Introduction
With the variety of process control systems available, it is often necessary to convert an input signal into
a format that the control system will accept. Signal conditioners take signals from an assortment of field
instruments such as thermocouples and RTDs, and convert those signals into any of several standard
instrument signals (1-5 V, 4-20 mA, etc.) while providing isolations.
Signal conditioners are also beneficial to the accurate transfer of these signals and the elimination of
ground loops.
Pepperl+Fuchs signal conditioners utilize the latest technology, offering unparalleled protection against
ground loops while maintaining optimum signal accuracy and complete isolation. There are three basic
types of KF signal conditioners:
Analog Isolators: These units require a separate power supply and provide signal
conditioning and 3-way isolation to various input signals.
Limit Alarms: This class of signal conditioners provides two Form C relay outputs with
adjustable high and low switchpoints and selectable control safe and normal operation.
They also require a separate power supply and provide 3-way isolation.
The latter two categories are fully field-configurable and provide 1,800 VDC isolation separating input,
output and power supply. Input and output ranges, modes of operation, switchpoints, etc., can be
programmed in the field via DIP switches on the side of the housing. Some models also offer a PC
interface. Input, zero, and span are adjustable by potentiometer to 50% for all input ranges. The wide-
ranging capabilities and field-configurable settings allow for numerous options in a diverse range of
applications.
All P+F analog isolators and limit alarms also contain the ASIC chip for increased reliability. ASIC (Appli-
cation Specific Integrated Circuitry) substantially reduces failures by virtually eliminating discrete com-
ponents and their solder joints where most faults occur. Printed circuit board connections are reduced
by 70%.
Power Dissipation
@ 25 mA (Vin < 26.1 V) < 150 mW
@ 25 mA (Vin > 26.1 V) < 400 mW
Output Terminals 1, 2
Output voltage:
10 V < Vin < 26.1 V 0.9 x Vin - (0.23 x current in mA) - 0.7
Vin > 26.1 V 23 V - (0.23 x current in mA)
Output current 4-20 mA
Model Number Short circuit current ≤ 65 mA @ Vin>26.1 V
KFD0-CS-1.50 Transfer current ≤ 40 mA
Connection Diagram
KFD0-CS-1.50
(+) 11 1 (+)
Input Output
(– ) 12 2 (–)
Power Dissipation
@ 25 mA (Vin < 26.1 V) < 150 mW
@ 25 mA (Vin > 26.1 V) < 400 mW
Signal Conditioners
voltage limitation and the internal voltage
drop, the maximum output voltage under
load is 23 VDC. The maximum internal
resistance is 230 ohms. At input voltages
greater than 26.1 V, the internal voltage
drop is lower than with input voltages
Note: For information about programming, below 26.1 V.
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD0-CS-2.50
(+) 11 1 (+)
Input 1 Output 1
(– ) 12 2 (– )
(+) 9 4 (+)
Output 2
Input 2 (– ) 10 5 (– )
(+) 8
Transfer Characteristics
Voltage surge 6.5 ppm / V
Model Number Calibrated accuracy ±0.1% of final value @ 20ºC
KFD0-CC-1 Linearity fault ≤ 0.04% of final value
Temperature drift 0.050% of range / ºC
■ Field selectable voltage or 0.060% of span / ºC
current input Response time ≤ 250 ms
Galvanic Isolation safe isolated per DIN VDE 01061
■ Loop-powered
design isolation voltage 253 VEff
■ Isolation of input/output
The KFD0-CC-1 loop powered, 2-wire Mechanical
isolator that converts 2-wire voltage/ Housing:
current signals to a 4-20 mA signal. Material Makrolon
Style KF housing (see page 387)
The KFD0-CC-1 provides galvanic
Mounting 35mm DIN rail or surface mount
isolation for the loop. The required input
Dimensions (mm) 115 x 20 x 118
range is set by a switch on the side of the
unit. Zero and span adjustment are Weight 100 g (3.5 oz.)
achieved by potentiometers on the top of Protection (IEC) IP20
the isolator.
OperatingTemperature -20ºC to +60ºC (-4ºF to +140ºF)
Signal Conditioners
Connection Diagram
KFD0-CC-1
(+) 1 9 (+)
Input Output
(– ) 2 8 (– )
Transfer Characteristics
Sensing range - 50 mV to +50 mV
Zero point 1% of final value
Span ± 3.5% of final value
Temperature drift Zero point 0.01% of the span / ºC or Model Number
±1 µV / ºC (whichever is larger) KFD0-VC-1.50m
Span 0.005% of span / ºC
Response time ≤ 250 ms ■ -50 mV to + 50 mV voltage in
Galvanic isolation safe isolated per DIN VDE 01061 current output isolator
design isolation voltage 253 VEff ■ Loop powered
■ Lead breakage monitoring
Mechanical
Housing: The KFD0-VC-1.50m receives a -50 to
Material Makrolon +50 mV signal input and produces a 4-20
Style KF housing (see page 387) mA output. This loop powered module also
Mounting 35mm DIN rail or surface mount provides galvanic isolation.
Dimensions (mm) 115 x 20 x 118 The sensing range of the bipolar input unit
Weight 100 g (3.5 oz.) isolates and conditions a 4-20 mA output.
Protection (IEC) IP20 Fine adjustment for zero and span are
performed with the potentiometer on top
Ambient Temperature -20ºC to +60ºC (-4ºF to +149ºF) of the unit.
Optional lead monitoring is available by the
Signal Conditioners
field configurable DIP switches. Enabling
this feature produces an output ≤ 3 mA
when the input wire is broken, while
disabling produces an output ≥ 22 mA.
Connection Diagram
KFD0-VC-1.50m
(+) 1 9 (+)
Input Output
(– ) 3 8 (– )
Transfer Characteristics
Operating voltage 6.5 ppm / V
Calibrated accuracy 0.1% of final value
Linearity faults ≤ 0.04% of final value
Sensing range -10 V to +10 V
Span ± 1.5% of final value
Model Number Zero point ±1% of final value
Temperature drift Span 0.005% of span / ºC
KFD0-VC-1.10
Zero point 0.060% of span / ºC
Response time 250 ms
■ -10 to +10 voltage input/4-20
Galvanic isolation Function isolation per EN 50178
mA output
design isolation voltage 253 Veff
■ Loop powered
Mechanical
■ Isolation of input/output Housing
The KFD0-VC-1.10 receives a -10 to +10 Material Makrolon
voltage input and produces a 4-20 mA Style KF housing (see page 387)
signal output. This loop powered module Dimensions (mm) 115 x 20 x 118
also provides galvanic isolation. Weight 100 g (3.5 oz.)
The sensing range of the bipolar input unit Protection IP20
isolates and conditions a 4-20 mA output. Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Fine adjustment for zero and span are
performed with the potentiometer on top
of the unit.
Signal Conditioners
Connection Diagram
KFD0-VC-1.10
(+) 1 9 (+)
Input Output
(– ) 2 8 (– )
Transfer Characteristics
Voltage surge 6.5 ppm / V
Measuring range (adjustable) Span 4 to 60 mV
Zero point -12 to 60 mV Model Number
Characteristics Output voltage is proportional to input KFD0-TT-1
Calibrated accuracy 0.1% of final value ±1ºC for cold point
Temperature drift Span 0.005% of span / ºC ■ Internal CJC
Zero point 0.01% of span / ºC or ±1µV/ºC
■ Loop powered
0.01% of span/ºC or ±0.03ºC/ºC (J,K,N,T,E)
0.01% of span/ºC or ±0.06ºC/ºC (R, S) ■ Lead breakage and short circuit
Cold point ±2.0ºC (calibrated at TA = 20ºC) monitoring
Response time ≤ 250 ms ■ Input/output isolation
Galvanic isolation Function isolation per EN50178
■ Field-selectable thermocouple inputs
design isolation voltage 253 Veff
The KFD0-TT-1 is a loop powered isolator
Mechanical that accepts thermocouple inputs and
Housing conditions to a 4-20 mA output.
Material Makrolon
Style KF housing (see page 387) Types E, J, K, N, R, S, and T thermocouple
Dimensions (mm) 115 x 20 x 118
inputs with internal cold junction
compensation (CJC) with galvanic
Weight 150 g (5.3 oz.)
isolation. The input voltage is linear to
Protection IP20
output current, not proportional to
Signal Conditioners
Operating Temperature -20ºC to +60ºC (-4ºF to +149ºF) temperature. Adjustable zero, span and
burnout detection are field-configurable.
Connection Diagram
KFD0-TT-1
(+) 1
8 (– )
(+) 1
(+) 1 8 (– )
Output
Input (– ) 2 9 (+)
(– ) 3
(– ) 2 9 (+)
Input for Passive Output
(– ) 3
Thermocouple
Transfer Characteristics
Voltage surge 6.5 ppm / V
Measuring range Span w/o linearization 25ºC to 800ºC
Span with linearization 25ºC to 430ºC
Model Number Zero point w/o linearization -200ºC to 466ºC
Zero point with linearization -86ºC to 405ºC
KFD0-TR-1
Calibrated accuracy 0.1% of final accuracy
Linearity fault w/o linearization ≤ 0.04% final value
■ Loop powered
with linearization ≤ 0.14% final value
■ PT100, 2- and 3-wire Temperature drift span and zero point 0.015% / ºC or
■ Lead breakage (LB) monitoring ± 10 mΩ / ºC
■ Input/output isolation Response time ≤ 250 ms
Galvanic isolation Function isolation per EN50178
■ Field-configurable inputs/outputs design isolation voltage 50 Veff
The KFD0-TR-1 is a loop powered isolator
Mechanical
that accepts Pt100 2- and 3-wire inputs and
Housing
conditions them to a 4-20 mA output.
Material Makrolon
The KFD0-TR-1 provides galvanic isolation Style KF housing (see page 387)
and burnout detection (≥22 mA). Field- Dimensions (mm) 115 x 20 x 100 mm
configurable DIP switches allow linearization Weight 150 g (5.3 oz.)
to be turned on and off. Protection (IEC) IP20
The loop powered 2-wire converter is suited
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
for the connection of the Pt100 in 2- or 3-
Signal Conditioners
wire mode.
KFD0-TR-1
(– ) 2 (– ) 2 8 (– )
(– ) 2 (– ) 2 8 (– )
Output
Input 1 1 1 9 (+)
(+) 3
9 (+)
Passive Ouput
(+) 3 (+) 3
Input for Pt100
Signal Conditioners
five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20 mA
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
or 4-20 mA. The KFDX-DCI accepts bipolar
inputs and offers selectable normal or reverse
output modes of operation (4-20 mA, 20-4
mA). For inputs that do not change in polarity,
select unipolar operation.
Note: For information about programming, refer to page
209 or to our website at www.am.pepperl-fuchs.com The KFDX-DCI is equipped with a dual
function power/signal status LED. When the
Connection Diagram unit is powered, this green LED turns on.
When the input signal is over 110% of the
full scale range, the LED flashes at 8 Hz;
below 0% it flashes at 4 Hz.
KFDX-DCI
This unit is not intrinsically safe.
(+) 1 8 (+)
DC Current Analog
Input 7 (– ) Output
(– ) 2
11 (+)
DC Power
12 (– ) Supply
(+) 1 8 (+)
DC Voltage Analog
Input 7 (– ) Output
(– ) 2
11 (+)
DC Power
12 (– ) Supply
Transfer Characteristics
Accuracy @ 20ºC ≤ ±10 µA
Temperature drift ≤ ±0.2 mA / ºC (0ºC to +60ºC) Model Number
±1.0 mA / ºC (-20ºC to 0ºC) KFD2-CR-1.300
Response time ≤ 50 µs
Galvanic isolation, 3 way Isolation per EN50178 ■ 2- or 3-wire input
Isolation voltage 253 Veff ■ 20-30 VDC power supply
Mechanical ■ 4-20 mA output
Housing ■ 3-way isolation
Material Makrolon
The KFD2-CR-1.300 is an isolator that
Style KF Housing (see page 387)
powers and repeats a 4-20 mA signal from
Dimensions (mm) 115 x 20 x 100 mm
a 2- or 3-wire transmitter. It can also isolate
Weight 100 g (3.5 oz.)
and repeat signals from a current source.
Protection (IEC) IP20
For 2-wire transmitters, connected to
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF) terminals 1 and 3, there is 17.5 V at 20 mA
available to the transmitter.
For 3-wire transmitters, the power is supplied
on terminals 1 and 2 with a 4-20 mA signal
flowing into terminal 3. The voltage available
Signal Conditioners
is approximately 16.5 V at 25 mA between
terminals 1 and 2. Power, input and output
are galvanically isolated.
This unit is not intrinsically safe.
For information about programming, refer to page 209 or to our website
at www.am.pepperl-fuchs.com
Connection Diagram
KFD2-CR-1.300
(+) 1 (+) 1
(– ) 2
(+) 1 8 (+)
(– ) 2 Analog
(– ) 2 7 (– )
Output
3 9 (– )
3
11 (+) DC Power
12 (–) Supply
3 3
Input
Transfer Characteristics
Calibration accuracy ≤ ±20 µA
Temperature drift ≤ 20 ppm / ºC
Rise time 20 µs with 4-20 mA stage Model Number
De-energized delay 20 µs with 20-4 mA stage KFD2-CR4-1.20
Galvanic isolation, 3-way Isolation per EN50178
Isolation Voltage 253 Veff ■ Single-channel input /
dual output
Mechanical ■ 20-30 VDC supply voltage
Housing
Material Makrolon
■ Outputs isolated from each other
Style KF housing (see page 387) ■ Power Rail Bus
Dimensions (mm) 115 x 20 x 100 mm ■ 3-way isolation
Weight 100 g (3.5 oz.)
Protection (IEC) IP20 The KFD2-CR4-1.20 is suited for the
connection of 2- and 3-wire transmitters.
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF) It may also be employed as a repeater for
0-20 mA signals (current source).
Both outputs provide a 0-20 mA current
corresponding to the input signal.
2-wire transmitters are connected to
Signal Conditioners
terminals 1 and 3. The input for the signal
is terminal 3. The minimum available
voltage is 16V at 20 mA. Current sources
are connected to terminals 2 and 3.
The input, output and power supply are
Note: For information about programming, refer to page 209 or to our galvanically isolated from each other.
website at www.am.pepperl-fuchs.com
This unit is not intrinsically safe.
Connection Diagram
KFD2-CR4-1.20
(+) 1 (+) 1
(+) 1 7 (– )
(– ) 2 Output 1
8 (+)
(– ) 2
10 (– )
(– ) 2 3 Output 2
11 (+)
14 (+)
DC Power
3 3 3 15 (– ) Supply
Input
Input Terminals 1, 2, 3
Input signal 0/4-20 mA
Available voltage at 20 mA ≥16 V
Transfer Characteristics
Calibrated accuracy ≤ 20 µA
Temperature drift ≤ 20 ppm / ºC
Frequency range:
Input/Output:
Model Number Band width at 0.5 VppSignal 0 Hz to 7.5 kHz (-3 dB)
KFD2-STC4-1.20 Output/Input:
Band width at 0.5 VppSignal 300 Hz to 7.5 kHz (-3 dB)
■ Single channel input /dual output Galvanic isolation Isolation per EN 50178
Isolation voltage 253 Veff
■ HART compatible
■ 4-20mA current source output Mechanical
■ 3-way isolation Housing
Material Makrolon
SMART transmitter powers a 2-wire Style KF housing (see page 387)
SMART transmitter and isolates the analog Dimensions (mm) 107 x 20 x 115 mm
4-20 mA signal from the field to the control Weight 100 g (3.5 oz.)
room as two current sources. Protection (IEC) IP20
Digital signals which can be modulated onto
the analog signal, can also be transmitted Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
bidirectionally.
The SMART transmitters are delivered with
the KF-STP-GN terminals. Connector jacks
are integrated in these terminals for the
Signal Conditioners
KFD2-STC4-1.20
(+) 1 (+) 1
Communicator
(+) 1 7 (– )
(– ) 2 (– ) 2
SMART
Output 1
8 (+)
(– ) 2
10 (– )
3 Output 2
11 (+)
14 (+)
3 3 3 DC Power
15 (– ) Supply
Input
Signal Conditioners
1 mA, 0-20 mA or 4-20 mA.
Span and zero potentiometers provide 50%
adjustability of offset and span turndown for
each input range. To ensure accurate
temperature measurement, the KFDX-RTD
Note: For information about programming, refer to page 209 or to our contains constant current circuitry which uses
website at www.am.pepperl-fuchs.com
the third lead of the RTD as a sense line for
lead resistance compensation.
Connection Diagram
The KFDX-RTD is equipped with three LEDs:
INPUT (green), TROUBLE (yellow) and CAL
KFDX-RTD (yellow). Upon power-up, the INPUT and CAL
LEDs will alternately flash for 10 seconds.
This unit is not intrinsically safe.
(+) 1
8 (+)
(– ) 2 Analog
7 (– ) Output
(R) 3
RTD Input 11 (+)
DC Power
12 (– ) Supply
Input Terminals 1, 2
Maximum overload ± 10 VDC on input
Range selectable
Impedance ≥ 1 MΩ
Burnout detection selectable up/downscale
Zero 50% of full scale input
Span 50% of full scale input
Transfer Characteristics
Calibrated accuracy ± (0.01% of value in ºC + 0.05% of
Model Number
range + 0.1 ºC) (4-wire)
Thermocouple ± (0.05% of value in ºC + 0.05% of
KFD2-UT-1
range + 1ºC) (inc. ± 0.8ºC error for CJC)
■ Universal temperature inputs
Rise time ≤ 430 ms
Galvanic isolation Isolation per EN50178 ■ Current output
Isolation voltage 253 Veff ■ Programming & calibration via PC
Mechanical ■ 3-way isolation
Housing ■ CJC for thermocouple and lead
Material Makrolon resistance compensation for RTDs
Style KF housing (see page 387)
The KFD2-UT-1 is designed for connection to
Dimensions (mm) 115 x 20 x 118
RTDs (Pt100 and Ni100) or thermocouples (B, E,
Weight 100 g (3.5 oz.)
J, K, L, N, R, S and T), and provides three-way
Protection (IEC) IP20
isolation. The inputs, outputs and power supply
Operating Temperature +4ºC to +60ºC (+40ºF to +140ºF) are galvanically isolated.
Signal Conditioners
monitoring for RTDs.
Transfer Characteristics
Calibrated accuracy ± (0.01% of value in ºC + 0.05% of
Model Number
range + 0.1 ºC) (4-wire)
KFD2-UT-1-1 Thermocouple ± (0.05% of value in ºC + 0.05% of
range + 1ºC) (inc. ± 0.8ºC error for CJC)
■ Universal temperature inputs Rise time ≤ 430 ms
■ Voltage output Galvanic isolation Isolation per EN50178
Isolation voltage 253 Veff
■ Programming & calibration via PC
■ 3-way isolation Mechanical
■ CJC for thermocouples and lead Housing
resistance compensation for RTDs Material Makrolon
Style KF housing (see page 387)
The KFD2-UT-1-1 is designed for connection to
Dimensions (mm) 115 x 20 x 118
RTDs (Pt100 and Ni100) or thermocouples (B,
E, J, K, L, N, R, S and T), and provides three- Weight 100 g (3.5 oz.)
way isolation. The inputs, outputs and power Protection (IEC) IP20
supply are galvanically isolated.
Operating Temperature +4ºC to +60ºC (+40ºF to +140ºF)
This device also features internal/external cold
junction compensation, burnout monitoring for
thermocouples and burnout and short circuit
Signal Conditioners
A signal at terminals 2 and 3 is transmitted across Note: For information about programming,
the isolator and converted to an equivalent refer to our website at www.am.pepperl-fuchs.com
output at terminals 7 and 8. Terminal 7 has the
same polarity as terminal 2. Connection Diagram
All parameters are programmable through a K- KFD2-UT-1-1
ADP1 cable (sold separately) that provides the
connection between the programming socket CJC (+) 4
Type K-CJC-GN
of the KFD2-UT and the RS232 PC interface. (+) 3 (+) 3 (+) 3
7 (+) Analog
4
Accessories include removable terminals with 8 (– )
Output
3
internal cold junction compensation (K-CJC) and (– ) 2
2
a K-SK programming software kit. The K-ADP1 (– ) 2 (– ) 2 (– ) 2 11 (+) DC
1
and K-SK are required unless the KFD2-UT-1-1 12 (– )
Power
Supply
is configured by P+F. (+) 1 (– ) 1 (– ) 1
PC
Signal Conditioners
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
The KFDX-AC is outfitted with a green dual
function power/signal status LED. When the
unit is powered, the LED is illuminated. When
the input signal is over 110% of the full scale
range, the LED flashes at 8 Hz.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com This unit is not intrinsically safe.
Connection Diagram
KFDX-AC
(+) 1 8 (+)
AC Input Analog
Current/Voltage (– ) 2 7 (– ) Output
11 (+)
DC Power
12 (– ) Supply
(+) 1 8 (+)
Frequency Analog
Input (– ) 2 7 (– ) Output
11 (+)
DC Power
12 (– ) Supply
Signal Conditioners
of the unit. An overspeed or underspeed
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF) condition is signaled via the relay outputs.
Lead breakage and short circuits in the
sensor are indicated by a red LED. The
start-up override feature sets relay outputs
to default conditions programmed by the
Note: For information about programming, user, for up to 1,000 seconds.
refer to our website at www.am.pepperl-fuchs.com
This unit is not intrinsically safe.
Connection Diagram
KFA5-DWB-1.D
Input II Input I 11
10 Output 1
(+) 1 (+) 1 (+) 1 (+) 1 (+) 1 (+) 1
12
17
R2
2 2 16 Output 2
R1
18
R1
13 (+) Start Up
14 (– ) Override
(– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3
23 Supply
LB/SC LB/SC LB 24 120 VAC
Outputs
■ Operating range 0.06-720,000 Relay output 1 (SPDT) Terminals 10, 11, 12
RPM (0.001-12,000 kHz) Relay output 2 (SPDT) Terminals 16, 17, 18
■ Relay outputs Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
of the unit. An overspeed or underspeed Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
condition is signaled via the relay outputs.
Lead breakage and short circuits in the
sensor are indicated by a red LED. The
start-up override feature sets relay outputs
to default conditions programmed by the
Note: For information about programming,
user, for up to 1,000 seconds. refer to our website at www.am.pepperl-fuchs.com
This unit is not intrinsically safe.
Connection Diagram
KFA6-DWB-1.D
Input II Input I 11
10 Output 1
(+) 1 (+) 1 (+) 1 (+) 1 (+) 1 (+) 1 12
Signal Processor
17
R2 16
2 2 Output 2
R1 18
R1
13 (+) Start Up
14 (– ) Override
(– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 23 Supply
LB/SC LB/SC LB 24 240 VAC
Signal Conditioners
panel. An overspeed or underspeed
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF) condition is signaled via the relay outputs.
Lead breakage and short circuits in the
sensor are indicated by a red LED and
through the collective error output via
Power Rail. The start-up override feature
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com sets relay outputs to default conditions
programmed by the user, for up to 1,000
Connection Diagram seconds.
This unit is not intrinsically safe.
KFD2-DWB-1.D
Input II Input I 11
10 Output 1
(+) 1 (+) 1 (+) 1 (+) 1 (+) 1 (+) 1 12
Signal Processor
17
R2 16
2 2 Output 2
R1 18
R1
13 (+) Start Up
14 (– ) Override
(– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 23 (+) Supply
LB/SC LB/SC LB 24 (– ) 24 VDC
Connection Diagram
KFU8-UFC-1
Input II Input I 11
RxD 10 Output 1
TxD Programming
(+) 1 (+) 1 (+) 1 (+) 1 (+) 1 (+) 1 12
GND Jack
17
16 Output 2
18
R2
2 2 19 (+) Output 3
R1 20 (– )
R1 8 (+) Output 4
7 (– ) 0/4-20 mA
13 Start Up
(– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 14 Override
LB/SC LB/SC LB 23 Supply
24 24 VDC
120 VAC
240 VAC
Signal Conditioners
Housing Makrolon KF housing (see page 387) programmable with a PC and the
Dimensions (mm) 118 x 40 x 115 PACTware configuration software. A
Weight 300 g (10.6 oz.) debounce circuit eliminates extraneous
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF) signals from relay bounce.
Lead breakage and short circuits in the
Note: For information about programming, sensor are indicated by a red LED and
refer to our website at www.am.pepperl-fuchs.com through the collective error output via
Power Rail.
Connection Diagram
This unit is not intrinsically safe.
KFD2-UFC-1.D
Input II Input I 11
RxD 10 Output 1
TxD Programming
(+) 1 (+) 1 (+) 1 (+) 1 (+) 1 (+) 1 12
GND Jack
17
16 Output 2
R2 18
2 2 19 (+) Output 3
R1 20 (– )
R1 Output 4
8 (+)
7 (– ) 0/4-20 mA
13 (+) Start Up
(– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 14 (– ) Override
LB/SC LB/SC LB 23 (+)
Supply
24 (– ) 24 VDC
KFD2-UFC-1
Input II Input I 11
RxD 10 Output 1
(+) 1 (+) 1 (+) 1 (+) 1 (+) 1 (+) 1 TxD Programming
12
GND Jack
17
16 Output 2
R2 18
2 2 19
R1 Output 3
20
R1
8 Output 4
7 0/4-20 mA
13 Start Up
(– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 14 Override
LB/SC LB/SC LB 23
Supply
24 24 VDC
Signal Conditioners
Housing Makrolon KF housing (see page 387)
PACTware configuration software. A
Dimensions (mm) 118 x 40 x 115
debounce circuit eliminates extraneous
Weight 300 g (10.6 oz.) signals from relay bounce.
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Lead breakage and short circuits in the
sensor are indicated by a red LED.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com This unit is not intrinsically safe.
Connection Diagram
KFU8-UFC-1.D
Input II Input I 11
RxD 10 Output 1
TxD Programming
(+) 1 (+) 1 (+) 1 (+) 1 (+) 1 (+) 1 12
GND Jack
17
16 Output 2
18
R2 19 (+)
2 2 Output 3
R1 20 (–)
R1 8 (+) Output 4
7 (–) 0/4-20 mA
13 (+) Start Up
(– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 (– ) 3 14 (– ) Override
23
LB/SC LB/SC LB Supply
24 24 VDC
120 VAC
240 VAC
which indicates DC power and input signal Dimensions (mm) 115 x 20 x 118
status. If this LED is not illuminated upon Weight 100 g (3.5 oz.)
Signal Conditioners
KFDA-DCI
(+24 VDC) 3
(+) 1
DC Input
(– ) 2
4 7
Output A 5 8 Output B
6 9
11 (+) DC Power
12 (– ) Supply
Signal Conditioners
the input varies slightly on either side of the
setoint. The input must remain beyond the
setpoint for 100ms, uninterrupted, to qualify
as a valid trip condition. To return the alarm
to an untripped condition, the input signal
Note: For information about programming, must be outside the deadband and remain
refer to our website at www.am.pepperl-fuchs.com there for 100 ms. This time-based dynamic
deadband, in addition to the evaluation of
Connection Diagram hysteresis, improves setpoint stability. Select
unipolar operation for inputs that do not
change in polarity.
KFDA-DCV The KFDA-DCV is equipped with three LEDs.
The first is a green INPUT LED which indicates
DC power and input signal status. If this LED
does not illuminate on power-up, check wiring
(+24 VDC) 3
connections. When the signal input is over
(+) 1
DC Input 110% of the full scale range, the INPUT LED
(– ) 2
4 7 will flash at 8 Hz; below 0% it will flash at 4
Output A 5 8 Output B Hz. Each setpoint has its own LED which
6 9
indicates the relay state; an illuminated LED
11 (+) DC Power
12 (– ) Supply indicates a tripped condition.
This unit is not intrinsically safe.
Input
Measuring range voltage (terminals 1+, 3-) 0/1-5 V
Input load 50 kΩ
Measuring range voltage (terminals 1+, 3-) 0/2-10 V
Input load 100 kΩ
Measuring range voltage (terminals 2+, 3) 0/4-20 mA
Input load 50 Ω
Output
Output I (terminals 7, 8, 9) trip value 1
Output II (terminals 10, 11, 12) trip value 2
Model Number Contact load AC: 250V / 5A / 1250VA
DC: 125V / 5A / 150 W
KFD2-GS-1.2W
Function
■ Single-channel, 24 VDC supply Response time 100 ms
■ Current and voltage analog inputs Accuracy/repeatability < 0.5%
Temperature drift 0.01% / ºC in reference to set limits
■ 2 programmable trip points
Isolation 1000 V
The KFD2-GS-1.2W is a trip amplifier for two Mechanical
independently field-configurable limit alarms.
Housing
Three-way galvanic isolated units convert 0/4-20
mA, 0/1-5 V and 0/2-10 V signals into trip point Material Makrolon
outputs. Style KF housing (see page 387)
Dimensions (mm) 115 x 20 x 118
For high alarm indication, the status of the contact
Weight 120 g (4.2 oz.)
output changes when the setpoint is exceeded
and will not reset until a lower value is met. The Protection (IEC) IP20
difference between these states is the adjustable
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
hysteresis.
The trip alarm is adjustable by a selector switch
High-/Low alarm
and potentiometer. Dip switch Mode of
ON: Limit 1
Signal Conditioners
Input responds to
operation
functions range both outputs
A monitoring voltage output of 0-10 V can be used on side 1
to adjust limit values and hysteresis without of unit
interrupting the input signal.
This unit is not intrinsically safe. 0 1 2 3 4 5 6
Output
Output I Terminals 10, 11, 12
Output II Terminals 16, 17, 18
Output I & II type Form C, SPDT contact
Contact loading 250 VAC / 2A / cos ϕ ≥ 0.7; 40 VDC/2A
Maximum voltage (Um) 40 VDC
Pull-in/drop-out delay ≈ 20 ms / ≈ 20 ms
Mechanical life 5 x 107 operations
Output III Terminals 7, 8: analog signal
Model Number
Current range 0/4-20 mA KFD2-CRG-1.D
Quiescent voltage ≤ 24 VDC
Load ≤ 650Ω ■ Current source or transmitter
inputs
Transfer Characteristics
■ Analog output 0/4-20 mA
Accuracy 0.1% of full scale value (output < 10µA)
Temperature current measurement: 0.003% / ºC ■ 2 relay outputs
current output: 0.005% / ºC ■ Lead breakage and
current measurement & output: 0.006% / ºC short-circuit monitoring
Linearization current measurement and ■ Galvanic isolation
current output 0.025%
Input delay ≤ 200 ms
Isolation Galvanic isolation The KFD2-CRG-1.D transmitter power
supply is suited for a variet of measuring
Mechanical tasks. 2- and 3-wire transmitters as well
Housing Makrolon KF style housing (see page 387) as active power supplies with 0/4-20 MA
Dimensions (mm) 115 x 40 x 118 signals can be connected. Two relays and
Weight 300 g (10.5 oz.) an active 0/4-20 mA current output are
Signal Conditioners
Protection (IEC) IP20 available.
Operating Temperature -20ºC to +60ºC (-4ºF to +149ºF) The input has lead breakage and short-
circuit monitoring.
Programming is via a PC (using
PACTware) or by using the control panel
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com on the front of the device.
This unit is not intrinsically safe.
Connection Diagram
KFD2-CRG-1.D
KFU8-CRG-1.D
3 3 Universal
Power
Input
Signal Conditioners
Setpoints can be configured as HI or LO in
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
selectable controlsafe or non-controlsafe
operating modes. The KFDA-TC relies on
deadband (hysteresis) and constant sampling of
the input to prevent false switching when the input
varies slightly on either side of the setpoint. The
Note: For information about programming, input must remain uninterrupted beyond the
refer to our website at www.am.pepperl-fuchs.com
setpoint for 100 ms to qualify as a valid trip
Connection Diagram condition. To return the alarm to an untripped
condition, the input signal must fall outside the
deadband and remain there for 100 ms. This
time-based dynamic deadband improves
KFDA-TC
setpoint stability.
Input Terminals 1, 2, 3, 4, 5, 6
Type Pt100, Ni100
Thermocouple B,E,J,K,L,N,R,S or T
0-10 V, 0-20 mA, configuration with
programming jack
Max. lead resistance ≤ 50 Ω per lead
Test current 400 µA with RTDs
NOTE: Switch off current for lead breakage monitoring during measurement
Output
Output I (Limit 1) Terminals 7, 8 and 9
Output II (Limit 2) Terminals 10, 11 and 12
Contact load 253 VAC / 2 A / cos ø ≥ 0.6 Model Number
Mechanical life 2 x 107 operations KFD2-GU-1
Response time ≤ 370 ms
Temperature drift ±0.007% of switchpoint per ºC∆T ■ Universal temperature input
Power ≤ 0.0035% of span ■ Programming & calibration via PC
Isolation Galvanic isolation
■ 3-way isolation
Mechanical
■ CJC for thermocouples and lead
Housing Makrolon KF style housing (see page 387)
resistance compensation for RTDs
Dimensions (mm) 115 x 20 x 118
Weight 100 g (3.5 oz.) The KFD2-GU-1 universal input limit alarm is
Protection (IEC) IP20 field-configurable for 0-10 V, 0-20 mA, Pt100/
Ni100 and all thermocouple inputs with three-
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
way galvanic isolation. This unit also features
internal/external cold junction compensation
(CJC) and burnout detection for thermocouples
and lead short circuit monitoring for RTDs and
current/voltage inputs. Calibration, adjustments
and monitoring are achieved through a serial
interface to a PC.
Signal Conditioners
All parameters are programmable through a K-
ADP1 cable (sold separately) that provides the
connection between the programming
receptacle of the KFD2-GU and the RS232 PC
interface.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com Accessories include removable terminals with
internal cold junction compensation (K-CJC)
Connection Diagram and a K-SK programming software kit. The K-
ADP1 cable and K-SK software kit are required
(+) 6 unless the KFD2-GU is configured by P+F.
KFD2-GU-1 This unit is not intrinsically safe.
(+) 5
(+) 4
CJC
Type K-CJC-GN
(+) 3 (+) 3 (+) 3
7
Signal Processor
(+) 6 8 Output 1
(+) 5 9
(+) 1 (+) 4 10
11 Output 2
(– ) 1 (– ) 1 (+) 3
12
(– ) 1
(– ) 2 11 (+) DC
12 (– ) Power
PC
(– ) 2 (– ) 2 (– ) 2 (– ) 2 (– ) 2 (– ) 2
Supply
K-ADPI