Before buying an inverter for, It is very important to understand what is the right
inverter for our requirement for that we do understand the basics criteria of Inverter.
In order to make a good estimate of your power needs, you’ll need to take a look at all
of the devices you plan on plugging into your new inverter.
If we only need to use one device at a time, then that’s the only one you’ll need to look
at. However, you’ll need to add together the numbers from multiple devices (like an
LCD screen and a video game system) if you plan on using them at the same time.
One of the most important factors that we must know before buying an inverter is
Power requirement.
Power requirement means all electrical appliances (like fan, tube lights,
television,Pumps, CFL etc.), we want to run at the time of power failure. The power
requirement is simply addition of the power consumed by various electrical
equipments.
The thing we must understand that Inverter is not a Generator. Inverter has its own
limitations. If power requirement is more than our estimation, then an inverter alone
cannot create demands effectively.
High power inverter can run our refrigerator and air conditioners, but ba ery will not
last more than few hours. Hence it be er to estimate Inverter Load Carefully
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 1/8
12/12/2019 Selection of Various Types of Inverter-(Part-3) | Electrical Notes & Articles
The selection of correct size Inverter is very important, If we need to power small
appliances like energy efficient light bulbs, we do not need to buy a 2000W power
inverter because it will consume more power even in standby mode and work very
inefficiently with small appliances. On the other hand, if we connect a coffee machine
to a 150W inverter we will quickly blow a fuse, Therefore power estimation is
important thing.
The size of Inverter depends on the wa s (or amps) of what we want to run. It is
recommend that we choose at least 10% to 20% more than our requirement.
Suppose you want 1No Fans, 1No Tube lights, 1No CFL and 1No television to operate
at the time of power failure. Therefore the total power requirement to be (1×90 + 1×50 +
1×25 + 1×120) = 285 wa s. Here Total Load is 285 wa s.
Starting and running power requirement of all electric appliances are different.
Starting power of Electrical Equipment is several times greater than their normal
working power.
An 18 Wa s CFL takes around 25 Wa s power to start and after few seconds it works
on 18 Wa s. Some appliances like Refrigerator, Washing Machine etc take almost
double power to start as compared to the normal running power.
For example Gridding Machine have normal working power 1000W, their starting
power is higher than 4000W, so inverters with continuous power 2000W are not
suitable because their peak power is limited by 4000W.
For selecting right Inverter, Always take into account starting power requirements of
your equipment, especially devices with electric motors, Electronics Choke, Capacity,
inductive
The Size of the inverter should be chosen based on the power consumption of your
load.
Resistive loads: All resistive loads like toaster, coffee maker, electric range, iron,
Incandescent lamps, flood lighting. Laser Printers use Nichrome resistance wire in their
heating
The Starting Power or Surge Power rating should be 6 times the Wa rating
Inductive Loads: All Inductive Load like induction motor, reciprocating pumps and
compressors, refrigeration, air-conditioning, Oxygen Concentrators have more starting
current.
The Starting current (LRA) should be 5 times the full load current (FLA).
Capacitive Loads: Switched Mode Power Supplies (SMPS), electronic equipment like
ba ery chargers, computers, audio and video devices, radio etc.
The Starting Power or Surge Power rating should be 3 times the Wa rating
Microwaves :
The Initial power consummation by the microwave will be 2 times the cooking
power.
A Water Supply Pump:
The starting surge can be 3 times the normal running rating of the pump
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 2/8
12/12/2019 Selection of Various Types of Inverter-(Part-3) | Electrical Notes & Articles
The inverter should, therefore, be sized adequately to withstand the high inrush
current.
Starting Factor
It stands for the Volt ampere rating. It is the voltage and current supplied by the
inverter to the equipments.
If an inverter operates with 100% efficiency, then the power requirement of the
electrical items and power supplied by inverter is same. But 100% or ideal conditions
does not exist in real. Most inverters have the efficiency range from 60 % to 80%. This
efficiency is also called power factor of an inverter and is simply the ratio of power
required by the appliances to power supplied by an inverter. Power factor of most
inverters ranges from 0.6 to 0.8.
Rating of inverter (VA) =Power consumed by equipments (wa s) / Power factor
(efficiency).
Power of inverter (VA) = 535/0.7 = 765 VA
In the market 800 VA inverters are available. So Size of an inverter with 800 VA.
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 3/8
12/12/2019 Selection of Various Types of Inverter-(Part-3) | Electrical Notes & Articles
Capacity of a ba ery is expressed in terms of Ampere Hour (Ah). It is decide the back
up hours of Inverter.
It indicates the rate of current a ba ery can supply for a given duration. If the capacity
of a ba ery is 100 Ah, that ba ery can supply 100 Ampere current for 1 Hour or 1
Ampere Current for 100 Hrs
Ba ery capacity = Power requirement (wa s) x Back up hours (hrs) / Ba ery Voltage
(volts) x Ba ery Efficiency x No of Ba ery
Example: If Inverter Load is 390 Wa , We need 3 hours back up and Ba ery Voltage is
12V, Ba ery Efficiency is 90%
Ba ery Capacity = (390 x3) / 12×0.9×1 = 109 Ah
Therefore a ba ery capacity of 120 Ah.
In reality ba ery performance degrades with usage, so you are recommended to buy 5-
10% higher capacity ba ery.
Therefore a ba ery with a capacity of 150 Ah is suitable for our requirement.
If we use series – parallel ba ery combination for backup is
Backup capacity(hours) = N series X Volts X Ba ery Ah X N parallel / (UPS capacity
in VA)
Where, N series = no. of ba eries in series and N parallel = no. of parallel ba ery banks
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 4/8
12/12/2019 Selection of Various Types of Inverter-(Part-3) | Electrical Notes & Articles
We can choose Ba ery Voltage of 12V, 24Vor 48V for inverter. The selection is very
important for Voltage drop and Cable size of Inverter.
To control load current within limit, as load increase, we should select higher size of
Ba ery Voltage.
Let’s take example.
The ba ery capacity is limited to the size of the charger. Usually, the ba ery capacity
should be no more than 12x the maximum charge current i.e. a 5A charger can only
accommodate 60AH of ba eries (5 x 12 =60).
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 5/8
12/12/2019 Selection of Various Types of Inverter-(Part-3) | Electrical Notes & Articles
If discharges are expected to be less frequent than once in every 10 days, We may use
formula of 20x the maximum charge current.
Lead acid ba eries have few Amps hour if the discharge rate is fast.
Generally, the lead acid ba ery discharge rate is slow. It is 20 hours.
At high discharge rate, the capacity of the ba ery drops steeply. Suppose the ba ery is
10 Ah and its discharge rate is 1C. One hour discharge of the ba ery at the rate of 1C
(10 Amps in 1 hour), the capacity reduces to 5 Ah in one hour.
Suppose we want to run a load at 20 Amps for 1hour. Then the capacity of the ba ery is
20A x 1 Hour = 20Ah.
Keep discharge rate to maximum 80%. Then the ba ery capacity should be 20Ah / 0.8 =
25 Ah
So a 25 Ah ba ery can give 20 Amps current for 1 hour to run the load.
But it is be er to drain the ba ery to 50% only then, 25 Ah / 0.5 = 50 Ah.
Hence it is be er to use a 50Ah ba ery to run the load at 20 Amps per Hour to keep
50% charge in the ba ery.
About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is
member of Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He
has more than 16 years experience in Transmission -Distribution-Electrical Energy theft
detection-Electrical Maintenance-Electrical Projects (Planning-Designing-Technical
Review-coordination -Execution). He is Presently associate with one of the leading
business group as a Deputy Manager at Ahmedabad,India. He has published numbers of
Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting India”,”Smart
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 6/8
12/12/2019 Selection of Various Types of Inverter-(Part-3) | Electrical Notes & Articles
Olakunle Roleola
> Jignesh.Parmar posted: “How to select Right Inverter Before buying an > inverter for,
It is very important to understand what is the right inverter > for our requirement for
that we do understand the basics criteria of > Inverter. In order to make a good estimate
of your power need” >
Reply
Mahmoud Awad says:
January 2, 2019 at 8:27 am
Dear Sir,
how to select ba ery charger 110 VDC in parallel feeding loads & ba ery banks for
power plant
Thanks
Reply
panayioti says:
January 7, 2019 at 5:30 pm
Thank you very much sir.
I think its nice to talk, maybe useful, to see’ power factor issue.
I don’t remember if converters can do this.
Reply
sadashiv salaskar says:
February 15, 2019 at 1:22 pm
How to calculate ba ery sizing is also needed
Sadashiv Salaskar
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 7/8
12/12/2019 Selection of Various Types of Inverter-(Part-3) | Electrical Notes & Articles
________________________________
Reply
This site uses Akismet to reduce spam. Learn how your comment data is processed.
https://electricalnotes.wordpress.com/2019/01/01/selection-of-various-types-of-inverter-part-3/ 8/8