HANLA IMS CO., LTD.

MT-DL-1100
115, Hwajeonsandan 1(il)-ro, Gangseo-gu, Busan, Korea Rev.0
-Tel: 82-51-601-7000 2016-01-12
-Fax: 82-51-831-1850 Page 1/6
-Email: hanla@hanlaims.com

DL-1100 Manual

TECHNICAL MANUAL

 Analog input : 4~20mA

 Two wire RS-485 communication (Modbus protocol)


MT-DL-1100
Rev.0
2016-01-12
Page 2/6

TABLE OF CONTENTS
1. Introduction ................................................................................................................................................. 3

2. Specification ............................................................................................................................................... 3

3. Outline & Pin assignment........................................................................................................................... 3

3.1 Outline ................................................................................................................................................... 3

3.2 Pin assignment ...................................................................................................................................... 4

4. Connection .................................................................................................................................................. 5

4.1 Analog input signal connection ............................................................................................................ 5

4.2 Power & communication connection ................................................................................................... 5

5. Communication ........................................................................................................................................... 6

5.1 Read long integer data ......................................................................................................................... 6

5.2 Read float data ...................................................................................................................................... 6


MT-DL-1100
Rev.0
2016-01-12
Page 3/6

1. Introduction
 DL-1100 is an analog input (only 4~20mA) module with 8 input channels.
 This module is an extremely effective solution for industrial measuring and monitoring
applications.
 To satisfy Modbus users, these DL-1100 modules support Modbus RTU protocol.
 DL-1100 own a series of LED display on the face.(POWER,COMMUNICATION)
 Easy programming by software.
 Easy installation and wiring.

2. Specification
 Power supply: 24VDC
 Power consumption: 6VA
 Input: 8 X 4~20mA input
 Accuracy: +/- 0.2% Full Scale
 Input resistance: 50Ω
 Communication: 2 X RS-485 Modbus RTU
 Operating Temperature: 0~70℃
 Storage Temperature: -20~70℃
 Installation: DIN Rail mounting (35mm)
 Material: AL, CHROMATE, 105x27x74mm.
 IP20.

3. Outline & Pin assignment


3.1 Outline
MT-DL-1100
Rev.0
2016-01-12
Page 4/6

3.2 Pin assignment

Pin Name Description Pin Name Description

1 1+ 1CH Power output 13 5+ 5CH Power output

2 1- 1CH Sensor signal input 14 5- 5CH Sensor signal input

3 2+ 2CH Power output 15 6+ 6CH Power output

4 2- 2CH Sensor signal input 16 6- 6CH Sensor signal input

5 3+ 3CH Power output 17 7+ 7CH Power output

6 3- 3CH Sensor signal input 18 7- 7CH Sensor signal input

7 4+ 4CH Power output 19 8+ 8CH Power output

8 4- 4CH Sensor signal input 20 8- 8CH Sensor signal input

9 A RS-485 Modbus signal A 21 A AUX. RS-485 Modbus signal A

10 B RS-485 Modbus signal B 22 B AUX. RS-485 Modbus signal B

11 24+ Power input 24+V 23 SET+ For setting device

12 24- Power input 24-V 24 SET- For setting device


MT-DL-1100
Rev.0
2016-01-12
Page 5/6

4. Connection
4.1. Analog input signal connection

4.2 Power & communication connection


MT-DL-1100
Rev.0
2016-01-12
Page 6/6

5. Communication
Master should have next communication setting:
 Baud Rate: 1200, 2400, 4800, 9600, 38400, 57600, 115200.
 Stop bit: 1 Data bit: 8 Parity: None.
 Default setting: Baud Rate: 9600bps, Slave address: 0x01.

5.1 Read long integer data


Slave Function Modbus Data type
Description remark
Address Code Address (4 byte)
0x01 0x03 0x1001 Engineer unit Long integer 1CH
0x01 0x03 0x1003 Engineer unit Long integer 2CH
0x01 0x03 0x1005 Engineer unit Long integer 3CH
0x01 0x03 0x1007 Engineer unit Long integer 4CH
0x01 0x03 0x1009 Engineer unit Long integer 5CH
0x01 0x03 0x100B Engineer unit Long integer 6CH
0x01 0x03 0x100D Engineer unit Long integer 7CH
0x01 0x03 0x100F Engineer unit Long integer 8CH

5.2 Read float data


Slave Function Modbus Data type
Description remark
Address Code Address (4 byte)
0x01 0x03 0x2000 Engineer unit Float 1CH
0x01 0x03 0x2002 Engineer unit Float 2CH
0x01 0x03 0x2004 Engineer unit Float 3CH
0x01 0x03 0x2006 Engineer unit Float 4CH
0x01 0x03 0x2008 Engineer unit Float 5CH
0x01 0x03 0x200A Engineer unit Float 6CH
0x01 0x03 0x200C Engineer unit Float 7CH
0x01 0x03 0x200E Engineer unit Float 8CH