PROBLEM OF FRTU

1. How many ampere does FRTU can be supply to all output?

Modem Power : DC24V 1A Output

Battery : DC24V MAX 15A Input

Motor Power : AC MAX 15A Input


2. LBS can be use Auto Sectionalize function to trip but Led trip not lit.

Green LED is On in your RT-200P Photo

사진상 OPEN 상태 LED On 되어 있음

3. Simulation current to test sectionalize function by Test JIG. Insert only one phase but the screen displayed
two phases and neutral.
=> You have to check the connection of current input.
We think that A Phase and Current Com may be changed each other.
So, you need to check it

=> 전류 입력 배선 확인 필요. A 상과 전류 Com 단자 바뀐 것 같음


4. Insert current only one phase but event log FI recorded three phases and neutral.

We have a question about No.3 and No.4. Is the above screen events field data or testing data?

Question :
Q1. Current and Voltage input equipment : Testing Jig ? or Relay testing equipment?
Q2. If you carried out by relay testing equipment, What is the relay setting value
[input current and phase] ?
Q3. Operating Mode : If you operated RT-200P as a Sectionalizer, we need operating mode value
and operating count value?
Q4. What is the firmware version of RT-200P when you carried out RT-200P?,
Pls inform us firmware version number?

# 3 번과 4 번 이력이 필드에서 나온 것인가요 아니면 테스트 상황에서 나온 것 인가요

문의 :
테스트 할 때 조건
전류 전압 입력 장비 : 시험용 JIG 인지 계전기 시험기 인지
계전기 시험기로 입력 하였다면 계정기 설정 값(입력 전류 및 위상)
동작 모드 : 섹션이라면 동작 Mode, 동작 Count