cover defects due to wearing, dirt, modification and alteration of the instrument not
authorized by Isoil Impianti S.p.A..
Warranty is given free of charge ex our works.
Warranty of instruments and accessories not manufactured by Isoil Impianti S.p.A., will be covered by warranty of the sub supplier.
Warranty is valid only if original spares are used and is invalidated in case of improper use or not following the technical specification of the instrument.
Only Isoil Impianti S.p.A. has the right to decide if the warranty can be applied.
If the purchasing order calls for different warranty conditions, above stated conditions are superseded.
Above warning are reported on the plate; the installing position of the unit must allow an easy reading.
WARNING The user is responsible for a good reading in the time: clean periodically without using solvents; don’t over paint
VEGA II must be installed & maintained according to the applicable standards regarding electrical installations in hazardous area classified Zone 1 or Zone 2
(example: EN 60079-14, EN 60079-17, etc…).
Before the installation READ CAREFULLY the INSTALLATION MANUAL.
The user cannot perform any UNAUTHORIZED MODIFICATION of the apparatus.
WARNING:
VEGA II should be shaded from direct sunlight
For temperatures lower then –5°C the internal heating device must be always maintained switched on
Cables have to be selected according to par. 9.3.3 and 9.3.4 of the EN60079-14.
Nevertheless different practice can be used, as conduit systems according to EN60079-14.
In case of use of conduit system the sealing joints must be mounted at a maximum
distance of 50 mm from the cable entry holes of the VEGA II according to EN 60079-14.
Take care to choose accessories threaded NPT.
WARNING
VEGA II is delivered with cable entries closed by plastic screw-cap. The entries not
utilized must be closed with metallic screw-plugs.
fig.4
------------------------------------------------
NOTE: BACK SIDE VIEW INTERNAL RACK
Use cable entry n°2 (see fig.3)
When the minimum operating temperature is between –25 to -5°C the power supply of the INTERNAL HEATING
DEVICE (F1-1 and F1-2) must be provided an hour before the power supply of the ELECTRONIC (SW1=POS1)
When the minimum operating temperature is greater of -5°C the power supply of the HEATING DEVICE can be the
same of the ELECTRONIC (SW1=POS2). In this case the connector F1-1 and F1-2 are not used.
NOTE:
When the minimum operating temperature is between –25 to -5°C the power supply of the INTERNAL HEATING DEVICE (F3-1)
must be provided an hour before the power supply of the ELECTRONIC (F3-2)
When the minimum operating temperature is greater of -5°C the power supply of the INTERNAL HEATING DEVICE can be the
same of the ELECTRONIC.
NOTE: These connectors are suitable for wires of AWG 2814 – Use cable entries n° 1 and 3 (see fig.5 and 6)
NOTE: These connectors are suitable for wires of AWG 2814 – Use cable entries n° 1 and 3 (see fig.5 and 6)
NOTE:
The internal voltage is 15Vdc 0,5 A max
Use cable entries n° 2 and 4 (see fig.5 and 6)
These connectors are suitable for wires of AWG 2814
The DEFAULT functions associate to each output are described on PARAMETERS MANUAL (par. 7 – AUTOMATION) S7 OPEN= EXTERNAL FEEDING
S7 CLOSED =INTERNAL FEEDING
NOTE:
Use cable entries n° 2 and 4 (see fig.5)
These connectors are suitable for wires of AWG 2812
Do not use the same power supply of electronic. Use a separate power supply.
The DEFAULT functions associate to each output are described on PARAMETERS MANUAL (par. 7 – AUTOMATION)
NOTE:
Use cable entries n° 2 and 4 (see fig.6)
These connectors are suitable for wires of AWG 2812
For inductive loads install a diode (see figure)
The DEFAULT functions associate to each output are described on PROGRAMM PARAMETERS MANUAL (par. 7 – AUTOMATION)
NOTE:
Use cable entries n° 2 and 4 (see fig.5 and 6)
These connectors are suitable for wires of AWG 2814
To use internal voltage (15 Vdc) close the jumper S6. WARNING: in this case the external power supply can’t be present. S6 OPEN= external voltage
The DEFAULT functions associate to each output are described on PROGRAMM PARAMETERS MANUAL (par. 7 – AUTOMATION) S6 CLOSED =internal voltage
6.7.1 FOR VEGA II POWERED BY VAC VOLTAGE (SES-1 DIGITAL I/O BOARD)
RIGHT SIDE VIEW
DIGITAL I/O BOARD
(see pos.D fig.5)
NOTE:
Use cable entries n° 2 and 4 (see fig.5)
The connector is suitable for wires of AWG 2812
The above drawing is relative to the board type SES-1
For inductive loads install a RC filter (see figure)
Do not use the same power supply of electronic. Use a separated power supply.
The DEFAULT functions associate to each output are described on PROGRAM PARAMETERS MANUAL (par. 7 – AUTOMATION)
NOTE:
Use cable entries n° 2 and 4 (see fig.6)
The connector is suitable for wires of AWG 2812
The above drawing is relative to the board type SES-2.
For inductive loads install a DIODE (see figure)
The DEFAULT functions associate to each output are described on PROGRAM PARAMETERS MANUAL (par. 7 – AUTOMATION)
NOTE: J9 POSITION
WARNING:
The cable must still be four wires. The fourth wire must be
connected together on the third terminal of Pt100.
NOTE:
Use temperature probe PT100 class A (alpha 0.00385) IEC751, DIN 43760
Use shielded cable type BELDEN 9842 or equivalent
Use cable entries n° 2 and 3 (see fig.5)
These connectors are suitable for wires of AWG 2814
WARNING:
THE CONNECTION CABLE MUST BE ALWAYS 4 WIRES.
NOTE:
Use temperature probe Pt100 class A (alpha 0.00385) IEC751, DIN 43760
Use shielded cable type BELDEN 9842 or equivalent
Use cable entries n° 2 and 3 (see fig.5)
These connectors are suitable for wires of AWG 2814
NOTE:
Use cable entry n° 6 (see fig.5).
These connectors are suitable for wires of AWG 2814.
Use shielded cable.
The DEFAULT functions associate to each input or output are shown on PROGRAM PARAMETERS MANUAL par. 7 – AUTOMATION
NOTE:
Use cable entry n° 5 (see fig.5)
These connectors are suitable for wires of AWG 2814.
LINE 1 and LINE 2 can be RS232 or RS485 (see position of S3 and S4)
LINE 3 can be used for RS485/422 4 wires and 2 wires
Use the cables suggested on the next page or equivalent
The protocol associate to each line can be set on PROGRAM PARAMETERS MANUAL par. 6 – SERIAL LINES
NOTE:
Use cable entry n° 5 (see fig.5).
NOTES:
The cables can be different types but with the same characteristics
Suitable anti over-voltages protection devices must be considered against atmospheric (Suggested: ISOIL PL360/3)
The communication lines must be segregated from power leading cables. Ducts must be separated
For W&M reasons is preferable that communication lines for SPD and for other systems (PC, PLC, DCS…) are separated. Using the same multi-cable can occur
problems in case a sealing of the path is required.
Limiting the number of the devices connected in multi-point; avoid for example to connect together all the VEGAII for the same product. Consider to use more SPD
and printers.
Choosing cables suitable as electrical characteristics and mechanical strength.
NOTE: MULTIPRO 6 = Surge protection device for serial communication lines type RS422/RS485
NOTE:
- ST500-A = Printer with 80 columns, 24 needles and RS232 communication line
- PL360/1 = Surge protection device for serial communication lines type RS232
NOTE:
ST500-B = Printer with 80 columns, 24 needles and RS422/RS485 (4 wires) communication line
PL360/2 = Surge protection device for serial communication lines type RS422/RS485
NOTE:
ST500-M = Printer with 80 columns, 24 needles and RS422/RS485 (4 wires) communication line. It gives the possibility to use the same printer to print the data
coming from many VEGA T (max n.16)
MULTIPRO 6 = Surge protection device for serial communication lines type RS422/RS485
NOTE:
ST501 = Printer with 80 columns, 24 needles and parallel CENTRONICS port
SPD-02 = SHARED PRINTING DEVICE. It gives the possibility to use the same printer to print the data coming from many VEGA II
MULTIPRO 6 = Surge protection device for serial communication lines type RS422/RS485
VEGA II X 2 X X - X N X X
TOTALIZER + PRESETTER 3
TOTALIZER + COMPENSATOR + PRESETTER 4
ONE METER 9
TWO METERS 6
BLENDING 4
Pulse emitter “Encoder EM6422”, developed by ISOIL IMPIANTI, converts the rotary
motion of a Positive Displacement Meter into electric pulses representing the
delivered volume. It allows the pdmeter to interface with an electronic control device
(electronic register, flow computer).
The pulse emitter can be factory installed directly on to the front cover af any new
Isoil pdmeter. By the use of suitable flanges it can be retrofitted onto any existing
ISOIL pdmeter, in place of the mechanical register or other pulse emitters.
Installation on most other manufacturer’s pdmeter is possible as well by means of
special adaptors.
Unlike most similar devices, which use optical sensors, the EM6422 utilizes a state-
of–the-art method, that detects the rotary motion of the pdmeter’s shaft through a
thin separating wall.
The electronic circuit is placed in a sealed housing completely insulated from the
process fluid in the pdmeter. The housing is closed by a cover with o-ring seal and
there is a threaded female inlet for cable glands or counduit entrance.
The number of pulses for every litre changes depending on the type of ISOIL
PDMETER on which is installed the EM6422.
In the following tables are included the nominal number of pulses for litre emitted by
fig.31 – EM6422 EM6422 when is mounted directly on the relative PDMETER.
The “number of pulses” must be programmed inside the parameter K-FACTOR of the
VEGAII.
The wiring REED is used only when the automatic switch on is enabled. The wiring REED is used only when the automatic switch on is enabled.
The wiring REED is used only when the automatic switch on is enabled. The wiring REED is used only when the automatic switch on is enabled.
Standard address 21 hex (see SW2 of the EM6422) Standard address 22 hex (see SW2 of the EM6422)
WARNING
Brembilla
ISOIL FONTANA
N. DESCRIPTION N. DESCRIPTION
1 DISPLAY BOARD 13 VDC FILTER BOARD (only for VEGAII supplied in VDC)
2 KEYBOARD 14 BUS BOARD
3 SERIAL LINE N.4 RS232 15 HEATING DEVICE
4 Free position for future expansions 16 KIT WITH ALL PUSH BUTTONS
5 MEMORY PROGRAMM BOARD 17 KIT WITH ALL SCREWS OF CLOSURE
6 CPU BOARD 18 KIT WITH ALL SCREWS FOR FIXING
7 ANALOG I/O BOARD 19 KIT WITH DEVICES FOR FIXING OF RACK
8 DIGITAL I/O BOARD (optional) 20 INTERNAL ENCODER FRICTION
9 DC/DC POWER SUPPLY BOARD 21 INTERNAL ENCODER
10 RACK WITHOUT BOARDS 22 WHEIGHT&MEASURE SWITCH
11 AC/DC POWER SUPPLY BOARD (only for VEGAII supplied in Vac) 23 O-RING SEAL
12 BATTERIE
13 VAC CONNECTION BOARD ((only for VEGAII supplied in Vac) 30 RACK WITH ALL ITEMS (1÷15)
ATTENTION
To ask for SPARE PARTS please give the SERIAL NUMBER of the device. The SERIAL NUMBER is written on the ATEX plate fixed on the external housing.