Why
Maintenance
?!
2
Tools
Tools for Anti-static
Brush, tweezers, wrist strap, glove…
3
Tools
Tools for Hardware Maintenance
simulator, process calibrator, FLUKE,
signal generator, resistance box…..
4
Tools
Tools for Software Maintenance
SC-Diagnose, real-time monitoring…
5
Tools
Tools for Network Maintenance
6
Content
7
Routine Maintenance
8
Routine Maintenance
9
Routine Maintenance
• Central Control Room
System grounding
Anti-Interference
Anti-Corrosion
10
Routine Maintenance
• Central Control Room
• System power supply
Compliance to IEC61000-3-2
11
Routine Maintenance
• Central Control Room
• UPS power supply maintenance
Temperature: 20℃-30℃
Check battery capacity
Charge and discharge periodically
Grounding of UPS shell
13
Routine Maintenance
• Central Control Room
grounding system
14
Routine Maintenance
• Central Control Room
• Seal up cable holes
un-sealed ,
excrement of mouse
15
Routine Maintenance
• Central Control Room
• Temperature and Humidity control
Condensation 16
Routine Maintenance
• Central Control Room
• Anti-Interference
electromagnetic shielding
17
Routine Maintenance
• Central Control Room
• Anti-Corrosion
Modules have be
corroded
18
Routine Maintenance
• Central Control Room
• Anti-Corrosion
20
Routine Maintenance
• Central Control Room
• Anti-Corrosion
Fresh air to
control room
21
Routine Maintenance
• Central Control Room
• Anti-Corrosion
Fresh air to
operation room
22
Routine Maintenance
• Central Control Room
• Anti-Corrosion
23
Routine Maintenance
• Central Control Room
• Anti-Corrosion
24
Routine Maintenance
• Control Station
25
Routine Maintenance
• Control Station
interference due to
transformer
26
Routine Maintenance
• Operation Station
27
Routine Maintenance
• Network
Check connection
28
Overhaul Maintenance
29
Overhaul Maintenance
30
Overhaul Maintenance
• Preparations before power-off
32
Overhaul Maintenance
• Overhaul Maintenance
33
Overhaul Maintenance
• Procedure of power-on
adjuster
setting
35
Overhaul Maintenance
• PID parameter setting and Commissioning
• Cascade
Step 1: internal loop adjusting
stable
Manual status : MV Auto status: SV
★ SV gradually increased.
36
Overhaul Maintenance
• PID parameter setting and Commissioning
37
Overhaul Maintenance
After overhaul, the system behaviors as :
Start up normally
No fault left
No abnormal sound
38
Hardware Maintenance
39
Hardware Maintenance
40
Hardware Maintenance
• Power supply fault
Corrosion
42
Hardware Maintenance
• MCU fault
case 1
Problem :
When power ON, FAIL is ON, FAIL on the I/O modules a
re aslo ON. Then download the configuration, the fault
disappears.
43
Hardware Maintenance
• MCU fault
Analysis :
Check the Li-battery.
Solution : ?
44
Hardware Maintenance
• MCU fault
case 2
Problem :
Control Station can’t communicate with Operation Station.
45
Hardware Maintenance
• MCU fault
Analysis :
Check the address of the whole system, whether there is
address conflict.
Solution : ?
46
Hardware Maintenance
• MCU fault
47
Hardware Maintenance
• DTM fault
Common fault :
FAIL is ON.
Analysis :
Check module status by Diag. panel on HMI.
Check DB9 cable connection among I/O racks.
48
Hardware Maintenance
• DTM fault
Common fault :
COM is OFF, Diag. panel on HMI shows
SBUS failure, I/O controller of MCU failure.
Analysis :
49
Hardware Maintenance
• DTM fault
case
Problem :
Replace a new DTM, but COM is OFF.
50
Hardware Maintenance
• DTM fault
Analysis :
Check the address.
Solution : ?
51
Hardware Maintenance
• I/O module fault
Disturbance
Poor grounding
Transmitter failure
Motherboard failure
52
Hardware Maintenance
• I/O module fault
Common fault :
Real-time data display abnormal.
Analysis :
Wrong setting(configuration, jumper, signal wire connection)
I/O module failure
Motherboard failure
Disturbance
53
Hardware Maintenance
• I/O module fault
Common fault :
Real-time data jump.
Analysis :
Disturbance
Transmitter failure
I/O module failure
Motherboard failure
54
Hardware Maintenance
• I/O module fault
Common fault :
Real-time data can't display.
Analysis :
Transmitter failure
Wrong setting( configuration, jumper, signal wire
connection)
Terminal board failure
Network failure
I/O module or rack failure
55
Hardware Maintenance
• I/O module fault
Problem :
case 1 A flow signal display “?” on
graphics.
Analysis :
First, check the configuration.
Second, check the signal wire.
Solution : ?
56
Hardware Maintenance
• I/O module fault
Problem :
case 2 Real-time data of signals on the same TC
module display abnormal.
Analysis :
First, replace the I/O module.
Second, check environment (disturbance, humidity,
corrosion ).
Solution : ?
57
Hardware Maintenance
• I/O module fault
Problem :
case 3 Set DO signal value ON, but the
solenoid valve related to the tag don't
work in the field.
Analysis :
First, check other channels on the same module.
Second, check the status of MCU.
Third, check 24V output to relay.
Solution : ?
58
Hardware Maintenance
• Operation Station fault
Common fault :
Display fault
Analysis :
First, change the display.
Second, change video card or motherboard.
59
Hardware Maintenance
• Operation Station fault
Common fault :
Operator keyboard fault
Analysis :
Check individual key
Check connection between computer and keyboard
Replace keyboard
Check configuration
60
Hardware Maintenance
• Operation Station fault
Common fault :
Operation Station crashes
Check Hard disk
Hardware Check motherboard
reason Check memory
Check video card
Analysis :
…
Virus
Software System default file deleted
reason Not enough hard disk capacity
Illegal operation
Memory conflict
61
Hardware Maintenance
• Operation Station fault
Problem :
case Monitor flashes heavily, replace the monitor,
the problem still exist.
Analysis :
First, check the host.
Second, check environment (disturbance,
humidity, corrosion ).
Solution : ? 62
Software Maintenance
63
Software Maintenance
windows system
configuration software
monitoring software
64
Software Maintenance
• Tools
• Diagnosis
• Network test
• History data tool
65
Software Maintenance
• Common faults
66
Software Maintenance
• Trouble shooting
Problem :
case 1 Part of real-time data show “?”, and the
real-time data of the same tag is
different among operator stations.
67
Software Maintenance
• Trouble shooting
Analysis :
possibility1:
communication/module/signal fault;
possibility2:
no publish or no download.
Solution:?
68
Software Maintenance
• Trouble shooting
Problem :
case 2 There are breakpoints in the trend.
69
Software Maintenance
• Trouble shooting
Analysis :
If period of trend record are set like this , interrupt point
maybe happens.
Solution :?
70
Software Maintenance
• Trouble shooting
case 3
Problem :
Trend record interrupted in engineer station , but was
normal in operator station.
71
Software Maintenance
• Trouble shooting
Analysis :
File of Trend record can be set in configuration.
Solution :?
72
Software Maintenance
• Trouble shooting
case 4
Problem :
Time is different among operator stations
73
Software Maintenance
• Trouble shooting
Analysis :
Time Synchronization function need setting server and
client nodes.
Solution :?
74
Network Maintenance
75
Network Maintenance
• Analyze Tools
76
Network Maintenance
• Analyze Tools
77
Network Maintenance
• Common Problems
78
Network Maintenance
• Common Problems
• Communication errors in the diagnose of all operator
stations ,and configuration can’t be downloaded.
79
Network Maintenance
• Common Reasons
• network equipment failure ( communication
cable ,network card , HUB or switch… )
80
Network Maintenance
• Common Problems
• One operator station is showing communication
errors while other operator stations are normal.
81
Network Maintenance
• Common Reasons
• setting errors ( network card drivers 、 IP address ,
subnet mask , communication protocol )
82
Network Maintenance
• Common Problems
• Diagnose window shows: MCU I/O controller
failure , DTM I/O failure , SBUS failure.
83
Network Maintenance
• Common Reasons
• Setting errors ( MCU address , DTM addres
s)
• MCU fault, Network cable fault
• SBUS are not connected correctly
84
Network Maintenance
• Common Problems
• Data not refreshed
85
Network Maintenance
• Common Reasons
• IO module fault
• MCU fault
• Power supply of MCU and switch fault
• IP setting of new computer fault
86
Network Maintenance
• Trouble shooting
Case
Problem :
one project has 2 control stations , when one power
supply power off , control stations work well individual
, but they can’t communicate , failure indicator of
MCU flash.
87
Network Maintenance
• Trouble shooting
Analysis :
2 redundant AC supplies of the switches are not
connected correctly, 1# control station switch A use
electric supply, switch B switch use UPS , 2# control
station just the opposite choice 。
Solution :?
88
Configuration Maintenance
89
Configuration Maintenance
90
Configuration Maintenance
• Configuration management
• save
Disk D
91
Configuration Maintenance
• Configuration management
• backup
before modification
after modification
Disk E or Disk F
92
Configuration Maintenance
• Control station modification
• add tag
93
Configuration Maintenance
• Control station modification
• delete tag
94
Configuration Maintenance
• Control station modification
• attentions
Standard panel
Alarm panel
Graphics
…
Compile, publish
96
Configuration Maintenance
• Download
necessary to download
modification related with control station
(controller, I/O module, signal point and control
scheme etc).
not necessary to download
modification related with operation station
(standard panel, alarm panel, graphics and report etc).
97
Function
• Function
Usually used for motor control panel
• Workflow
98