Professional Documents
Culture Documents
7 Upgrades to
Reduce Building
Electrical Demand
By Kirby P. Nelson, P.E., Life Member ASHRAE demand reduction and are not presented
A
as a typical 1970s building system.
pproximately 37,000 CFC chillers still operated in North The evaluations are based on finding
the steady-state point of the simple one
America at the end of 2004.1 The article makes a compelling chiller system given by Figure 1 and
succeeding figures. Figure 1 defines
argument for replacing chillers of the 1970s and 1980s with today’s the base system and the next five figures
present component changes made to
more efficient chillers, improving the efficiency of auxiliaries (pumps the base system of Figure 1. The evalu-
ations rely on tower4 and chiller5 manu-
and fans) through variable speed pumping and more efficient fan facturer selection data as a requisite
input to the analysis. The steady state
systems, and installing more efficient lighting systems. This article
point of each system is found by simple
will add to the argument by assuming an inefficient central chilled desktop calculations and/or by using a
spreadsheet. The base system, Figure
water system (CCWS)2,3 and show the effect of upgrading CCWS 1, assumes a pre-1980 CFC chiller of
0.785 kW/ton (COP = 4.48), consistent
components and installing more efficient building lighting. with Table 2 of Todesco1 that shows
pre-1980 chiller performance of 0.72
A base building assumption has been demand of the assumed 350,000 ft2 (32
used as a starting point. Seven potential 515 m2) building. The assumed building About the Author
upgrades are evaluated resulting in more and CCWS components are selected to Kirby P. Nelson, P.E., is an energy management
than a 50% reduction in the electrical illustrate maximum potential electrical engineer and consultant.