0 Loading Analysis:

WE HAVE,
From Section Detail-A,

Clear center between supporting


Frame, L = 1.116m

From wind load analysis, 6.0 M


Wind Pressure= 1.6 KPa
So, UDL from wind load to frame, W= 1.6 * 1.116 = 1.786 KN/M

So, Span, S= 6.0 m

Moment, M = W*S2/10 = 6.43 KN-M

Let, design strength, Ps=170 N/mm2

So, Need Minimum Section Modulus, Sx = 6.43*1.4*106/170 = 53.0 cm3


5.0 Design of ACP Supporting Frame
@ Top:
As per detail-F, MS Box 20x40x1.5mm at front chord & L-100x100x6mm
At back chord both of which are connected with MS Box 20x40x1.5mm @
1mspaces.
At first, We will check MS Box capacity at 1.0 m spaces.
We found from top figure of MS Box, Section Modulus,
Sxx = 2.67 cm3
Moment for 1m, M= W*S2/12 = 1.786x1x1/12 = 0.150 KN-M

So, Required Section Modulus, Sreq = 1.50 * 0.15*106/ 170


= 1.32 cm3 < Sxx(Provided)=2.67 cm3

(SO, MS BOX Section is SAFE @ FRONT)

We will check now frame capacity which is having 6m span.

Lets check the total section modulus of the 190mm spaced frame.

Ibox = 1.152 cm4


Iangle = 164.324 cm4
So, Total Moment of Inertia of the frame section, ITotal
= Ibox + Iangle + Abox*D2 + Aangle*D2 = 1.152+164.324 + (1.62*9.52)+
(17.19*9.52) = 1863.00 cm4

So, Provided Section Modulus, Sprov = I/D= 1863/12= 155.25 cm3


However,
Moment, M = W*S2/10 = 6.43 KN-M
Let, design strength, Ps=170 N/mm2

So,
Need Minimum Section Modulus,
Sreq = 6.43*1.4*106/170 = 53.0 cm3 < Sprov=155cm3

(SO, Proposed Frame is SAFE)