MAINTENANCE MANUAL
Translation of the Original Instructions
CRC
Direct expansion and chilled water
rack cooling units
All series with frontal and side air delivery. 50/60Hz range.
COOLSIDE DX-I COOLSIDE DF-I SPLIT EVO INV OUT COOLSIDE CW-I
COOLSIDE DX-E COOLSIDE DF-E SPLIT EVO INV OUT LT COOLSIDE CW-E
UM_CRC_00_Z_08_20_EN
EN
The information contained in this document may be modified without notice.
Reproduction and or disclosure through any means is prohibited unless written authorization from MEHITS SpA.
CRC Index
1. ............... GENERAL REQUIREMENTS ......................................................................................................................................................................................................................................................... 4
1.1 ........ GENERAL INFORMATION AND SAFETY .................................................................................................................................................................................................................................... 4
1.1.1 ..........OBJECTIVE OF THIS MANUAL .......................................................................................................................................................................................................................................... 4
1.1.2 ..........GLOSSARY AND TERMS .................................................................................................................................................................................................................................................... 4
1.1.3 ..........ENCLOSED DOCUMENTATION ......................................................................................................................................................................................................................................... 5
1.1.4 ..........SAFETY REGULATIONS ..................................................................................................................................................................................................................................................... 5
1.1.5 ..........PRECAUTIONS AGAINST RESIDUAL RISKS ................................................................................................................................................................................................................... 5
1.1.6 ..........DISCONNECTOR EXTERNAL TO THE MACHINE (NOT SUPPLIED) ............................................................................................................................................................................. 6
1.1.7 ..........SAFETY SIGNS .................................................................................................................................................................................................................................................................... 6
1.1.8 ..........REQUEST FOR ASSISTANCE ............................................................................................................................................................................................................................................ 6
1.2 ........ MACHINE IDENTIFICATION .......................................................................................................................................................................................................................................................... 7
1.2.1 ..........NOMENCLATURE AND IDENTIFICATION LABEL ............................................................................................................................................................................................................ 7
2 ................ OPERATING LIMITS....................................................................................................................................................................................................................................................................... 7
3 ................ CONFIGURATIONS ........................................................................................................................................................................................................................................................................ 8
3.1 ........ “I” VERSION ................................................................................................................................................................................................................................................................................... 8
3.2 ........ “E” VERSION .................................................................................................................................................................................................................................................................................. 8
4 ................ RECEIPT, TRANSPORT AND HANDLING ................................................................................................................................................................................................................................... 8
4.1 ........ STANDARD PACKAGING – INDOOR UNIT ................................................................................................................................................................................................................................. 9
4.2 ........ PACKAGING WITH WOODEN CRATE (OPTIONAL) – INDOOR UNIT ...................................................................................................................................................................................... 9
4.3 ........ STANDARD PACKAGING – OUTDOOR UNIT ........................................................................................................................................................................................................................... 10
4.4 ........ RECEIVING THE UNIT ................................................................................................................................................................................................................................................................. 11
5 ................ OVERVIEW DIAGRAM ................................................................................................................................................................................................................................................................. 12
5.1 ........ CRCC ............................................................................................................................................................................................................................................................................................. 12
5.2 ........ CRCX ............................................................................................................................................................................................................................................................................................. 12
5.2.1 ..........REFRIGERANT DIAGRAM – INDOOR UNIT – CRCX ..................................................................................................................................................................................................... 12
5.2.2 ..........REFRIGERANT DIAGRAM – OUTDOOR MOTOCONDENSING UNIT – I-HCAT .......................................................................................................................................................... 12
5.3 ........ CRCD ............................................................................................................................................................................................................................................................................................. 13
5.3.1 ..........REFRIGERANT / HYDRAULIC DIAGRAM – INDOOR UNIT – CRCD ............................................................................................................................................................................ 13
5.3.2 ..........REFRIGERANT DIAGRAM – OUTDOOR MOTOCONDENSING UNIT – I-HCAT .......................................................................................................................................................... 13
5.4 ........ I-HCAT LT ..................................................................................................................................................................................................................................................................................... 14
5.4.1 ..........REFRIGERANT DIAGRAM – OUTDOOR MOTOCONDENSING UNIT – I-HCAT LT ..................................................................................................................................................... 14
6 ................ INSTALLATION ............................................................................................................................................................................................................................................................................ 15
6.1 ........ CRC ............................................................................................................................................................................................................................................................................................... 15
6.2 ........ I-HCAT ........................................................................................................................................................................................................................................................................................... 15
6.3 ........ POSITIONING ............................................................................................................................................................................................................................................................................... 15
6.4 ........ CLEARANCE ................................................................................................................................................................................................................................................................................ 15
6.4.1 ..........CLEARANCE – I-HCAT - 0021-0051-0071-0121 .............................................................................................................................................................................................................. 15
6.4.2 ..........CLEARANCE – I-HCAT - 0151 – 0251 .............................................................................................................................................................................................................................. 15
6.5 ........ INSTALLAZIONE CONSIGLIATA PER CRCX-CRCD / I-HCAT ................................................................................................................................................................................................ 16
7 ................ REFRIGERANT CONNECTIONS ................................................................................................................................................................................................................................................. 17
7.1 ........ REFRIGERANT CONNECTIONS (CRCX-CRCD / I-HCAT) ....................................................................................................................................................................................................... 17
7.2 ........ RECOMMENDED REFRIGERANT LINES .................................................................................................................................................................................................................................. 17
7.3 ........ EQUIVALENT LENGHT IN METERS OF CURVED SECTIONS, ON-OFF AND NON RETURN VALVE ................................................................................................................................ 18
7.4 ........ REFRIGERANT CHARGE ............................................................................................................................................................................................................................................................ 18
7.5 ........ REFRIGERANT CONTENT PER LINEAR METER ..................................................................................................................................................................................................................... 18
7.6 ........ COMPRESSOR OIL CHARGE ..................................................................................................................................................................................................................................................... 18
7.7 ........ ADDITION OF EXTRA OIL FOR TRAPS ..................................................................................................................................................................................................................................... 18
7.8 ........ SUCTION LINES ........................................................................................................................................................................................................................................................................... 18
7.9 ........ LIQUID LINES ............................................................................................................................................................................................................................................................................... 18
8 ................ COMMISSIONING AND TESTING ............................................................................................................................................................................................................................................... 19
8.1 ........ CRCX-CRCD / I-HCAT .................................................................................................................................................................................................................................................................. 19
8.2 ........ CHECKING FOR LEAKS.............................................................................................................................................................................................................................................................. 19
8.3 ........ PREPARING FOR FIRST START UP .......................................................................................................................................................................................................................................... 19
8.4 ........ COMMISSIONING (AFTER THE 2 HOURS) ............................................................................................................................................................................................................................... 19
8.5 ........ STARTING AND STOPPING THE UNIT ...................................................................................................................................................................................................................................... 20
8.6 ........ COMMISSIONING PROCEDURE ................................................................................................................................................................................................................................................ 20
9 ................ WATER CONNECTIONS AND WATER CHARACTERISTICS (CRCC/CRCD) ........................................................................................................................................................................ 20
9.1 ........ CORRECTION FACTOR .............................................................................................................................................................................................................................................................. 21
9.1.1 ..........ETHYLENE GLYCOL SOLUTIONS ................................................................................................................................................................................................................................... 21
10 .............. ELECTRICAL CONNECTIONS .................................................................................................................................................................................................................................................... 22
10.1 ...... ELECTRICAL PANEL ................................................................................................................................................................................................................................................................... 22
10.2 ...... ACCESS TO THE CONTROL BOARD ........................................................................................................................................................................................................................................ 23
10.3 ...... CONNECTION CONFIGURATION - CRCX/CRCD 0021-0051-0071-0121 ................................................................................................................................................................................ 24
10.4 ...... CONNECTION CONFIGURATION - CRCX 0151-0251 .............................................................................................................................................................................................................. 24
10.5 ...... ELECTRICAL CONNECTIONS CRCX/CRCD 0021-0051-0071-0121 ....................................................................................................................................................................................... 25
10.6 ...... CONNECTION CONFIGURATION CRCC ................................................................................................................................................................................................................................... 26
10.7 ...... ELECTRICAL SPECIFICATIONS ................................................................................................................................................................................................................................................ 27
10.7.1 ........POWER SUPPLY 230V/1/50HZ – 400V/3N/50HZ ............................................................................................................................................................................................................ 27
10.7.2 ........POWER SUPPLY 230V/1/60HZ – 230V/3/60HZ ............................................................................................................................................................................................................... 28
10.7.3 ........POWER SUPPLY 380V/3/60HZ ........................................................................................................................................................................................................................................ 29
10.7.4 ........POWER SUPPLY 460V/3/60HZ ........................................................................................................................................................................................................................................ 30
11 .............. CONDENSATE DRAIN ................................................................................................................................................................................................................................................................. 31
12 .............. INSTRUMENTS AND ALARMS ................................................................................................................................................................................................................................................... 31
12.1 ...... CALIBRATING THE CONTROL AND SAFETY DEVICES ......................................................................................................................................................................................................... 31
12.2 ...... CALIBRATING THE DIRTY FILTER SENSOR ........................................................................................................................................................................................................................... 31
13 .............. OPERATION AND CONTROL ..................................................................................................................................................................................................................................................... 31
13.1 ...... ELECTRONIC EXPANSION VALVE............................................................................................................................................................................................................................................ 31
13.2 ...... MODULATING WATER VALVE ................................................................................................................................................................................................................................................... 32
13.3 ...... WATER VALVE – VALUE OF∆PS AND ∆PMAX ....................................................................................................................................................................................................................... 32
13.4 ...... 2-WAY ON/OFF VALVE (OPTIONAL) ......................................................................................................................................................................................................................................... 33
13.5 ...... TEMPERATURE AND HUMIDITY PROBE (OPTIONAL) ........................................................................................................................................................................................................... 33
13.6 ...... FLOW METER (OPTIONAL) ........................................................................................................................................................................................................................................................ 33
14 .............. OPTIONAL .................................................................................................................................................................................................................................................................................... 35
14.1 ...... MAINS ANALYZER....................................................................................................................................................................................................................................................................... 35
14.2 ...... DUAL POWER SUPPLY............................................................................................................................................................................................................................................................... 35
14.3 ...... ELECTRIC HEATERS .................................................................................................................................................................................................................................................................. 35
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 2 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Index
14.4 ...... HUMIDIFIER .................................................................................................................................................................................................................................................................................. 35
14.4.1 ........SYSTEM COMPONENTS .................................................................................................................................................................................................................................................. 35
14.4.2 ........HUMIDIFIER OPERATING PRINCIPLE ............................................................................................................................................................................................................................ 36
14.4.3 ........STEAM CYLINDER ............................................................................................................................................................................................................................................................ 36
14.4.4 ........FILL AND DRAIN ASSEMBLIES ........................................................................................................................................................................................................................................ 36
14.4.5 ........HUMIDIFIER POWER SUPPLY ......................................................................................................................................................................................................................................... 36
14.5 ...... HUMIDIFIER AND CONDENSATE DRAIN.................................................................................................................................................................................................................................. 37
14.6 ...... CONDENSATE DRAIN PUMP AND HUMIDIFIER DRAIN PUMP.............................................................................................................................................................................................. 37
14.7 ...... STD CONDENSATE DRAIN PUMP (LOW WATER TEMPERATURE) ..................................................................................................................................................................................... 37
14.8 ...... CONDENSATE DRAIN PUMP FOR HIGH WATER TEMPERATURE (HUMIDIFIER) .............................................................................................................................................................. 38
15 .............. MAINTEINANCE ........................................................................................................................................................................................................................................................................... 39
15.1 ...... REPLACING THE FANS .............................................................................................................................................................................................................................................................. 39
15.2 ...... CLEANING THE AIR FILTER ....................................................................................................................................................................................................................................................... 39
15.3 ...... CHECKING AND CLEANING THE CONDENSER COILS ......................................................................................................................................................................................................... 39
15.4 ...... CHECKING AND CLEANING THE DRAINS ............................................................................................................................................................................................................................... 39
15.5 ...... GENERAL EXAMINATION OF OPERATION .............................................................................................................................................................................................................................. 39
15.6 ...... VISUAL CHECK OF THE CONDITION OF THE PRESSURISED CONTAINERS .................................................................................................................................................................... 39
16 .............. DISPOSAL OF THE MACHINE .................................................................................................................................................................................................................................................... 40
17 .............. TROUBLESHOOTING .................................................................................................................................................................................................................................................................. 41
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 3 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC General Requirements
1. GENERAL REQUIREMENTS
BEFORE CARRYING OUT ANY OPERATION ON THE MACHINE READ THIS MANUAL CAREFULLY AND MAKE SURE YOU UNDERSTAND
ALL INDICATIONS AND INFORMATION CONTAINED IN THE DOCUMENT
KEEP THIS DOCUMENT IN A KNOWN PLACE AND EASILY REACHABLE FOR THE WHOLE PERIOD OF THE MACHINE'S
OPERATIONAL LIFE.
Apart from adopting a good usage technique, the persons who receive this information must read it carefully and must implement it strictly.
The time devoted to the reading of this information will allow you to avoid any health and safety hazard, as well as any financial damage.
This information has been written by the manufacturer in its original language (Italian) as “ORIGINAL INSTRUCTION”.
The information is even available in English as “TRANSLATION OF ORIGINAL INSTRUCTION” and may be translated into other languages to meet any legislative and/or business requirements.
Even though this information does not fit the machine perfectly, this does not prejudice its function.
Keep this manual in a well-known and easily accessible place, so that it will be always available for future reference, when necessary.
The manufacturer reserves the right to modify the product without prior notice.
To highlight the most important sections of this text, some symbols have been adopted whose meaning is described below.
DANGER
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury
MANDATORY
Indicates that any unsafe practices must be avoided which could prejudice health and safety and cause financial damage
INFORMATION
Indicates any important technical information that must not be neglected
Manufacturer: is the company that has designed and built the machine in compliance with current laws and adopting all the rules of good construction techniques, paying attention to the safety and
health of people interacting with the machine.
Purchaser: he is responsible for any purchase and must supervise the organization and assignment of tasks, ensuring compliance with all applicable laws.
Owner: Legal representative of the company, body or natural person who owns the plant in which the machine is installed: he is responsible for checking compliance with all the safety regulations
indicated by this manual as well as by current national legislation.
Designer: a competent skilled person appointed and authorized to prepare a project that must consider all the legislative, regulatory, and workmanlike performance principles applicable to the plant.
In any case, apart from conforming to the manufacturer’s instructions, he must consider all safety-related matters for the people who must interact with the machine during its expected useful life.
Installer: a competent skilled person duly authorized and responsible for the setting-up of the machine/plant, according to project specifications and the manufacturer’s directions and in conformity
with the applicable industrial safety laws.
User: a person authorized to control the use of the machine according to the "instructions for use" and the industrial safety laws in force.
Carriers: those who deliver the machine using suitable means of transportation. They must load and position the machine properly, to prevent any sudden displacement during the transportation.
When any loading/unloading means are used, these must conform to the markings affixed on the machine to ensure their safety and for the safety of all the people who could interact with these
operations.
Handlers: they arrange the machine properly and affix all the necessary markings for safe and correct handling. On receipt of the machine, they ensure handling to the installation point, according to
the instructions affixed on it. All these operators must have adequate skills and must comply with the instructions provided for their safety and for the safety of the people who could interact with these
jobs.
Maintenance technician: Person authorized by the owner to perform on the machine all the adjustment and control operations specifically indicated in this manual, to which it must strictly follow,
limiting its action to what is clearly permitted.
Expert operator: a person appointed and authorized by the User or the Purchaser to proceed with the use of the machine and the relevant ordinary maintenance jobs, according to the
manufacturer’s instructions. In case of failures not covered by this manual, he must request the intervention of a skilled Engineer.
Skilled Engineer: Person authorized directly by the Manufacturer to carry out all the ordinary and extraordinary maintenance operations, as well as any adjustment, control, repair and replacement
of parts that may be necessary during the life of the machine.
Outside the Italian territory and in the countries where the Manufacturer is directly present with his own subsidiary, the Distributor is obliged, under his own complete responsibility, to equip himself
with adequate and proportional Technicians to the territorial extension and to the business.
Ordinary maintenance: all the jobs necessary for maintaining the machine in perfect working order. These jobs are scheduled by the manufacturer, who sets out the necessary core competences
and procedures.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 4 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC General Requirements
Extraordinary maintenance: all the jobs necessary for maintaining the machine in perfect working order. These jobs cannot be predicted, are not scheduled by the manufacturer and must be carried
out by a specialized Engineer only.
The installation of this machine within a plant requires a global project that considers all “workmanlike performance” requirements, as well as legislative and regulatory principles. Special care must
be devoted to all the technological instructions and information indicated by the manufacturer.
Do not tamper with, remove, or bypass the safety devices installed on the machine. Failure to meet this requirement will result in serious safety and health hazard to people.
The personnel that carries out any type of job during the life of the machine must be adequately qualified and skilled from a technical standpoint and must have gained experience in this specific
sector.
The lack of these requirements could prejudice the health and safety of people.
During the normal use or for any job on the machine, keep the perimeter space in adequate conditions, to prevent any safety and health hazard to people.
Some stages may require the help of one or more assistants. In these cases, we recommend that you train and inform them properly on the type of activity to be carried out, to prevent any safety and
health hazard to people.
Handle the machine according to the information provided directly on the packaging and in the instructions for use delivered by the manufacturer.
During handling, if necessary, seek the help of one or more assistants to receive adequate signals.
The personnel that loads, unloads and handles the machine must be adequately qualified, skilled, and experienced in this specific sector and must be in command of the lifting equipment to be used.
During the installation stage, respect the perimeter space indicated by the manufacturer, considering also any other surrounding activity. This requirement must be met also according to the applicable
industrial safety laws.
The installation and connections must be carried out, about the machine, according to the manufacturer’s instructions. The person responsible for these operations must consider also all the
applicable regulatory and legislative requirements, ensuring the workmanlike execution of the installation and connection jobs. Once the installation is completed and before starting the machine, he
must make sure, through a general check, that these requirements have been met.
If the machine is to be transferred using any means of transportation, check that these are fit for their intended use and load/ unload the machine in such a way that there is no hazard to the operator
and the people directly involved.
Before moving the machine using the said means of transportation, make sure that the machine and its components are anchored to such means firmly and that their profile does not exceed the
maximum fixed volume. If necessary, prepare the appropriate DANGERs.
The operator, apart from being well-informed about the use of the machine, must be properly qualified and experienced, based on the type of job to be effectuate.
Use the machine only for the purposes recommended by the manufacturer. Using the machine for any improper job may result in serious safety and health hazard and financial damage.
The machine has been designed and manufactured in such a way that it can satisfy all the working conditions indicated by the manufacturer.
Tampering with any device to obtain any different performance may result in safety and health hazard and financial damage.
Do not use the machine if the safety devices have not been perfectly installed and are not effective. Failure to meet this requirement may result in serious safety and health hazard.
Keep the machine in perfect working order, carrying out the scheduled maintenance jobs recommended by the manufacturer.
Proper maintenance will ensure better performance, longer life, and the constant maintenance of safety requirements.
Before carrying out any regulation and maintenance job on the machine, activate all the safety devices provided and consider whether the personnel involved and the operators nearby must be
informed properly or not. In particular, carefully indicate the neighbouring areas and prevent the access to all devices that, if activated, are likely to cause unpredictable dangers, causing damage to
people’s safety and health.
The regulation and maintenance jobs must be effectuating by authorized operators, who must arrange all the necessary safety conditions, according to the procedures indicated by the manufacturer.
All maintenance jobs that require any specific technical skill or expertise must be carries out only by qualified personnel, adequately experienced in the relevant sector of intervention.
To carry out any maintenance jobs in areas that are difficult of access or dangerous, ensure proper safety conditions for yourself and for other people, according to the applicable industrial safety laws.
Replace any worn components with original spare parts only. Use the components recommended by the manufacturer, so as to ensure the machine performance and the expected safety level.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 5 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC General Requirements
Prevention of residual electrical risks
• disconnect the machine from the mains using the external disconnector before opening the electrical panel;
• verify the correct grounding of the machine before starting it;
• the machine must be installed in a suitable place; if it is intended for indoor use, it cannot be installed outdoors;
• do not use cables with inadequate section or non-compliant connections even for limited periods or for emergencies;
• in case of a machine with power factor correction capacitors, wait 3 minutes, since the power supply to the machine has been removed, before accessing the electrical panel.
Refrigerant gas:
The refrigerant circuit contains fluorinated greenhouse gases covered by the Kyoto Protocol.
The fluorinated greenhouse gases contained in the refrigeration circuit cannot be discharged into the atmosphere.
The refrigerant gas must be recovered in accordance with the regulations in force.
Lubricating oil:
The compressors and the refrigerant circuit contain lubricating oil.
The oil must be recovered in accordance with the regulations in force.
Do not dispose of oil in the environment.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 6 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC General Requirements
1.2 MACHINE IDENTIFICATION
1.2.1 NOMENCLATURE AND IDENTIFICATION LABEL
Nomenclature: The alphanumeric code of the machine model, shown on the identification plate, represents precise technical specifications that are indicated in the figure shown.
Identification label: The type of machine is shown on the label applied directly on the machine, normally inside the panel of the electrical panel. It contains the references and all the information
necessary for safe operation.
NOMENCLATURE IDENTIFICATION LABEL
Type Modèle
CRC Series identification Modello Modelo
Model Typ
CRCC: air conditioner for chilled water feeding; Item Article
CRCX: direct expansion air conditioner with scroll BLDC inverter compressors; Articolo
Einzelteil
Articulo
Produktkodning
CRCD: direct expansion air conditioner with Dual Fluid system; Serial number Matricule unitè
Matricola unità Matricula unidad
Seriennummer Seriennummer
Air flow Manufact. Year
Anno di costruz.
Anneé construction
Año de costrucción
I IN-ROW air flow Baujahr Tillverkningsår
Operating weight Poids en fonction.
E ENCLOSURE air flow Peso di funzionam. Peso en funcionam.
Betriebsgewicht Driftsvikt
Refrigerant Gaz réfrigérant
0051 Model Gas refrigerante Gas refrigerante
Kältemittel Köldmedium
GWP 100
Circuits Refr. charge Q.té gaz réfrig.
BASIC Single refrigerant circuit (CRCX, CRCD version); Carica refrigerante
Füllgewicht
Carga refrigerante
Köldmediefyllining
Single hydraulic circuit (CRCC, CRCD version); CO2 T
DUAL Double hydraulic circuit (version CRCC). ELECTRICAL SUPPLY
Auxiliary
Main
F. L. I. kW
Water circuit:
Manual n.:
Wiring diagrams:
INFORMATION
Tampering with or the removal or absence of rating plates or other means enabling the unit to be identified causes problems during installation and
maintenance.
2 OPERATING LIMITS
The units are designed for operation within the following operating ranges (the limits are considered for new units that have been correctly installed and maintained):
OPERATING RANGE
INROW ENCLOSURE
CRCX – CRCD / i-HCAT
Room air temperature 23°C/53% r.h.÷ 40°C/20% r.h. 30°C/35% r.h.÷ 50°C/12% r.h.
Outside air temperature -20°C ÷ 45°C (with i-HCAT BASIC version)
-35°C ÷ 45°C (with i-HCAT LT version)
CRCC
Room air temperature 16°C/82% r.h ÷ 55°C/7% r.h.
Water inlet temperature 6°C ÷ 16°C delta T 3°C ÷ 10°C
Maximum operating pressure in the chilled water circuit 16 bar
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 7 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Receipt, transport and handling
3 CONFIGURATIONS
The desired configuration must be selected during the order phase.
H H H
P L P
P
L L
(*) Increased frame dimensions for in-row version with frontal air delivery. Optional mandatory for in-row version with frontal air delivery with Humidifier (optional) and/or electric heater (optional) for
models 0021, 0051, 0071, 0121.
P
L
DIMENSIONS
L (mm) 300 600
P (mm) 1200
H (mm) 2085
FRAGILE: handle with care. TOP: indicates the correct position of the packaged unit.
CENTRE OF GRAVITY: indicates the centre of gravity of the USE NO HOOK: indicates that hooks cannot be used to handle or
packaged unit. lift the packaged unit.
KEEP AWAY FROM HEAT: indicates that the packaged unit must
be kept away from sources of heat. DO NOT STACK the packages
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 8 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Receipt, transport and handling
4.1 STANDARD PACKAGING – INDOOR UNIT
RACK X 1000 X 42U
CRCC-I 0020 0025 0035 0036 0038 0040 0050 0060 0055
L mm 1100 1100 1100 1100 1100 1100 1100 1100 1100
H mm 2248 2248 2248 2248 2248 2248 2248 2248 2248
P mm 800 800 800 800 800 800 800 800 800
Weight Kg 205 207,5 210 220 220 250 255 262 270
Net weight Kg 190 192,5 195 205 205 235 240 247 255
CRCC-I
0020 0025 0035 0036 0038 0040 0050 0060 0055
CRCC-E
L mm 1300 1300 1300 1300 1300 1300 1300 1300 1300
H mm 2248 2248 2248 2248 2248 2248 2248 2248 2248
P mm 800 800 800 800 800 800 800 800 800
Weight Kg 215 218 220 230 230 275 280 287 295
Net weight Kg 200 202,5 205 215 215 260 265 272 280
CRCC-I 0020 0025 0035 0036 0038 0040 0050 0060 0055
L mm 1130 1130 1130 1130 1130 1130 1130 1130 1130
H mm 2320 2320 2320 2320 2320 2320 2320 2320 2320
P mm 830 830 830 830 830 830 830 830 830
Weight Kg 250 253 255 265 265 295 300 307 315
Net weight Kg 190 192,5 195 205 205 235 240 247 255
CRCC-I
0020 0025 0035 0036 0038 0040 0050 0060 0055
CRCC-E
L mm 1330 1330 1330 1330 1330 1330 1330 1330 1330
H mm 2320 2320 2320 2320 2320 2320 2320 2320 2320
P mm 830 830 830 830 830 830 830 830 830
Weight Kg 260 263 265 275 275 320 325 332 340
Net weight Kg 200 202,5 205 215 215 260 265 272 280
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 9 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Receipt, transport and handling
INFORMATION
Do not repeatedly bend the metal slides to prevent them from breaking (max 5 times).
ATTENTION
All handling operations must be carried out by 2 people
5,6,7 Slowly slide the unit long the slides until vertical and completely resting on the floor.
ATTENTION
When the unit starts tilting the weight needs to be supported by the operators and movements managed from the side of the unit. It is very dangerous to
support the unit from the front (see crossed out picture)
Size i-HCAT
0021 0051 0071 0121
L mm 1035 1035 1630 1630
P mm 540 485 650 650
H mm 1123 1390 1400 1900
Gross weight Kg 115 123 205 270
Net weight Kg 100 108 190 255
To lift and move the unit, use metal tubes (max dia. 1/2"), inserting them in the feet
provided, and same-length lifting cables
BARCODE
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 10 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Receipt, transport and handling
Size i-HCAT
0151 0251
A mm 1825 2395
B mm 1195 1195
H mm 1865 1865
Weight Kg 440 500
To lift and move the unit, USE 4 SAME-LENGTH LIFTING CABLES (min. 3000)
The unit must be handled by qualified and suitably equipped personnel only using equipment appropriate for the weight of the condensing unit.
If a forklift truck is used, insert the forks under the base, spacing the forks as wide apart as possible.
If a crane is used, pass the cables through the bottom of the base, making sure they do not exert pressure on the unit.
ATTENTION
Do not dispose of packaging materials in the environment or leave them within reach of children as they may represent a hazard.
ATTENTION
The weight of the condensing unit is biased towards the compressor side (side of the packaging with the bar code, see the figure).
During transport, the condensing unit should be kept in a vertical position.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 11 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Overview diagram
5 OVERVIEW DIAGRAM
5.1 CRCC
SINGLE HYDRAULIC CIRCUIT – BASIC VERSION DOUBLE HYDRAULIC CIRCUIT – DUAL VERSION
Models 0020, 0025, 0035, 0038, 0040, 0050, 0060 Models 0036, 0055
LEGENDA
Direction of
MV 3-way modulating valve
Air flow
OV 2-way on/off 2 valve (optional)
BA Heat exchanger
TW Water temperature probe
MP Water flow meter (optional)
Direction of TI Air intake temperature probe
Air flow TO Air outlet temperature probe
V Fans
Water
Water Water Water
out
in out in
5.2 CRCX
5.2.1 REFRIGERANT DIAGRAM – INDOOR UNIT – CRCX
INDOOR UNIT
1. Refrigerant connection
2. High pressure transducer
3. Electronic expansion valve
4. Fans
5. Evaporator
6. Low pressure switch – automatic reset
7. Low pressure transducer
8. Temperature probe
9. Refrigerant Connection
10. Pressure test fitting 5/6 SAE
11. Air intake temperature probe
12. Air outlet temperature probe
OUTDOOR UNIT
1 Refrigerant connection
2 Pressure test fitting 5/16 SAE
3 Compressor
4 Sump oil heater
5 Oil separator
6 Mesh filter
7 Capillary tube
8 High pressure switch
9 Condenser
10 Fan
11 Liquid receiver
12 Filter drier
13 Liquid and moisture indicator
14 Outside air temperature probe
15 Refrigerant Connection
16 Capillary tube (for models 0071, 0121, 0151, 0251)
17 Liquid separator (for models 0071, 0121, 0151, 0251)
18 Non-return valve
19 Solenoid valve (for model 0151, 0251)
20 Temperature probe
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 12 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Overview diagram
5.3 CRCD
5.3.1 REFRIGERANT / HYDRAULIC DIAGRAM – INDOOR UNIT – CRCD
OUTDOOR UNIT
1 Refrigerant connection
2 Pressure test fitting 5/16 SAE
3 Compressor
4 Sump oil heater
5 Oil separator
6 Mesh filter
7 Capillary tube
8 High pressure switch
9 Condenser
10 Fan
11 Liquid receiver
12 Filter drier
13 Liquid and moisture indicator
14 Outside air temperature probe
15 Refrigerant connection
16 Capillary tube (for model 0071)
17 Liquid separator (for model 0071)
18 Non-return valve
19 Temperature probe
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 13 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Overview diagram
5.4 I-HCAT LT
5.4.1 REFRIGERANT DIAGRAM – OUTDOOR MOTOCONDENSING UNIT – i-HCAT LT
REFRIGERANT DIAGRAM – OUTDOOR MOTOCONDENSING UNIT – LT VERSION – 0071 – 0121 – 0151 - 0251
OUTDOOR UNIT
1 Refrigerant connection 12 Filter drier.
2 Pressure test fitting 5/16 SAE. 13 Liquid and moisture indicator.
3 Compressor. 14 Outside air temperature probe.
4 Sump oil heater. 15 Refrigerant connection
5 Oil separator. 16 Liquid separator.
6 Mesh filter. 17 Pressure regulating valve.
7 Capillary tube. 18 Non return valve.
8 High pressure switch. 19 Solenoid valve.
9 Condenser. 20 Safety valve.
10 Fan. 21 Temperature probe.
11 Liquid receiver.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 14 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Installation
6 INSTALLATION
6.1 CRC
The CRC indoor unit can rest directly on the floor, perfectly level, using the adjustable feet: incorrect levelling may cause condensate to overflow from the collection pan.
ATTENTION
The air-conditioner must be installed indoors and in non-aggressive environments.
MEHITS accepts no liability for incorrect installation when positioning the unit.
6.2 i-HCAT
Before installing the i-HCAT unit, verify the following points:
- check that the support surface is adequate to support the weight of the unit.
- respect safety distances between the unit and other equipment or structures so that the fan air intake and outlet are not blocked in any way.
- the unit must be placed in an equipment compartment sized according to standards in force in the country concerned, and large enough to allow access for maintenance.
6.3 POSITIONING
Before handling the unit, check the capacity of the lifting equipment used, respecting the instructions on the packaging.
To move the unit horizontally, make appropriate use of a fork lift truck or similar, bearing in mind the weight distribution of the unit.
To lift the unit, insert pipes long enough to allow positioning of the lifting slings and safety pins in the special holes in the base of the unit.
To avoid the slings damaging the unit, place protection between the slings and the unit.
Position the unit in the site indicated by the customer; place either a layer of rubber (min. thickness 10 mm) or vibration damper feet between the base and support surface.
Fix the unit, making sure it is level and that there is easy access to refrigerant and electrical components.
If the site is installed in a place exposed to strong winds, fix the unit adequately using tie rods if necessary.
6.4 CLEARANCE
6.4.1 CLEARANCE – i-HCAT - 0021-0051-0071-0121
SUPPORTING BASEMENT
SPAZIO DI RISPETTO
MINIMUM CLEARANCE
Size i-HCAT
0151 0251
R1 mm 1000 1000
R2 mm 1000 1000
R3 mm 1000 1000
R4 mm 1000 1000
SPAZIO DI RISPETTO
MINIMUM CLEARANCE
TOP VIEW
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 15 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Installation
6.5 RECOMMENDED INSTALLATION FOR CRCX-CRCD / i-HCAT
MANDATORY
CARRY OUT PIPING WITH SLOPES INDICATED TO FAVOR THE
RETURN OF THE LUBRICANT OIL TO THE COMPRESSOR
LEGENDA
1. Air conditioner – indoor unit
2. Condensing unit – outdoor unit
3. Liquid line
4. Suction line
5. Trap. Foresee a trap every 5m of the rising pipe.
MANDATORY
INSULATE THE SUCTION PIPE
INFORMATION
Create traps as shown in the figure, making sure to fill them with oil when commissioning the system.
The liquid pipes must be protected against sunlight
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 16 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
COOLSIDE Refrigerant connections
7 REFRIGERANT CONNECTIONS
7.1 REFRIGERANT CONNECTIONS (CRCX-CRCD / i-HCAT)
MANDATORY
The execution of the refrigerant connection must be carried out by qualified personnel.
All the works, the choice of the components and the materials used must be carried out in compliance with the "Good Rule", according to the regulations
in force in the various countries taking into account the operating conditions and uses to which the plant is intended. Errors in the design and / or
execution of the refrigerant connection can cause irreparable damage to the compressor or malfunctions of the machine. The moto-condensing unit is
delivered with a minimum refrigerant charge. The refrigerant charge must be carried out on site by the customer. Do not open the taps of the moto-
condensing unit during the realization of the refrigerant line with the indoor evaporating unit.
INVERTER COMPRESSOR
Nominal EQUIVALENT LENGHT [m] FOR INVERTER COMPRESSORS R410A
Model Line diameter
Ø 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Gas 5/8" 16 16 16 16 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
0021
Liquid 3/8" 10 10 10 10 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
Gas 18mm 18 18 18 18 18 18 18 22 22 22 22 22 22 22 22 22 22 22 22 22
0051
Liquid 12mm 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
Gas 22mm 18 18 18 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22
0071
Liquid 16mm 12 12 12 12 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Gas 28mm 22 22 22 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28
0121
Liquid 18mm 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
Gas 28mm 22 22 28 28 28 28 28 35 35 35 35 35 35 35 35 35 35 35 35 35
0151
Liquid 18mm 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
Gas 35mm 28 28 28 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
0251
Liquid 22mm 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22
For equivalent lengths over 100m, please contact the Manufacturer's Sales Office.
INVERTER COMOPRESSOR
Nominal EQUIVALENT LENGHT [ft] FOR INVERTER COMPRESSORS R410A
Model Line diameter
15 35 50 65 80 100 115 130 150 165 180 195 215 230 245 260 280 295 310 330
Ø
Gas 5/8" 5/8" 5/8" 5/8" 5/8" 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
0021
Liquid 3/8" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Gas 18mm 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"
0051
Liquid 12mm 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Gas 22mm 3/4” 3/4” 3/4” 3/4” 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"
0071
Liquid 16mm 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8”
Gas 28mm 7/8" 7/8" 7/8" 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8”
0121
Liquid 18mm 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
Gas 28mm 7/8” 7/8” 1 1/8” 1 1/8” 1 1/8” 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
0151
Liquid 18mm 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
Gas 35mm 1 1/8” 1 1/8” 1 1/8” 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
0251
Liquid 22mm 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8”
For equivalent lengths over 330ft please contact the Manufacturer's Sales Office.
INFORMATION
The diameter of the refrigerant lines between the air-conditioner and the condensing unit must be sized according to the length, and therefore these will not
always match the inside diameter of the weld fittings supplied by the manufacturer.
The pressure drops generated in the connecting pipes in the machines in two sections, cause a reduction in the cooling capacity and an increase in the
electrical energy required by the compressor to perform its work.
Special care must be taken when insulating the suction line pipes, to avoid formation of condensate.
Check and make sure the indoor thermal heat load is never less than 30-35% of the air-conditioning capacity installed.
ATTENTION
The piping installed by the installer to connect the indoor unit to the outdoor unit must undergo pressure strength testing (in accordance with EN378§6.3.3)
and tightness testing (in accordance with EN378§6.3.4). The tests must be documented. The pressure used for pressure strength testing depends on the
category of piping and the maximum allowable pressure shown on the unit's rating plate: Cat. I or lower, test pressure at least 1.10 X PS
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 17 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
COOLSIDE Refrigerant connections
7.3 EQUIVALENT LENGHT IN METERS OF CURVED SECTIONS, ON-OFF AND NON RETURN VALVE
External pipe diameter inch 1/4" 3/8" 1/2" 5/8" 3/4" 7/8" 1" 1 1/8" 1 3/8"
Liquid (1) gr/m 14 66 83 140 211 297 398 --- ---
Gas (2) gr/m --- --- 8 13 20 28 38 45 70
INFORMATION
Add lubricating oil equivalent to 10% of the weight of the gas calculated only for the refrigerant connection lines between indoor and outdoor unit.
INFORMATION
Flaring the pipes directly helps limit impurities inside the lines. All the pipes must be perfectly clean (clean using nitrogen or dry air before connecting to the two units)
and free from moisture to allow efficient venting.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 18 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Commissioning and testing
ON
OFF
ON
OFF
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 19 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Water connections
8.5 STARTING AND STOPPING THE UNIT
Move remote switch SA1 (if featured) on the ON position. ON
- The operations for STARTING and STOPPING the unit are controlled by the combined CRC indoor unit.
CRCC
When power is supplied to the unit, wait around 35 seconds (time taken for the program to load) and then start the unit from the keypad (ENTER + USER PASSWORD) and the fans will start
automatically.
Make sure that the chilled water valve is working correctly;
Check that the sections of corrugated pipe for draining condensate have been filled with water during installation.
INFORMATION
The flexible connections available in the price list are PN10.
- joints in three pieces, near the fittings, to simplify the removal of the unit;
- on-off valves to disconnect the unit from the water circuit: where possible use ball valves with full opening to minimise
pressure drop.
The water pipes can be connected either from the top or the bottom. On the side uses, remove the cap from the inlet and out- let
manifolds and connect the flexible piping.
Make sure that the cross-section of the chilled waterlines and the characteristics of the circulating pump are suitable: an insufficient
water flow-rate affects performance of the air-conditioner. Check that the water inlet and outlet connections are correct.
Insulate all the chilled water lines with closed cell material (e.g.: Armaflex or equivalent), to prevent condensation; the insulation
must allow access to the valves and the three-piece joints.
Make sure that the water circuit has been filled with an antifreeze mixture containing the right percentage of ethylene glycol.
INFORMATION
To select the pipes see the tables on “Continuous pressure drop for STEEL PIPES”
Make sure that the water contained in the water circuit meets the following requirements throughout the entire life of the system:
Explanatory notes:
ref.1: A greater concentration of hydrogen ions (pH) than 9 implies a high risk of deposits, whereas a lower pH than 7 implies a high risk of corrosion.
ref.2: The hardness measures the amount of Ca and Mg carbonate dissolved in the water with a temperature lower than 100°C (temporary hardness). A high hardness implies a high
risk of deposits.
ref.3: The concentration of chloride ions with higher values than those indicated causes corrosion.
ref. 4 - 5 - 8: The presence of iron and manganese ions and oxygen leads to corrosion.
ref.6 - 7: Carbon dioxide and hydrogen sulphide are impurities that promote corrosion.
ref.9: Usually in water from the waterworks it is a value of between 0.2 and 0.3 ppm. High values cause corrosion.
ref.10: The presence of ammonia reinforces the oxidising power of oxygen
ref.11: Below the value shown in the table, there is a risk of corrosion due to the trigger of galvanic currents between copper and other less noble metals.
Values of the parameters outside the indicated ranges can lead to the formation of deposits and limescale and/or favour corrosive phenomena within the plant. For operating fluids other than water
(mixtures of ethylene and propylene glycol) it is recommended to use specific inhibitors, designed to offer thermal stability within the operating temperature range and protection against corrosion. It
is necessary that, in the presence of dirty and / or aggressive waters, an intermediate heat exchanger is installed upstream of the heat exchangers.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 20 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Water connections
9.1 CORRECTION FACTOR
9.1.1 ETHYLENE GLYCOL SOLUTIONS
Water and ethylene glycol solutions used as a heat carrier in the place of water reduce the performance of the unit. Multiply the performance figures by the values given in the following table.
Continuous pressure drop for STEEL PIPES (inches) – Water temperature = 10°C
Water flow, l/h
SELECTION EXAMPLE:
• consider a limit speed inside the pipe of 1-1,2m/s
• cross-reference the required water flow-rate (in the example 5.000 l/h)
• determine the pressure drop according to the selected diameter (in the example 35mm c.a./m)
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 21 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10 ELECTRICAL CONNECTIONS
ATTENTION
All work must be performed, components selected and materials used in complete accordance with the legislation in force in material in the country
concerned, and considering the operating conditions and intended uses of the system, by qualified personnel.
CRCX-CRCD / i-HCAT
ATTENTION
Before performing any work on the electrical parts, make sure that there is no live voltage and that the disconnecting switch on the i-HCAT is open (in
position “O”).
The condensing units leave the factory fully wired and simply require connection to the mains power supply and the remote switch (ON OFF), operations that must be carried out by qualified
personnel in compliance with current legislation. For all electrical work, refer to the electrical wiring diagrams in this manual. It is also recommended to check that:
- The characteristics of the mains electricity supply are adequate for the power ratings indicated in the electrical specifications below, also bearing in mind the possible use of other equipment at
the same time.
ATTENTION
Power to the unit must be turned on only after installation work (refrigerant circuit and electrical) has been completed.
All electrical connections must be carried out by qualified personnel in accordance with legislation in force in the country concerned.
Respect instructions for connecting phase, neutral and earth conductors. The power line should be fitted upstream with a suitable device to protect against short-circuits
and leakage to earth, isolating the installation from other equipment.
Voltage must be within a tolerance of ±10% of the rated power supply voltage for the unit (for three phase units, the unbalance between the phases must not exceed
2%). If these parameters are not respected, contact the electricity supply company.
For electrical connections use double insulation cable in conformity with legislation in force in the country concerned
If local and national standards require installation of a residual current circuit breaker upstream, use a type B device with threshold Id=300 mA.
Choose a model that features:
- High frequency current filtering
- Timer to help prevent disconnection due to the load of stray capacitance on start-up.
Before starting the unit, check the tightness of all the electrical connections and cables on the unit, as these may have come loose during handling and
transport.
If these devices are not visible from the electrical panel of the unit, they should be lockable
An effective earth connection is obligatory.
The manufacturer cannot be held liable for any damage caused by the failure to correctly earth the unit.
In the case of three phase units, ensure the phases are connected correctly.
ATTENTION
Do not use water pipes to earth the unit.
Before performing any work on the electrical parts, make sure that there is no live voltage.
Check that the mains voltage corresponds to the rated values for the unit (voltage, no. of phases, frequency) shown on the electrical panel. The power
supply voltage must be between ± 10% of the rated value: operation at voltages outside of these limits may void the warranty.
Connect the power cable to the IEC male plug supplied with the (see the photo on the side) and plug this into socket "P", shown in the figure,
located on the top of the unit.
Also connect the signal and auxiliary cable (as indicated on the wiring diagram supplied with the unit) to connector S on the top of the unit.
ATTENTION
- terminals that are not adequately tight may generate heat and sparks, causing fire.
- use suitably rated power supply cables.
- cables that are too small and undersized may generate heat and cause fires.
- do not run signal cables together with high voltage power cables (AC220-240V or higher), as interference may cause operating problems.
- do not lay low voltage cables together (30 Vdc or lower), as the interference from these cables may cause malfunctions.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 22 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
Signal (A)
auXiliary (D)
Use specific cables for wiring. Tightly secure the electrical connections and prevent any forces exerted on the cables being applied to the terminals
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 23 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10.3 CONNECTION CONFIGURATION - CRCX/CRCD 0021-0051-0071-0121
POWER TRANSDUCER KIT (#1)+
HEATERS AND/OR HUMIDIFIER POWER TRANSDUCER KIT (#1)+
STANDARD DUAL POWER SUPPLY KIT (#2)+
DUAL POWER SUPPLY KIT (#2) HEATERS AND/OR HUMIDIFIER
ATTENTION
KEEP SIGNAL CABLES AND POWER CABLES SEPARATE
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 24 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10.5 ELECTRICAL CONNECTIONS CRCX/CRCD 0021-0051-0071-0121
i-HCAT
TERMINALS
SIGNAL
CABLES
POWER
CABLES
CRCX/CRCD
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 25 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10.6 CONNECTION CONFIGURATION CRCC
STANDARD
CRCC
HEATERS AND/OR HUMIDIFIER POWER TRANSDUCER KIT
TERMINALS POWER SUPPLY
WITH/WITHOUT HEATERS
POWER TRANSDUCER KIT
AND/OR HUMIDIFIER
POWER TRANSDUCER KIT +
HEATERS AND/OR HUMIDIFIER
CRCC CRCC
SIGNAL
CABLES POWER
CABLES
TERMINALS
DATA CENTER
MANAGER
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 26 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10.7 ELECTRICAL SPECIFICATIONS
The cross section of the power cable must be chosen according to the length of the cable and the type of installation, based on the maximum current draw of the air-conditioner and so as to prevent
excessive voltage drops (the power supply voltage must be between ± 10% of the rated value).
POWER SUPPLY
CRC Evaporator fans STD heaters HIGH POWER heaters Humidifier STD heater + humidifier HP heaters + Humidifier
V/Ph/Hz
FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A)
CRCC 20 230/1/50 0,51 4,35 2,91 14,78 4,11 20,00 2,76 14,15 5,16 24,58 6,36 29,80
CRCC 25 230/1/50 0,68 5,80 3,08 16,23 4,28 21,45 2,93 15,60 5,33 26,03 6,53 31,25
CRCC 35 230/1/50 0,85 7,25 4,45 22,90 5,65 28,12 3,10 17,05 6,70 32,70 7,90 37,92
CRCC 36 230/1/50 0,85 7,25 4,45 22,90 5,65 28,12 3,10 17,05 6,70 32,70 7,90 37,92
CRCC 38 230/1/50 0,85 7,25 4,45 22,90 5,65 28,12 3,10 17,05 6,70 32,70 7,90 37,92
CRCC 40 400/3N/50 2,64 4,20 8,04 11,99 9,84 14,59 4,89 7,40 10,29 15,19 12,09 17,79
CRCC 50 400/3N/50 2,64 4,20 8,04 11,99 9,84 14,59 4,89 7,40 10,29 15,19 12,09 17,79
CRCC 60 400/3N/50 3,96 6,30 11,16 16,69 14,76 21,89 6,21 9,50 13,41 19,89 17,01 25,09
CRCC 55 400/3N/50 3,96 6,30 11,16 16,69 14,76 21,89 6,21 9,50 13,41 19,89 17,01 25,09
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 27 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10.7.2 POWER SUPPLY 230V/1/60HZ – 230V/3/60HZ
Evaporator fans STD electric heaters HIGH POWER electric heaters Humidifier
CRC V/Ph/Hz FLI FLA No. FLI FLA No. FLI FLA FLI FLA
V/Ph/Hz qty V/Ph/Hz V/Ph/Hz V/Ph/Hz qty kg/h
(kW) (A) elements (kW) (A) elements (kW) (A) (kW) (A)
CRCC 20 230/1/60 230/1/60 3 0,17 1,45 230/3/60 4 0,60 2,61 230/3/60 6 0,60 2,61 230/3/60 1 2,25 9,80 3
CRCC 25 230/1/60 230/1/60 4 0,17 1,45 230/3/60 4 0,60 2,61 230/3/60 6 0,60 2,61 230/3/60 1 2,25 9,80 3
CRCC 35 230/1/60 230/1/60 5 0,17 1,45 230/3/60 6 0,60 2,61 230/3/60 8 0,60 2,61 230/3/60 1 2,25 9,80 3
CRCC 36 230/1/60 230/1/60 5 0,17 1,45 230/3/60 6 0,60 2,61 230/3/60 8 0,60 2,61 230/3/60 1 2,25 9,80 3
CRCC 38 230/1/60 230/1/60 5 0,17 1,45 230/3/60 6 0,60 2,61 230/3/60 8 0,60 2,61 230/3/60 1 2,25 9,80 3
CRCC 40 230/3/60 230/3/60 3 1,00 2,90 230/3/60 9 0,60 2,61 230/3/60 12 0,60 2,61 230/3/60 1 2,30 5,60 3
CRCC 50 230/3/60 230/3/60 4 1,00 2,90 230/3/60 9 0,60 2,61 230/3/60 12 0,60 2,61 230/3/60 1 2,30 5,60 3
CRCC 60 230/3/60 230/3/60 5 1,00 2,90 230/3/60 12 0,60 2,61 230/3/60 18 0,60 2,61 230/3/60 1 2,30 5,60 3
CRCC 55 230/3/60 230/3/60 5 1,00 2,90 230/3/60 12 0,60 2,61 230/3/60 18 0,60 2,61 230/3/60 1 2,30 5,60 3
POWER SUPPLY
i-HCAT STD condenser fans EC condenser fans
V/Ph/Hz
FLI (kW) FLA (A) SA [A] FLA (A) FLI (kW) SA [A]
0021 230/1/60 5,76 17,90 3,7 5,7 18,00 3,8
0051 230/1/60 6,12 19,52 5 5,81 18,80 4
POWER SUPPLY
CRC Evaporator fans STD heaters HIGH POWER heaters Humidifier STD heater + humidifier HP heater + humidifier
V/Ph/Hz
FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A)
CRCC 20 230/1/60 0,51 4,35 2,91 14,78 4,11 20,00 2,76 14,15 5,16 24,58 6,36 29,80
CRCC 25 230/1/60 0,68 5,80 3,08 16,23 4,28 21,45 2,93 15,60 5,33 26,03 6,53 31,25
CRCC 35 230/1/60 0,85 7,25 4,45 22,90 5,65 28,12 3,10 17,05 6,70 32,70 7,90 37,92
CRCC 36 230/1/60 0,85 7,25 4,45 22,90 5,65 28,12 3,10 17,05 6,70 32,70 7,90 37,92
CRCC 38 230/1/60 0,85 7,25 4,45 22,90 5,65 28,12 3,10 17,05 6,70 32,70 7,90 37,92
CRCC 40 230/3/60 3,00 8,70 8,40 22,26 10,20 26,77 5,30 14,30 10,70 27,86 12,50 32,37
CRCC 50 230/3/60 4,00 11,60 9,40 25,16 11,20 29,67 6,30 17,20 11,70 30,76 13,50 35,27
CRCC 60 230/3/60 5,00 14,50 12,20 32,57 15,80 41,61 7,30 20,10 14,50 38,17 18,10 47,21
CRCC 55 230/3/60 5,00 14,50 12,20 32,57 15,80 41,61 7,30 20,10 14,50 38,17 18,10 47,21
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 28 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10.7.3 POWER SUPPLY 380V/3/60HZ
Evaporator fans STD electric heaters HIGH POWER electric heaters Humidifier
CRC V/Ph/Hz FLI FLA No. FLI FLA No. FLI FLA FLI FLA
V/Ph/Hz qty V/Ph/Hz V/Ph/Hz V/Ph/Hz qty kg/h
(kW) (A) elements (kW) (A) elements (kW) (A) (kW) (A)
CRCC 20 230/1/60 230/1/60 3 0,17 1,45 380/3/60 4 0,60 2,73 380/3/60 6 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 25 230/1/60 230/1/60 4 0,17 1,45 380/3/60 4 0,60 2,73 380/3/60 6 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 35 230/1/60 230/1/60 5 0,17 1,45 380/3/60 6 0,60 2,73 380/3/60 8 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 36 230/1/60 230/1/60 5 0,17 1,45 380/3/60 6 0,60 2,73 380/3/60 8 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 38 230/1/60 230/1/60 5 0,17 1,45 380/3/60 6 0,60 2,73 380/3/60 8 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 40 380/3/60 380/3/60 2 1,32 2,10 380/3/60 9 0,60 2,73 380/3/60 12 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 50 380/3/60 380/3/60 2 1,32 2,10 380/3/60 9 0,60 2,73 380/3/60 12 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 60 380/3/60 380/3/60 3 1,32 2,10 380/3/60 12 0,60 2,73 380/3/60 18 0,60 2,73 380/3/60 1 2,11 3,40 3
CRCC 55 380/3/60 380/3/60 3 1,32 2,10 380/3/60 12 0,60 2,73 380/3/60 18 0,60 2,73 380/3/60 1 2,11 3,40 3
POWER SUPPLY
i-HCAT
STD condenser fans EC condenser fans
V/Ph/Hz
FLI (kW) FLA (A) SA [A] FLA (A) FLI (kW) SA [A]
0071 380/3/60 10,76 22,95 8 10,79 23,13 9
0121 380/3/60 17,53 31,68 23 17,59 32,04 23
0151 380/3/60 14,84 27,54 51 14,72 29,82 53
0251 380/3/60 21,28 40,22 54 21,09 43,64 57
POWER SUPPLY
CRC Evaporator fans STD heaters HIGH POWER heaters Humidifier STD heater + humidifier HP heater + humidifier
V/Ph/Hz
FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A)
CRCC 20 230/1/60 0,51 4,35 2,91 8,45 4,11 9,82 2,62 7,75 5,02 11,85 6,22 13,22
CRCC 25 230/1/60 0,68 5,80 3,08 9,90 4,28 11,27 2,79 9,20 5,19 13,30 6,39 14,67
CRCC 35 230/1/60 0,85 7,25 4,45 12,72 5,65 15,45 2,96 10,65 6,56 16,12 7,76 18,85
CRCC 36 230/1/60 0,85 7,25 4,45 12,72 5,65 15,45 2,96 10,65 6,56 16,12 7,76 18,85
CRCC 38 230/1/60 0,85 7,25 4,45 12,72 5,65 15,45 2,96 10,65 6,56 16,12 7,76 18,85
CRCC 40 380/3/60 2,64 4,20 8,04 12,40 9,84 15,14 4,75 7,60 10,15 15,80 11,95 18,54
CRCC 50 380/3/60 2,64 4,20 8,04 12,40 9,84 15,14 4,75 7,60 10,15 15,80 11,95 18,54
CRCC 60 380/3/60 3,96 6,30 11,16 17,24 14,76 22,71 6,07 9,70 13,27 20,64 16,87 26,11
CRCC 55 380/3/60 3,96 6,30 11,16 17,24 14,76 22,71 6,07 9,70 13,27 20,64 16,87 26,11
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 29 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Electrical connections
10.7.4 POWER SUPPLY 460V/3/60HZ
Evaporator fans STD electric heaters HIGH POWER electric heaters Humidifier
CRC V/Ph/Hz FLI FLA No. FLI FLA No. FLI FLA FLI FLA
V/Ph/Hz qty V/Ph/Hz V/Ph/Hz V/Ph/Hz qty kg/h
(kW) (A) elements (kW) (A) elements (kW) (A) (kW) (A)
CRCC 20 230/1/60 230/1/60 3 0,17 1,45 460/3/60 4 0,60 2,26 460/3/60 6 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 25 230/1/60 230/1/60 4 0,17 1,45 460/3/60 4 0,60 2,26 460/3/60 6 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 35 230/1/60 230/1/60 5 0,17 1,45 460/3/60 6 0,60 2,26 460/3/60 8 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 36 230/1/60 230/1/60 5 0,17 1,45 460/3/60 6 0,60 2,26 460/3/60 8 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 38 230/1/60 230/1/60 5 0,17 1,45 460/3/60 6 0,60 2,26 460/3/60 8 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 40 460/3/60 460/3/60 2 1,32 2,10 460/3/60 9 0,60 2,26 460/3/60 12 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 50 460/3/60 460/3/60 2 1,32 2,10 460/3/60 9 0,60 2,26 460/3/60 12 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 60 460/3/60 460/3/60 3 1,32 2,10 460/3/60 12 0,60 2,26 460/3/60 18 0,60 2,26 460/3/60 1 2,25 2,80 3
CRCC 55 460/3/60 460/3/60 3 1,32 2,10 460/3/60 12 0,60 2,26 460/3/60 18 0,60 2,26 460/3/60 1 2,25 2,80 3
POWER SUPPLY
i-HCAT
STD condenser fans EC condenser fans
V/Ph/Hz
FLI (kW) FLA (A) SA [A] FLA (A) FLI (kW) SA [A]
0071 460/3/60 10,85 16,42 8 10,88 16,60 9
0121 460/3/60 18,55 28,75 23 18,61 29,11 23
0151 460/3/60 14,84 27,54 51 14,72 29,82 53
0251 460/3/60 21,28 40,22 54 21,09 43,64 57
POWER SUPPLY
CRC Evaporator fans STD heaters HIGH POWER heaters Humidifier STD heater + Humidifier HP heater + humidifier
V/Ph/Hz
FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A) FLI (kW) FLA (A)
CRCC 20 230/1/60 0,51 4,35 2,91 7,74 4,11 8,87 2,76 7,15 5,16 10,54 6,36 11,67
CRCC 25 230/1/60 0,68 5,80 3,08 9,19 4,28 10,32 2,93 8,60 5,33 11,99 6,53 13,12
CRCC 35 230/1/60 0,85 7,25 4,45 11,77 5,65 14,03 3,10 10,05 6,70 14,57 7,90 16,83
CRCC 36 230/1/60 0,85 7,25 4,45 11,77 5,65 14,03 3,10 10,05 6,70 14,57 7,90 16,83
CRCC 38 230/1/60 0,85 7,25 4,45 11,77 5,65 14,03 3,10 10,05 6,70 14,57 7,90 16,83
CRCC 40 460/3/60 2,64 4,20 8,04 10,98 9,84 13,24 4,89 7,00 10,29 13,78 12,09 16,04
CRCC 50 460/3/60 2,64 4,20 8,04 10,98 9,84 13,24 4,89 7,00 10,29 13,78 12,09 16,04
CRCC 60 460/3/60 3,96 6,30 11,16 15,34 14,76 19,86 6,21 9,10 13,41 18,14 17,01 22,66
CRCC 55 460/3/60 3,96 6,30 11,16 15,34 14,76 19,86 6,21 9,10 13,41 18,14 17,01 22,66
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 30 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Instruments and alarms
11 CONDENSATE DRAIN
Condensate is removed from the pan located underneath the unit; the end of the drain pipe should be connected to the sewer- age system in the building via a rubber or plastic hose with an inside
diameter of 16 mm. During installation, pour water into the condensate collection pan so as to fill the drain trap with water.
i-HCAT unit
- High pressure switch with manual reset;
CRCX/CRCD/CRCC unit
- Low pressure switch with automatic reset;
- Dirty filter sensor (optional) (differential pressure switches);
- Temperature sensor or room temperature and humidity sensor (on units with humidity control).
The calibration values of the control and safety devices must not be altered.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 31 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Operation and control
13.2 MODULATING WATER VALVE
The CRCC/CRCD units with chilled water circuit are fit-ted with a 2- or 3-way modulating valve complete with 3- position or 0-10 V servomotor.
ATTENTION
Disconnect power before working on the servomotor.
The servomotor position is proportional to the control voltage applied, between 0 and 10 Vdc.
Description
This servomotor with 0-10 V control is used to drive 2- or 3- way valves with 5.5 mm travel.
Functions
When the actuator is powered at 0-10 Vdc or with a 3 position signal, it transmits motion to the valve.
Auto-calibration - SSC619
When 24V AC/DC is supplied, the servomotor automatically and independently performs auto-calibration,
regardless of the signal.
This process takes around 60 seconds.
Maintenance
The servomotors are maintenance-free. If maintenance is required on the system, remember to:
• disconnect power (unplugging the connector);
• the servomotor must only be tested when the valve has been installed correctly.
Manual override
The knob on the servomotor can be used to move the actuator to all positions between 0 and 1. If the control
signal is applied, this has priority in determining the valve position.
In position 1: In position 0:
valve open valve closed
Repair
The servomotor cannot be repaired and if necessary, must be replaced completely.
*close off = Maximum pressure differential allowed for the motorised valve to close against system pressure
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 32 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Operation and control
13.4 2-WAY ON/OFF VALVE (OPTIONAL)
The on-off valve shuts off water flow into the CRCD/CRCC unit (see OVERVIEW DIAGRAM) in the event of a flood alarm.
The 2-way ON/OFF valve kit comprises:
- Valve body
- 24 VAC electric servo control with limit switch
- 2 x 3-piece joints
- Close off ∆Ps=500kPa
Connect the servomotor power cable to the special terminals in the CRCD/CRCC electrical panel (see wiring diagram).
Assembly
For correct assembly of the valve any position is allowed, except where the servo control is facing downward
OK OK Incorrect
Technical information
The vortex flow meter exploits the sequence of vortices produced by the fluid that comes into contact perpendicularly with a bluff body. The
frequency of such vortices is proportional to the flow rate of the fluid.
A special detector converts this frequency into an electrical signal for determining the fluid flow-rate.
Specifications
Mod. CRCC-CRCD Mod. CRCC-CRCD
Flow
0020-0025-0035-0036 0038-0040-0050-0060
Measuring range 5 to 100 l/min 20 to 400 l/min
Accuracy (±1σ), from 0 to 100°C ±1.5% FS ±1.5% FS
Resolution 0.5 l/min 2.0 l/min
Temperature
Measuring range 0 to 100 °C
Accuracy (±1σ), 25 to 80°C ±1 °C
Accuracy (±1σ), 0 to 100°C ±2 °C
Resolution 0.5 °C
Media and environment
Media types The sensor is compatible with liquids (kinematic viscosity ≤2 mm2/s)
Media temperature (operation) 0 to 100°C
Media temperature (peak) -25 to 120°C, non-freezing
Ambient air temperature (operation) -25 to 60°C
Ambient air temperature (peak) -55 to 90°C
Humidity 0 – 95% (relative), non-condensing
System burst pressure > 16 bar
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 33 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Operation and control
Flow (l/min)
Temperature response
Temperature (°C)
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 34 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Optional
14 OPTIONAL
14.1 MAINS ANALYZER
This device provides continuous measurement of power consumption, monitoring current, voltage and power.
These values can be sent to BMS systems via a serial connection, fitting the unit with a communication board to manage the specific protocol.
Connect the device to the CRC indoor unit via RS485 serial cable, as shown on the unit wiring diagram.
14.4 HUMIDIFIER
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 35 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Optional
14.4.2 HUMIDIFIER OPERATING PRINCIPLE
In the immersed electrode humidifier, the current that runs between the electrodes, through the water contained in the boiler cylinder, generates the heat required to boil the water.
By controlling the level of the water and the concentration of salts inside the steam cylinder (6) using the fill (7) and drain (8) solenoid valves, the amount of current delivered can be regulated, and
measured using a current transformer (2).
When steam production is required, the humidifier contactor CU closes (see the wiring diagram) so as to supply power to the immersed electrodes.
When the current falls below the set value due to the lowering of the water level, the fill valve (7) is opened.
The drain valve (8) is activated cyclically, depending on the characteristics of the supply water, so as to maintain the optimum salt concentration inside the cylinder (6).
The only periodical maintenance operations required are the inspection and cleaning of the parts in the steam production unit. The operations indicated below should be performed annually,
preferably before shutting down the unit in summer.
Proceed as follows:
- completely drain the water from the boiler using the MANUAL CONTROLS on the controller A1;
- disconnect the power supply by opening the main switch on the electrical panel;
- remove the fill pipe from the 3/4 GAS fitting on the fill solenoid valve;
- remove and clean the filter located inside the solenoid valve fitting;
- dismantle the drain assembly (shown in Figure 13), clean the pipes and remove any flakes of scale from the
cup-drain trap.
To supply the humidifier, use drinking water without any chemical treatment or demineralisation.
The characteristics of the water that supplies the humidifier must be within the following values:
IN 3/4”G Ф6mm
LIMIT VALUES FOR IMMERSED ELECTRODE HUMIDIFIER FEED WATER Normal water Water with low salt content
Min Max Min Max
Mains pressure bar 1 8 1 8
Hydrogen ions pH 7 8,5 7 8,5
Specific conductivity at 20°C σR, 20 °C μS/cm 350 1250 75 350
Total dissolved solids TDS mg/l (1) (1) (1) (1)
Dry residue at 180°C R180 mg/l (1) (1) (1) (1)
Total hardness TH mg/l CaCO3 100 (2) 400 50 (2) 160
Temporary hardness mg/l CaCO3 60 (3) 300 30 (3) 100
Iron + Manganese mg/l Fe + Mn 0 0,2 0 0,2
Chlorides ppm Cl 0 30 0 20
Silica mg/l SiO2 0 20 0 20
Residual chlorine mg/l Cl- 0 0,2 0 0,2
Calcium sulphate mg/l CaSO4 0 100 0 60
Metallic impurities mg/l 0 0 0 0
Solvents, diluents, soaps, lubricants mg/l 0 0 0 0
(1) Values depending on specific conductivity; in general: TDS ≅ 0,93 * σR, 20 °C; R180 ≅ 0,65 * σR
(2) Not lower than 200% of the chloride content in mg/l of Cl-
(3) Not lower than 300% of the chloride content in mg/l of Cl-
CYLINDER CONDUCTIVITY LOW CONDUCTIVITY CILINDER MEDIUM CONDUCTIVITY CILINDER HIGH CONDUCTIVITY CILINDER
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 36 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Optional
14.5 HUMIDIFIER AND CONDENSATE DRAIN
Underneath the drain solenoid valve on the steam production unit is an attachment for draining the water.
This is already fitted with a hose coupling for connecting the hose running to the sewerage system in the
building.
A rubber or plastic hose should be used, resistant to 100°C, with an inside diameter of 32 mm. Fit a trap in
the section of the hose outside of the unit to avoid bad odours and to prevent water from overflowing from
the humidifier pan. During installation, pour water into the condensate collection pan and the humidifier pan,
so as to fill the drain traps outside and inside the unit with water. Downstream of the drain trap ensure a
minimum slope of 1%.
ATTENTION
the water exiting the steam cylinder is very hot. The humidifier drain hose must not be fastened to electrical cables and must run down vertically so as to
avoid any contact with these cables.
TECHNICAL SPECIFICATIONS
Maximum flow rate 30 l/h
Maximum suction height 4m
Maximum discharge height 13 m (flow-rate 8 l/h)
Maximum pressure 18 m (flow-rate 0 l/h)
6m - 6 5 4
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 37 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Optional
14.8 CONDENSATE DRAIN PUMP FOR HIGH WATER TEMPERATURE (HUMIDIFIER)
These pumps are designed to collect the hot water produced by the humidifier drain cycles, as well as the condensate produced. The
pump body is made from Cycoloy, a heat-resistant material, the pre-wired safety float is a low voltage switch used to stop the drain cycle in
the unlikely event where the pump malfunctions.
The pump is started by internal float switches.
TECHNICAL SPECIFICATIONS
Tank capacity 4 litres
Recommended maximum head 6m
Maximum water flow-rate
900 l/h
With zero prevalence
Rated power 0.6A, 230V AC
Power cable (2 m long)
Safety switch 4A max
Power supply voltage 220/240 AC
Current draw 0,7A
Power consumption 175W
Dimensions
Height 205 mm
Width 300 mm
Depth 150 mm
Weight 3,6 kg
Electrical connections
Brown Line
Blue Neutral
Green/Yellow Earth
2xBlack Safety switch
Installation notes:
This pump is designed to be installed only horizontally, resting the base on a perfectly flat,
Portata acqua (l/h)
horizontal surface or fastening it horizon- tally to the wall through the holes provided on the frame.
The pump requires a drain hose with an inside diameter of 9 mm. Make sure the hoses are not
choked or twisted along the path between the pump and the point of drainage.
Securely fasten the hoses with a clamp to the pump outlet fitting, to prevent them from coming
loose and consequently causing water to be released at high pressure.
Maintenance guide
At least once every 6 months, pour a bactericidal solution into the tank, to prevent accumulation
of residues and sludge at the bottom that may cause the pump to malfunction.
Prevalenza (m)
SAFETY SWITCH
BLACK
BLACK
PUMP LINE
PUMP START
MOTOR
SWITCH NEUTRAL
EARTH
PUMP FRAME
INFORMATION
The pre-wired safety switch must always be used.
ATTENTION
Users must check that any chemicals contained in the condensate are compatible with operation of the pump.
Test pump operation by filling it with water until the motor starts, to check for any leaks and verify correct drainage of the water.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 38 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Maintenance
15 MAINTEINANCE
ATTENTION
Every components replacement (compressor, safety pressostat, liquid receiver, ecc.) have to consider the main
component list enclosed in the unit.
This section, aimed above all for the end user, is extremely important for the correct operation of the appliance.
Just a few operations completed scrupulously and regularly will avoid serious damage to the components. Only authorized and specialist personnel can operate into the units.
The maintenance operations can be summarised as follows:
- Clean the air filter.
- Check and clean the condenser coils
- Check the water-cooled condensers for fouling.
- Check and clean the drains.
- Check the humidification system.
- General examination of the overall operation of the appliance.
- Visual check of the condition of the pressurised containers.
ATTENTION
BEFORE REMOVING THE FAN FROM THE FRAME, MAKE SURE IT HAS COMPLETELY STOPPED.
The remaining fans will operate at maximum speed to compensate for the missing fan during maintenance.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 39 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Maintenance
MANDATORY
The machine contains fluorinated greenhouse gases governed by the Kyoto protocol. The law prohibits the dispersion in the environment and obliges the
recovery and delivery to the dealer or collection centre.
When components are removed to be replaced or when the entire machine reaches the end of its life and it is necessary to remove it from the installation, to
minimize the environmental impact, comply with the following disposal regulations:
• the refrigerant gas must be fully recovered by specialized personnel and equipped with the necessary qualifications and be transferred to the collection
centres;
• the lubricating oil contained in the compressors and in the refrigerant circuit must be recovered and transferred to the collection centres;
• the structure, the electrical and electronic equipment and the components must be subdivided according to their product type and type of material and
given to the collection centres;
• if the water circuit contains mixtures with antifreezes, the contents must be collected and transferred to the collection centres
• comply with the national laws in force
MANDATORY
THE MACHINE CONTAINS ELECTRIC AND ELECTRONIC EQUIPMENT WHICH MAY IN TURN CONTAIN SUBSTANCES THAT ARE HARMFUL TO THE
ENVIRONMENT AND HUMAN HEALTH, AND CANNOT BE DISPOSED OF IN MIXED URBAN WASTE.
Buyers play an important role in the reuse, recycling and other forms of recovery of the machine.
The machine is classified as PROFESSIONAL for the purposes of the WEEE Directive 2012/19/EU. When it is disposed of, the User must manage it as waste and may contact the dealer to have it
collected, or take it to a collection centre.
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 40 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Troubleshooting
17 TROUBLESHOOTING
Troubleshooting is simplified by the information provided by the microprocessor controller: if an alarm is signalled, refer to the control panel instruction manual. If required, contact the nearest service
centre, indicating the probable causes of the fault.
The electrical panel is not powered Check for voltage; close the main switch.
THE AIR CONDITIONER Check that the cutout IM in the auxiliary circuits is armed.
The auxiliary circuits are not powered
DOESN’T START Check the fuse on the main board.
The control panel does not start the air-conditioner. Check for DC power.
The parameter settings on the microprocessor controller are not
See the controller manual
correct.
The air flow-rate is too low or null. See "LOW OR NO AIR FLOW".
The probe isn't working. Check the electrical connections and the configuration of the controller.
ROOM TEMPERATURE Thermal load higher than expected. Check the thermal load in the room being air-conditioned.
TOO HIGH
Check the electrical connections to the valve servomotor. Open the valve using the
Three-way valve not working
manual control knob.
Check the electrical connections to the valve servomotor.
No flow of chilled water.
Open the valve using the manual control knob.
High temperature of the chilled water. Check the operation of the water chiller.
The parameter settings on the microprocessor controller are not
See the controller manual.
ROOM TEMPERATURE correct.
TOO LOW The three-way valve in the chilled water circuit is stuck in the open
Close the valve using the manual control knob and replace the servomotor.
position.
The parameter settings on the microprocessor controller are not
See the controller manual.
correct.
Check and calculate the latent load; check the flow-rate and the conditions of the
Latent load higher than expected.
outside air; check the inflow of outside air.
AMBIENT HUMIDITY
TOO HIGH The compressor isn't working during the dehumidification phase. See "THE COMPRESSOR/COMPRESSORS DON'T START".
The dehumidification valve doesn't close. Check the operation of the solenoid valve that controls the dehumidification circuit.
The control system isn't working. See the controller manual; check the operation of the panel and/or the probe
The parameter settings on the microprocessor controller are not
Check the room temperature setting (see the control panel manual).
correct.
AMBIENT HUMIDITY Latent load lower than expected. Check the amount of latent load
TOO LOW Check the pressure of the supply water; Check the operation of the manual control
The humidifier isn't working.
system and the steam production unit (see the control panel manual)
The control system isn't working. See the control panel manual; check the operation of the panel and/or the probe.
The fans are not powered. Check the power supply to the fans.
Clean the filter using a vacuum cleaner after having shaken off the larger particles of
The filters are blocked (possible activation of the dirty filter alarm). dust. Replace the filter if excessively clogged. Check the correct calibration of the
dirty filter differential pressure switch F4.
Obstructions to the air flow. See the paragraph on AIR DISTRIBUTION
LOW OR NO AIR FLOW
Check the resistance of the fan windings; after resetting, measure the voltage and
The fan thermal cutout has tripped.
power input.
EC radial fan speed set too low
Check the sizing of the air distribution system (ducting, false-ceiling, underfloor
Excessive pressure drop in the air distribution system.
plenum, grills)
Insufficient air flow-rate See "LOW OR NO AIR FLOW".
HEATER SAFETY
Check the continuity of the connection from the safety thermostat to the control
THERMOSTAT Thermostat connection wire cut or broken
system.
ACTIVATED
Faulty thermostat Replace the heater safety thermostat.
A) Air or incondensable gas in the refrigerant circuit, seen by the
Empty and recharge the circuit.
presence of bubbles, despite measuring a high subcooling.
Check the operation and the correct direction of rotation of the fans on the outdoor
heat exchanger. Check that the exchanger is not dirty and remove any material that
B) Insufficient air flow-rate to the remote heat exchanger or air too may be blocking it (leaves, paper, seeds, dust, etc.) with a jet of compressed air or
hot with a brush; Check the outdoor unit for any obstacles to the flow of air and any
HIGH COMPRESSOR
recirculation of the cooling air; Check that the temperature of the cooling air does not
DISCHARGE
exceed the design value.
PRESSURE
Check the flow-rate, the pressure and the temperature of the cooling water in the
Insufficient water flow-rate to the condenser or water too hot.
closed circuit; Check the calibration and the operation of the pressure control valve.
Excessive refrigerant charge; condenser partially flooded.
Remove refrigerant from the circuit.
Excessive subcooling of the liquid at the condenser outlet.
Valves on the high pressure side of the circuit partially closed. Check the opening of the valves.
Check the operation of the condenser fans and the corresponding protection device;
HIGH PRESSURE repair or replace the faulty fans; Check the calibration and the operation of the
SWITCH ACTIVATED The condensing pressure control system isn't working.
remote condenser fan pressure switch or the speed controller. (See CONTROLLING
(high pressure THE CONDENSING PRESSURE)
discharge pressure)
The system is affected by an excessive discharge pressure See "HIGH COMPRESSOR DISCHARGE PRESSURE".
MEHITS S.p.A.
UM_CRC_00_Z_08_20_EN 41 TRANSLATION OF THE ORIGINAL INSTRUCTIONS
CRC Troubleshooting
The air flow-rate is too low or null See "LOW OR NO AIR FLOW".
LOW COMPRESSOR
SUCTION PRESSURE Liquid receiver outlet valve not completely open
Check the opening of the valve.
(and possible defrosting Check that the thermostatic valve superheating value is correct; check that the valve
of the coil)
Refrigerant filter blocked sensor bulb is not discharged and that it is correctly positioned, secured and
insulated".
Insufficient refrigerant charge Check the liquid subcooling at the condenser outlet; if necessary, restore the charge.
Thermostatic valve not correctly calibrated or faulty Check that the thermostatic valve superheating value is correct (around 5°C).
LOW PRESSURE
SWITCH ACTIVATED ( Check and if necessary replace the dewatering filter cartridge; the temperature
Dewatering filter cartridge dirty
low compressor suction difference measured upstream and downstream of the filter must be less than 2°C.
pressure)
The system is affected by an excessively low discharge pressure See "LOW COMPRESSOR DISCHARGE PRESSURE".