2. LBS can be use Auto Sectionalize function to trip but Led trip not lit.
We think that it may cause that you might have changed the current channel switch during flowing
flowing the fault current.
Some data are not reasonable data during single phase input power and 3 phase input power.
RT-200P has been saved the peak fault current between starting fault current and finishing no voltage
of opening LBS.
Please check it again that you carried out the testing under changing the current channel switch.
We want you to inform us more detailed test condition and test method
if you didn’t carry out the testing under changing the current channel switch before.
Question :
Q1. Current and Voltage input equipment : Testing Jig ? or Relay testing equipment?
Testing Jig, current : Ic=1235, In=1223, Va=Vb=Vc=Vr=Vs=Vt=12.7 (insert
only phase C)
Q2. If you carried out by relay testing equipment, What is the relay setting value
[input current and phase] ? No, only by Testing Jig.
Q3. Operating Mode : If you operated RT-200P as a Sectionalizer, we need operating mode value
and operating count value?
Q4. What is the firmware version of RT-200P when you carried out RT-200P?,
Pls inform us firmware version number? Firmware 1.2.7
Please update 1.2.8 firmware of RT-200 if you set to change the source side and the load side of LBS each
other.
Please set menu 2. system Config -> 1. I/O Config -> 6. CT Direction -> Direction [FWD/REV]