You are on page 1of 97

Installation and Maintenance Manual IMM AGSD-1

Group: Chiller
Part Number: 331375301
Date: July 2007
Supersedes: June 2007

Air-Cooled Screw Compressor Chiller


AGS 225D - AGS 450D
210 to 450 Tons, 740 to 1580 kW
Packaged or with Remote Evaporator

60 Hertz, R-134a
Introduction

General Description
McQuay air-cooled water chillers are complete, self-contained automatic refrigerating units that
include the latest in engineered components arranged to provide a compact and efficient unit. Each
unit is completely assembled, factory wired, evacuated, charged, tested and comes complete and ready
for installation. Each circuit (two or three, depending on unit size) consists of an air-cooled condenser
section with an integral subcooler section, a semi-hermetic, single-screw compressors with starter, a
multi-circuit, shell-and-tube, direct expansion evaporator, an economizer and complete refrigerant
piping. Each compressor has an independent refrigeration circuit. Liquid line components included
are a manual liquid line shutoff valve, charging port, filter-drier, sight-glass/moisture indicator,
solenoid valve and electronic expansion valve. A combination discharge check and shutoff valve is
included and a compressor suction shutoff valve is optional. Other features include compressor
heaters, evaporator heaters for freeze protection, automatic, one-time pumpdown of each refrigerant
circuit upon circuit shutdown, and an advanced fully integrated microprocessor control system.
Model AGS D units are available as standard efficiency (DS) or high efficiency (DE)
A high ambient option is required for operation in ambient temperatures above 105°F and up to 125°F
and when the VFD low ambient option is selected.
Information on the operation of the unit MicroTech II® controller is in the OM AGS manual.
Operation and maintenance of the optional unit-mounted pump package is in IOMM AGSD Pump
Pkg, which is included on all units so equipped.

Nomenclature

A G S - XXX D S
Air-Cooled S=Standard Efficiency, Packaged
Global E=High Efficiency, Packaged
M=Standard, Remote Evaporator
Rotary Screw Compressor F=High Efficiency, Remote Evaporator

Design Vintage
Nominal Tons

Inspection
When the equipment is received, carefully check all items against the bill of lading to verify for a
complete shipment. Check all units for damage upon arrival. All shipping damage must be reported to
the carrier and a claim must be filed with the carrier. Check the unit’s serial plate before unloading the
unit to be sure that it agrees with the power supply available. Physical damage to a unit after shipment
is not McQuay International’s responsibility.
Note: Unit shipping and operating weights are shown in the Physical Data Tables beginning on page
28.

IMM AGSD 3
Weights and Isolator Locations
Standard Efficiency
Figure 1, Lifting and Isolator Locations, Model AGS 225DS - 315DS (looking down from
above)

E
D
84.6
(2150)
25.6
L5 L3 L1 (650)

M7 M5 M3 M1

CONTROL PANEL
M8 M6 M4 M2

L6 L4 L2
32.6
(826)
B
C

B C D E
AGS Model
in. (mm) in. (mm) in. (mm) in. (mm)
225DS N/A 210.8 (5354) N/A 217.7 (5530)
250DS 102.1 (2594) 255.9 (6500) 194.1 (4930) 253.2 (6431)
275DS 102.1 (2594) 250.1 (6353) 199.7 (5072) 288.6 (7330)
300DS 102.1 (2594) 250.1 (6353) 199.7 (5072) 288.6 (7330)

Figure 2, Lifting and Isolator Locations, Model AGS 330DS - 450DS (looking down from
above)
G
F
E
84.6
(2150)
25.6
L7 L5 L3 L1 (650)

M9 M7 M5 M3 M1
CONTROL PANEL

M10 M8 M6 M4 M2

L8 L6 L4 L2
32.6
(826)
B
C
D

B C D E F G
AGS Model
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
330DS, 350DS 141.2 (3586) 262.0 (6655) 339.3 (8618) 177.0 (4496) 269.3 (6840) 361.6 (9185)
360DS 141.2 (3586) 262.0 (6655) 339.3 (8618) 177.0 (4496) 269.3 (6840) 361.6 (9185)
390DS 141.2 (3586) 262.0 (6655) 348.3 (8847) 177.0 (4496) 269.3 (6840) 361.6 (9185)
400DS 141.2 (3586) 262.0 (6655) 348.3 (8847) 177.0 (4496) 269.3 (6840) 361.6 (9185)
450DS 137.6 (3495) 297.4 (7554) 383.8 (9749) 169.3 (4299) 304.7 (7739) 397.0 (10085)
4 IMM AGSD
Table 1, Standard Efficiency, Shipping and Lifting Weights, Aluminum Fins
Shipping Location
Unit Unit
Weight L1 L2 L3 L4 L5 L6 L7 L8
Size Fans
lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg
225DS 12 12007 5451 3743 1699 4059 1843 - - - - 2018 916 2188 993 - - - -
250DS 14 12849 5833 2653 1204 2824 1282 2241 1017 2386 1083 1330 603 1416 642 - - - -
275DS 16 14053 6380 2642 1199 2780 1262 2381 1081 2505 1137 1825 828.6 1920 871 - - - -
300DS 16 14049 6378 2642 1199 2780 1262 2379 1080 2503 1136 1825 828.6 1920 871 - - - -
330DS 20 19596 8897 3758 1706 3707 1683 2884 1309 2845 1292 1918 870 1892 859 1305 592 1287 584
350DS 20 19596 8897 3758 1706 3707 1683 2884 1309 2845 1292 1918 870 1892 859 1305 592 1287 584
360DS 20 19639 8916 3761 1707 3710 1684 2892 1313 2853 1295 1926 874 1900 862 1308 593 1290 585
390DS 22 20278 9206 3559 1616 3559 1616 2850 1294 2850 1294 2109 957 2109 957 1621 735 1621 735
400DS 22 20549 9329 3572 1622 3572 1622 2905 1319 2905 1319 2164 982 2164 982 1634 741 1634 741
450DS 24 21326 9682 3693 1677 3693 1677 3094 1405 3094 1405 2184 991 2184 991 1692 768 1692 768

Table 2, Standard Efficiency, Shipping and Lifting Weights, Copper Fins


Shipping Location
Unit Unit
Weight. L1 L2 L3 L4 L5 L6 L7 L8
Size Fans
lbs. kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg
225DS 12 13584 6167 4154 1886 4470 2029 - - - - 2430 1103 2600 1180 - - -
250DS 14 14689 6669 2660 1208 2810 1276 2546 1156 2690 1221 1980 899 2085 947 - - - -
275DS 15 15807 7176 2672 1213 2745 1246 2647 1202 2720 1235 2526 1147 2591 1176 - - - -
300DS 16 16100 7309 2639 1198 2796 1269 2632 1195 2788 1266 2595 1178 2746 1247 - - - -
330DS 20 22224 10090 4086 1855 4035 1832 3213 1459 3174 1441 2247 1020 2221 1008 1633 741 1615 733
350DS 20 22224 10090 4086 1855 4035 1832 3213 1459 3174 1441 2247 1020 2221 1008 1633 741 1615 733
360DS 20 22267 10109 4089 1856 4038 1833 3221 1462 3182 1445 2255 1024 2229 1012 1636 743 1618 735
390DS 22 23169 10519 3920 1780 3920 1780 3212 1458 3212 1458 2470 1121 2470 1121 1982 900 1982 900
400DS 22 23440 10642 3933 1786 3933 1786 3266 1483 3266 1483 2526 1147 2526 1147 1995 906 1995 906
450DS 24 24480 11114 4087 1855 4087 1855 3488 1584 3488 1584 2579 1171 2579 1171 2086 947 2086 947

Table 3, Standard Efficiency, Operating and Mounting Weights, Aluminum Fins


Operating Location
Unit Unit
.Weight M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
Size Fans
lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg
225DS 12 12556 5700 2382 1081 2582 1172 2118 962 2297 1043 - - - - 1525 692 1653 750 - - - -
250DS 14 13398 6083 2411 1095 2566 1165 2002 909 2131 967 1243 564 1324 601 834 379 888 403 - - - -
275DS 16 14958 6791 2523 1145 2697 1224 2183 991 2333 1059 1519 690 1624 737 1006 457 1073 487 - - - -
300DS 16 14954 6789 2522 1145 2696 1224 2182 991 2332 1059 1518 689 1623 737 1006 457 1075 488 - - - -
330DS 20 20507 9310 2818 1279 2780 1262 2535 1151 2500 1135 2095 951 2067 938 1657 752 1634 742 1219 553 1202 546
350DS 20 20507 9310 2818 1279 2780 1262 2535 1151 2500 1135 2095 951 2067 938 1657 752 1634 742 1219 553 1202 546
360DS 20 20517 9315 2818 1279 2780 1262 2537 1152 2502 1136 2097 952 2069 939 1658 753 1635 742 1219 553 1202 546
390DS 22 21156 9605 2678 1216 2678 1216 2488 1130 2488 1130 2112 959 2112 959 1750 795 1750 795 1550 704 1550 704
400DS 22 21708 9855 2678 1216 2678 1216 2488 1130 2488 1130 2192 995 2192 995 1896 861 1896 861 1600 726 1600 726
450DS 24 22485 10208 2721 1235 2721 1235 2558 1161 2558 1161 2323 1055 2323 1055 1948 884 1948 884 1693 769 1693 769

Table 4, Standard Efficiency, Operating and Mounting Weights, Copper Fins


Operating. Location
Unit
Fans Weight M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
Size
lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
225DS 12 14133 6416 2642 1199 2843 1291 2379 1080 2571 1167 - - - - 1785 810 1913 869 - - - -
250DS 14 15238 6918 2641 1199 2796 1269 2232 1013 2361 1072 1473 669 1554 706 1064 483 1118 507 - - - -
275DS 16 17060 7745 2786 1265 2959 1343 2445 1110 2605 1183 1780 808 1883 855 1269 576 1333 605 - - - -
300DS 16 17056 7743 2785 1264 2958 1343 2444 1110 2605 1183 1780 808 1883 855 1267 575 1334 606 - - - -
330DS 20 23135 10503 3081 1399 3043 1382 2798 1270 2763 1254 2358 1071 2330 1058 1920 872 1897 861 1481 672 1464 665
350DS 20 23135 10503 3081 1399 3043 1382 2798 1270 2763 1254 2358 1071 2330 1058 1920 872 1897 861 1481 672 1464 665
360DS 20 23145 10508 3081 1399 3043 1382 2800 1271 2765 1255 2360 1071 2332 1059 1921 872 1898 862 1481 672 1464 665
390DS 22 24047 10917 2967 1347 2967 1347 2777 1261 2777 1261 2401 1090 2401 1090 2039 926 2039 926 1839 835 1839 835
400DS 22 24599 11168 2967 1347 2967 1347 2777 1261 2777 1261 2481 1126 2481 1126 2185 992 2185 992 1889 858 1889 858
450DS 24 25639 11640 3036 1378 3036 1378 2873 1304 2873 1304 2638 1198 2638 1198 2263 1027 2263 1027 2009 912 2009 912

IMM AGSD 5
Isolator Identification
Table 5, Standard Efficiency, Neoprene-in-Shear Isolators, Aluminum Fins
Unit Model Rubber-In-Shear Mounts Kit Number
M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
225DS - - - - 330904171
Green Green Green Green Red Red
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
250DS - - 330904172
Green Green Green Green Red Red Black Black
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
275DS - - 330904172
Green Green Green Green Red Red Black Black
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
300DS - - 330904172
Green Green Green Green Red Red Black Black
330DS, 350DS RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
330904181
360DS Green Green Green Green Green Green Red Red Red Red
390DS RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
330904181
400DS Green Green Green Green Green Green Red Red Red Red
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
450DS 330904181
Green Green Green Green Green Green Red Red Red Red

Table 6, Standard Efficiency, Neoprene-in-Shear Isolators, Copper Fins


Unit Model Rubber-In-Shear Mounts Kit Number
M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
225DS - - - - 330904171
Green Green Green Green Red Red
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
250DS - - 330904172
Green Green Green Green Red Red Black Black
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
275DS - - 330904172
Green Green Green Green Red Red Black Black
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
300DS - - 330904172
Green Green Green Green Red Red Black Black
330DS, 350DS RP-4 RP-4 RP-4 RP-4 PR-4 RP-4 RP-4 RP-4 RP-4 P-4
330904183
360DS Gray Gray Gray Gray Green Green Green Green Red Red
390DS RP-4 RP-4 RP-4 RP-4 PR-4 RP-4 RP-4 RP-4 RP-4 P-4
330904183
400DS Gray Gray Gray Gray Green Green Green Green Red Red
RP-4 RP-4 RP-4 RP-4 PR-4 RP-4 RP-4 RP-4 RP-4 P-4
450DS 330904183
Gray Gray Gray Gray Green Green Green Green Red Red

Table 7, Standard Efficiency, Spring Isolators, Aluminum Fins


Unit Model Spring-Flex Mounts Kit Number
M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26
225DS - - - - 330904151
Green Green Green Green Purple Purple
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25
250DS - - 330904152
Green Green Green Green Purple Purple Red Red
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25
275DS - - 330904152
Green Green Green Green Purple Purple Red Red
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25
300DS - - 330904152
Green Green Green Green Purple Purple Red Red
330DS, 350DS CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-26 CP-4-26
330904161
360DS Green Green Green Green Orange Orange Purple Purple Purple Purple
390DS CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
330904162
400DS Green Green Green Green Orange Orange Orange Orange Purple Purple
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
450DS 330904162
Green Green Green Green Orange Orange Orange Orange Purple Purple
NOTE: The Kit Number refers to the McQuay part number for the entire set of isolators for a specific unit.

6 IMM AGSD
Table 8, Standard Efficiency, Spring Isolators, Copper Fins
Spring-Flex Mounts
Unit Model Kit Number
M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27
225DS - - - - 330904154
Green Green Green Green Orange Orange
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25
250DS - - 330904152
Green Green Green Green Purple Purple Red Red
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25
275DS - - 330904152
Green Green Green Green Purple Purple Red Red
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25
300DS - - 330904152
Green Green Green Green Purple Purple Red Red
330DS CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
330904162
360DS 350DS Green Green Green Green Orange Orange Orange Orange Purple Purple
390DS CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-27
330904163
400DS Green Green Green Green Orange Orange Orange Orange Orange Orange
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27
450DS 330904164
Green Green Green Green Green Green Orange Orange Orange Orange
NOTE: The Kit Number refers to the McQuay part number for the entire set of isolators for a specific unit.

High Efficiency
Figure 3, Lifting and Isolator Locations, Model AGS 225DE – 300DE
View is looking down at base from above.
E
D
84.6
(2150)
25.6
L5 L3 L1 (650)

M7 M5 M3 M1
CONTROL PANEL

M8 M6 M4 M2

L6 L4 L2
32.6
(826)
B
C

B C D E
AGS Model
in. (mm) in. (mm) in. (mm) in. (mm)
225DE 69.6 (1768) 255.9 (6500) 194.1 (4930) 253.2 (6431)
250DE 69.6 (1768) 250.1 (6353) 199.7 (5072) 288.6 (7330)
260DE 69.6 (1768) 250.1 (6353) 199.7 (5072) 288.6 (7330)
275DE 69.6 (1768) 266.4 (6767) 198.8 (5050) 324.0 (8230)
300DE 69.6 (1768) 266.4 (6767) 198.8 (5050) 324.0 (8230)

IMM AGSD 7
Figure 4, Lifting and Isolator Locations, Model AGS 330DE – 450DE
View is looking down at base from above.

G
F
E
84.6
(2150)
25.6
L7 L5 L3 L1 (650)

M9 M7 M5 M3 M1

CONTROL PANEL
M10 M8 M6 M4 M2

L8 L6 L4 L2
32.6
(826)
B
C
D

B C D E F G
AGS Model
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
330DE 141.2 (3586) 262.0 (6655) 348.3 (8847) 177.0 (4496) 269.3 (6840) 361.6 (9185)
350DE 137.6 (3495)) 297.4 (7554) 383.8 (9749) 169.3 (4299) 304.7 (7739) 397.0 (10085)
400DE 137.6 (3495) 297.4 (7554) 383.8 (9749) 169.3 (4299) 304.7 (7739) 397.0 (10085)
450DE 137.6 (3495) 297.4 (7554) 419.2 (10648) 169.3 (4299) 304.7 (7739) 432.5 (10986)

Table 9, High Efficiency, Shipping and Lifting Weights, Aluminum Fins


Shipping Lifting Weight Lbs (kg)
Unit Unit
Weight. L1 L2 L3 L4 L5 L6 L7 L8
Size Fans
lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg
225DE 14 12869 5843 2653 1204 2824 1282 2246 1020 2391 1086 1335 606 1420 645 - - - -
250DE 16 13639 6192 2565 1165 2698 1225 2311 1049 2431 1104 1771 804 1863 845.8 - - - -
260DE 16 14808 6723 2562 1163 2738 1243 2341 1063 2503 1136 1867 848 1997 907 - - - -
275DE 18 14766 6704 2615 1187 2737 1243 2470 1121 2586 1174 2129 966.6 2229 1012 - - - -
300DE 18 14808 6723 2547 1156 2708 1229 2440 1108 2595 1178 2189 994 2329 1057 - - - -
330DE 22 20235 9187 3548 1611 3548 1611 2845 1292 2845 1292 2104 955 2104 955 1620 735 1620 735
350DE 24 21040 9552 3661 1662 3661 1662 3055 1387 3055 1387 2144 973 2144 973 1660 754 1660 754
400DE 24 21326 9682 3693 1677 3693 1677 3095 1405 3095 1405 2184 992 2184 992 1691 768 1691 768
450DE 26 22244 10099 3658 1661 3658 1661 3171 1440 3171 1440 2429 1103 2429 1103 1864 846 1864 846

Table 10, High Efficiency, Shipping and Lifting Weights, Copper Fins
Shipping Lifting Weight Lbs (kg)
Unit Unit
Weight L1 L2 L3 L4 L5 L6 L7 L8
Size Fans
lbs. kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg
225DE 14 14709 6678 2660 1208 2810 1276 2550 1158 2695 1224 1986 902 2090 949 - - - -
250DE 16 15741 7146 2915 1324 3048 1384 2661 1208 2781 1263 2121 963.1 2213 1005 - - - -
260DE 16 16110 7314 2639 1198 2796 1269 2632 1195 2788 1266 2594 1178 2747 1247 - - - -
275DE 18 17131 7777 3009 1366 3131 1421 2864 1300 2980 1353 2523 1146 2623 1191 - - - -
300DE 18 17173 7797 2707 1229 2854 1296 2747 1247 2898 1316 2957 1342 3119 1416 - - - -
330DE 22 23126 10499 3909 1775 3909 1775 3206 1456 3206 1456 2466 1120 2466 1120 1982 900 1982 900
350DE 24 24194 10984 4055 1841 4055 1841 3449 1566 3449 1566 2538 1152 2538 1152 2055 933 2055 933
400DE 24 24480 11114 4087 1855 4087 1855 3489 1584 3489 1584 2578 1170 2578 1170 2086 947 2086 947
450DE 26 25660 11650 4085 1855 4085 1855 3598 1633 3598 1633 2856 1297 2856 1297 2291 1040 2291 1040

8 IMM AGSD
Table 11, High Efficiency, Operating and Mounting Weights, Aluminum Fins
Operating Isolator Location Weight
Unit Unit
Weight M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
Size Fans
lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg
225DE 14 13418 6092 2411 1095 2566 1165 2005 910 2134 969 1247 566 1328 603 836 380 891 405 - - - -
250DE 16 14544 6603 2513 1141 2643 1200 2160 981 2273 1032 1473 669 1549 703 942 428 991 450 - - - -
260DE 16 14913 6771 2514 1141 2687 1220 2177 988 2327 1056 1515 688 1620 735 1002 455 1071 486 - - - -
275DE 18 15671 7115 2491 1131 2650 1203 2229 1012 2371 1076 1717 780 1826 829 1158 526 1231 559 - - - -
300DE 18 15669 7114 2491 1131 2650 1203 2228 1012 2370 1076 1717 780 1826 829 1158 526 1231 559 - - - -
330DE 22 21146 9600 2678 1216 2678 1216 2488 1130 2488 1130 2109 957 2109 957 1748 794 1748 794 1550 704 1550 704
350DE 24 21918 9951 2716 1233 2716 1233 2470 1121 2470 1121 2230 1012 2230 1012 1850 840 1850 840 1693 769 1693 769
400DE 24 22485 10208 2721 1235 2721 1235 2558 1161 2558 1161 2323 1055 2323 1055 1948 884 1948 884 1693 769 1693 769
450DE 26 23403 10625 2688 1220 2688 1220 2568 1166 2568 1166 2404 1091 2404 1091 2142 972 2142 972 1899 862 1899 862

Table 12, High Efficiency, Operating and Mounting Weights, Copper Fins
Operating Isolator Location Weight Lbs (kg)
Unit Unit
Weight M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
Size Fans
lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
225DE 14 15258 6927 2643 1200 2798 1270 2234 1014 2363 1073 1475 670 1556 706 1068 485 1120 508 - - - -
250DE 16 16646 7557 2776 1260 2905 1319 2422 1100 2536 1151 1736 788 1812 823 1205 547 1254 569 - - - -
260DE 16 17015 7725 2789 1266 2962 1345 2450 1112 2600 1180 1788 812 1893 859 1277 580 1346 611 - - - -
275DE 18 18036 8188 2787 1265 2946 1337 2524 1146 2666 1210 2013 914 2122 963 1455 661 1523 691 - - - -
300DE 18 18034 8187 2787 1265 2946 1337 2524 1146 2666 1210 2013 914 2122 963 1454 660 1522 691 - - - -
330DE 22 24037 10913 2967 1347 2967 1347 2777 1261 2777 1261 2398 1089 2398 1089 2037 925 2037 925 1839 835 1839 835
350DE 24 25072 11383 3031 1376 3031 1376 2785 1264 2785 1264 2545 1155 2545 1155 2165 983 2165 983 2010 913 2010 913
400DE 24 25639 11640 3036 1378 3036 1378 2873 1304 2873 1304 2638 1198 2638 1198 2263 1027 2263 1027 2008 912 2008 912
450DE 26 26819 12176 3030 1376 3030 1376 2910 1321 2910 1321 2746 1247 2746 1247 2484 1128 2484 1128 2240 1017 2240 1017

Isolator Identification
Table 13, High Efficiency, Neoprene-in-Shear Isolators, Aluminum Fins
Unit Location
Kit Number
Model M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
225DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
250DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
260DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
275DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
300DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
330DE 330904181
Green Green Green Green Green Green Red Red Red Red
350DE RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
330904181
400DE Green Green Green Green Green Green Red Red Red Red
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
450DE 330904182
Green Green Green Green Green Green Green Green Red Red
NOTE: The Kit Number refers to the McQuay part number for the entire set of isolators for a specific unit.

IMM AGSD 9
Table 14, High Efficiency, Neoprene-in-Shear Isolators, Copper Fins
Unit Location Kit Number
Model M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
225DE RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - - 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
250DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
260DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
275DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 - -
300DE 330904172
Green Green Green Green Red Red Black Black - -
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
330DE 330904183
Gray Gray Gray Gray Green Green Green Green Red Red
350DE RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
330904183
400DE Gray Gray Gray Gray Green Green Green Green Red Red
RP-4 RP-4 PR-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
450DE 330904184
Gray Gray Gray Gray Gray Gray Green Green Green Green

Table 15, High Efficiency, Spring Isolators, Aluminum Fins


Unit Spring-Flex Mountings Kit Number
Model M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
225DE CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25 - - 330904152
Green Green Green Green Purple Purple Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25 - -
250DE 330904152
Green Green Green Green Purple Purple Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25 - -
260DE 330904152
Green Green Green Green Purple Purple Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-25 CP-4-25 - -
275DE 330904153
Green Green Green Green Orange Orange Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-25 CP-4-25 - -
300DE 330904153
Green Green Green Green Orange Orange Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
330DE 330904162
Green Green Green Green Orange Orange Orange Orange Purple Purple
350DE CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
330904162
400DE Green Green Green Green Orange Orange Orange Orange Purple Purple
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27
450DE 330904164
Green Green Green Green Green Green Orange Orange Orange Orange

Table 16, High Efficiency, Spring Isolators, Copper Fins


Unit Spring-Flex Mountings
Kit Number
Model M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25 - -
225DE 330904152
Green Green Green Green Purple Purple Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25 - -
250DE 330904152
Green Green Green Green Purple Purple Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-26 CP-4-26 CP-4-25 CP-4-25 - -
260DE 330904152
Green Green Green Green Purple Purple Red Red - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-26 CP-4-26 - -
275DE 330904155
Green Green Green Green Orange Orange Purple Purple - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-26 CP-4-26 - -
300DE 330904155
Green Green Green Green Orange Orange Purple Purple - -
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-27
330DE 330904163
Green Green Green Green Orange Orange Orange Orange Orange Orange
350DE CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27
330904164
400DE Green Green Green Green Green Green Orange Orange Orange Orange
CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27
450DE 330904164
Green Green Green Green Green Green Orange Orange Orange Orange
NOTE: The Kit Number refers to the McQuay part number for the entire set of isolators for a specific unit.

10 IMM AGSD
Isolator Data
Table 17, Spring Flex Isolators
Spring Max. Load Defl.
Housing Each
Color In. (mm)
Lbs. (kg)
1300
CP-4-24 Brown
(590)
1800 1.22
CP-4-25 Red
(816) (30.9)
2400 1.17
CP 4-26 Purple
(1089) (29.7)
3000 1.06
CP-4-27 Orange
(1361) 26.9)
3600 1.02
CP-4-28 Green
(1633) (25.9)

Table 18, Neoprene-in-Shear Isolators


Max. Load Defl.
Type Each In. (mm)
Lbs. (kg)
1500 0.25
RP-4 Black
(681) (6.4)
2250 0.25
RP-4 Red
(1019) (6.4)
3300 0.25
RP-4 Green
(1497) (6.4)
4000 0.25
RP-4 Gray
(1816) (6.4)

Figure 5, Spring Flex Mountings,CP-4 Figure 6, Neoprene-in-Shear


Mounting, RP-4

IMM AGSD 11
Installation and Start-up
WARNING
Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar
with local codes and regulations, and experienced with this type of equipment.
Start-up by McQuay Factory Service is included on all units sold for installation within the U.S. and
Canada and must be performed by them to initiate the standard Limited Product Warranty. Start-up by
any party other than McQuay Factory Service or a McQuay Authorized Service Representative will
void the Limited Product Warranty. Two-week prior notification of start-up is required. The
contractor should obtain a copy of the Start-up Scheduled Request Form from the sales representative
or from the nearest McQuay Factory Service office.

WARNING
Escaping refrigerant can displace air and cause suffocation. Immediately evacuate and ventilate
the equipment area. If the unit is damaged, follow Environmental Protection Agency (EPA)
requirements. Do not expose sparks, arcing equipment, open flame or other ignition source to
the refrigerant.

Handling
Avoid rough handling shock due to impact or dropping the unit. Do not push or pull the unit.
Never allow any part of the unit to fall during unloading or moving, as this can result in serious
damage.
To lift the unit, lifting tabs with 2½" (64 mm) diameter holes are provided on the base of the unit. All
lifting holes must be used when lifting the unit. Spreader bars and cables should be arranged to
prevent damage to the condenser coils or unit cabinet (see Figure 7).

DANGER
Improper lifting or moving of a unit can result in property damage, severe
personal injury or death. Follow rigging and moving instructions carefully.
Figure 7, Required Lifting Method

NOTES:
1. All rigging points on a unit must be used. See location
and weights at lifting points beginning on page 4 for a
specific size unit.
2. Crosswise and lengthwise spreader bars must be used
to avoid damage to unit. Lifting cables from the unit
mounting holes up must be vertical.
3. The number of condenser sections, fans, and lifting
points can vary from this diagram.

Location
Locate the unit carefully to provide proper airflow to
the condenser. (See Figure 8 on page 14 for required
clearances.)
Due to the shape of the condenser coils on the AGS
chillers, it is recommended that the unit be oriented

12 IMM AGSD
so that prevailing winds blow parallel to the unit length, thus minimizing the wind effect on
condensing pressure and performance. If low ambient temperature operation is expected, optional
louvers should be installed if the unit has no protection against prevailing winds.
Using less clearance than shown in Figure 8 can cause discharge air recirculation to the condenser and
could have a significant, detrimental effect on unit performance.
See Restricted Airflow beginning on page 15 for further information.
For pad-mounted units, it is recommended that the unit be raised a few inches with suitable supports
such as neoprene waffle vibration pads, located at least under the mounting locations. This will allow
water to drain from under the unit and facilitate cleaning under it.

Service Access
Compressors, filter-driers, and manual liquid line shutoff valves are accessible on each side or end of
the unit. The evaporator heater is located on the barrel.
The control panels are located on the end of the chiller. The left-hand control box contains the unit
and circuit microprocessors as well as transformers, fuses and terminal. The right-hand panel has line
voltage and contains a circuit breaker and starter for each compressor plus fuses, fan VFD (optional)
and fan contactors. A minimum of four feet of clearance is required in front of the panels.
The side clearance required for airflow provides sufficient service clearance.
On all AGS units, the condenser fans and motors can be removed from the top of the unit. The
complete fan/motor assembly can be removed for service. The fan blade must be removed for access
to wiring terminals at the top of the motor.

WARNING
Disconnect, lockout and tag all power to the unit before servicing condenser fan motors or
compressors. Failure to do so can cause bodily injury or death.

Do not block access to the sides or ends of the unit with piping or conduit. These areas must be open
for service access. Do not block any access to the control panels with a field-mounted disconnect
switches.

IMM AGSD 13
Clearance Requirements
Figure 8, Clearance Requirements

No obstructions.
Recommended area
required for unit
operation, air flow
and maintenance
5ft (1.5m) if open fence or 50% open wall access.
6ft (1.8m) if solid wall (see note 3 for pit)

4ft (1.2m)
For electric
panel access

3ft (1m) for service


5ft (1.5m) if open fence or 50% open wall
6ft (1.8m) if solid wall (see note 3 for pit)

Air Flow
See notes 2 & 4
No obstructions allowed
concerning wall
above unit at any height
height at unit sides.

See Note 5

Wall or
Fence

Notes:
1. Minimum side clearance between two units is 12 feet (3.7 meters).
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit unless extra
clearance is provided per note 4.
3. Minimum clearance on each side is 8 feet (2.4 meters) when installed in a pit no deeper than the unit height.
4. Minimum side clearance to a side wall or building taller than the unit height is 6 feet (1.8 meters), provided
no solid wall above 6 feet (1.8 meters) is closer than 12 feet (3.7 meters) to the opposite side of the unit.
5. Do not mount electrical conduits where they can block service access to compressor controls, refrigerant
driers or valves.
6. There must be no obstruction of the fan discharge.
7. Field installed switches must not interfere with service access or airflow.
8. The evaporator can be removed from the side of the unit and may require the temporary removal of a coil
section support post. See dimension drawings beginning on page 29 for details.
9. If the airflow clearances cannot be met, see the following pages on Restricted Airflow.

14 IMM AGSD
Restricted Airflow
General
The clearances required for design operation of AGS air-cooled condensers are described in the
previous section. Occasionally, these clearances cannot be maintained due to site restrictions such as
units being too close together or a fence or wall restricting airflow, or both.
The McQuay AGS chillers have several features that can mitigate the problems attributable to
restricted airflow.
• The shape of the condenser section allows inlet air for these coils to come in from both sides and
the bottom. All the coils on one side serve one compressor. Every compressor always has its own
independent refrigerant circuit.
• The MicroTech II® control is proactive in response to off-design conditions. In the case of single
or compounded influences restricting airflow to the unit, the microprocessor will act to keep the
compressor(s) running (at reduced capacity) as long as possible, rather than allowing a shut-off on
high discharge pressure.

Figure 9, Coil and Fan Arrangement


Building

The following sections discuss the most common situations of condenser air restriction and give
capacity and power adjustment factors for each. Note that in unusually severe conditions, the
MicroTech II controller will adjust the unit operation to remain online until a less severe condition is
reached.

IMM AGSD 15
Case 1, Building or Wall on One Side of One Unit
The existence of a screening wall, or the wall of a building, in close proximity to an air-cooled chiller
is common in both rooftop and ground level applications. Hot air recirculation on the coils adjoining
the wall will increase compressor discharge pressure, decreasing capacity and increasing power
consumption.
When close to a wall, it is desirable to place chillers on the north or east side of them. It is also
desirable to have prevailing winds blowing parallel to the unit’s long axis. The worst case is to have
wind blowing hot discharge air into the wall.

Figure 10, Unit Adjacent to Wall

H
D

Figure 11, Adjustment Factors

5 ft. 5 ft.
(1.5m) (1.5m)

6 ft. 6 ft.
(1.8m) (1.8m)

16 IMM AGSD
Case 2, Two Units Side By Side
Two or more units sited side by side are common. If spaced closer than 12 feet (3.7 meters), or 8 feet
(2.5 meters), depending on size, it is necessary to adjust the performance of each unit. Circuits
adjoining each other are affected. NOTE: This case applies only to two units side by side. See Case 3
for three or more parallel units. If one of the two units also has a wall adjoining it, see Case 1. Add
the two adjustment factors together and apply to the unit located between the wall and the other unit.
Mounting units end to end will not necessitate adjusting performance. Depending on the actual
arrangement, sufficient space must be left between the units for access to the control panel door
opening and/or evaporator tube removal. See “Clearance” section of this guide for requirements for
specific units.

Figure 12, Two Units Side by Side

Figure 13, Adjustment Factor

3.0 6.0

2.0 4.0

1.0 2.0

0 0
9 10 11 12 9 10 11 12
(2.7) (3.0) (3.3) (3.6) (2.7) (3.0) (3.3) (3.6)

IMM AGSD 17
Case 3, Three or More Units Side By Side
When three or more units are side by side, the outside units (chillers 1 and 3 in this case) are
influenced by the middle unit only on their inside circuits. Their adjustment factors will be the same
as Case 2. All inside units (only chiller 2 in this case) are influenced on both sides and must be
adjusted by the factors shown below.

Figure 14, Three or More Units

Chiller 1 Chiller 2 Chiller 3

Figure 15, Adjustment Factor

4.0 8.0

3.0 6.0

2.0 4.0

1.0 2.0

0 0
15 16 17 18 15 16 17 18
(4.6) (4.9) (5.2) (5.5) (4.6) (4.9) (5.2) (5.5)

18 IMM AGSD
Case 4, Open Screening Walls
Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop. These
walls should be designed such that the combination of their open area and distance from the unit do
not require performance adjustment. It is assumed that the wall height is equal to or less than the unit
height when mounted on its base support. This is usually satisfactory for concealment. If the wall
height is greater than the unit height, see Case 5, Pit Installation.
The distance from the ends of the unit to the end walls must be sufficient for service, opening control
panel doors, and pulling evaporator tubes, as applicable.
If each side wall is a different distance from the unit, the distances can be averaged, providing either
wall is not less than 8 feet (2.4 meters) from the unit. For example, do not average 4 feet and 20 feet to
equal 12 feet.

Figure 16, Open Screening Walls

Figure 17, Wall Free Area vs. Distance

IMM AGSD 19
Case 5, Pit/Solid Wall Installation
Pit installations can cause operating problems and great care must be exercised if they are to be used
on an installation. Recirculation and restriction can both occur. A solid wall surrounding a unit is
substantially the same as a pit and the data presented in this case should be used.
Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit. The
grating material and installation design must be strong enough to prevent such accidents, yet provide
abundant open area or serious recirculation problems will occur. Have any pit installation reviewed by
the McQuay Factory Service prior to installation to discuss whether it has sufficient airflow
characteristics. The installation design engineer must approve the work and is responsible for design
criteria.

Figure 18, Pit Installation

Figure 19, Adjustment Factor

20 IMM AGSD
Chilled Water
It is recommended that the chilled water pumps' starters be wired to, and controlled by, the chiller's
microprocessor. The controller will energize the pump whenever at least one circuit on the chiller is
enabled to run, whether there is a call for cooling or not. The control will also start the pump when
freezing temperatures are approached. Wiring connection points are shown in Figure 28 on page 48.

Water Piping
Due to the variety of piping practices, follow the recommendations of local authorities. They can
supply the installer with the proper building and safety codes required for a proper installation.
Design the piping with a minimum number of bends and changes in elevation to keep system cost
down and performance up. It should contain:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system and drains at the low parts in
the system. The evaporator should not be the highest point in the piping system.
4. Some means of maintaining adequate system water pressure (i.e., expansion tank or regulating
valve).
5. Water temperature and pressure indicators located at the evaporator inlet and outlet to aid in unit
servicing. Any connections should be made prior to filling the system with water.
6. A strainer to remove foreign matter from the water before it enters the pump. Place the strainer far
enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for
recommendations). The use of a strainer will prolong pump life and help maintain high system
performance levels.

NOTE: A 20-mesh strainer must also be placed in the supply water line just prior to the inlet of the
evaporator. This will aid in preventing foreign material from entering the evaporator and causing
damage or decreasing its performance. Care must also be exercised if welding pipe or flanges to the
evaporator connections to prevent any weld slag from entering the vessel. Units equipped with the
optional pump package will have a strainer in the pump suction.

7. Any water piping to the unit must be protected to prevent freeze-up if below freezing temperatures
are expected.

CAUTION
If a separate disconnect is used for the 115V supply to the unit, it should power the entire control
circuit. It should be clearly marked so that it is not accidentally shut off during cold seasons.
Freeze damage to the evaporator could result. If the evaporator is drained for winter freeze
protection, the heaters must be de-energized to prevent burnout.
8. If the unit is used as a replacement chiller on a previously existing piping system, flush the system
thoroughly prior to unit installation. Perform regular chilled water analysis and chemical water
treatment immediately at equipment start-up.
9. In the event glycol is added to the water system as a late addition for freeze protection, recognize
that the refrigerant suction pressure will be lower, cooling performance less, and water side
pressure drop greater. If the percentage of glycol is large, or if propylene is employed in lieu of
ethylene glycol, the added pressure drop and loss of performance could be substantial.

IMM AGSD 21
10. For ice making or low temperature glycol operation, a different freezestat pressure value is usually
required. The freezestat setting can be manually changed through the MicroTech II controller.
Make a preliminary leak check prior to insulating the water piping and filling the system.
Include a vapor barrier with the piping insulation to prevent moisture condensation and possible
damage to the building structure. It is important to have the vapor barrier on the outside of the
insulation to prevent condensation within the insulation on the cold surface of the pipe.

System Water Volume


All chilled water systems need adequate time to recognize a load change, respond to that load change
and stabilize, without undesirable short cycling of the compressors or loss of control. In air
conditioning systems, the potential for short cycling usually exists when the building load falls below
the minimum chiller plant capacity or on close-coupled systems with very small water volumes.
Some of the things the designer should consider when looking at water volume are the minimum
cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time
for the compressors.
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a
rule of thumb of “gallons of water volume equal to two to three times the chilled water gpm flow rate”
is often used.
A properly designed storage tank should be added if the system components do not provide sufficient
water volume.

Variable Speed Pumping


Variable water flow involves reducing the water flow through the evaporator as the load decreases.
McQuay chillers are designed for this duty, provided that the rate of change in water flow is slow, and
the minimum and maximum flow rates for the vessel are not exceeded.
The recommended maximum change in water flow is 10 percent of the change per minute.
The water flow through the vessel must remain between the minimum and maximum values listed on
page 27. If flow drops below the minimum allowable, large reductions in heat transfer can occur. If
the flow exceeds the maximum rate, excessive pressure drop and tube erosion can occur.

Evaporator Freeze Protection


AGS chillers are equipped with thermostatically controlled evaporator heaters that help protect against
freeze-up down to -20°F (-28°C).

NOTE: The heaters come from the factory connected to the control power circuit. The control power
can be rewired in the field to a separate 115V supply (do not wire directly to the heater). See the field
wiring diagram on page 48. If this is done, mark the disconnect switch clearly to avoid accidental
deactivation of the heater during freezing temperatures. Exposed chilled water piping also requires
protection.

For additional protection, at least one of the following procedures should be used during periods of
sub-freezing temperatures:
1. Adding of a concentration of a glycol anti-freeze with a freeze point 10 degrees F. below the
lowest expected temperature. This will result in decreased capacity and increased pressure drop.

Note: Do not use automotive grade antifreezes as they contain inhibitors harmful to chilled water
systems. Use only glycols specifically designated for use in building cooling systems.

22 IMM AGSD
2. Draining the water from outdoor equipment and piping and blowing the chiller tubes dry from the
chiller. Do not energize the chiller heater when water is drained from the vessel.

CAUTION
If fluid is absent from the evaporator, the evaporator heater must be de-energized to avoid
burning out the heater or causing damage from the high temperatures.
1. Providing operation of the chilled water pump, circulating water through the chilled water system
and through the evaporator.
Table 19, Freeze Protection
Percent Volume Glycol Concentration Required
Temperature
For Freeze Protection For Burst Protection
°F (°C)
Ethylene Glycol Propylene Glycol Ethylene Glycol Propylene Glycol
20 (6.7) 16 18 11 12
10 (-12.2) 25 29 17 20
0 (-17.8) 33 36 22 24
-10 (-23.3) 39 42 26 28
-20 (-28.9) 44 46 30 30
-30 (-34.4) 48 50 30 33
-40 (-40.0) 52 54 30 35
-50 (-45.6) 56 57 30 35
-60 (-51.1) 60 60 30 35
Notes:
1. These figures are examples only and cannot be appropriate to every situation. Generally, for an extended
margin of protection, select a temperature at least 15°F lower than the expected lowest ambient temperature.
Inhibitor levels should be adjusted for solutions less than 25% glycol.
2. Glycol of less than 25% concentration is not recommended because of the potential for bacterial growth and
loss of heat transfer efficiency.

IMM AGSD 23
Operating Limits:
Maximum standby ambient temperature, 130°F (55°C)
Maximum operating ambient temperature, 105°F. See High Ambient Option below.
Minimum operating ambient temperature (standard), 35°F (2°C)
Minimum operating ambient temperature (optional low-ambient control), 0°F (-18°C)
Leaving chilled water temperature, 40°F to 60°F (4°C to 16°C)
Leaving chilled fluid range (with anti-freeze), 20°F to 60°F (-7°C to 16°C). Unloading is not
permitted with fluid leaving temperatures below 30°F (-1°C).
Operating Delta-T range, 6 degrees F to 16 degrees F (10.8°C to 28.8°C)
Maximum operating inlet fluid temperature, 76°F (24°C)
Maximum startup inlet fluid temperature, 90°F (32°C)
Maximum non-operating inlet fluid temperature, 100°F (38°C)
NOTE: Contact the local McQuay sales office for operation outside any of these limits.
High Ambient Option, A factory-installed option that allows operation in high ambient temperature
locations with operating temperatures above 105°F up to 125°F (40.6°C to 51.7°C).

Flow Switch
A flow switch must be included in the chilled water
system to prove that there is adequate water flow to the Figure 20, Flow Switch
evaporator before the unit can start. It also serves to Flow direction marked
on switch
shut down the unit in the event that water flow is
1" (25mm) NPT flow
interrupted in order to guard against evaporator freeze- switch connection

up.
Tee
A solid state, thermal dispersion flow switch that is
factory-mounted in the chiller leaving water nozzle and
factory-wired is available as an option.
1 1/4" (32mm) pipe
A paddle-type flow switch for field mounting and 1 1/4" (32mm) pipe dia. min. before switch
dia. min. after switch
wiring in the leaving chilled water is also available as
an option from McQuay under ordering number 017503300. It is adaptable to any pipe size from 1"
(25mm) to 8" (203mm) nominal.
Certain minimum flow rates are required to close the switch and are listed in Table 20. Installation
should be as shown in Figure 17.
Electrical connections in the unit control center should be made at terminals 60 and 67 from switch
terminals Y and R. The normally open contacts of the flow switch should be wired between these two
terminals. Flow switch contact quality must be suitable for 24 VAC, low current (16ma). Flow switch
wire must be in separate conduit from any high voltage conductors (115 VAC and higher) and have an
insulation rating of 600 volts.

24 IMM AGSD
Table 20, Paddle Type Flow Switch Flow Rates
Pipe Size inch 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8
(NOTE !) mm 32 (2) 38 (2) 51 63 (3) 76 102 (4) 127 (4) 153 (4) 204 (5)
gpm 5.8 7.5 13.7 18.0 27.5 65.0 125.0 190.0 205.0
Flow
Min. Lpm 1.3 1.7 3.1 4.1 6.2 14.8 28.4 43.2 46.6
Adjst. No gpm 3.7 5.0 9.5 12.5 19.0 50.0 101.0 158.0 170.0
Flow Lpm 0.8 1.1 2.2 2.8 4.3 11.4 22.9 35.9 38.6
gpm 13.3 19.2 29.0 34.5 53.0 128.0 245.0 375.0 415.0
Flow
Max. Lpm 3.0 4.4 6.6 7.8 12.0 29.1 55.6 85.2 94.3
Adjst. No gpm 12.5 18.0 27.0 32.0 50.0 122.0 235.0 360.0 400.0
Flow Lpm 2.8 4.1 6.1 7.3 11.4 27.7 53.4 81.8 90.8
NOTES:
1. A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose.
2. Flow rates for a 2-inch paddle trimmed to fit the pipe.
3. Flow rates for a 3-inch paddle trimmed to fit the pipe.
4. Flow rates for a 3-inch paddle.
5. Flow rates for a 6-inch paddle.

Figure 21, Typical Field Water Piping


Suction
Vent Water
In Strainer
Flow
Vibration Gate
Valved Eliminator Valve
Pressure
Gauge
Protect All Field Piping
Out Against Freezing
Flow
Vibration Flow
Liquid Balancing Gate
Eliminator Switch
Drain Valve Valve

Notes:
1. Connections for vent and drain fittings are located on the top and bottom of the evaporator.
2. Piping must be supported to avoid putting strain on the evaporator nozzles.

Refrigerant Charge
All packaged units are designed for use with R-134a and are shipped with a full operating charge. The
operating charge for each unit is shown in the Physical Data Tables beginning on page 28.

Glycol Solutions
When using glycol anti-freeze solutions, the chiller's capacity, glycol solution flow rate, and pressure
drop through the evaporator can be calculated using the following formulas and tables.

Note: The procedure below does not specify the type of glycol. Use the derate factors found in Table
21 for corrections when using propylene glycol and those in Table 22 for ethylene glycol.

1. Capacity - Cooling capacity is reduced from that with plain water. To find the reduced value,
multiply the chiller’s water system tonnage by the capacity correction factor to find the chiller’s
capacity when using glycol.
2. Flow - To determine flow (or Delta-T) knowing Delta-T (or flow) and capacity:

GPM =
(24) (tons ) ( flow factor )
Delta − T
3. Pressure drop - To determine pressure drop through the evaporator when using glycol, enter the
water pressure drop curve at the water flow rate. Multiply the water pressure drop found there by
the "PD" factor to obtain corrected glycol pressure drop.

IMM AGSD 25
4. Power - To determine glycol system kW, multiply the water system kW by the factor designated
"Power".
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service stations)
to determine the freezing point. Obtain percent glycol from the freezing point table below. On glycol
applications, the supplier normally recommends that a minimum of 25% solution by weight be used
for protection against corrosion or that additional inhibitors should be employed.
NOTE: Do not use automotive grade antifreeze. Industrial grade glycols must be used. Automotive
antifreeze contains inhibitors that will cause plating on the copper tubes within the chiller evaporator.
The type and handling of glycol used must be consistent with local codes.

Table 21, Ethylene Glycol Factors Table 22, Propylene Glycol Factors
Freeze Freeze
% Point Point Capacit
Capacity Power Flow PD % P.G. Power Flow PD
E.G. o o o o y
F C F C
10 26 -3.3 0.996 0.998 1.036 1.097 10 26 -3.3 0.991 0.996 1.016 1.092
20 18 -7.8 0.988 0.994 1.061 1.219 20 19 -7.2 0.981 0.991 1.032 1.195
30 7 -13.9 0.979 0.991 1.092 1.352 30 9 -12.8 0.966 0.985 1.056 1.345
40 -7 -21.7 0.969 0.986 1.132 1.532 40 -5 -20.6 0.947 0.977 1.092 1.544
50 -28 -33.3 0.958 0.981 1.182 1.748 50 -27 -32.8 0.932 0.969 1.140 1.906

Water Flow and Pressure Drop


Adjust the chilled water flow through the evaporator to meet specified conditions. The flow rates must
fall between the minimum and maximum values shown in the table on the following page. Flow rates
below the minimum values shown can result in laminar flow that will reduce efficiency, cause erratic
operation of the electronic expansion valve and could cause low temperature cutouts. On the other
hand, flow rates exceeding the maximum values shown can cause erosion on the evaporator water
connections and tubes.
Measure the chilled water pressure drop through the evaporator at field-installed pressure taps. It is
important not to include valve or strainer pressure drops in these readings.

26 IMM AGSD
Figure 22, Standard Efficiency, Evaporator Pressure Drop

Standard Efficiency, Minimum/Nominal/Maximum Flow Rates


AGS CURVE MINIMUM FLOW NOMINAL FLOW MAXIMUM FLOW
MODEL GPM FT L/S KPA GPM FT L/S KPA GPM FT L/S KPA
225DS A 252 3.9 15.9 11.6 507 14.3 32.0 42.6 845 37.0 53.3 110.3
250DS A 252 3.9 15.9 11.6 556 17.0 35.1 50.7 926 43.0 58.5 128.1
275DS B 292 2.2 18.4 6.6 631 9.5 39.8 28.3 1052 26.5 66.4 79.0
300DS C 355 3.7 22.4 11.0 713 12.2 45.0 36.4 1188 33.3 75.0 99.2
330DS D 356 2.7 22.5 8.0 765 11.4 48.3 34.0 1275 30.0 80.4 89.4
350DS D 356 2.7 22.5 8.0 809 12.6 51.1 37.5 1349 34.0 85.1 101.3
360DS E 407 3.9 25.7 11.6 843 15.4 53.2 45.9 1404 40.0 88.6 119.2
390DS E 407 3.9 25.7 11.6 896 17.3 56.5 51.6 1493 45.0 94.2 134.1
400DS F 470 3.3 29.7 9.8 937 12.2 59.1 36.4 1562 32.0 98.6 95.4
450DS F 470 3.3 29.7 9.8 1044 15.0 65.9 44.7 1740 37.0 109.8 110.3

IMM AGSD 27
Figure 23, High Efficiency, Evaporator Pressure Drops

High Efficiency, Minimum/Nominal/Maximum Flow Rates


AGS CURVE MINIMUM FLOW NOMINAL FLOW MAXIMUM FLOW
MODEL gpm ft l/s kpa gpm ft l/s kpa gpm ft l/s kpa
225DE A 260 2.3 16.4 6.9 516 8.7 32.5 25.9 860 23.4 54.2 69.7
250DE A 260 2.3 16.4 6.9 565 10.4 35.7 31.0 942 28.0 59.4 83.4
260DE B 292 2.2 18.4 6.6 599 8.7 37.8 25.9 998 23.5 63.0 70.0
275DE B 292 2.2 18.4 6.6 642 9.8 40.5 29.2 1070 26.5 67.5 79.0
300DE C 355 3.6 22.4 10.7 719 13.4 45.3 39.9 1198 36.0 75.6 107.3
330DE D 356 2.6 22.5 7.7 778 11.4 49.1 34.0 1296 28.0 81.8 83.4
350DE E 407 3.9 25.7 11.6 823 15.0 51.9 34.0 1372 38.4 86.5 114.4
400DE F 470 3.2 29.7 9.5 953 12.1 60.2 44.7 1589 31.0 100.3 92.4
450DE F 470 3.2 29.7 9.5 1051 14.5 66.3 36.1 1751 38.1 110.5 113.5

28 IMM AGSD
Physical Data, Standard Efficiency
Table 23, Standard Efficiency, AGS 225DS – AGS 275DS
AGS-DS MODEL NUMBER
DATA 225DS 250DS 275DS
Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI tons (kW) 211.2 (742.6) 231.6 (814.3) 263.1 (925.1)
Unit Operating Charge lbs (kg) 185 (84) 185 (84) 210 (95) 210 (95) 210 (95) 240 (109)
Cabinet Dimensions 243x88x97 279x88x97 314x88x97
L x W x H, in. (mm) (6172x2225x2464) (7087x2225x2464) (7984x2225x2464)
Unit Operating Weight, lbs. (kg) 12556 (5700) 13398 (6069) 14958 (6785)
Unit Shipping Weight, lbs (kg) 12007 (5451) 12849 (5821) 14049 (6374)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 125 (4370 125 (4370 150 (525)
Minimum Capacity (% of Full Load) 15 15 15
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 249 (113) 249 (113) 287 (130) 287 (130) 287 (130) 325 (148)
Coil Inlet Face Area, sq. ft. (sq m.) 129.2 (12.0) 129.2 (12.0) 150.8 (14.0) 150.8 (14.0) 150.8 (14.0) 172.5 (16.0)
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Circuit – 30 in. Fan Dia. 6 6 7 7 8 8
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 137328 (64819) 160216 (75622) 183104 (86425)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia.-Tube Length
16x108 (406x2750) 16x108 (406x2750) 20x108 (508x2750)
in.(mm) - in. (mm)
Water Volume, gallons (liters) 65.8 (249.4) 65.8 (249.4) 108.5 (411.1)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

Table 24, Standard Efficiency, AGS 300DS


AGS MODEL NUMBER
DATA 300DS
Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI, tons (kW) 297.0 (1042.5)
Unit Operating Charge lbs (kg) 240 (109) 240 (109)
Cabinet Dimensions 314x88x97
L x W x H, in. (mm) (7984x2225x2464)
Unit Operating Weight (1), lbs. (kg) 14903 (6751)
Unit Shipping Weight(1), lbs (kg) 14954 (6760)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 150 (525) 150 (525)
Minimum Capacity (% of Full Load) 15
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE
Pumpdown Capacity, lbs (kg) 325 (148) 325 (148)
Coil Inlet Face Area, sq. ft. (sq m.) 172.5 (16.0) 172.5 (16.0)
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Circuit – 30 in. Fan Dia 8 8
Fan Motor -- hp (kW) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 183104 (86425)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia.-Tube Length
20x108 (508x2750)
in.(mm) - in. (mm)
Water Volume, gallons (liters) 103.2 (391.2)
Max. Water Pressure, psi (kPa) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413)

IMM AGSD 29
Table 25, Standard Efficiency, AGS 330DS – AGS 360DS
AGS MODEL NUMBER
DATA 330DS 350DS 360DS
Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW) 318.7 (1120.5) 337.2 (1185.6) 351.1 (1234.5)
Unit Operating Charge, lbs (kg) 210 (95) 210 (95) 190 (86 210 (95) 210 (95) 190 (86) 210 (95) 210 (95) 190 (86)
Cabinet Dim., 403x88x97 403x88x97 403x88x97
L x W x H, in. (mm) (10239x2225x2459) (10239x2225x2459) (10239x2225x2459)
Operating Weight(1), lbs. (kg) 20507 (9302) 20507 (9302) 20517 (9307)
Shipping Weight(1), lbs (kg) 19596 (8889) 19596 (8889) 19639 (8908)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 100 (350) 125 (437) 100 (350) 125 (437) 125 (437) 100 (350)
Minimum Capacity (% of Full Load) 10 10 10
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 287 (130) 287 (130) 243 (110) 287 (130) 287 (130) 243 (110) 287 (130) 287 (130) 243 (110)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14) 150.8 (14) 128.5 (12) 150.8 (14) 150.8 (14) 128.5 (12) 150.8 (14) 150.8 (14) 128.5 (12)
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Cir, Fan Dia. 30 in 7 7 6 7 7 6 7 7 6
Fan Motor -- hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 228880 (108031) 228880 (108031) 228880 (108031)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia.,Tube Length in.(mm) 20x108 (508x2750) 20x108 (508x2750) 20x108 (508x2750)
Water Volume, gallons (liters) 107.0 (405.4) 107.0 (405.4) 103.2 (391.2)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

Table 26, Standard Efficiency, AGS 390DS – AGS 450DS


AGS MODEL NUMBER
DATA 390DS 400DS 450DS
Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW) 373.2 (1311.8) 390.4 (1373.3)) 434.8 (1529.1)
Unit Operating Charge, lbs (kg) 210 (95) 210 (95) 230 (104) 215 (97) 215 (97) 235 (106) 140 (109) 140 (109) 140 (109)
439x88x97 439x88x97 474x88x97
Cabinet Dim., L x W x H, in. (mm)
11140x2225x2459) 11140x2225x2459) 12040x2225x2459)
Operating Weight(1), lbs. (kg) 21156 (9596) 21708 (9847) 22485 (10199)
Shipping Weight(1), lbs (kg) 20278 (9198) 20549 (9321) 21326 (9674)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 125 (437) 125 (437) 125 (437) 125 (437) 125 (437) 150 (525) 150 (525) 150 (525) 150 (525)
Minimum Capacity (% of Full Load) 10 10 10
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 287 (130) 287 (130) 316 (144) 287 (130) 287 (130) 316 (144) 325 (147) 325 (147) 316 (144)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14) 150.8 (14) 171.7 (16) 150.8 (14) 150.8 (14) 171.7 (16) 172.5 (16) 172.5 (16) 171.7 (16
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Circuit – 30 in. Fan Dia 7 7 8 7 7 8 8 8 8
Fan Motor -- hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 251768 (118835) 251768 (118835) 274656 (129637)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia.,Tube Length in.(mm) 20x108 (508x2750) 20x149 (508x3785) 20x149 (508x3785)
Water Volume, gallons (liters) 103.2 (391.2) 97.2 (368.5) 97.2 (368.5)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

30 IMM AGSD
Physical Data, High Efficiency
Table 27, High Efficiency, AGS 225DE – AGS 260DE
AGS-DE MODEL NUMBER
DATA 225DE 250DE 260DE
Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI, Tons (Kw) 214.9 (755.6) 235.5 (828.0) 249.6 (877.6)
R-134a, Operating Charge lbs (kg) 210 (95) 210 (95) 210 (95) 210 (95) 240 (109) 240 (109)
Cabinet Dimensions 279x88x97 314x88x97 314x88x97
L x W x H, in. (mm) (7087x2225x2464) (7984x2225x2464) (7984x2225x2464)
Unit Operating Weight, lbs. (kg) 13418 (6086) 14544 (6597) 14913 (6765)
Unit Shipping Weight, lbs (kg) 12869 (5837) 13639 (6187) 14008 (6354)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 125 (437) 125 (4370 125 (437)
Minimum Capacity (% of Full Load) 15 151 15
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 249 (13) 249 (113) 287 (130) 287 (130) 325 (147) 325 (147)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14.0) 150.8 (14.0) 150.8 (14.0) 172.5 (16) 172.5 (16.0) 172.5 (16.0)
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Circuit – 30 in. Fan Dia. 7 7 8 8 8 8
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 160216 (75622) 18310 (86424) 183104 (86425)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia.-Tube Length
16x108 (406x2750) 16x108 (406x2750) 20x108 (508x2750)
in.(mm) - in. (mm)
Water Volume, gallons (liters) 63.6 (241.0) 63.6 (241.0) 108.5 (411.1)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

Table 28, High Efficiency, AGS 275DE – AGS 300DE


AGS MODEL NUMBER
DATA 275DE 300DE
Ckt 1 Ckt 2 Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI, tons (kW) 267.7 (940.9) 299.5 (1053.0)
Unit Operating Charge lbs (kg) 240 (109) 260 (118) 265 (120) 265 (120)
Cabinet Dimensions 350x88x97 350x88x97
L x W x H, in. (mm) (8890x2225x2464) (8890x2225x2464)
Unit Operating Weight (1), lbs. (kg) 15671 (7109) 15669 (7107)
Unit Shipping Weight(1), lbs (kg) 14766 (6698) 14808 (6717)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 125 (437) 150 (525) 150 (525) 150 (525)
Minimum Capacity (% of Full Load) 15 15
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 325 (147) 361 (164) 361 (164) 361 (164)
Coil Inlet Face Area, sq. ft. (sq m.) 172.5 (16.0) 194.2 (18.0) 194.2 (18.0) 194.2 (18.0)
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Circuit – 30 in. Fan Dia. 9 9 9 9
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 205992 (97228) 205992 (97228)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia.-Tube Length
20x108 (508x2750) 20x108 (508x2750)
in.(mm) - in. (mm)
Water Volume, gallons (liters) 108.5 (411.1) 103.2 (391.2)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413)

IMM AGSD 31
Table 29, High Efficiency, AGS 330DE – AGS 400DE
AGS MODEL NUMBER
DATA 330DE 350DE 400DE
Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW) 324.1 (1139.6) 342.9 (1205.6) 397.1 (1396.6)
Unit Operating Charge, lbs (kg) 210 (95) 210 (95) 230 (104) 210 (95) 240 (109) 240 (109) 240 (109) 240 (109) 240 (109)
439x88x97 474x88x97 474x88x97
Cabinet Dim., L x W x H, in. (mm)
(11140x2225x2459) (12040x2225x2459) (12040x2225x2459)
Operating Weight(1), lbs. (kg) 21146 (9592) 21918 (9942) 22485 (10199)
Shipping Weight(1), lbs (kg) 20235 (9178) 21040 (9544) 21326 (9674)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 100 (350) 125 (437) 100 (350) 125 (437) 125 (437) 150 (525)
Minimum Capacity (% of Full Load) 10 10 10
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 287 (130) 287 (130) 316 (1440 325 (147) 325 (147) 316 (144) 325 (147) 325 (147) 316 (144)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14) 150.8 (14) 171.7 (16) 150.8 (14) 172.5 (16) 171.7 (16) 172.5 (16) 172.5 (16) 171.7 (16)
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Circuit – 30 in. Fan Dia. 7 7 8 8 8 8 8 8 8
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 251768 (118834) 274656 (129638) 274656 (129638)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia.,Tube Length in.(mm) 20x108 (508x2750) 20x108 (508x2750) 20x142 (508x3600)
Water Volume, gallons (liters) 103.2 (391.2) 102.1 (387.0) 90.5 (343.0)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

Table 30, High Efficiency, AGS 450DE


AGS MODEL NUMBER
DATA 450DE
Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW) 438.0 (1540.0)
Unit Operating Charge, lbs (kg) 270 (122) 270 (122) 240 (109)
509x88x97
Cabinet Dim., L x W x H, in. (mm)
(12939x2225x2459)
Unit Operating Weight, lbs. (kg) 23403 (10616)
Unit Shipping Weight, lbs (kg) 22244 (10090)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 150 (525) 150 (525) 150 (525)
Minimum Capacity (% of Full Load) 10
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE
Pumpdown Capacity, lbs (kg) 361 (164) 361 (164) 316 (144)
Coil Inlet Face Area, sq. ft. (sq m.) 172.5 (16) 194.2 (18) 171.7 (16)
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans/Circuit – 30 in. Fan Dia. 9 9 8
Fan Motor hp (kW) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 297544 (140440)
EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE
Shell Dia. -- Tube Length
20x142 (508x142)
in.(mm) - in. (mm)
Water Volume, gallons (liters) 90.5 (343.0)
Max. Water Pressure, psi (kPa) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413)

32 IMM AGSD
Dimensions
Standard Efficiency
Figure 24, Standard Efficiency, AGS 225DS – AGS 300DS

Note:
1. See page 4 and following pages for weights and mounting loads.
2. A 14-fan unit is illustrated. See tables below of the number of fans on a specific model.
3. Mounting holes are ¾-inch diameter.
4. Allow 1-inch manufacturing tolerance on all dimensions.

Weights and Dimensions (lb, in)


Shipping Operating No. of Mounting Lifting Center of Gravity
Unit Size A F G H J K
Weight Weight Fans B C D E X Y Z
AGS225DS 12007 12556 12 243.3 N/A 210.8 N/A 217.7 6.0 95.0 116.4 26.6 18.4 45.6 39.9 95.0
AGS250DS 12849 13398 14 278.7 102.1 255.9 194.1 253.2 6.0 95.0 116.4 26.6 18.4 45.2 40.8 105.3
AGS275DS 14053 14958 16 314.2 102.1 250.1 199.7 288.6 8.0 92.9 117.7 25.3 20.4 44.9 40.6 114.7
AGS300DS 14049 14954 16 314.2 102.1 250.1 199.7 288.6 8.0 92.9 117.7 25.3 20.4 45.3 41.0 116.6
NOTE: Weights are with aluminum fins, add 131 pounds per fan section for copper fins.

Weights and Dimensions (kg, mm)


Shipping Operating No. of Mounting Lifting Center of Gravity
Unit Size A F G H J K
Weight Weight Fans B C D E x y z Z
AGS225DS 5446 5695 12 6180 N/A 5354 N/A 5530 152 2413 2956 676 467 1157 1014 2412
AGS250DS 5828 6077 14 7079 2594 6500 4930 6431 152 2413 2956 676 467 1147 1037 2675
AGS275DS 6374 6784 16 7981 2594 6353 5072 7330 203 2360 2989 643 518 1141 1031 2914
AGS300DS 6349 6760 16 7981 2594 6353 5072 7330 203 2360 2989 643 518 1150 1041 2961
NOTE: Weights are with aluminum fins, add 59 kilograms per fan section for copper fins.

IMM AGSD 33
Figure 25, Standard Efficiency, AGS 330DS – 450DS

Note:
1. See page 4 and following pages for weights and mounting loads.
2. A 20-fan unit is illustrated. See tables below of the number of fans on a specific model.
3. Mounting holes are ¾-inch diameter.
4. Allow 1-inch manufacturing tolerance on all dimensions.

Weights and Dimensions (lb, in)


Shipping Operating No. of Lifting Locations Mounting Locations Center of Gravity
Unit Size A H
Weight Weight Fans B C D E F G X Y Z
AGS330DS-
19596 20507 20 403.1 140.8 262.0 339.3 177.0 269.3 361.6 92.9 43.5 39.7 149.6
350DS
AGS360DS 19639 20517 20 403.1 140.8 262.0 339.3 177.0 269.3 361.6 92.9 43.5 39.7 149.6
AGS390DS 20278 21156 22 438.6 140.8 262.0 348.3 177.0 269.3 361.6 92.9 43.8 40.1 158.2
AGS400DS 20549 21708 22 438.6 140.8 262.0 348.3 177.0 269.3 361.6 126.4 43.8 40.1 161.8
AGS450DS 21326 22485 24 474.0 140.8 297.4 383.8 177.0 304.7 397.0 126.4 43.8 40.1 173.0
NOTE: Weights are with aluminum fins, add 131 pounds per fan section for copper fins.

Weights and Dimensions (kg, mm)


Shipping Operating No. of Lifting Locations Mounting Locations Center of Gravity
Unit Size A H
Weight Weight Fans B C D E F G X Y Z
AGS330DS-
8889 9302 20 10239 3576 6655 8618 4496 6840 9185 2360 1105 1008 3800
350DS
AGS360DS 8908 9307 20 10239 3576 6655 8618 4496 6840 9185 2360 1105 1008 3800
AGS390DS 9198 9596 22 11140 3576 6655 8847 4496 6840 9185 2360 1113 1019 4018
AGS400DS 9321 9847 22 11140 3576 6655 8847 4496 6840 9185 3211 1113 1019 4110
AGS450DS 9674 10199 24 12040 3576 7554 9749 4496 7739 10085 3211 1113 1019 4395
NOTE: Weights are with aluminum fins, add 59 kilograms per fan section for copper fins.

34 IMM AGSD
High Efficiency
Figure 26 , High Efficiency, Dimensions, AGS 225DE –300DE
CONTROL POWER POWER
PANEL PANEL PANEL

EVAP EVAP
OUTLET INLET FIELD MAIN DISC
96.81 CONTROL SWITCH
88.91 2459
2258

Y 32.85 POWER E
834

K Z 32.53 CIR # 1 CIR # 2


F
826 X
B 87.60
G H 2225
C
.75 3.15
19 80

81.30
2065

25.59
BOTTOM VIEW 84.65 650
2150
D 3314901 D 00
E
A

Note:
1. See page 4 and following pages for weights and mounting loads.
2. A 14-fan unit is illustrated. See tables below of the number of fans on a specific model.
3. Mounting holes are ¾-inch diameter.
4. Allow 1-inch manufacturing tolerance on all dimensions.

Inch-Pound Units of Measure


Unit Shipping Operating Number Lifting Loc. Mount Loc. Center of Gravity
A F G H J
Model Weight. Weight of Fans B C D E X Y Z
AGS225DE 12869 13418 14 278.7 102.1 255.9 194.1 253.2 6.0 95.0 116.4 26.6 18.4 45.2 40.8
AGS250DE 13639 14544 16 314.2 102.1 250.1 199.7 288.6 6.0 95.0 116.4 26.6 18.4 44.9 40.6
AGS260DE 14008 14913 16 314.2 102.1 250.1 199.7 288.6 8.0 92.9 117.7 25.3 20.4 45.3 41.0
AGS275DE 14766 15671 18 349.6 102.1 266.4 198.8 324.0 8.0 92.9 117.7 25.3 20.4 44.8 41.6
AGS300DE 14808 15669 18 349.6 102.1 266.4 198.8 324.0 8.0 92.9 117.7 25.3 20.4 45.1 42.4
NOTES:
1. Dimensions in inches, weights in pounds.
2. Weights are with aluminum fins, add 131 pounds per fan section for copper fins

SI Units of Measure
Unit Shipping Operating Number Lifting Loc. Mount Loc. Center of Gravity
A F G H J
Model Weight. Weight of Fans B C D E X Y Z
AGS225DE 5837 6086 14 7079 2594 6500 4930 6431 152 2413 2956 676 467 1147 1037
AGS250DE 6187 6597 16 7981 2594 6353 5072 7330 152 2413 2956 676 467 1141 1031
AGS260DE 6354 6765 16 7981 2594 6353 5072 7330 203 2360 2989 643 518 1150 1041
AGS275DE 6698 7109 18 8880 2594 6767 5050 8230 203 2360 2989 643 518 1138 1057
AGS300DE 6717 7107 18 8880 2594 6767 5050 8230 203 2360 2989 643 518 1145 1077
NOTES:
1. Dimensions in millimeters, weights in kilograms.
2. Weights are with aluminum fins, add 59 kilograms per fan section for copper fins

IMM AGSD 35
Figure 27, High Efficiency, Dimensions, AGS 330DE - AGS 450DE

CONTROL POWER POWER


PANEL PANEL PANEL
EVAP EVAP FIELD
OUTLET INLET CONTROL MAIN DISCONNECT
96.80 SWITCH HANDLE
89.89 2459
2283

Y 33.83 POWER
ENTRY
859

18.40 32.53 CIR # 1 CIR # 2


8.0 467 826 X
203 H 131.30
3335 87.60
B 2225
Z
C
D
12.98
330 .75 3.15
19 80

81.30
2065

3314901 D 00

25.59
BOTTOM VIEW 650
84.65
2150
E
F
G
A

NOTES::
1. See page 4 and following pages for weights and mounting loads.
2. A 20-fan unit is illustrated. See tables below of the number of fans on a specific model.
3. Mounting holes are ¾-inch diameter.
4. Allow 1-inch manufacturing tolerance on all dimensions.

Inch-Pounds Units of Measure


Unit Shipping Operating No. of Lifting Locations Mounting Locations Center of Gravity
A H
Model Weight. Weight Fans B C D E F G X Y Z
AGS330DE 20235 21146 22 438.6 140.8 262.0 348.3 177.0 269.3 361.6 92.9 43.8 40.1 158.2
AGS350DE 21040 21918 24 474.0 140.8 297.8 383.8 177.0 304.7 397.0 92.9 43.8 40.1 169.4
AGS400DE 21326 22485 24 474.0 140.8 297.8 383.8 177.0 304.7 397.0 126.4 43.8 40.1 173.0
AGS450DE 22244 23403 26 509.4 140.8 297.4 419.2 177.0 304.7 432.5 126.4 43.8 41.4 185.2
NOTES:
1. Dimensions in inches, weights in pounds.
2. Weights are with aluminum fins; add 131 pounds per fan section for copper fins.

SI Units of Measure
Unit Shipping Operating No. of Lifting Locations Mounting Locations Center of Gravity
A H
Model Weight. Weight Fans
B C D E F G X Y Z
AGS330DE 9178 9592 22 11140 3576 6655 8847 4496 6840 9185 2360 1113 1019 4018
AGS350DE 9544 9942 24 12040 3576 7564 9749 4496 7739 10085 2360 1113 1019 4303
AGS400DE 9674 10199 24 12040 3576 7564 9749 4496 7739 10085 3211 1113 1019 4395
AGS450DE 10090 10616 26 12939 3576 7554 10648 4496 7739 10986 3211 1113 1050 4705
NOTES:
1. Dimensions in millimeters, weights in kilograms.
2. Weights are with aluminum fins; add 59 kilograms per fan section for copper fins.

36 IMM AGSD
Electrical Data

Field Wiring
General
Wiring must comply with all applicable codes and ordinances. The Limited Product Warranty does not
cover damage to the equipment caused by wiring not complying with specifications.
An open fuse indicates a short, ground, or overload. Before replacing a fuse or restarting a compressor
or fan motor, the trouble must be found and corrected.
Copper wire is required for all power lead terminations at the unit, and copper must be used for all
other wiring to the unit.
AGS-D units can be ordered with main power wiring for either multiple-point power (standard) or
single-point connection (optional).
If the standard multiple-point power wiring is ordered, two or three separate power connections are
made to power blocks (or optional circuit breaker disconnects) in power panel. See the dimension
drawings beginning on page 29 for entry locations. Separate disconnects are required for each
electrical circuit if the McQuay optional factory-mounted disconnects are not ordered.
If the optional single-point power connection is ordered, a single power connection is made to a power
block (or optional circuit breaker disconnect) in the unit power panel. A separate disconnect is
required if the McQuay optional factory-mounted disconnect is not ordered. Isolation circuit breakers
for each circuit are included.
It can be desirable to have the unit evaporator heaters on a separate disconnect switch from the main
unit power supply so that the unit power can be shut down without defeating the freeze protection
provided by the evaporator heaters. See the field wiring diagram on page 48 for connection details.
The 115-volt control transformer is factory mounted and wired.

CAUTION
If a separate disconnect is used for the 115V supply to the unit, it must power the entire control
circuit, not just the evaporator heaters. It must be clearly marked so that it is not accidentally
shut off during cold seasons. Freeze damage to the evaporator could result. If the evaporator is
drained for winter freeze protection, the heaters must be de-energized to prevent heater burnout.

CAUTION
AGS unit compressors are single-direction rotation compressors and can be damaged if rotated
in the wrong direction. For this reason, proper phasing of electrical power is important.
Electrical phasing must be A, B, C for electrical phases 1, 2 and 3 (A=L1, B=L2, C=L3) for single
or multiple point wiring arrangements. The solid-state starters contain phase reversal
protection. DO NOT ALTER THE WIRING TO THE STARTERS.

IMM AGSD 37
Standard Efficiency
Table 31, Standard Efficiency, AGS 225DS/M – 450DS/M, Electrical Data,
Optional Single-Point, without Pump Package
POWER SUPPLY
AGS MIN. CIRCUIT FIELD FUSE OR
UNIT VOLTS HZ AMPACITY FIELD SUPPLIED BREAKER SIZE
FIELD WIRE
SIZE (MCA) HUB (IN.)
QTY WIRE GA QTY NOM. SIZE RECOM. MAX.
460 488 6 250 MCM 2 2.0 600 600
225DS 60
575 421 6 4/0 AWG 2 2.0 500 500
460 534 6 300 MCM 2 2.5 600 700
250DS 60
575 451 6 4/0 AWG 2 2.0 500 600
460 604 6 350 MCM 2 2.5 700 800
275DS 60
575 501 6 250 MCM 2 2.0 600 700
460 629 6 400 MCM 2 2.5 700 800
300DS 60
575 521 6 300 MCM 2 2.5 600 700
460 716 6 500 MCM 2 3.0 800 800
330DS 60
575 640 6 400 MCM 2 2.5 700 700
460 754 6 500 MCM 2 3.0 800 800
350DS 60
575 664 6 400 MCM 2 2.5 700 800
460 784 12 300 MCM 2 3.5 800 800
360DS 60
575 683 6 500 MCM 2 3.0 800 800
460 822 12 300 MCM 2 3.5 1000 1000
390DS 60
575 684 6 500 MCM 2 3.0 800 800
460 853 12 300 MCM 2 3.5 1000 1000
400DS 60
575 709 6 500 MCM 2 3.0 800 800
460 911 12 300 MCM 2 3.5 1000 1000
450DS 60
575 755 6 500 MCM 2 3.0 800 800

NOTES
1. Table based on 75°C field wire.
2. Recommended fuse size is for ambient temperature of 105°F or less. Use the maximum fuse size above 105°F.
3. Complete notes are on page 51.

38 IMM AGSD
Table 32, Standard Efficiency, AGS 225DS/M – 450DS/M, Electrical Data, Standard
Multi-Point Connection, without Pump Package
ELECTRICAL CIRCUIT 1 (COMPRESSOR 1) ELECTRICAL CIRCUIT 2 (COMPRESSOR 2)

MIN. POWER SUPPLY FIELD FUSE MIN. POWER SUPPLY FIELD FUSE
AGS
OR OR
UNIT VOLTS HZ CIRCUIT FIELD CIRCUIT FIELD
AM- FIELD WIRE SUPPLIED BREAKER AM- FIELD WIRE SUPPLIED BREAKER
SIZE
PACITY HUB (IN.) SIZE PACITY HUB (IN.) SIZE
(MCA) QTY WIRE GA QTY SIZE RECOM. MAX. (MCA) QTY WIRE GA QTY SIZE RECOM. MAX.

460 269 3 300 MCM 1 2.5 350 450 269 3 300 MCM 1 2.5 350 450
225DS/M 60
575 232 3 250 MCM 1 2.0 300 400 232 3 250 MCM 1 2.0 300 400
460 273 3 300 MCM 1 2.5 350 450 310 3 400 MCM 1 2.5 400 500
250DS/M 60
575 235 3 250 MCM 1 2.0 300 400 259 3 300 MCM 1 2.5 350 400
460 310 3 400 MCM 1 2.5 400 500 346 3 500 MCM 1 3.0 450 500
275DS/M 60
575 259 3 300 MCM 1 2.5 350 400 287 3 350 MCM 1 2.5 350 450
460 346 3 500 MCM 1 3.0 450 500 346 3 500 MCM 1 3.0 450 500
300DS/M 60
575 287 3 350 MCM 1 2.5 350 450 287 3 350 MCM 1 2.5 350 450
460 273 3 300 MCM 1 2.5 350 450 273 3 300 MCM 1 2.5 350 450
330DS/M 60
575 235 3 250 MCM 1 2.0 300 400 235 3 250 MCM 1 2.0 300 400
460 273 3 300 MCM 1 2.5 350 450 310 3 400 MCM 1 2.5 400 500
350DS/M 60
575 235 3 250 MCM 1 2.0 300 400 259 3 300 MCM 1 2.5 350 400
460 310 3 400 MCM 1 2.5 400 500 310 3 400 MCM 1 2.5 400 500
360DS/M 60
575 259 3 300 MCM 1 2.5 350 400 259 3 300 MCM 1 2.5 350 400
460 310 3 400 MCM 1 2.5 400 500 310 3 400 MCM 1 2.5 400 500
390DS/M 60
575 259 3 300 MCM 1 2.5 350 400 259 3 300 MCM 1 2.5 350 400
460 310 3 400 MCM 1 2.5 400 500 310 3 400 MCM 1 2.5 400 500
400DS/M 60
575 259 3 300 MCM 1 2.5 350 400 259 3 300 MCM 1 2.5 350 400
460 346 3 500 MCM 1 3.0 450 500 346 3 500 MCM 1 3.0 450 500
450DS/M 60
575 287 3 350 MCM 1 2.5 350 450 287 3 350 MCM 1 2.5 350 450

Table 33, Electrical Data, AGS 330DS/M – 450DS/M, Standard Multi-Point, Circuit 3
AGS MIN. CIRCUIT POWER SUPPLY FIELD FUSE OR HACR
UNIT VOLTS HZ AMPACITY FIELD WIRE FIELD SUPPLIED HUB (IN.) BREAKER SIZE
SIZE (MCA)
QTY WIRE GA QTY SIZE RECOM. MAX.
460 269 3 300 MCM 1 2.5 350 450
330DS/M 60
575 232 3 250 MCM 1 2.0 300 400
460 269 3 300 MCM 1 2.5 350 450
350DS/M 60
575 232 3 250 MCM 1 2.0 300 400
460 269 3 300 MCM 1 2.5 350 450
360DS/M 60
575 232 3 250 MCM 1 2.0 300 400
460 315 3 400 MCM 1 2.5 400 500
390DS/M 60
575 262 3 300 MCM 1 2.5 350 450
460 346 3 500 MCM 1 3.0 450 500
400DS/M 60
575 287 3 350 MCM 1 2.5 350 450
460 346 3 500 MCM 1 3.0 450 500
450DS/M 60
575 287 3 350 MCM 1 2.5 350 450
NOTES:
1. Table based on 75°C field wire.
2. Complete notes are on page 51.

IMM AGSD 39
Table 34, Standard Efficiency, AGS 225DS/M – 450DS/M, Compressor and Condenser
Fan Motor Amp Draw, without Pump Package
NO. FAN FAN Solid State Wye-Delta
AGS RATED LOAD AMPS
OF MTRS MTRS LRA (Note 3) LRA
UNIT VOLTS HZ
SIZE CIRC. CIRC. CIRC. FAN FLA LRA CIRC. CIRC. CIRC. CIRC. CIRC. CIRC.
#1 #2 #3 MTRS (EA) (EA) #1 #2 #3 #1 #2 #3

460 195 195 -- 12 4.1 23 1008 1008 -- 310/1008 310/1008 --


225DS/M 60
575 171 171 -- 12 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 195 225 -- 14 4.1 23 1008 1485 -- 310/1008 457/1485 --
250DS/M 60
575 171 190 -- 14 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 225 250 -- 16 4.1 23 1485 1485 -- 457/1485 457/1485 --
275DS/M 60
575 190 210 -- 16 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 250 250 -- 16 4.1 23 1485 1485 -- 457/1485 457/1485 --
300DS/M 60
575 210 210 -- 16 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 250 250 -- 16 4.1 23 1485 1485 -- 457/1485 457/1485 --
315DS/M 60
575 210 210 -- 16 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 195 195 195 20 4.1 23 1008 1008 1008 310/1008 310/1008 310/1008
330DS/M 60
575 171 171 171 20 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 195 225 195 20 4.1 23 1008 1485 1008 310/1008 457/1485 310/1008
350DS/M 60
575 171 190 171 20 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 225 225 195 20 4.1 23 1485 1485 1008 457/1485 457/1485 457/1485
360DS/M 60
575 190 190 171 20 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 225 225 225 22 4.1 23 1485 1485 1485 457/1485 457/1485 457/1485
390DS/M 60
575 190 190 190 22 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 225 225 250 22 4.1 23 1485 1485 1485 457/1485 457/1485 457/1485
400DS/M 60
575 190 190 210 22 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 250 250 250 24 4.1 23 1485 1485 1485 457/1485 457/1485 457/1485
450DS/M 60
575 210 210 210 24 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310

NOTES:
1. Table based on 75°C field wire.
2. Complete notes are on page 51.
3. For solid state starters, inrush amps are 58% of the LRA.

40 IMM AGSD
Table 35, Standard Efficiency, AGS 225DS/M – AGS 450DS/M, Customer Wiring
Information With Optional Single-Point Power, with or without Pump Package
POWER BLOCK DISCONNECT SWITCH DISCONNECT SWITCH (High Interrupt
AGS (Std. Short Circuit Current Rating) (Std. Short Circuit Current Rating) or High Short Circuit Current Rating)
UNIT VOLTS HZ TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG
SIZE
SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE
460 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 1000A #1-500 (2/PH)
225DS/M 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 800A #1-500 (2/PH)
460 620A #6-350 (2/PH) 800A #1-500 (2/PH) 1000A #1-500 (2/PH)
250DS/M 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 800A #1-500 (2/PH)
460 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
275DS/M 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 1000A #1-500 (2/PH)
460 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
300DS/M 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 1000A #1-500 (2/PH)
460 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
330DS/M 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 840A #2-600 (2/PH) 1000A #1-500 (2/PH) 1400A 300-600 (5/PH)
350DS/M 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 840A #2-600 (2/PH) 1000A #1-500 (2/PH) 1400A 300-600 (5/PH)
360DS/M 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 840A #2-600 (2/PH) 1000A #1-500 (2/PH) 1400A 300-600 (5/PH)
390DS/M 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 1520A #4-500 (4/PH) 1000A #1-500 (2/PH) 1600A 300-600 (5/PH)
400DS/M 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 1520A #4-500 (4/PH) 1200A #1-500 (2/PH) 1600A 300-600 (5/PH)
450DS/M 60
575 840A #2-600 (2/PH) 1000A #1-500 (2/PH) 1400A 300-600 (5/PH)

NOTES:
1. Terminal size amps are the maximum amps that the power block is rated for.
2. Complete notes are on page 51.
3. Data based on 75°C wire.
4. (2/C) notation means two cables per conduit.

IMM AGSD 41
Table 36, Standard Efficiency, AGS 225DS/M – 450DS/M, Wiring with Standard Multiple-
Point Power and Disconnect Switches, with or without Pump Package
AGS DISCONNECT SW-CIRCUIT #1 DISCONNECT SW-CIRCUIT #2 DISCONNECT SW-CIRCUIT #3
UNIT VOLTS HZ TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG
SIZE
SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
225DS/M 60
575 350A 3/0-500 (2/PH) 350A 3/0-500 (2/PH) -- --
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
250DS/M 60
575 350A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
275DS/M 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 500A 3/0-500 (2/PH) 500A 3/0-500 (2/PH) -- --
300DS/M 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 500A 3/0-500 (2/PH) 500A 3/0-500 (2/PH) -- --
315DS/M 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
330DS/M 60
575 350A 3/0-500 (2/PH) 350A 3/0-500 (2/PH) 350A 3/0-500 (2/PH)
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
350DS/M 60
575 350A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 350A 3/0-500 (2/PH)
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
360DS/M 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 350A 3/0-500 (2/PH)
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
390DS/M 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 500A 3/0-500 (2/PH)
400DS/M 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
460 500A 3/0-500 (2/PH) 500A 3/0-500 (2/PH) 500A 3/0-500 (2/PH)
450DS/M 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)

NOTES:
1. Terminal size amps are the maximum amps that the disconnect switch is rated for.
2. Data based on 75°C wire.
3. (2/C) notation means two cables per conduit.
4. Complete notes are on page 51.

42 IMM AGSD
High Efficiency
Table 37, High Efficiency, AGS 225DE/F–450DE/F, Electrical Data, Optional Single-
Point, without Pump Package
POWER SUPPLY
AGS MIN. CIRCUIT FIELD FUSE OR
UNIT VOLTS HZ AMPACITY FIELD SUPPLIED BREAKER SIZE
FIELD WIRE
SIZE (MCA) HUB (IN.)
QTY WIRE GA QTY NOM. SIZE RECOM. MAX.
460 497 6 250 MCM 2 2.0 600 600
225DE 60
575 427 6 4/0 AWG 2 2.0 500 500
460 542 6 300 MCM 2 2.5 600 700
250DE 60
575 457 6 4/0 AWG 2 2.0 600 600
460 572 6 350 MCM 2 2.5 700 700
260DE 60
575 476 6 250 MCM 2 2.0 600 600
460 612 6 350 MCM 2 2.5 700 800
275DE 60
575 507 6 250 MCM 2 2.0 600 700
460 637 6 400 MCM 2 2.5 700 800
300DE 60
575 527 6 300 MCM 2 2.5 600 700
460 724 6 500 MCM 2 3.0 800 800
330DE 60
575 622 6 400 MCM 2 2.5 700 700
460 770 12 300 MCM 2 3.5 800 800
350DE 60
575 652 6 400 MCM 2 2.5 700 800
460 861 12 300 MCM 2 3.5 1000 1000
400DE 60
575 715 6 500 MCM 2 3.0 800 800
460 920 12 350 MCM 2 3.5 1000 1000
450DE 60
575 761 12 300 MCM 2 3.5 800 800
NOTES
1. Table based on 75°C field wire.
2. Recommended fuse size is for ambient temperature of 105°F or less. Use the maximum fuse size above 105°F.
3. Complete notes are on page 51.

IMM AGSD 43
Table 38, High Efficiency, AGS 225DE/F – 450DE/F, Electrical Data, Standard Multiple-
Point Connection, without Pump Package
ELECTRICAL CIRCUIT 1 (COMPRESSOR 1) ELECTRICAL CIRCUIT 2 (COMPRESSOR 2)

MIN. POWER SUPPLY FIELD FUSE MIN. POWER SUPPLY FIELD FUSE
AGS
OR OR
UNIT VOLTS HZ CIRCUIT FIELD CIRCUIT FIELD
AMP- FIELD WIRE SUPPLIED BREAKER AMP- FIELD WIRE SUPPLIED BREAKER
SIZE
ACITY HUB (IN.) SIZE ACITY HUB (IN.) SIZE
(MCA) QTY WIRE GA QTY SIZE RECOM. MAX. (MCA) QTY WIRE GA QTY SIZE RECOM MAX.

460 273 3 300 MCM 1 2.5 350 450 273 3 300 MCM 1 2.5 350 450
225DE/F 60
575 235 3 250 MCM 1 2.0 300 400 235 3 250 MCM 1 2.0 300 400
460 273 3 300 MCM 1 2.5 350 450 315 3 400 MCM 1 2.5 400 500
250DE/F 60
575 235 3 250 MCM 1 2.0 300 400 262 3 300 MCM 1 2.5 350 450
460 315 3 400 MCM 1 2.5 400 500 315 3 400 MCM 1 2.5 400 500
260DE/F 60
575 262 3 300 MCM 1 2.5 350 450 262 3 300 MCM 1 2.5 350 450
460 315 3 400 MCM 1 2.5 400 500 350 3 500 MCM 1 3.0 450 600
275DE/F 60
575 262 3 300 MCM 1 2.5 350 450 290 3 350 MCM 1 2.5 350 500
460 350 3 500 MCM 1 3.0 450 600 350 3 500 MCM 1 3.0 450 600
300DE/F 60
575 290 3 350 MCM 1 2.5 350 500 290 3 350 MCM 1 2.5 350 500
460 273 3 300 MCM 1 2.5 350 450 273 3 300 MCM 1 2.5 350 450
330DE/F 60
575 235 3 250 MCM 1 2.0 300 400 235 3 250 MCM 1 2.0 300 400
460 277 3 300 MCM 1 2.5 350 450 315 3 400 MCM 1 2.5 400 500
350DE/F 60
575 238 3 250 MCM 1 2.0 300 400 262 3 300 MCM 1 2.5 350 450
460 315 3 400 MCM 1 2.5 400 500 315 3 400 MCM 1 2.5 400 500
400DE/F 60
575 262 3 300 MCM 1 2.5 350 450 262 3 300 MCM 1 2.5 350 450
460 350 3 500 MCM 1 3.0 450 600 350 3 500 MCM 1 3.0 450 600
450DE/F 60
575 290 3 350 MCM 1 2.5 350 500 290 3 350 MCM 1 2.5 350 500

Table 39, High Efficiency, AGS 330DE/F – 450DE/F, Electrical Data, Standard Multiple-
Point, Circuit 3
AGS MIN. CIRCUIT POWER SUPPLY FIELD FUSE OR HACR
UNIT VOLTS HZ AMPACITY FIELD WIRE FIELD SUPPLIED HUB (IN.) BREAKER SIZE
SIZE (MCA)
QTY WIRE GA QTY SIZE RECOM. MAX.
460 277 3 300 MCM 1 2.5 350 450
330DE/F 60
575 238 3 250 MCM 1 2.0 300 400
460 277 3 300 MCM 1 2.5 350 450
350DE/F 60
575 238 3 250 MCM 1 2.0 300 400
460 346 3 500 MCM 1 3.0 450 500
400DE/F 60
575 287 3 350 MCM 1 2.5 350 450
460 315 3 400 MCM 1 2.5 400 500
450DE/F 60
575 262 3 300 MCM 1 2.5 350 450
NOTES
1. Table based on 75°C field wire.
2. Complete notes are on page 51.

44 IMM AGSD
Table 40, High Efficiency, AGS 225DE/F - 500DE/F, Compressor & Condenser Fan
Motor Amp Draw
FAN FAN Solid State Wye-Delta
AGS RATED LOAD AMPS NO OF
MTRS MTRS LRA (Note 1) LRA
UNIT VOLTS HZ FAN
SIZE CIRCUIT CIRCUIT CIRCUIT MTRS FLA LRA CIRCUIT CIRCUIT CIRCUIT CIRCUIT CIRCUIT CIRCUIT
#1 #2 #3 (EA) (EA) #1 #2 #3 #1 #2 #3

460 195 195 -- 14 4.1 23 1008 1008 -- 310/1008 310/1008 --


225DE/F 60
575 171 171 -- 14 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 195 225 -- 16 4.1 23 1008 1485 -- 310/1008 457/1485 --
250DE/F 60
575 171 190 -- 16 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 225 225 -- 16 4.1 23 1485 1485 -- 457/1485 457/1485 --
260DE/F 60
575 190 190 -- 16 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 225 250 -- 17 4.1 23 1485 1485 -- 457/1485 457/1485 --
275DE/F 60
575 190 210 -- 17 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 250 250 -- 18 4.1 23 1485 1485 -- 457/1485 457/1485 --
300DE/F 60
575 210 210 -- 18 3.0 20 1310 1310 -- 403/1310 403/1310 --
460 195 195 195 22 4.1 23 1008 1008 1008 310/1008 310/1008 310/1008
330DE/F 60
575 171 171 171 22 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 195 225 195 24 4.1 23 1008 1485 1008 310/1008 457/1485 310/1008
350DE/F 60
575 171 190 171 24 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 225 225 250 24 4.1 23 1485 1485 1485 457/1485 457/1485 457/1485
400DE/F 60
575 190 190 210 24 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310
460 250 250 225 26 4.1 23 1485 1485 1485 457/1485 457/1485 457/1485
450DE/F 60
575 210 210 190 26 3.0 20 1310 1310 1310 403/1310 403/1310 403/1310

NOTES:
1. For Solid State - Inrush Amps58% of the LRA
2. Table based on 75°C field wire.
3. Complete notes are on page 51.

IMM AGSD 45
Table 41, High Efficiency, AGS 225DE/F – AGS 450DE/F, Customer Wiring Information
With Standard Single-Point Power, without Pump Package
POWER BLOCK DISCONNECT SWITCH DISCONNECT SWITCH (High Interrupt
AGS (Std. Short Circuit Current Rating) (Std. Short Circuit Current Rating) or High Short Circuit Current Rating)
UNIT VOLTS HZ TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG
SIZE
SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE
460 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 1000A #1-500 (2/PH)
225DE/F 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 800A #1-500 (2/PH)
460 620A #6-350 (2/PH) 800A #1-500 (2/PH) 1000A #1-500 (2/PH)
250DE/F 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 800A #1-500 (2/PH)
460 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1000A #1-500 (2/PH)
260DE/F 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 1000A #1-500 (2/PH)
460 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
275DE/F 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 1000A #1-500 (2/PH)
460 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
300DE/F 60
575 620A #6-350 (2/PH) 600A 3/0-500 (2/PH) 1000A #1-500 (2/PH)
460 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
330DE/F 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 840A #2-600 (2/PH) 1000A #1-500 (2/PH) 1400A 300-600 (5/PH)
350DE/F 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 1520A #4-500 (4/PH) 1000A #1-500 (2/PH) 1600A 300-600 (5/PH)
400DE/F 60
575 760A #4-500 (2/PH) 800A #1-500 (2/PH) 1200A #1-500 (2/PH)
460 1520A #4-500 (4/PH) 1200A #1-500 (2/PH) 1600A 300-600 (5/PH)
450DE/F 60
575 840A #2-600 (2/PH) 1000A #1-500 (2/PH) 1400A 300-600 (5/PH)

NOTES:
1. Terminal size amps are the maximum amps that the power block is rated for.
2. Complete notes are on page 51.
3. Data based on 75°C wire.
4. (2/C) notation means two cables per conduit.

46 IMM AGSD
Table 42, High Efficiency, AGS 225DE/F – 450DE/F Wiring with Standard Multiple-Point
Power and Disconnect Switches, without Pump Package
AGS DISCONNECT SW-CIRCUIT #1 DISCONNECT SW-CIRCUIT #2 DISCONNECT SW-CIRCUIT #3
UNIT VOLTS HZ TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG TERMINAL CONNECTION LUG
SIZE
SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE SIZE AMPS RANGE PER PHASE
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
225DE/F 60
575 350A 3/0-500 (2/PH) 350A 3/0-500 (2/PH) -- --
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
250DE/F 60
575 350A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
260DE/F 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
275DE/F 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 500A 3/0-500 (2/PH) 500A 3/0-500 (2/PH) -- --
300DE/F 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) -- --
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
330DE/F 60
575 350A 3/0-500 (2/PH) 350A 3/0-500 (2/PH) 350A 3/0-500 (2/PH)
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
350DE/F 60
575 350A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 350A 3/0-500 (2/PH)
460 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 500A 3/0-500 (2/PH)
400DE/F 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
460 500A 3/0-500 (2/PH) 500A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)
450DE/F 60
575 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH) 400A 3/0-500 (2/PH)

NOTES:
1. Terminal size amps are the maximum amps that the disconnect switch is rated for.
2. Data based on 75°C wire.
3. (2/C) notation means two cables per conduit.
4. Complete notes are on page 51.

IMM AGSD 47
Field Wiring Diagram
Figure 28, Typical Field Wiring Diagram

Updated JUL07- Supersedes all previous versions

48 IMM AGSD
FIELD WIRING DIAGRAM continued

IMM AGSD 49
FIELD WIRING DIAGRAM continued

50 IMM AGSD
Electrical Data Notes
1. The field wire size designation is explained in the
Sample No. of Wires No. of Conduit
table to the right that defines the number of wires and 350 MCM 3 1
conduit recommended. A “2” in parenthesis (2) 2-250 MCM 6 1
indicates that two conduits are required. (2) 250 MCM 6 2
2. Allowable voltage limits (2) 2-250 MCM 12 2
Unit nameplate 460V/60Hz/3Ph: 414V to 506V
Unit nameplate 575V/60Hz/3Ph: 517V to 633V
Maximum of 2 percent voltage unbalance.
3. Unit wire size ampacity (MCA) is equal to 125% of the largest compressor-motor RLA plus 100%
of RLA of all other loads in the circuit including control transformer. Wire size ampacity for separate
115V control circuit power is 15 amps.
4. Compressor RLA values are for wire sizing purposes only but do reflect normal operating current
draw at unit rated capacity.
5. Single point power supply requires a single disconnect to supply electrical power to the unit. This
power must be fused.
6. Multiple point power supply requires two independent power circuits.
7. All field wiring to unit power block or optional non-fused disconnect switch must be copper.
8. Field wire size values given in tables apply to 75°C rated wire per NEC.
9. External disconnect switch(s) or HACR breakers must be field supplied.

Note: On single point power units a non-fused disconnect switch in the cabinet is available as an
option.

10. All wiring must be done in accordance with applicable local and national codes.
11. Recommended time delay fuse size or HACR breakers is equal to 150% of the largest compressor
motor RLA plus 100% of remaining compressor RLAs and the sum of condenser fan FLAs.
12. Maximum time delay fuse size or HACR breakers is equal to 225% of the largest compressor-
motor RLA plus 100% of remaining compressor RLAs and the sum of condenser fan FLAs.
Power Limitations:
1. Voltage within ± 10 percent of nameplate rating.
2. Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to 10 times the voltage
unbalance per NEMA MG-1, 1998 Standard.
BAS Interface
Connection to the chiller for all building automation systems (BAS) protocols is at the unit controller.
An optional interface module, depending on the protocol being used, may have been factory-installed
in the unit controller (or it can be field installed).
Table 23, Standard Protocol Data
Protocol Physical Layer Data Rate Controller Other
BACnet®/IP or Reference ED
Ethernet 10 Base-T 10 Megabits/sec MicroTech II
BACnet/Ethernet 15100
9600, 19200 or Reference ED
BACnet MSTP RS-485 MicroTech II
38400 bits/sec 15062
Reference ED
LONWORKS® FTT-10A 78kbits/sec MicroTech II 15062
9600 or 19200 Reference ED
Modbus RTU RS-485 or RS-232 MicroTech II
bits/sec 15063

IMM AGSD 51
The interface kits on the MicroTech II controller are as follows:
• BACnet Kit P/N 350147404: BACnet MS/TP
• BACnet Kit P/N 350147406: BACnet IP or BACnet Ethernet
• LONWORKS Kit P/N 350147401: LonTalk (FTT-10A)
• Modbus: Modbus RTU
Optional Protocol Selectability BAS interfaces. The locations and interconnection requirements for
the various standard protocols are found in their respective installation manuals.
Modbus: IM 743 LONWORKS: IM 735 BACnet -MS/TP: IM 736
BACnet -IP/Ethernet: IM 837
Referenced documents may be obtained from the local McQuay sales office, from the local
McQuayService office, or from the McQuay Technical Response Center, located in Staunton, Virginia
(540-248-0711).
These documents can also be found on www.mcquay.com under Product Information > (chiller type) >
Control Integration.
®™ The following are trademarks or registered trademarks of their respective companies: BACnet
from the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., LonTalk,
LONMARK and LONWORKS from Echelon Corporation, and Modbus and Modbus RTU from
Schneider Electric.

Remote Operator Interface Panel


The box containing the optional remote interface panel will have installation instructions, IOM MT II
Remote, in it. The manual is also available for downloading from www.mcquay.com.

52 IMM AGSD
Solid State Starters
Solid state starters are standard on all AGS units. A solid state starter uses a silicon-controlled rectifier
(SCR) power section to allow a motor to be brought to full speed with a reduced initial voltage that
increases to full line voltage over a given time. The McQuay motor starter, custom designed for this
specific application, is microprocessor controlled. Along with this starting technique, the motor starter
also provides protection for the motor and monitors its load conditions.
The starter offers:
• Solid state design.
• Closed-loop motor current control.
• Programmable motor protection.
• Programmable operating parameters.
• Programmable metering options.
The three-phase starter contains a six-SCR power section with two SCRs per phase connected in
inverse parallel. This power section is capable of providing maximum torque per amp throughout the
motor’s speed-torque curve with minimal motor and starter heating. At the same time, the starter
continually monitors the amount of current being delivered to the motor, thus helping to protect the
motor from overheating or drawing excessive current. The starter will automatically stop the motor if
the line-to-line current is not within acceptable ranges, or if the current is lost in a line. The motor
current scaling is set according to the motor size and the specific application. The starter circuitry is
contained on a single printed circuit board, which contains all the logic and SCR gate drive circuitry.
Operating messages are displayed on a three-character LED display located in the unit control panel.
The LED display on the control card displays:
• Operating messages that indicate the status of the motor and/or starter.
• Operating parameters that are programmed into the starter.
• Fault codes that indicate a problem with the motor application or starter.

Operating Messages
Possible operating messages are as follows:

Message Meaning
noL Line voltage is not present.

rdy Line voltage is present and starter is ready.

acc Motor is accelerating after a start command has been received.

uts The motor has achieved full speed.

run Motor is operating at full speed, and ramp time has expired.

dCL A Stop command was received and the motor is decelerating with the set deceleration
profile.

OL OL will alternately blink with the normal display on the LED display when motor
thermal overload content has reached 90% to 99% of its capacity.

IMM AGSD 53
OLL The motor thermal overload content has reached 100%, and the motor has stopped.
The motor cannot be restarted until the overloaded motor has cooled and OLt is
displayed.

OLt The motor thermal overload content has been reduced to 60% or less, and the motor
can be restarted.

ena Passcode protection is enabled.

dis Passcode is disabled.

oxx xx = overload thermal content in percentage. Press the Down button to toggle to this
display.

cxx xx = pending fault.

no Attempted to change a passcode protected parameter without proper security.

… Three decimal places blink when remote display is active.

Fxx xx Fault Code


Table 43, Fault Codes
Controlled Auto
Number Description
Stop Reset
00 No Fault -- --
01 UTS Time Limit Expired Y Y
02 Motor Thermal Overload Trip Y N
10 Phase Rotation Error, Not A-B-C N Y
12 Low Line Frequency N Y
13 High Line Frequency N Y
15 Input Power Not Three phase N Y
21 Low Line L1-L2 Voltage Y Y
22 Low Line L2-L3 Voltage Y Y
23 Low Line L3-L1 Voltage Y Y
24 High Line L1-L2 Voltage Y Y
25 High Line L2-L3 Voltage Y Y
26 High Line L3-L1 Voltage Y Y
27 Phase loss N Y
28 No Line Voltage N Y
30 I.O.C. (Instantaneous Overcurrent) N N
31 Overcurrent Y N
37 Current Imbalance Y Y
38 Ground Fault Y N
39 No Current At Run N Y
40 Shorted/Open SCR N N
47 Stack Protection Fault N Y
48 Bypass Contactor Fault (on STOP input) Y N
50 Control Power Low N Y
Continued next page

54 IMM AGSD
Controlled Auto
Number Description
Stop Reset
51 Current Sensor Offset Error -- N
52 Burden Switch Error N N
60 Thermistor Trip N N
61 Stack OT Switch Trip N N
71 Analog Input Trip Y Y
82 Modbus Time-out Y Y
94 CPU Error – Software Fault N N
95 CPU Error – Parameter Storage Fault N N
96 CPU Error – Illegal Instruction Trap N N
97 CPU Error – Software Watchdog Fault N N
98 CPU Error – Spurious Interrupt N N N
99 CPU Error – Program Storage Fault N N

Starter Planned Maintenance


During commissioning:
• Torque all power connections during commissioning. This includes factory-wired components.
• Check all of the control wiring in the package for loose connections.

During the first month after the starter has been put in operation:
• Re-torque all power connections every two weeks. This includes factory-wired components.
• Inspect cooling fans (if applicable) after two weeks for proper operation.

After the first month of operation:


• Re-torque all power connections every year.
• Clean any accumulated dust from the starter using a clean source of compressed air.
• Inspect the cooling fans every three months for proper operation.
• Clean or replace any air vent filters on the starter every three months.

NOTE: If mechanical vibrations are present at the installation site, inspect the connections more
frequently.

IMM AGSD 55
Figure 29, Trouble Shooting Guide

Start

3
Yes
Low or Missing
Line?

No

1 4
No Phase Order Yes
Fuses OK? Fault

Yes No

2 5
No Circuit Yes Swap Any
Replace
Breaker OK? Thermal Trip? 2 Power
Fuses
Leads
Yes No

6
Replace No Yes Interlock
Circuit In-Line OK? Open?
Breaker
Yes No

7 8
Correct Power No No
Correct High
Source Wiring OK?
Inline Fault Ambient?
Problem
Yes Yes

9
Yes Bad Air
Replace Correct and
Control Card Wait to Cool Circulation?

No

10
Correct No
Return To No Motor
Does Problem
Interlock Still Exist Service Overloaded?
State
Yes Yes

7
Correct Go to Page 39 No Lower Motor
Wiring Wiring OK? Load

Yes

Correct Correct and


Wiring Wait to Cool

Return To
Service

56 IMM AGSD
From Previous Page

11
Current No
Imbalance Fault?

Yes

7
No Fuses Blown or No
Wiring Good? Breaker Tripped?

Yes Yes

12
Motor Yes
Correct Wiring Winding Short? Replace Fuse
or Reset Breaker

No

13 12
No No
SCRs OK? Motor Problem?

Yes Yes

14 15
All Gate Yes CT Burden No
Replace Repair or
Pulses Present? Switches Set
Defective SCRs Replace Motor Correctly?

No Yes

Replace Contact Check Jumpers


Replace
Control Card Benshaw Parameters
Control Card
For Assistance and CTs

Return to No
Normal Does Problem
Operation Still Exist?

Yes

Contact
McQuay
For Assistance

IMM AGSD 57
FLOW CHART DETAILS:
1. Fuses Determine if power line fuses have been installed, and if they are operating properly.
2. Circuit Breaker Determine if the circuit breaker is off, or has tripped and disconnected the line
from the starter.
3. Power Line Voltage Verify that line voltage is present, and that it is the correct voltage.
4. Phase Order Fault If Fault Codes F10 or F2 are displayed on the control card LED
display, exchange any two incoming power line cable connections.
5. Heat Sink Switch Investigate whether heat sink thermal switch is open.
6. Safety Device Determine if an equipment protection device attached to the starter is
disabling the start command.
7. Wiring Connections Verify that the wiring connections are correct and that the
terminations are tightened.
8. Air Temperature Investigate whether the air temperature surrounding the heat sink is hot.
9. Air Circulation Determine if the airflow around the heat sink fins is being restricted, or if a
fan has failed.
10. Motor Overload Determine if the motor’s load is too large for the motor size.
11. Current Imbalance Fault If Fault Code 37 is displayed on the control card LED display,
diagnose and correct the cause of the current imbalance parameter P20.
12. Motor Winding Problem Conducting a megger test of the motor can identify an internal motor
winding problem. NOTE: To avoid damaging the starter, isolate the motor before conducting the
megger test.

WARNING
Hazardous voltages exist at the starter terminals. Lock out and tag all power sources before
making resistance measurements to avoid personal injury or death.
13. SCRs This step can help determine if a problem exists with the SCRs. Using a multi-meter
or similar device, measure the resistance between:
• L1 terminal and T1 terminal
• L2 terminal and T2 terminal
• L3 terminal and T3 terminal
The resistance should be more than 50k ohms. Measure the gate resistance between the white and
red of each twisted pair (6 total). The gate resistance should be between 8 and 50 ohms.
14. Gate Pulses This step can help to determine if the control card is functioning properly.
Check for gate firing voltage between 0.3 and 1.5 volts when the card is operating.
15. Motor Current Determine if motor current signal scaling is correct.

58 IMM AGSD
Solid State Starter Settings
Operating Parameters Settings for Default Value and Settable Range:
Table 44, Starter Settings
No. Operating Parameter Default Range of Setting
P1 Motor Full Load Amps (FLA) 1OA 1 to 9999A
P2 Motor Rated Load Amps (RLA) 1OA 1 to 9999A
P3 Motor Service Factor 1.25 1-1.99
P4 Motor Overload Class 10 1-40,Off
P5 Initial Motor Starting Current 225% 50 - 400%
P6 Max. Motor Starting Current 300% 100 – 800%
P7 Motor Ramp Time 7 sec 0 - 300 sec
P8 UTS time 10 sec 1 - 900 sec
P9 Stop Mode Cos Coast/Voltage decel
P10 Deceleration Level 1 40% 0 – 100%
P11 Deceleration Level 2 20% 0 – 50%
P12 Deceleration Time 2 sec 1 – 180 sec
P13 Default Meter Display 0(Status) 0-19
P14 Overcurrent Trip Level 140% Off, 50 to 800%RLA
P15 Overcurrent Trip Time 2 sec Off, .1 – 90 sec
100,110,120,200,208,220,230,24
Set to Data
P16 Rated RMS Voltage 0,350,380,400,415,440,460,480,
Plate
500,525,575,600,660,690,1000
P17 Overvoltage Trip Level 10% Off, 1 – 40% rated volts
P18 Undervoltage Trip Level 10% Off, 1 – 40% rated volts
P19 Over/Under Voltage Delay Time 2 Sec .1-90 Sec
P20 Current Imbalance Trip Level 20% 5 - 40%
P21 Controlled Fault Stop Off Off, On
P22 Auto Fault Reset Delay Time 60 Off, 1 – 120 sec
72,96,144,288,864,2640,2880,57
P23 CT Ratio 2640
60,8000,14400,28800
P24 Control Source Ter Terminal/Network
P25 Modbus Address 2 1 - 247
P26 Modbus Baud Rate 19.2 Kbps 1.2,2.4,4.8,9.6,19.2 kbps
P27 Modbus Timeout 1 sec Off, 1 – 120 sec
P28 Analog Output Function 1 1 - 11
P29 Analog Output Span 100% 1 – 125%
P30 Analog Output Offset 0% 0 – 99%
P31 Passcode 0-9999
P32 Fault Log Display faults

IMM AGSD 59
Component Location

Major Component Location


Figure 30, 3-Compressor Unit Cutaway View

Condenser # 3

Condenser # 1

Compressor # 1
Left Side Condenser # 2
(Cutaway)

Economizer # 2. & # 3
Behind Leg, # 1 on
Opposite Side

Compressor # 3

Optional Suction Shutoff Valve, # 3

Compressor # 2

Starter Panel

Control Panel, Fan


Contactors Behind

60 IMM AGSD
Figure 31, Piping Schematic, One of Two or Three Circuits

AIR DISCHARGE DISCHARGE


RELIEF
SCHRADER FLOW TRANSDUCER TEMP. SENSOR
DISCHARGE VALVE SCHRADER
VALVE (WH1, WH2) (WD1, WD2)
TUBING VALVE
(HEADER) DISCHARGE (MOUNTED ON SUCTION VALVE
CHECK VALVE BODY AT BACK SEAT PORT)

CHARGING
AIR
VALVE CHARGING
FLOW
VALVE
OIL
CHARGING AIR TRANSDUCER SUCTION
VALVE FLOW (WO1, WO2) SHUT-OFF
KING VALVE
SCHRADER
VALVE OUTSIDE AIR
CONDENSER
TEMPERATURE CHARGING
ASSEMBLY (WAA)
FRAME 4 VALVE
COMPRESSOR
OIL (MOUNTED ON SUCTION
SEPARATOR VALVE BODY)

STUB
TUBE SCHRADER
ECONOMIZER FLASH GAS TO COMPRESSOR INTERSTAGE
VALVE

SHUT-OFF RELIEF
TO VALVE FIELD
CONNECTION VALVE
COMPRESSOR
OIL FILTER POINT
LIQUID
TUBING SCHRADER
VALVE SUCTION
SIGHT FIELD PIPING
TUBING
GLASS FROM SHOWN DASHED
OIL SEPARATOR
SHUT-OFF VALVE
SOLENOID COMPRESSOR
VALVE SUCTION
OIL SUPPLY TRANSDUCER
CHECK
SCHRADER (WL1, WL2)
VALVE
VALVE

THERMAL
EXPANSION FIELD IMPORTANT:
WATER OUT WATER IN THESE TWO COMPONENT
VALVE CONNECTION
LIQUID (WOE TEMP. (WIE TEMP. MUST BE MOUNTED NEA
POINT SOLENOID SCHRADER SCHRADER
SHUT-OFF SENSOR) SENSOR) REMOTE EVAPORATOR
VALVE VALVE VALVE
VALVE

FL OW

STUB SCHRADER
TUBE VALVE SUCTION
SHUT-OFF ELECTRONIC TEMP. SENSOR
ECONOMIZER FILTER SIGHT
FILTER BALL VALVE EXPANSION (ST1, ST2)
SCHRADER DRIER #2 GLASS DX EVAPORATOR
DRIER #1 VALVE
VALVE
FIELD INSTALLED LIQUID LINE COMPONENTS
(NOTE: FILTER DRIER #2 REQUIRED IN FIELD PIPING)

The above diagram illustrates the piping for the remote evaporator option. For the standard packaged
version, the field piping shown as dotted would be installed in the factory.
The diagram illustrates one of the two or three circuits (depending on unit size). The evaporator has
two or three single-pass refrigerant circuits on the tube side with water passing over baffles in a single
pass on the shell side.
The vertical and slanted coils on one side of the unit comprise a condensing circuit. All models have
an external economizer circuit consisting of a brazed-plate heat exchanger, solenoid valve, and
expansion valve.

IMM AGSD 61
Power Panel
The power panel is located on the front of the unit, to the right of the control panel.

Figure 32, Power Panel Components (Optional Single Point Power)

Unit
Breaker, Disconnect Breaker,
Contol Breaker,
Circuit #3 Switch Circuit #2
Transformer Circuit #1
and fuses

Starter, Starter,
Circuit #1 Line Circuit #2
Starter,
Circuit #3 Terminals

NOTE: A three-compressor unit with standard solid state starters is illustrated. Breaker and starter #3
are absent on two-compressor models.

62 IMM AGSD
Control Panel
The control panel is located on the front of the unit, to the left of the power panel.

Figure 33, Control Panel Components

MicroTech II
Controller, CP1

Expansion I/O
Controllers

Switch and Fuse


Panel

Location for Optional


115V Outlet

Expansion Valve
Drivers, One Per
Circuit

NOTE: A two-compressor unit is illustrated. Three-compressor models have an additional controller, CP2,
located under CP1.

IMM AGSD 63
Remote Evaporator
Models AGS-DM are standard efficiency, remote evaporator; AGS-DF are high efficiency, remote
evaporator.
This section contains data that is unique to AGS-DM/F remote evaporator models including:
Refrigerant piping beginning on page 65.
Dimensions beginning on page 69.
Physical data beginning on page 29
Data common to both packaged and remote evaporator models are:
Electrical data beginning on page 37.
Evaporator pressure drop on page 26.

Field Wiring
The following field connections are required:

Figure 34, Remote Evaporator Field Wiring

DETAIL VIEW OF
MCQUAY JUNCTION BOX

R1
R1 R2
R2
W1 W
FIELD SUPPLIED

R3
L1
W2 W3
SOLENOID

L1
FIELD
MCQUAY R W JUNCTION BOX
R1 W1
JUNCTION BOX
R W R W R2
(ON BASE RAIL) L2
W2 SOLENOID
L2 L3
R3 W3

FIELD SUPPLIED

R1 W1 L3
SOLENOID
R2
R1
DETAIL VIEW OF R2 W2
LEGEND
FIELD JUNCTION BOX
R3 R3
3 CIRCUIT UNITS ONLY
W3 WIRE NUTS
W
R RED 14GA WIRE (MIN.)
W WHITE 14GA WIRE (MIN.)

331687601 REV.00

1. The 110V liquid line solenoid valves have to be wired back to the outdoor unit. Install a junction
box adjacent to the evaporator and wire from each valve (two or three depending on model) to it.
All the wiring, in conduit, can then be run from the box back to the unit junction box located on a
unit base cross-frame between the compressors. The connections are made to marked terminals as
shown in Figure 34. Wiring from the unit terminal box to the unit control panel is done in the
factory.

64 IMM AGSD
2. The electronic expansion valve has a 40-foot long cable attached and can be used, as is, when the
outdoor unit is less than 40 feet away. Beyond that, a junction box must be located within 40-feet
of the evaporator, and up to 60 additional feet of 14GA wire connected from the cable to the unit,
allowing up to a total distance of 100 feet (40 feet of cable and up to 60 feet of 14GA).
3. Two evaporator water temperature sensors (WOE-outlet nozzle and WIE-inlet nozzle) with 100
feet of cable coiled up and attached to the unit base for extension to the evaporator and insertion in
fittings located on the side of the inlet and outlet nozzles.
4. One suction line refrigerant temperature sensor (ST1/2/3) per circuit with 100 feet of cable coiled
up and attached to the unit base for extension to the evaporator.
5. One suction line pressure transducer per circuit (WL1/2/3) with 100 feet of cable is factory-
mounted on the outdoor unit’s suction line. Move the transducer to the field-installed suction line,
adjacent to the evaporator, securing the cable as required.

Refrigerant Piping
Piping Layout
IMPORTANT NOTE: A drawing of the refrigerant piping showing all fittings, line sizes and lengths,
and elevations should have be submitted to McQuay, through the local sales office, for approval before
entering order. It is prudent for the installing contractor to confirm that this was done before actually
installing any piping.
All field piping, wiring, and procedures must be performed to ASHRAE, EPA and industry standards
Figure 35 shows the piping layout for one of the two or three refrigerant circuits for AGS units with a
remote evaporator. Note that the refrigerant specialties are field installed adjacent to the evaporator
and that the suction shutoff valve is standard on remote evaporator units. The outdoor unit, the
evaporator, and a kit of refrigerant components are shipped as separate pieces.
The outdoor unit will have a full charge of refrigerant pumped down into the condensers. Additional
charge of refrigerant and oil will be required in the field, supplied by the customer, for the additional
field piping.
The location and size of the refrigerant connections are shown on the dimension drawings beginning
on page 69.
Layout and size the refrigerant piping in accordance with the latest edition of the ASHRAE Handbook.
A line-sizing guide is below. Keep the refrigerant suction line pressure drop to a maximum of 2-
degree F. in saturated temperature equivalent. Each suction line’s velocity must be sufficient to carry
oil when considering a capacity reduction of 25% in each circuit.
NOTE: The following applies to all size units
• Maximum linear line length cannot exceed 75 feet.
Maximum total equivalent length (TEL) cannot exceed 180 feet.
The evaporator cannot be located more than 15 feet above the outdoor unit
The evaporator cannot be located more than 20 feet below the outdoor unit.
Suction line connection at unit = 4 1/8-inch OD each.
A piping drawing showing altitudes, line lengths, slopes and all fittings, using Form SF 99006
(Revised 5/02), must be sent to the local McQuay sales office for transmittal to the McQuay Technical
Response Center for review prior to entering a unit order.
Underground refrigerant piping is not permitted
When facing the unit control box, the left-hand compressor is circuit # 1, and the right-hand is circuit #
2. The compressor behind #2, on the right side, is circuit #3.
The liquid line can be subcooled below ambient temperature and must be insulated to prevent loss of
subcooling and consequent liquid refrigerant flashing and capacity loss.

IMM AGSD 65
Table 45, Fitting Equivalent Feet of Pipe
Line Size 90 Degree Std. 90 Degree Long
Angle Valve Globe Valve Ball Valve
In. OD Radius Elbow Radius Elbow
2 5/8 29.00 69.0 1.0 6.0 4.1
3 1/8 35.0 84.0 1.0 7.5 5.0
3 5/8 41.0 100.0 1.0 9.0 5.9
4 1/8 47.0 120.0 1.0 10.0 6.7

Table 46, Recommended Horizontal or Downflow Suction Line Size


Up to 50 Up to 75 Up to 100 Up to 125 Up to 150
AGS-D
Circuit Equiv. Ft. Equiv. Ft. Equiv. Ft. Equiv. Ft. Equiv. Ft.
Model
Size PD Size PD Size PD Size PD Size PD
225DM 225DF Both 3 5/8 1.47 4 1/8 1.19 4 1/8 1.59 4 1/8 1.98 4 1/8 2.38
1 3 5/8 1.47 4 1/8 1.19 4 1/8 1.59 4 1/8 1.98 4 1/8 2.38
250DM 250DF
2 3 5/8 2.01 4 1/8 1.63 4 1/8 2.17 4 1/8 2.72 4 1/8 3.26
275DM 260DF 1 4 1/8 1.09 4 1/8 1.63 4 1/8 2.17 4 1/8 2.72 4 1/8 3.26
275DF 2 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02 5 1/8 1.33 5 1/8 1.60
300DF 300DM Both 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02 5 1/8 1.33 5 1/8 1.60
330DF 330DM All 3 3 5/8 1.47 4 1/8 1.19 4 1/8 1.59 4 1/8 1.98 4 1/8 2.38
1& 3 3 5/8 1.47 4 1/8 1.19 4 1/8 1.59 4 1/8 1.98 4 1/8 2.38
350DF 350DM
2 3 5/8 2.01 4 1/8 1.63 4 1/8 2.17 4 1/8 2.72 4 1/8 3.26
1&2 3 5/8 2.01 4 1/8 1.63 4 1/8 2.17 4 1/8 2.72 4 1/8 3.26
360DM
3 3 5/8 1.47 4 1/8 1.19 4 1/8 1.59 4 1/8 1.98 4 1/8 2.38
390DM All 3 4 1/8 1.09 4 1/8 1.63 4 1/8 2.17 4 1/8 2.72 4 1/8 3.26
1&2 4 1/8 1.09 4 1/8 1.63 4 1/8 2.17 4 1/8 2.72 4 1/8 3.26
400DF 400DM
3 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02 5 1/8 1.33 5 1/8 1.60
450DF 450DM All 3 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02 5 1/8 1.33 5 1/8 1.60
Notes:
1. “Size” is tubing size in inches. Pressure drop is shown in degrees F, multiply by 0.97 for psi.
2. For equivalent lengths between table values, use the column higher than the length and calculate pressure
drop based on a direct ratio of the length compared to column value. .Example: for 90 ft equivalent length,
use (90/100) times the pressure drop shown in the 100 Eqiv. Ft column.
Table 47, Recommended Upflow Suction line Size
Up to 50 Up to 75 Up to 100
AGS-D
Circuit Equiv. Ft. Equiv. Ft. Equiv. Ft.
Model
Size PD Size PD Size PD
225DF 225DM Both 3 5/8 1.47 3 5/8 2.20 3 5/8 2.94
1 3 5/8 1.47 3 5/8 2.20 3 5/8 2.94
250DF 250DM
2 3 5/8 2.01 4 1/8 1.63 4 1/8 2.17
260DF 275DM 1 4 1/8 1.09 4 1/8 1.63 4 1/8 2.17
275DF 2 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02
300DF 300DM Both 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02
330DF 330DM All 3 3 5/8 1.47 3 5/8 2.20 3 5/8 2.94
1& 3 3 5/8 1.47 3 5/8 2.20 3 5/8 2.94
350DF 350DM
2 3 5/8 2.01 4 1/8 1.63 4 1/8 2.17
1&2 3 5/8 2.01 4 1/8 1.63 4 1/8 2.17
360DM
3 3 5/8 1.47 3 5/8 2.20 3 5/8 2.94
390DM All 3 4 1/8 1.09 4 1/8 1.63 4 1/8 2.17
1&2 4 1/8 1.09 4 1/8 1.63 4 1/8 2.17
400DF 400DM
3 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02
450DF 450DM All 3 4 1/8 1.51 4 1/8 2.26 4 1/8 3.02
Notes are on the following page:
1. Pressure Drop is shown in degrees F., multiply by 0.97 for psi.
2. Do not use pipe size larger than shown in table for suction upflow line as flow velocity must be maintained
with compressor unloaded in order to return oil to the compressor at light load conditions.

Table 48, Recommended Liquid line Size.


AGS-D Circuit Up to 50 Up to 75 Up to 100 Up to 125 Up to 150

66 IMM AGSD
Model Equiv. Ft. Equiv. Ft. Equiv. Ft. Equiv. Ft. Equiv. Ft.
Size PD Size PD Size PD Size PD Size PD
225 DF 225 DM Both 1 5/8 0.84 1 5/8 1.26 1 5/8 1.68 1 5/8 2.11 1 5/8 2.53
1 1 5/8 0.84 1 5/8 1.26 1 5/8 1.68 1 5/8 2.11 1 5/8 2.53
250 DF 250 DM
2 1 5/8 1.15 1 5/8 1.73 1 5/8 2.31 1 5/8 2.88 1 5/8 3.46
260 DF 275 DM 1 1 5/8 1.15 1 5/8 1.73 1 5/8 2.31 1 5/8 2.88 1 5/8 3.46
275 DF 2 1 5/8 1.60 1 5/8 2.40 1 5/8 3.20 1 5/8 4.00 1 5/8 4.80
300 DF 300 DM Both 1 5/8 1.60 1 5/8 2.40 1 5/8 3.20 1 5/8 4.00 1 5/8 4.80
330 DF 330 DM All 3 1 5/8 0.84 1 5/8 1.26 1 5/8 1.68 1 5/8 2.11 1 5/8 2.53
1& 3 1 5/8 0.84 1 5/8 1.26 1 5/8 1.68 1 5/8 2.11 1 5/8 2.53
350 DF 350 DM
2 1 5/8 1.15 1 5/8 1.73 1 5/8 2.31 1 5/8 2.88 1 5/8 3.46
1&2 1 5/8 1.15 1 5/8 1.73 1 5/8 2.31 1 5/8 2.88 1 5/8 3.46
360 DM
3 1 5/8 0.84 1 5/8 1.26 1 5/8 1.68 1 5/8 2.11 1 5/8 2.38
390 DM All 3 1 5/8 1.15 1 5/8 1.73 1 5/8 2.31 1 5/8 2.88 1 5/8 3.46
1&2 1 5/8 1.15 1 5/8 1.73 1 5/8 2.31 1 5/8 2.88 1 5/8 3.46
400 DF 400 DM
3 1 5/8 1.60 1 5/8 2.40 1 5/8 3.20 1 5/8 4.00 1 5/8 4.80
450 DM 450 DF All 3 1 5/8 1.60 1 5/8 2.40 1 5/8 3.20 1 5/8 4.00 1 5/8 4.80
NOTE:
1. “Size” is tubing size in inches, “PD” is the pressure drop in degrees F. Multiply by 2.2 for psi.
2. Liquid line size shown is recommended selection based on cost and performance considerations.
3. Exceeding 1 5/8 liquid line size will cause problems with pumpdown capacity. Liquid subcooling is
adequate for line sizing shown in he table.
Figure 35, Remote Evaporator Piping Schematic
AIR DISCHARGE DISCHARGE
RELIEF
SCHRADER FLOW TRANSDUCER TEMP. SENSOR
DISCHARGE VALVE SCHRADER
VALVE (WH1, WH2) (WD1, WD2)
TUBING VALVE
(HEADER) DISCHARGE (MOUNTED ON SUCTION VALVE
CHECK VALVE BODY AT BACK SEAT PORT)

CHARGING
AIR
VALVE CHARGING
FLOW
VALVE
OIL
CHARGING AIR TRANSDUCER SUCTION
VALVE FLOW (WO1, WO2) SHUT-OFF
KING VALVE
SCHRADER
VALVE OUTSIDE AIR
CONDENSER
TEMPERATURE CHARGING
ASSEMBLY (WAA)
FRAME 4 VALVE
COMPRESSOR
OIL (MOUNTED ON SUCTION
SEPARATOR VALVE BODY)

STUB
TUBE SCHRADER
ECONOMIZER FLASH GAS TO COMPRESSOR INTERSTAGE
VALVE

SHUT-OFF RELIEF
TO VALVE FIELD
CONNECTION VALVE
COMPRESSOR
OIL FILTER POINT
LIQUID
TUBING SCHRADER
VALVE SUCTION
SIGHT FIELD PIPING
TUBING
GLASS FROM SHOWN DASHED
OIL SEPARATOR
SHUT-OFF VALVE
SOLENOID COMPRESSOR
VALVE SUCTION
OIL SUPPLY TRANSDUCER
CHECK
SCHRADER (WL1, WL2)
VALVE
VALVE

THERMAL
EXPANSION FIELD IMPORTANT:
WATER OUT WATER IN THESE TWO COMPONENTS
VALVE CONNECTION
LIQUID (WOE TEMP. (WIE TEMP. MUST BE MOUNTED NEAR
POINT SOLENOID SCHRADER SCHRADER
SHUT-OFF SENSOR) SENSOR) REMOTE EVAPORATOR
VALVE VALVE VALVE
VALVE

FLOW

STUB SCHRADER
TUBE VALVE SUCTION
SHUT-OFF ELECTRONIC TEMP. SENSOR
ECONOMIZER FILTER SIGHT
FILTER BALL VALVE EXPANSION (ST1, ST2)
SCHRADER DRIER #2 GLASS DX EVAPORATOR
DRIER #1 VALVE
VALVE
FIELD INSTALLED LIQUID LINE COMPONENTS
(NOTE: FILTER DRIER #2 REQUIRED IN FIELD PIPING)

Refrigerant Specialties Kit Components (shipped with the unit)


Filter-drier and cores for field piping Sight glass
Electronic expansion valve Solenoid valve
Evaporator vent and drain shutoff valves Charging Valve
Suction coupling and flange for attachment to the evaporator

Performance Derate Data


There is a derate to the packaged AGS performance due to field installed refrigerant line losses
exceeding those found on the packaged arrangement. Once the pipe design is finalized, the actual
adjustment is easily determined using the procedure shown below. For preliminary purposes, the
following can be used as a conservative estimate:

IMM AGSD 67
Table 49, Approximate Derate Factors
Actual Line Length
Capacity Derate Power Derate EER Derate
Up To
75 0.94 0.97 0.97
50 0.96 0.98 0.98
25 0.98 0.99 0.99

Derate Procedure
1. Sketch the liquid and suction piping, including the actual pipe lengths and all fittings.
2. Using the recommended pipe sizes from Table 46 and Table 47, add up the equivalent pressure
drop for the fittings in the suction line. Add this value to the actual linear feet of tubing to determine
the total equivalent feet for the piping run.
3. Again using Table 46 and Table 47, determine the pressure drop (in degrees F) based on the
TEL. Interpolation is encouraged.
4. Determine the derate factors from Table 50 based on the suction line pressure drop.
Table 50, Performance Derate Factors
Suction Line Unit Unit Unit
Press Drop °F Capacity % Power % EER %
0 100.0 100.0 100.0
1.0 98.3 99.0 99.3
2.0 96.2 98.1 98.1
3.0 94.4 97.2 97.1
4.0 92.5 96.3 96.1

68 IMM AGSD
Physical Data
Standard Efficiency
Table 51, Standard Efficiency, Remote Evaporator, AGS 225DM – AGS 275DM
AGS-DM MODEL NUMBER
DATA 225DM 250DM 275DM
Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI tons (kW)
211.2 (742.6) 231.6 (814.3) 263.1 (925.1)
(Before Refrigerant Piping Derate)
Unit Operating Charge lbs (kg) 185 (84) 185 (84) 210 (95) 210 (95) 210 (95) 240 (109)
Cabinet Dimensions 243x88x97 279x88x97 314x88x97
L x W x H, in. (mm) (6172x2225x2464) (7087x2225x2464) (7984x2225x2464)
Unit Operating Weight, lbs. (kg) 10814 (4905) 11518 (5225) 12226 (5546)
Unit Shipping Weight, lbs (kg) 10814 (4905) 11518 (5225) 12226 (5546)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 125 (4370 125 (4370 150 (525)
Min. Unit Capacity (% of Full Load) 15 15 15

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 249 (113) 249 (113) 287 (130) 287 (130) 287 (130) 325 (148)
Coil Inlet Face Area, sq. ft. (sq m.) 129.2 (12.0) 129.2 (12.0) 150.8 (14.0) 150.8 (14.0) 150.8 (14.0) 172.5 (16.0)
Rows Deep/Fins Per Inch 3/16 3/16 3/16 3/16 3/16 3/16

CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE


No. of Fans/Circuit – 30 in. Fan Dia. 6 6 7 7 8 8
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 137328 (64819) 160216 (75622) 183104 (86425)

REMOTE EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 330904451 330904451 330904453
Shell Dia.-Tube Length
16x108 (406x2750) 16x108 (406x2750) 20x108 (508x2750)
in.(mm) - in. (mm)
Operating Weight, lbs (kg) 1674 (759) 1674 (759) 2472 (1121)
Shipping Weight, ibs (kg) 1317 (597) 1317 (597) 1760 (798)
Water Volume, gallons (liters) 65.8 (249.4) 65.8 (249.4) 108.5 (411.1)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

IMM AGSD 69
Table 52, Standard Efficiency, AGS 300DM
AGS MODEL NUMBER
DATA 300DM
Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI, tons (kW)
297.0 (1042.5)
(Before Piping Loss Derate)
Unit Operating Charge lbs (kg) 240 (109) 240 (109)
Cabinet Dimensions 314x88x97
L x W x H, in. (mm) (7984x2225x2464)
Unit Operating Weight (1), lbs. (kg) 12226 (5909)
Unit Shipping Weight(1), lbs (kg) 12226 (5909)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 150 (525) 150 (525)
Min. Unit Capacity (% of Full Load) 15

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE


Pumpdown Capacity, lbs (kg) 325 (148) 325 (148)
Coil Inlet Face Area, sq. ft. (sq m.) 172.5 (16.0) 172.5 (16.0)
Rows Deep/Fins Per Inch 3/16 3/16

CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE


No. of Fans/Circuit – 30 in. Fan Dia 8 8
Fan Motor -- hp (kW) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 183104 (86425)

REMOTE EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 330904454
Shell Dia.-Tube Length
20x108 (508x2750)
in.(mm) - in. (mm)
Operating Weight, lbs (kg) 2471 (1121)
Shipping Weight, ibs (kg) 1802 (817)
Water Volume, gallons (liters) 103.2 (391.2)
Max. Water Pressure, psi (kPa) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413)

70 IMM AGSD
Table 53, Standard Efficiency, Remote Evaporator, AGS 330DM – AGS 360DM
AGS MODEL NUMBER
DATA 330DM 350DM 360DM
Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW)
318.7 (1120.5) 337.2 (1185.6) 351.1 (1234.5)
Before Piping Loss Derate0
Unit Operating Charge, lbs (kg) 210 (95) 210 (95) 190 (86 210 (95) 210 (95) 190 (86) 210 (95) 210 (95) 190 (86)
Cabinet Dim., 403x88x97 403x88x97 403x88x97
L x W x H, in. (mm) (10239x2225x2459) (10239x2225x2459) (10239x2225x2459)
Operating Weight(1), lbs. (kg) 17798 (8073) 17798 (8073) 17798 (8073)
Shipping Weight(1), lbs (kg) 17798 (8073) 17798 (8073) 17798 (8073)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 100 (350) 125 (437) 100 (350) 125 (437) 125 (437) 100 (350)
Min. Unit Capacity (% of Full Load) 10 10 10

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 287 (130) 287 (130) 243 (110) 287 (130) 287 (130) 243 (110) 287 (130) 287 (130) 243 (110)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14) 150.8 (14) 128.5 (12) 150.8 (14) 150.8 (14) 128.5 (12) 150.8 (14) 150.8 (14) 128.5 (12)
Rows Deep/Fins Per Inch 3/16 3/16 3/16 3/16 3/16 3/16 3/16 3/16 3/16

CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE


No. of Fans/Cir, Fan Dia. 30 in 7 7 6 7 7 6 7 7 6
Fan Motor -- hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 228880 (108031) 228880 (108031) 228880 (108031)

REMOTE EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 330904455 330904455 330904456
Shell Dia.,Tube Length in.(mm) 20x108 (508x2750) 20x108 (508x2750) 20x108 (508x2750)
Operating Weight, lbs (kg) 2460 (1116) 2460 (1116) 2471 (1121)
Shipping Weight, ibs (kg) 1760 (798) 1760 (798) 1802 (817)
Water Volume, gallons (liters) 107.0 (405.4) 107.0 (405.4) 103.2 (391.2)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

IMM AGSD 71
Table 54, Standard Efficiency, Remote Evaporator, AGS 390DM – AGS 450DM
AGS MODEL NUMBER
DATA 390DM 400DM 450DM
Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW)
373.2 (1311.8) 390.4 (1373.3)) 434.8 (1529.1)
Before Piping Loss Derate
Unit Operating Charge, lbs (kg) 210 (95) 210 (95) 230 (104) 215 (97) 215 (97) 235 (106) 140 (109) 140 (109) 140 (109)
439x88x97 439x88x97 474x88x97
Cabinet Dim., L x W x H, in. (mm)
11140x2225x2459) 11140x2225x2459) 12040x2225x2459)
Operating Weight(1), lbs. (kg) 18632 (8451) 18632 (8451) 18632 (8451)
Shipping Weight(1), lbs (kg) 18632 (8451) 18632 (8451) 18632 (8451)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 125 (437) 125 (437) 125 (437) 125 (437) 125 (437) 150 (525) 150 (525) 150 (525) 150 (525)
Min. Unit Capacity (% of Full Load) 10 10 10

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 287 (130) 287 (130) 316 (144) 287 (130) 287 (130) 316 (144) 325 (147) 325 (147) 316 (144)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14) 150.8 (14) 171.7 (16) 150.8 (14) 150.8 (14) 171.7 (16) 172.5 (16) 172.5 (16) 171.7 (16
Rows Deep/Fins Per Inch 3/16 3/16 3/16 3/16 3/16 3/16 3/16 3/16 3/16
CONDENSER FANS, DIRECT DRIVE PROPELLER
TYPE
No. of 30-in Fans/Circuit 7 7 8 7 7 8 8 8 8
Fan Motor -- hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 251768 (118835) 251768 (118835) 274656 (129637)

EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 330904456 330904457 330904457
Shell Dia.,Tube Length in.(mm) 20x108 (508x2750) 20x149 (508x3785) 20x149 (508x3785)
Operating Weight, lbs (kg) 2471 (1121) 2996 (1360) 2996 (1360)
Shipping Weight, ibs (kg) 1802 (817) 2072 (940) 2072 (940)
Water Volume, gallons (liters) 103.2 (391.2) 97.2 (368.5) 97.2 (368.5)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

72 IMM AGSD
High Efficiency
Table 55, High Efficiency, Remote Evaporator, AGS 225DF – AGS 260DF
AGS-DE MODEL NUMBER
DATA 225DF 250DF 260DF
Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI, Tons (Kw)
214.9 (755.6) 235.5 (828.0) 249.6 (877.6)
Before Piping Loss Derate
R-134a, Operating Charge lbs (kg) 210 (95) 210 (95) 210 (95) 210 (95) 240 (109) 240 (109)
Cabinet Dimensions 279x88x97 314x88x97 314x88x97
L x W x H, in. (mm) (7087x2225x2464) (7984x2225x2464) (7984x2225x2464)
Unit Operating Weight, lbs. (kg) 11518 (5225) 12226 (5646) 12226 (5646)
Unit Shipping Weight, lbs (kg) 11518 (5225) 12226 (5646) 12226 (5646)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 125 (437) 125 (4370 125 (437)
Min. Unit Capacity (% of Full Load) 15 15 15

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 249 (13) 249 (113) 287 (130) 187 (130) 325 (147) 325 (147)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14.0) 150.8 (14.0) 150.8 (14.0) 172.5 (16) 172.5 (16.0) 172.5 (16.0)
Rows Deep/Fins Per Inch 3/16 3/16 3/16 3/16 3/16 3/16

CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE


No. of Fans/Circuit – 30 in. Fan Dia. 7 7 8 8 8 8
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 160216 (75622) 18310 (86424) 183104 (86425)

REMOTE EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 330904452 330904452 330904453
Shell Dia.-Tube Length
16x108 (406x2750) 16x108 (406x2750) 20x108 (508x2750)
in.(mm) - in. (mm)
Operating Weight, lbs (kg) 1675 (760) 1675 (760) 2472 (1121)
Shipping Weight, ibs (kg) 1336 (606) 1336 (606) 1760 (798)
Water Volume, gallons (liters) 63.6 (241.0) 63.6 (241.0) 108.5 (411.1)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

IMM AGSD 73
Table 56, High Efficiency, Remote Evaporator, AGS 275DF – AGS 300DF
AGS MODEL NUMBER
DATA 275DF 300DF
Ckt 1 Ckt 2 Ckt 1 Ckt 2
BASIC DATA
Unit Cap. @ ARI, tons (kW)
267.7 (940.9) 299.5 (1053.0)
Before Piping Loss Derate
Unit Operating Charge lbs (kg) 240 (109) 260 (118) 265 (120) 265 (120)
Cabinet Dimensions 350x88x97 350x88x97
L x W x H, in. (mm) (8890x2225x2464) (8890x2225x2464)
Unit Operating Weight (1), lbs. (kg) 13027 (5909) 13027 (5909)
Unit Shipping Weight(1), lbs (kg) 13027 (5909) 13027 (5909)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 125 (437) 150 (525) 150 (525) 150 (525)
Min. Unit Capacity (% of Full Load) 15 15

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 325 (147) 361 (164) 361 (164) 361 (164)
Coil Inlet Face Area, sq. ft. (sq m.) 172.5 (16.0) 194.2 (18.0) 194.2 (18.0) 194.2 (18.0)
Rows Deep/Fins Per Inch 3/16 3/16 3/16 3/16

CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE


No. of Fans/Circuit – 30 in. Fan Dia. 9 9 9 9
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 205992 (97228) 205992 (97228)

EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 330904453 330904454
Shell Dia.-Tube Length
20x108 (508x2750) 20x108 (508x2750)
in.(mm) - in. (mm)
Operating Weight, lbs (kg) 2472 (1121) 2471 (1121)
Shipping Weight, ibs (kg) 1760 (798) 1802 (817)
Water Volume, gallons (liters) 108.5 (411.1) 103.2 (391.2)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413)

74 IMM AGSD
Table 57, High Efficiency, Remote Evaporator, AGS 330DF – AGS 400DF
AGS MODEL NUMBER
DATA 330DF 350DF 400DF
Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3 Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW)
324.1 (1139.6) 342.9 (1205.6) 397.1 (1396.6)
Before Piping Loss Derate
Unit Operating Charge, lbs (kg) 210 (95) 210 (95) 230 (104) 210 (95) 240 (109) 240 (109) 240 (109) 240 (109) 240 (109)
439x88x97 474x88x97 474x88x97
Cabinet Dim., L x W x H, in. (mm)
(11140x2225x2459) (12040x2225x2459) (12040x2225x2459)
Operating Weight(1), lbs. (kg) 18632 (8451) 19305 (8757) 19305 (8757)
Shipping Weight(1), lbs (kg) 18632 (8451) 19305 (8757) 19305 (8757)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 100 (350) 100 (350) 100 (350) 100 (350) 125 (437) 100 (350) 125 (437) 125 (437) 150 (525)
Min. Unit Capacity (% of Full Load) 10 10 10

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Pumpdown Capacity, lbs (kg) 287 (130) 287 (130) 316 (1440 325 (147) 325 (147) 316 (144) 325 (147) 325 (147) 316 (144)
Coil Inlet Face Area, sq. ft. (sq m.) 150.8 (14) 150.8 (14) 171.7 (16) 150.8 (14) 172.5 (16) 171.7 (16) 172.5 (16) 172.5 (16) 171.7 (16)
Rows Deep/Fins Per Inch 3/16 3/16 3/16 3/16 3/16 3/16 3/16 3/16 3/16

CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE


No. of Fans/Circuit – 30 in. Fan Dia. 7 7 8 8 8 8 8 8 8
Fan Motor hp (kW) 2.5 (1.8) 2.5 (1.8) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45) 8954 (45) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 251768 (118834) 274656 (129638) 274656 (129638)

REMOTE EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 330904455 330904456 330904457
Shell Dia.,Tube Length in.(mm) 20x108 (508x2750) 20x108 (508x2750) 20x142 (508x3600)
Operating Weight, lbs (kg) 2460 (1116) 2471 (1121) 2996 (1360)
Shipping Weight, ibs (kg) 1760 (798) 1802 (817) 2072 (940)
Water Volume, gallons (liters) 103.2 (391.2) 102.1 (387.0) 90.5 (343.0)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413) 350 (2413) 350 (2413)

IMM AGSD 75
Table 58, High Efficiency, Remote Evaporator, AGS 450DF
AGS MODEL NUMBER
DATA 450DF
Ckt. 1 Ckt. 2 Ckt. 3
BASIC DATA
Unit Cap. @ ARI, tons (kW)
438.0 (1540.0)
Before Piping Loss Derate
Unit Operating Charge, lbs (kg) 270 (122) 270 (122) 240 (109)
509x88x97
Cabinet Dim., L x W x H, in. (mm)
(12939x2225x2459)
Unit Operating Weight, lbs. (kg) 20294 (9205)
Unit Shipping Weight, lbs (kg) 20383 (9254)

COMPRESSORS, SCREW, SEMI-HERMETIC


Nominal Capacity, tons (kW) 150 (525) 150 (525) 150 (525)
Min Unit Capacity (% of Full Load) 10

CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE


Pumpdown Capacity, lbs (kg) 361 (164) 361 (164) 316 (144)
Coil Inlet Face Area, sq. ft. (sq m.) 172.5 (16) 194.2 (18) 171.7 (16)
Rows Deep/Fins Per Inch 3/16 3/16 3/16

CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE


No. of Fans/Circuit – 30 in. Fan
9 9 8
Dia.
Fan Motor hp (kW) 2.5 (1.8)
Fan & Motor RPM, 60Hz 1140
60 Hz Fan Tip Speed, fpm (m/s) 8954 (45)
60 Hz Total Unit Airflow, cfm (l/s) 297544 (140440)

EVAPORATOR, DIRECT EXPANSION SHELL AND TUBE


Model Number 303904457
Shell Dia. -- Tube Length
20x142 (508x142)
in.(mm) - in. (mm)
Operating Weight, lbs (kg) 2996 (1360)
Shipping Weight, ibs (kg) 2072 (940)
Water Volume, gallons (liters) 90.5 (343.0)
Max. Water Pressure, psi (kPa) 152 (1048)
Max. Refrigerant Press., psi (kPa) 350 (2413)

76 IMM AGSD
Dimensions and Weights
Figure 36, Two-Compressor, Remote Evaporator Models, Standard and High Efficiency

CONTROL BOX
CIR
LIQUID SUCTION #2
CONNECTION
( 1.62 O.D. ) CONNECTION
( 4.12 O.D. )
CIR
#1

"D”

"E”
"F”
"G”

CONTROL POWER POWER


PANEL PANEL PANEL
96.72
2457 MAIN
DISCONNECT
FIELD SWITCH
89.89 CONTROL
2283 HANDLE

"Y" POWER
33.83 ENTRY
859

"Z"
CIR #1 CIR #2
"A”
"B”
"X"
"C”
88.10
"H” 2238
(INCLUDES
331695201D010A LIFTING BRKTS)

NOTE:
1. Allow a 1-inch manufacturing tolerance on all dimensions.
2. See Figure 24 on page 33 for location dimensions of the control and power knockouts.

INCH-POUND UNITS OF MEASURE

SHIPPING OPERATING NO. OF Lifting Locations Mounting Locations Center of Gravity


UNIT SIZE H
WEIGHT WEIGHT FANS
A B C D E F G X Y Z
STD EFF.
AGS225DM 10814 10814 12 32.5 N/A 210.8 25.6 84.7 N/A 217.7 243.3 45.4 42.3 86.6
AGS250DM 11518 11518 14 32.5 102.1 255.9 25.6 84.7 194.1 253.2 278.7 45.5 43.7 97.5
AGS275DM 12226 12226 16 32.5 102.1 250.1 25.6 84.7 199.7 288.6 314.2 45.2 44.4 109.0
AGS300DM 12226 12226 16 32.5 102.1 250.1 25.6 84.7 199.7 288.6 314.2 45.2 44.4 109.0
HIGH EFF.
AGS225DF 11518 11518 14 32.5 102.1 255.9 25.6 84.7 194.1 253.2 278.7 45.5 43.7 97.5
AGS250DF 12226 12226 16 32.5 102.1 250.1 25.6 84.7 199.7 288.6 314.2 45.2 44.4 109.0
AGS260DF 12226 12226 16 32.5 102.1 250.1 25.6 84.7 199.7 288.6 314.2 45.2 44.4 109.0
AGS275DF 13027 13027 18 32.5 102.1 266.4 25.6 84.7 198.8 324.0 349.6 45.2 45.9 122.1
AGS300DF 13027 13027 18 32.5 102.1 266.4 25.6 84.7 198.8 324.0 349.6 45.2 45.9 122.1
SI UNITS OF MEASURE mm-kg
STD EFF.
AGS225DM 4905 4905 12 826 N/A 5354 650 2151 N/A 5530 6180 1153 1074 2200
AGS250DM 5225 5225 14 826 2594 6500 650 2151 4930 6431 7079 1156 1110 2477
AGS275DM 5546 5546 16 826 2594 6353 650 2151 5072 7330 7981 1148 1128 2769
AGS300DM 5546 5546 16 826 2594 6353 650 2151 5072 7330 7981 1148 1128 2769
HIGH EFF.
AGS225DF 5225 5225 14 826 2594 6500 650 2151 4930 6431 7079 1156 1110 2477
AGS250DF 5546 5546 16 826 2594 6353 650 2151 5072 7330 7981 1148 1128 2769
AGS260DF 5546 5546 16 826 2594 6353 650 2151 5072 7330 7981 1148 1128 2769
AGS275DF 5909 5909 18 826 2594 6767 650 2151 5050 8230 8880 1148 1166 3101
AGS300DF 5909 5909 18 826 2594 6767 650 2151 5050 8230 8880 1148 1166 3101

IMM AGSD 77
Figure 37, Three-Compressor, Remote Evaporator Models, Standard and High
Efficiency
CIR #3 CIR #2

CIR
#3
CIR
#2

LIQUID SUCTION
CONNECTION CIR
CONN.
( 1.62 O.D. ) ( 4.12 O.D. ) #1

CIR #1
"E”
"F”
"G”
"H”
"J”

96.72
2457
C/G MAIN
89.89 FIELD
CONTROL C/G DISCONNECT
2283 SWITCH
HANDLE

"Y" "Y"
CIR #1 POWER
ENTRY

"Z" "X"

"A" 88.10
"B" 2238
(INCLUDES
"C" LIFTING BRKT)
"D"
"K" 331695202D010A

NOTES:
1. Allow a 1-inch manufacturing tolerance on all dimensions.
2. See Figure 30 on page 34 for location dimensions for control and power knockouts.
INCH-POUND UNITS OF MEASURE
SHIP RUN NO. OF Lifting Locations Mounting Locations Center of Gravity
UNIT SIZE K
WT WT FANS
A B C D E F G H J X Y Z
STD EFF.
AGS330DM 17798 17798 20 32.5 140.8 262.0 339.3 25.6 84.7 177.0 269.3 361.6 403.1 42.0 42.8 144.1
AGS350DM 17798 17798 20 32.5 140.8 262.0 339.3 25.6 84.7 177.0 269.3 361.6 403.1 42.0 42.8 144.1
AGS360DM 17798 17798 20 32.5 140.8 262.0 339.3 25.6 84.7 177.0 269.3 361.6 403.1 42.0 42.8 144.1
AGS390DM 18632 18632 22 32.5 140.8 262.0 348.3 25.6 84.7 177.0 269.3 361.6 438.6 42.0 43.5 155.3
AGS400DM 18632 18632 22 32.5 140.8 262.0 348.3 25.6 84.7 177.0 269.3 361.6 438.6 42.0 43.5 155.3
AGS450DM 18632 18632 24 32.5 140.8 297.8 383.8 25.6 84.7 177.0 304.7 397.0 474.0 42.2 44.3 167.2
HIGH EFF.
AGS330DF 18632 18632 22 32.5 140.8 262.0 348.3 25.6 84.7 177.0 269.3 361.6 438.6 42.0 43.5 155.3
AGS350DF 19305 19305 24 32.5 140.8 297.4 383.8 25.6 84.7 177.0 304.7 397.0 474.0 42.2 44.3 167.2
AGS400DF 19305 19305 24 32.5 140.8 297.4 383.8 25.6 84.7 177.0 304.7 397.0 474.0 42.2 44.3 167.2
AGS450DF 20294 20294 26 32.5 140.8 297.4 419.2 25.6 84.7 177.0 304.7 432.5 509.4 42.1 45.1 181.2
SI UNITS OF MEASURE mm, kg
SHIP RUN NO. OF Lifting Locations Mounting Locations Center of Gravity
UNIT SIZE K
WT WT FANS
A B C D E F G H J X Y Z
STD EFF.
AGS330DM 8073 8073 20 826 3576 6655 8618 650 2150 4496 6840 9185 10239 1067 1087 3660
AGS350DM 8073 8073 20 826 3576 6655 8618 650 2150 4496 6840 9185 10239 1067 1087 3660
AGS360DM 8073 8073 20 826 3576 6655 8618 650 2150 4496 6840 9185 10239 1067 1087 3660
AGS390DM 8451 8451 22 826 3576 6655 8847 650 2150 4496 6840 9185 11140 1067 1105 3945
AGS400DM 8451 8451 22 826 3576 6655 8847 650 2150 4496 6840 9185 11140 1067 1105 3945
AGS450DM 8451 8451 22 826 3576 7564 9749 650 2150 4496 7739 10084 12040 1072 1125 4247
HIGH EFF.
AGS330DF 8451 8451 22 826 3576 6655 8847 650 2150 4496 6840 9185 11140 1067 1105 3945
AGS350DF 8757 8757 24 826 3576 7554 9749 650 2150 4496 7739 10084 12040 1072 1125 4247
AGS400DF 8757 8757 24 826 3576 7554 9749 650 2150 4496 7739 10084 12040 1072 1125 4247
AGS450DF 9205 9205 26 826 3576 7554 10648 650 2150 4496 7739 10986 12939 1069 1146 4602

78 IMM AGSD
Remote Evaporator Lifting and Mounting Weights
Table 59, Two-compressor Models
NOTE: refer to the dimension drawing on page 77 for location of the lifting tabs extending up from the base
rails and the location of the mounting holes located in the bottom of the base rails.

LIFTING WEIGHTS MOUNTING LOADS CU


AGS-D RUN SHIP
FIN
MODEL L1 L2 L3 L4 L5 L6 M1 M2 M3 M4 M5 M6 M7 M8 WEIGHT WEIGHT
ADD
STD. EFF.
lbs 3653 3883 N/A N/A 1589 1689 1826 1941 1462 1555 N/A N/A 643 684 10814 10814 1577
225DM
kg 1658 1763 N/A N/A 721 767 829 881 664 706 N/A N/A 292 311 4910 4910 716
lbs 2537 2709 2052 2192 981 1048 2225 2376 1793 1915 992 1060 560 598 11518 11518 1840
250DM
kg 1152 1230 932 995 445 476 1010 1079 814 869 450 481 254 271 5229 5229 835
275DM lbs 2429 2559 2106 2219 1419 1495 2213 2331 1868 1968 1196 1260 677 713 12226 12226 2102
300DM kg 1103 1162 956 1007 644 679 1005 1058 848 893 543 572 307 324 5551 5551 954
HIGH EFF.
lbs 2537 2709 2052 2192 981 1048 2225 2376 1793 1915 992 1060 560 598 11518 11518 1840
225DF
kg 1152 1230 932 995 445 476 1010 1079 814 869 450 481 254 271 5229 5229 835
250DF lbs 2429 2559 2106 2219 1419 1495 2213 2331 1868 1968 1196 1260 677 713 12226 12226 2102
260DF kg 1103 1162 956 1007 644 679 1005 1058 848 893 543 572 307 324 5551 5551 954
275DF lbs 2372 2499 2195 2312 1777 1872 2169 2286 1910 2012 1408 1483 857 903 13027 13027 2365
300DF kg 1077 1135 997 1050 807 850 985 1038 867 913 639 673 389 410 5914 5914 1074

Table 60, Three-compressor Models


NOTE: refer to the dimension drawing on page 78 for location of the lifting tabs extending up from the base
rails and the location of the mounting holes located in the bottom of the base rails.

LIFTING WEIGHTS MOUNTING LOADS CU


AGS-D RUN SHIP
FIN
MODEL L1 L2 L3 L4 L5 L6 L7 L8 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 WTS WTS
ADD
STD. EFF
330DM lbs 3695 3366 2774 2527 1750 1594 1095 997 2652 2416 2358 2147 1896 1727 1435 1307 974 887 17798 17798 2628
350DM
360DM kg 1678 1528 1259 1147 795 724 497 453 1204 1097 1071 975 861 784 651 593 442 403 8080 8080 1193
390DM lbs 3570 3252 2817 2566 1980 1804 1383 1260 2542 2315 2320 2114 1975 1799 1629 1484 1284 1170 18632 18632 2891
400DM kg 1621 1476 1279 1165 899 819 628 572 1154 1051 1053 960 897 817 740 674 583 531 8459 8459 1313
lbs 3625 3333 2978 2738 1994 1833 1462 1344 2541 2336 2357 2167 2095 1926 1675 1540 1389 1277 19305 19305 3154
450DM
kg 1646 1513 1352 1243 905 832 664 610 1154 1061 1070 984 951 874 760 699 631 580 8764 8764 1432
HIGH EFF.
lbs 3570 3252 2817 2566 1980 1804 1383 1260 2542 2315 2320 2114 1975 1799 1629 1484 1284 1170 18632 18632 2891
330DF
kg 1621 1476 1279 1165 899 819 628 572 1154 1051 1053 960 897 817 740 674 583 531 8459 8459 1313
350DF lbs 3625 3333 2978 2738 1994 1833 1462 1344 2541 2336 2357 2167 2095 1926 1675 1540 1389 1277 19305 19305 3154
400DF kg 1646 1513 1352 1243 905 832 664 610 1154 1061 1070 984 951 874 760 699 631 580 8764 8764 1432
lbs 3575 3272 3061 2801 2278 2085 1682 1539 2408 2204 2308 2212 2165 1981 1936 1772 1780 1629 20294 20294 3416
450DF
kg 1623 1485 1390 1272 1034 947 764 699 1093 1001 1048 1004 983 899 879 804 808 740 9213 9213 1551

IMM AGSD 79
Isolator Identification
Table 61, Spring Flex Isolators
Max. Load Each Defl.
Housing Spring Color
Lbs. (kg) In. (mm)
1300
CP-4-24 Brown
(590)
1800 1.22
CP-4-25 Red
(816) (30.9)
2400 1.17
CP 4-26 Purple
(1089) (29.7)
3000 1.06
CP-4-27 Orange
(1361) 26.9)
3600 1.02
CP-4-28 Green
(1633) (25.9)

Table 62, Neoprene (R.I.S.) Isolators


Max. Load Each Defl.
Type Spring Color
Lbs. (kg) In. (mm)
1500 0.25
RP-4 Black
(681) (6.4)
2250 0.25
RP-4 Red
(1019) (6.4)
3300 0.25
RP-4 Green
(1497) (6.4)
4000 0.25
RP-4 Gray
(1816) (6.4)

Figure 38, Spring Flex Mountings,CP-4 Figure 39, Neoprene-in-Shear


Mounting, RP-4

80 IMM AGSD
Table 63, AGS-D W/ Remote Evap, Spring Flex Isolators W/ Aluminum Fin Condensers

Unit Spring-Flex Mountings


Size M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
225DM CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-24 CP-4-24
Orange Orange Purple Purple Brown Brown
250DM CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
275DM CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
300DM CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
225DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown

250DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24


Orange Orange Orange Orange Red Red Brown Brown
260DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
275DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-24 CP-4-24
Orange Orange Orange Orange Purple Purple Brown Brown
300DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-24 CP-4-24
Orange Orange Orange Orange Purple Purple Brown Brown
330DM CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-25 CP-4-25
350DM Green Green Green Green Orange Orange Purple Purple Red Red
360DM
390DM CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
400DM Green Green Green Green Orange Orange Orange Orange Purple Purple
450DM CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
Green Green Green Green Orange Orange Orange Orange Purple Purple
330DF CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
Green Green Green Green Orange Orange Orange Orange Purple Purple
350DF CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
400DF Green Green Green Green Orange Orange Orange Orange Purple Purple
450DF CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27
Green Green Green Green Green Green Orange Orange Orange Orange

IMM AGSD 81
Table 64, AGS-D W/ Remote Evap, Spring Flex Isolators W/ Copper Fin Condensers

Unit Spring-Flex Mountings


Size M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
225DM CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-24 CP-4-24
Orange Orange Purple Purple Brown Brown
250DM CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
275DM CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
300DM CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
225DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown

250DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24


Orange Orange Orange Orange Red Red Brown Brown
260DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-25 CP-4-25 CP-4-24 CP-4-24
Orange Orange Orange Orange Red Red Brown Brown
275DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-24 CP-4-24
Orange Orange Orange Orange Purple Purple Brown Brown
300DF CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-24 CP-4-24
Orange Orange Orange Orange Purple Purple Brown Brown
330DM CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-26 CP-4-26 CP-4-25 CP-4-25
350DM
Green Green Green Green Orange Orange Purple Purple Red Red
360DM
390DM CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
400DM Green Green Green Green Orange Orange Orange Orange Purple Purple
450DM CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
Green Green Green Green Orange Orange Orange Orange Purple Purple
330DF CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
Green Green Green Green Orange Orange Orange Orange Purple Purple
350DF CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27 CP-4-26 CP-4-26
400DF Green Green Green Green Orange Orange Orange Orange Purple Purple
450DF CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-28 CP-4-27 CP-4-27 CP-4-27 CP-4-27
Green Green Green Green Green Green Orange Orange Orange Orange

82 IMM AGSD
Table 65, AGS-D w/ Remote Evap, Neoprene Isolators W/ Alum Fin Condensers
Unit Rubber-In-Shear Mounts
Size M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
225DM RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Red Red Black Black
250DM RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Black Black Black Black
275DM RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
300DM RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
225DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Black Black Black Black
250DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
260DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
275DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
300DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
330,350 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 RP-4 RP-4
360DM Green Green Green Green Red Red Red Red Black Black
390DM R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
400DM Green Green Green Green Red Red Red Red Red Red
450DM R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
Green Green Green Green Green Green Red Red Red Red
330DF R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
Green Green Green Green Green Green Red Red Red Red
350DF R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
400DF Green Green Green Green Green Green Red Red Red Red
450DF R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
Green Green Green Green Green Green Green Green Red Red

IMM AGSD 83
Table 66, AGS-D w/ Remote Evap, Neoprene Mounts w/ Copper Fin Coils

Unit Rubber-In-Shear Mounts


Size M1 M2 M3 M4 M5 M6 M7 M8 M9 M10
225DM RP-4 RP-4 RP-4 RP-4 n/a n/a RP-4 RP-4
Green Green Red Red n/a n/a Black Black
250DM RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Black Black Black Black
275DM RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
300DM RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
225DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Black Black Black Black
250DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
260DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
275DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
300DF RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red Black Black
330DM R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 RP-4 RP-4
350DM Green Green Green Green Red Red Red Red Black Black
360DM
390DM R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
400DM Green Green Green Green Green Green Red Red Red Red
450DM R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
Green Green Green Green Green Green Red Red Red Red
330DF R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
Green Green Green Green Green Green Red Red Red Red
350DF R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
400DF Green Green Green Green Green Green Red Red Red Red
450DF R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4 R-4
Green Green Green Green Green Green Green Green Red Red
Evaporators
Figure 40, Remote Evaporator Dimensions

NOTES:
1. Liquid line
connection is 1 5/8-inch IDS flange.
2. All dimensions are in inches (mm).
3. Insulated with ¾-inch Armaflex or equal UL approved insulation.
4. Tube side (refrigerant) maximum working pressure: 350 psig @ 175°F.
5. Shell side (water) maximum working pressure: 152 psig.

COND. DIMENSIONAL DATA, inches (mm)


AGS MODEL MODEL
'H' 'P' 'N'
NUMBER 'A' 'B' 'C' 'D' 'E' 'F' 'G' 'J' 'K' 'L' 'M'
I.D.S. DIA DIA.
20.3 11.0 16.0 13.2 90.2 17.8 121.2 4 1/8 9.2 103.9 114.9 108.3 6 18.5
225DM, 250DM 330904451
(515) (280) (406) (334) (2292) (452) (3078) (105) (234) (2640) (2918) (2750) (154) (470)
20.3 11.0 16.0 13.2 90.2 17.8 121.2 4 1/8 9.2 103.9 114.9 108.3 6 18.5
225DF, 250DF 330904452
(515) (280) (406) (334) (2292) (452) (3078) (105) (234) (2640) (2918) (2750) (154) (470)
260DF, 275DM 24.9 13.6 20.0 13.2 90.2 18.1 121.9 4 1/8 10.6 103.3 115.6 108.3 8 18.5
330904453
275DF (631) (345) (508) (334) (2292) (459) (3095) (105) (270) (2624) (2935) (2750) (203) (470)
24.9 13.6 20.0 13.5 90.2 18.1 121.9 4 1/8 10.6 103.3 115.6 108.3 8 18.5
300DM, 300DF 330904454
(631) (345) (508) (344) (2292) (459) (3095) (105) (270) (2624) (2935) (2750) (203) (470)
330DM, 330DF 22.8 11.5 20.0 14.6 88.2 17.1 119.9 3 1/8 10.6 103.3 115.6 108.3 8 18.5
330904455
350DM (578) (292) (508) (370) (2240) (435) (3045) (80) (270) (2624) (2935) (2750) (203) (470)
350DF, 360DM, 22.8 11.5 20.0 14.6 88.2 17.1 119.9 3 1/8 10.6 103.3 115.6 108.3 8 18.5
330904456
390DM (578) (292) (508) (370) (2240) (435) (3045) (80) (270) (2624) (2935) (2750) (203) (470)
400DM, 400DF 22.8 11.5 20.0 14.6 121.7 17.1 153.4 3 1/8 10.6 136.8 149.0 141.7 8 18.5
330904457
450DM, 450DF (578) (292) (508) (370) (3090) (435) (3895) (80) (270) (3474) (3785) (3600) (203) (470)

IMM AGSD 85
System Maintenance

General
On initial start-up and periodically during operation, it will be necessary to perform certain routine
service checks. Among these are checking the liquid line sight glasses, and the compressor oil level
sight glass. In addition, check the MicroTech II controller temperature and pressure readings with
gauges and thermometers to see that the unit has normal condensing and suction pressure and
superheat and subcooling readings. A recommended maintenance schedule is located at the end of this
section.
A Periodic Maintenance Log is located at the end of this manual. It is suggested that the log be copied
and a report be completed on a regular basis. The log will serve as a useful tool for a service
technician in the event service is required.
Initial start-up date, vibration readings, compressor megger readings and oil analysis information
should be kept for reference base-line data.

Compressor Maintenance
The semi-hermetic compressor requires no yearly scheduled maintenance. Compressor vibration is an
indicator of a possible problem requiring maintenance. It is recommended that the compressor be
checked with a vibration analyzer at, or shortly after, start-up and again on an annual basis. The load
should be maintained as closely as possible to the load of the original test. The initial vibration
analyzer test provides a benchmark of the compressor, and when performed routinely, can give a
warning of impending problems.

Lubrication
No routine lubrication is required on AGS units. The fan motor bearings are permanently lubricated.
No further lubrication is required. Excessive fan motor bearing noise is an indication of a potential
bearing failure.
Compressor oil must be ICI RL68HB, McQuay Part Number 735030446 in a 1-gallon container. This
is synthetic polyolester oil with anti-wear additives and is highly hygroscopic. Care must be taken to
minimize exposure of the oil to air when charging oil into the system.
On early units, an oil filter is located in the oil return line from the oil separator to the compressor.

Figure 41, Compressor Oil Filter


The oil filter resides in the compressor housing as shown in
Figure 41. Units without a suction service shutoff valve require
pumping down the circuit in order to change the filter.
Replace this filter if the pressure drop exceeds 7 psi (48 kPa) as
measured at Schrader fittings up and down stream from the filter.

Oil Filter Housing

86 IMM AGSD
Electrical Terminals
DANGER
Electric equipment can cause electric shock with a risk of severe personal injury or death. Turn
off, lock out and tag all power before continuing with following service. Panels can have more
than one power source.

CAUTION
Periodically check electrical terminals for tightness and tighten as required. Always use a back-
up wrench when tightening electrical terminals.
Condensers
The condensers are air-cooled and constructed of 3/8" (9.5mm) OD internally finned copper tubes
bonded in a staggered pattern into louvered aluminum fins. No maintenance is ordinarily required
except the routine removal of dirt and debris from the outside surface of the fins. McQuay
recommends the use of non-caustic, non-acidic, foaming coil cleaners available at most air
conditioning supply outlets. Flush the coil from the inside out.

WARNING
Use caution when applying coil cleaners. They can contain potentially harmful chemicals. Wear
breathing apparatus and protective clothing. Thoroughly rinse all surfaces to remove any
cleaner residue. Do not damage the fins during cleaning.

If the service technician has reason to believe that the refrigerant circuit contains noncondensables,
recovery of the noncondensables will be required, strictly following Clean Air Act regulations
governing refrigerant discharge to the atmosphere. The service Schrader valves are located on both
vertical coil headers on both sides of the unit at the control box end of the coil. Access panels are
located at the end of the condenser coil directly behind the control panel. Recover the
noncondensables with the unit off, after shutdown of 15 minutes or longer, to allow air to collect at the
top of the coil. Restart and run the unit for a brief period. If necessary, shut the unit off and repeat the
procedure. Follow accepted environmentally sound practices when removing refrigerant from the unit.
Liquid Line Sight Glass
Observe the refrigerant sight glasses (one per circuit) weekly. A clear glass of liquid indicates that
there is adequate refrigerant charge in the system to provide proper feed through the expansion valve.
Bubbling refrigerant in the liquid line sight glass, during stable run conditions, may indicate that there
can be an electronic expansion valve (EXV) problem since the EXV regulates liquid subcooling.
Refrigerant gas flashing in the sight glass could also indicate an excessive pressure drop in the liquid
line, possibly due to a clogged filter-drier or a restriction elsewhere in the liquid line (see page 27 for
maximum allowable pressure drops).
An element inside the sight glass indicates the moisture condition corresponding to a given element
color. If the sight glass does not indicate a dry condition after about 12 hours of operation, the circuit
should be pumped down and the filter-drier changed. An oil acid test is also recommended.
Do not use the sight glass on the EXV body for refrigerant charging. Its purpose is to view the position
of the valve.

IMM AGSD 87
Lead-Lag
A feature on all McQuay AGS air-cooled chillers is a system for alternating the sequence in which the
compressors start to balance the number of starts and run hours. Lead-Lag of the refrigerant circuits is
accomplished automatically through the MicroTech II controller. When in the auto mode, the circuit
with the fewest number of starts will be started first. If all circuits are operating and a stage down in
the number of operating compressors is required, the circuit with the most operating hours will cycle
off first. The operator can override the MicroTech II controller, and manually select the lead circuit as
circuit #1, #2 or #3.
Preventative Maintenance Schedule
PREVENTATIVE MAINTENANCE SCHEDULE
MONTHLY ANNUAL
OPERATION WEEKLY
(Note 1) (Note 2)
General
Complete unit log and review (Note 3) X
Visually inspect unit for loose or damaged components and visible
X
leaks
Inspect thermal insulation for integrity X
Clean and paint as required X

Electrical
Sequence test controls X
Check contactors for pitting, replace as required X
Check terminals for tightness, tighten as necessary X
Clean control panel interior X
Clean control box fan filter (Note 7) X
Visually inspect components for signs of overheating X
Verify compressor and oil heater operation X
Megger compressor motor X

Refrigeration/Lubricant
Leak test X
Check liquid line sight glasses for clear flow X
Check compressor oil sight glass for correct level (lubricant charge) X
Check filter-drier pressure drop (see manual for spec) X
Check lubricant filter pressure drop (Note 6) X
Perform compressor vibration test X
Perform oil analysis test on compressor oil X

Condenser (air-cooled)
Clean condenser coils (Note 4) X
Check fan blades for tightness on shaft (Note 5) X
Check fans for loose rivets and cracks, check motor brackets X
Check coil fins for damage and straighten as necessary X
Notes:
1. Monthly operations include all weekly operations.
2. Annual (or spring start-up) operations include all weekly and monthly operations.
3. Log readings can be taken daily for a higher level of unit observation.
4. Coil cleaning can be required more frequently in areas with a high level of airborne particles.
5. Be sure fan motors are electrically locked out.
6. Replace the filter if pressure drop exceeds 20 psi.
7. The weekly fan filter cleaning schedule can be modified to meet job conditions. It is important
that the filter allows full air flow.

88 IMM AGSD
Warranty Statement
Limited Warranty
McQuay’s written Limited Product Warranty, along with any extended warranty expressly
acknowledged in writing by McQuay are the only warranties provided by McQuay. Consult your local
McQuay Representative for warranty details. Refer to Form 933-430285Y-00A shipped with the unit.
To find your local McQuay Representative, go to www.mcquay.com.

Service

CAUTION
1. Service on this equipment must be performed by trained, experienced refrigeration
personnel familiar with equipment operation, maintenance, correct servicing procedures, and the
safety hazards inherent in this work. Causes for repeated tripping of equipment protection
controls must be investigated and corrected.
2. Anyone servicing this equipment must comply with EPA requirements regarding refrigerant
reclamation and venting.

DANGER
Disconnect all power before doing any service inside the unit to avoid bodily injury or death.
MULTIPLE POWER SOURCES CAN FEED THE UNIT.

Liquid Line Filter-Driers


Replace the filter-drier cores any time excessive pressure drop is read across the filter-drier and/or
when bubbles occur in the sight glass with normal subcooling. There is one, two-core drier in each
circuit. The maximum recommended pressure drop across the filter-drier is 7 psi at full load.
The filter-driers should also be changed if the moisture indicating liquid line sight glass indicates
excess moisture in the system, or an oil test indicates the presence of acid.
High acid cores may be used temporarily, but replaced after two day use.
The following is the procedure for changing the filter-drier core:
The standard unit pumpdown is set to stop pumpdown when 20 psig (138 kPa) suction pressure is
reached. To fully pump down a circuit beyond 20 psig (138 kPa) for service purposes, a "Full
Pumpdown" service mode can be activated using the keypad.
With Full Pumpdown = Yes, then the next time the circuit is pumped down, the pumpdown will
continue until the evaporator pressure reaches 5 psig (34 kPa) or 120 seconds (the pumpdown limit)
have elapsed, whichever occurs first. Upon completing the pumpdown, the "FullPumpDwn" setpoint
is automatically changed back to "No".

IMM AGSD 89
The procedure to perform a full service pumpdown for changing the filter-drier core is as follows:
1. Under the "Set Comp Spts", change the "Service Pumpdown" setpoint from "No" to "Yes".
2. Move the circuit switch to the OFF position. The compressor will unload to minimum slide
position and the unit will pump down.
3. Upon completing the full pumpdown per step 3, the "FullPumpDwn" setpoint is automatically
changed back to "No" which reverts back to standard 20 psig (138 kPa) pumpdown stop pressure.
4. If the pumpdown does not go to 5 psig (34 kPa) on the first attempt, one more attempt can be made
by repeating the above steps. Do not repeat "FullPumpDwn" more than once to avoid excessive screw
temperature rise under this abnormal condition.
5. The circuit is now in the deepest pumpdown that can be achieved by the use of the compressor.
Close the two liquid line shutoff valves upstream of the filter-drier, on the circuit to be serviced plus
the optional suction shutoff valve. Manually open the EXV and energize the liquid line solenoid valve
via the Test Mode. Then remove the remaining refrigerant from the evaporator by the use of a
refrigerant recovery unit.
6. Loosen the cover bolts, remove the cap and replace the filters.
7. Evacuate and open valves.
Evacuate the lines through the liquid line manual shutoff valve(s) to remove noncondensables that
could have entered during filter replacement. Perform a leak check before returning the unit to
operation.
Compressor Slide Valves
The slide valves used for unloading the compressor are hydraulically actuated by pulses from the
load/unload solenoid as controlled by the CP1 (and CP2, if present) controllers. See OM AGS for
details on the operation.
Evaporator Expansion Valve (EXV)
The expansion valve meters the amount of refrigerant entering the evaporator to match the cooling
load. It does this by maintaining constant suction superheat. (Superheat is the difference between the
actual refrigerant temperature of the gas as it leaves the evaporator and the saturation temperature
corresponding to the evaporating pressure.) The EXV logic controls the superheat between 4°F at 0%
slide position and 8°F at 100% slide position.
The position of the valve can be viewed at any time by using the MicroTech II controller keypad
through the View Refrigerant menus. There are 6386 steps between closed and full open. There is also
a sight glass on the EXV to observe valve movement and to check if it is open or closed visually.
Economizer Expansion Valve
The circuit must be operating at 100% load (energized when run & slide target > 95%, drops out <
60%).
Check that the bulb is mounted on the side of the economizer port/suction line from the brazed plate
economizer heat exchanger and that it is tightly mounted and insulated.
Check the economizer suction pressure and line temperature on vapor line leaving the brazed plate heat
exchanger to calculate the superheat.
Adjust TXV to obtain 8 to 12 degrees superheat. Periodically check and adjust, if necessary, the
superheat of the economizer leaving gas.

90 IMM AGSD
Figure 42, Economizer Piping

SV
To Filter From
Evaporator Drier Condenser
EXV
SV
Legend
TXV EXV
SV Solinoid Electronic
To Valve Expansion
Compressor Valve
Interstage
Economizer
Ball TXV
Valve Thermal
Expansion
Valve

Evaporator
The evaporator is a two-or three-circuit, direct expansion, shell-and-tube type with water flowing
through the shell and refrigerant flowing in one pass through the tubes. The tubes are internally
enhanced to provide extended heat transfer surface. Normally, no service work is required on the
evaporator other than cleaning the water side in the event of improper water treatment or
contamination.
Charging Refrigerant
Note:
It is useful to record the normal values of refrigerant pressures, subcooling, superheat, and evaporator
and condenser approach temperatures during startup by the McQuay service technician. This makes it
easier to spot errant unit behavior.
Indications of a low refrigerant R-134a charge:
• Condenser subcooling approaching 5 degrees F. or less at the liquid line solenoid valve.
• Suction superheat higher than 10 to 12 degrees F.
• Bubbles in the liquid line sightglass.
Indications of a high refrigerant R-134a charge:
• Condenser pressure is abnormally high.
• Subcooling is abnormally high. Take note of the subcooling on the unit at startup and use this
value as a benchmark.
• EXV is at minimum position and discharge superheat is low (below 22 degrees F). The circuit
controller View Refrigerant Screen #7 displays the valve position and the valve range. The minimum
position occurs when the valve position value remains at the lower limit of the range displayed.
AGS air-cooled screw compressor chillers are shipped factory-charged with a full operating charge of
refrigerant; but there can be times when a unit must be recharged at the job site. Follow these
recommendations when field charging. Refer to the unit operating charge found in the Physical Data
Tables beginning on page 28. An initial charge of 80% to 90% of the nameplate is assumed. Unit
charge adjustment should be done at 100% load, at normal cooling outdoor temperature (preferably
higher than 75°F (24°C), and with all fans on. Unit must be allowed to run 15 minutes or longer so
that the condenser fan staging and load is stabilized at normal operating discharge pressure. For best
results, charge with condenser pressure at design conditions.
Each circuit of the evaporator has a sight glass located in the liquid line. If the unit can be run at close
to ARI conditions (95°F ambient temperature and 44°F chilled water), there should be no bubbles in
the sight glass, but this does not necessarily mean that the unit is correctly charged. Charge until the
superheat and subcooling temperatures are within range. The discharge superheat should be above 22
degrees F.
Procedure to charge an undercharged AGS unit:
1. If a unit is low on refrigerant, first determine the cause before attempting to recharge the unit.
Locate and repair any refrigerant leak. Evidence of oil is a good indicator of leakage. However, oil
may not be visible at all leaks. Liquid leak detector fluids work well to show bubbles at medium size

IMM AGSD 91
leaks, but electronic leak detectors can be needed to locate small leaks. Do not use oil/refrigerant
detection additives.
2. Add the charge to the system at the suction-line charging valve as vapor or small amounts of liquid
while monitoring suction (SSH) and discharge (DSH) superheat. The SSH should be greater than 4-
degrees F. and the DSH greater than 20-degrees F.
3. Add sufficient charge to clear the conditions listed above under “Indications of a low refrigerant R-
134a charge”.
4. Overcharging of refrigerant will raise the condenser pressure and increase the condenser
subcooling.

Standard Controls
NOTE: A complete explanation of the MicroTech II controller and unit operation is contained in
the Operation Manual OM AGS.
Thermistor sensors
Evaporator leaving water temperature - This sensor is located on the evaporator water outlet
connection and is used for capacity control of the chiller and low water temperature freeze protection.
Evaporator entering water temperature - This sensor is located on the evaporator water inlet
connection and is used for monitoring purposes and return water temperature reset control.
Evaporator pressure transducer circuit #1, 2, 3 - This sensor is located on the suction side of the
compressor (evaporator outlet) and is used to determine saturated suction refrigerant pressure and
temperature. It also provides low pressure freeze protection.
Condenser pressure transducer circuit #1, 2, 3 - the sensor is located in the discharge line and is
used to read discharge pressure and saturated refrigerant temperature (calculated). The transducer will
signal the controller to hold load or unload the compressor if a rise in head pressure occurs which is
outside the MicroTech II controller setpoint limits. The signal is also used in the calculation of
discharge superheat.
Oil pressure transducers – located on the compressor and used to determine oil pressure and
differential pressure.
Outside air - This sensor is located on the back of the control box. It measures the outside air
temperature, is used to determine if low ambient start logic is necessary, and can be the reference for
low ambient temperature lockout.
Suction temperature circuit #1, 2, 3 - The sensor is located in a well on the suction line. The purpose
of the sensor is to measure refrigerant temperature and superheat.
Discharge line temperature circuit #1, 2, 3 - The sensor is located in a well on the discharge line. It
measures the refrigerant temperature and is used to calculate discharge superheat.
Demand limit - This requires a field connection of a 4-20 milliamp DC signal from an external source
such as a building automation system. It will determine the maximum number of cooling stages that
can be energized.
Evaporator water temperature reset - This requires a 4-20 milliamp DC signal from a building
automation system or temperature transmitter to reset the leaving chilled water setpoint.
Condenser pressure control
MicroTech II control is equipped with pressure transducers on each refrigerant circuit. The main
purpose of the pressure transducer is to maintain proper head pressure control. It also sends a signal to
the MicroTech II control to inhibit additional circuit loading on a rise to the setpoint and to unload the
compressor in the event of an excessive rise in discharge pressure. The high pressure switch trip setting
is 310 psig (2037 kPa). The high pressure alarm is in response to the signal sent by the pressure
transducer.

92 IMM AGSD
Mechanical high pressure equipment protection control
The high pressure equipment protection control is a single pole, pressure-activated switch that opens
on a pressure rise. When the switch opens, the control circuit is de-energized, dropping power to the
compressor and fan motor contactors. The switch is factory set (non-adjustable) to open at 310 psig
(2137 kPa) ±7 psig and reclose at 200 psig (1379 kPa) ±7 psig. Although the high pressure switch will
close again at 200 psig (1379 kPa), the control circuit will remain locked out and it must be reset
through the MicroTech II control.
The control is mounted on the body of the compressor near the discharge port.
Compressor motor protection
The compressors are supplied with two types of motor protection. Solid state electronic overloads
mounted in the control box sense motor current to within 2% of the operating amps. The MUST TRIP
amps are equal to 140% of unit nameplate compressor RLA. The MUST HOLD amps are equal to
125% of unit nameplate RLA. A trip of these overloads can result from the unit operating outside of
normal conditions. Repeat overload trips under normal operation can indicate wiring or compressor
motor problems. On wye-delta starters, the overloads are manual reset and must be reset at the
overload, as well as through the MicroTech II controller.
The compressors also have a solid state Guardister™ circuit that provides motor over temperature
protection. The Guardister circuit has automatic reset and gives a Starter Fault (F75) that is cleared
through the starter display and must also be reset through the MicroTech II control.
Head pressure control (standard)
The MicroTech II controller automatically cycles the condenser fans in response to condenser pressure.
Each fan in a circuit is cycled independently up to 8 steps per circuit, depending on the unit size. This
maintains head pressure and allows the unit to run at ambient air temperatures down to 35°F (1.7°C).
The settings are adjustable through the controller.
Unit operation with the standard control is satisfactory down to outdoor temperatures of 35°F (-1.7°C).
Below this temperature, the VFD option is required to regulate the speed of the first fan on the circuit
to adequately control the discharge pressure. The VFD option allows unit operation to 0°F (-17.8°C)
outdoor temperature, assuming no greater than 5-mph wind.
Head pressure control (optional low ambient)
The optional low ambient control includes a variable frequency drive (VFD) on the first fan on each
circuit. The remaining fans cycle based on discharge pressure. This control must be used for operation
in ambient temperatures below 35°F (1.7°C) down to 0°F (-17.8°C).

NOTE: VFD and standard fan cycling will provide proper operating refrigerant discharge pressures at
the ambient temperatures listed for them, provided the coil is not affected by the existence of wind.
Louvers must be utilized for low ambient operation if the unit is subjected to winds greater than 5 mph.

Compressor short cycling protection


The MicroTech II controller contains logic to prevent rapid compressor restarting. Excessive
compressor starts can be hard on starting components and create excessive motor winding
temperatures. The anti-cycle timers are set for a five-minute stop-to-start cycle and a 20-minute start-
to-start cycle. Both are adjustable through the MicroTech II control.

IMM AGSD 93
Controls, Settings and Functions
Table 67, Controls
DESCRIPTION FUNCTION SYMBOL SETTING RESET LOCATION
Oit Separator To provide heat to drive off liquid On, when On the
R1 N/A
Heaters refrigerant when compressor is off. compressor is off. Compressor
Compressor On the
Loads compressor Y12 N/A N/A
Solenoid - Load Compressor
Compressor On the
Unloads the compressor Y13 N/A N/A
Solenoid - Unload Compressor
o o
Evaporator Heaters Help prevent evaporator freeze-up R5 38 F (3.3 C) N/A Evap. Barrel
Electronic To provide power and step control to the
Expansion EXV stepper motors commanded by the EXVB-1 N/A N/A Control Panel
Valve Board MT II.
Electronic
To provide efficient unit refrigerant flow In Main Liquid
Expansion EV In Controller Code N/A
and control subcooling. Line
Valve
Solid State Starter To provide motor temperature protection None,
o o TC1 Auto Power Panel
Thermistor Card at about 220 F (104 C). Inherent in design
Mechanical High
For UL, ETL, etc., safety code to prevent F13 Refer to
High Pressure Auto Control Panel
high pressure above the relief valve. OM AGS
Switch
To control unit functions. Refer to OM UNIT Refer to
CP1 Controller N/A Control Panel
AGS. CONTROLLER OM AGS
To control individual circuit 3 functions. . CIRCUIT 3 Refer to
CP2 Controller N/A Control Panel
Refer to OM AGS. CONTROLLER OM AGS
Fan VFD (Optional) Controls discharge pressure FAN VFD In controller code N/A Power Panel
Control Panel
Maintain controller operation R70 R71 On at 40°F N/A Control Panel
Heater
To protect from high voltage spikes and
Line Reactor (Fan) LR1 N/A N/A Power Panel
surges.

94 IMM AGSD
Troubleshooting Chart
Table 68, Troubleshooting
PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS
1. Main power switch open. 1. Close switch.
2. Unit system switch open. 2. Check unit status on MicroTech II display. Close switch.
3. Circuit switch in pumpdown position. 3. Check circuit status on MicroTech II display. Close switch. Check
pump operation for flow.
4. Chilled water flow switch not closed. 4. Check unit status on MicroTech display. Close switch.
5. Circuit breakers open. 5. Close circuit breakers.
6. Fuse blown or circuit breakers tripped. 6. Check electrical circuits and motor windings for shorts or grounds.
Investigate for possible overloading. Check for loose or corroded
connections. Reset breakers or replace fuses after fault is corrected.
Compressor will 7. Overloads are manual reset. Reset overload at button on overload.
not run. 7. Compressor overload tripped.
Clear alarm on MicroTech II display.
8. Defective compressor contactor or contactor coil. 8. Check wiring. Repair or replace contactor.
9. System shut down by protection devices. 9. Determine type and cause of shutdown and correct problem before
attempting to restart.
10. No cooling required. 10. Check control settings. Wait until unit calls for cooling.
11. Motor electrical trouble. 11. See 6,7,8 above.
12. Loose wiring. 12. Check circuits for voltage at required points. Tighten all power wiring
terminals.
13. Cycle timer active 13. Check timer operation
1. Compressor Internal problem. 1. Contact McQuayService.
Compressor Noisy 2. Oil injection not adequate. 2. Check that oil sight glass has oil visible during steady operation
or Vibrating Check pressure drop across oil filter and oil separator sight glasses
3. Liquid slugging 3. Check suction and discharge superheat

Compressor 1. Low voltage during high load condition. 1. Check supply voltage for excessive voltage drop.
Overload K2 2. Loose power wiring. 2. Check and tighten all connections.
Tripped or Circuit 3. Power line fault causing unbalanced voltage. 3. Check supply voltage.
Breaker Trip or 4. Defective or grounded wiring in the motor. 4. Check motor and replace if defective.
Fuses Blown 5. High discharge pressure. 5. See corrective steps for high discharge pressure.
Compressor Will 1. Defective capacity control solenoids. 1. Check solenoids for proper operation. See capacity control section.
Not Load or Unload 2. Unloader mechanism defective. 2. Contact McQuayService .
1. Noncondensables in the system. 1. Remove noncondensables from the condenser coil after shutdown
per EPA regulations.
2. Fans not running. 2. Check fan fuses and electrical circuits.
3. Fan control out of adjustment. 3. Check that fan setup in the controller matches unit fan number.
High Discharge Check MicroTech II condenser pressure sensor for proper operation.
Pressure 4. Check discharge superheat and condenser subcooling. Remove the
4. System overcharged with refrigerant.
excess charge.
5. Dirty condenser coil. 5. Clean the condenser coil.
6. Air recirculation from fan outlet into unit coils. 6. Remove the cause of recirculation.
7. Air restriction into unit. 7. Remove obstructions near unit.
1. Wind effect or a low ambient temperature. 1. Protect unit against excessive wind into vertical coils.
2. Condenser fan control not correct. 2. Check that fan setup in the MicroTech II controller matches unit fan
Low Discharge number. Check VFD fan on units with VFD option.
Pressure 3. Low suction pressure. 3. See corrective steps for low suction pressure.
4. Compressor operating unloaded. 4. See corrective steps for failure to load.
5. Compressor problem, not pumping properly 5. Repair or replace compressor
1. Inadequate refrigerant charge quantity. 1. Check liquid line sight glass. Check unit for leaks. Repair and
recharge to clear sight glass at full load, all fans on, 75°F min OAT..
2. Clogged liquid line filter-drier. 2. Check pressure drop across the filter-drier. Replace filter-driers.
3. Expansion valve malfunctioning. 3. Check expansion valve superheat and valve opening position.
Low Suction Replace valve only if certain valve is not working.
Pressure 4. Insufficient water flow to evaporator. 4. Check water pressure drop across the evaporator and adjust gpm.
5. Water temperature leaving evaporator is too low. 5. Adjust water temperature to higher value.
6. Evaporator tubes fouled. 6. Inspect by removing water piping. Clean chemically.
7. Suction valve (partially) closed. 7. Open valve.
8. Glycol in chilled water system 8. Check glycol concentration
1. Insufficient oil. 1. Check oil line and separator sight glasses.
Low Oil Level Trip 2. Low discharge pressure. 2. Faulty EXV.
3. Low discharge superheat 3. Check and correct cause of low DSH
1. Excessive load - high water temperature. 1. Reduce load or add additional equipment.
2. Compressor unloaders not loading compressor. 2. See corrective steps below for failure of compressor to load.
High Suction 3. Superheat is too low. 3. Check superheat on MicroTech II display. Check suction line sensor
Pressure installation and sensor.
4. System overcharged 4. Check charge, an overcharge raises suction pressure
5. Compressor bypassing gas 5. Check evaporator, suction and discharge pressures

IMM AGSD 95
Periodic Maintenance Log
Date of inspection: Address:
Facility/job name: City/State:
Unit model number: Physical location of unit:
Unit serial number: Service technical (name):
Software identification:
Operating hours: Compressor #1 Compressor #2 Compressor #3
Number of starts Compressor #1 Compressor #2 Compressor #3
Follow up service required: Yes No

General Actions to be Taken


Upper part of report completed: Yes No Fill in above
Compressor operation: Yes No Explain all “No” checks
1. Mechanical operation acceptable (noise, vibration, etc.)?
2. Look at cycling and cooling, is unit controlling at set points?
3. No refrigerant leaks (full liquid sight glass)?
4. Liquid line moisture indicator shows dry system?
5. Proper condensing fan operation?
6. Condenser coil clean?
7. No corrosion or paint problems?
Compressor electrical operation:
8. Satisfactory electrical operation?
9. MicroTech II hardware operation satisfactory?
10. MicroTech II software operation satisfactory?

Data from MicroTech II Controller:


11. Unit status %
12. Circuit status 1 % Capacity Circuit status 2 % Capacity Circuit status 3 % Capacity
13. Water temperature – Evaporator: Entering/Leaving /
Circuit #1 Circuit #2 Circuit #3
14. No. of fan states active:
15. Evaporator pressure:
16. Condenser pressure:
17. EXV position – Steps open or percent open:
18. Suction Superheat:
19. Discharge Superheat
20. Subcooling:
21. Liquid line temperature:
22. Chiller % rated load amps – Unit:
23. Outside air temperature:
24. Leaving evaporator setpoint temperature:
25. Reset option programmed? Yes No Ice storage unit? Yes No
26. Is VFD included? Yes No VFD operation OK? Yes No
27. Current alarm: ___ ___ ___ Circuit #1 ______ Circuit #2 ______Circuit #3 ______
28. Previous alarm – Show all: Alarm Type Date
Circuit #1

Circuit #2

Circuit #3

Data at Job Site:


29. Volts: L1/L2___L2/L3___L3/L1_____
30. Amps: Comp #1 Ph 1____ PH 2____ PH 3____
31. Amps: Comp #2 PH 1____ PH 2____ PH 3____
32. Amps: Comp #3 PH 1____ PH 2____ PH 3____
33. Vibration – Read every six months using IRD (or equal) unfiltered at flat on top of motor end: ______ In/Sec Comp #1
______ In/Sec Comp #2
______ In/Sec Comp #3

96 IMM AGSD
Warranty and Terms of Sale
All McQuay equipment is sold pursuant to its Standard Terms and Conditions of Sale including the
Limited Product Warranty.

This document contains the most current product information as of this printing. For the most
up-to-date product information, please go to www.mcquay.com

(800) 432-1342 • www.mcquay.com IMM AGSD (07/07)

You might also like