You are on page 1of 16

EFFECTIVE

LOW DEW POINT


EFFICIENT
CONVENTIONAL COOLING – ACTIVE DESICCANT
DEHUMIDIFICATION SYSTEM

INDOOR AIR QUALITY


Category
HVAC systems have a
major impact on:
• Infection control
• Hazard control
Specialized • Internal climate control
solution for the • Building energy consumption
high demands
SEMCO’s solution includes:
of healthcare
• Active desiccant hybrid system
applications • High efficiency systems
• An improvement to the
building’s conventional HVAC
HVAC systems for hospital System operation and energy
and healthcare facilities have consumption
special requirements
because of the susceptibility
of patients to infection.
Heating and ventilation
systems play an important
part in providing a clean, safe
and comfortable environment
for patient recovery.

2
Specific Healthcare Demands

Healthcare facilities need more than just


heating and ventilation. SEMCO can deliver
equipment and complete systems for
control of infection, air movement, and odor,
yet maintain temperature, humidity, air
quality and noise at superior comfortable
levels for patients and staff.

Operating theaters specifically have unique


HVAC design challenges:

VENTILATION AND AIR MOVEMENT


• Minimum of 4 air changes of outdoor air with a
total of 20 air changes (ASHRAE 170-2013 table)

• Regardless of the amount outdoor air used


– total energy recovery should be utilized in
almost every region in the US. (ASHRAE 90.1-
2013 Table 6.5.6.1-2)

OPERATING ROOM HUMIDITY


CONTROL
• Must be able to maintain space humidity less
than 60% RH with a commonly requested
temperature of 65°F. (AIA/ASHRAE Guidelines)

• Both low end temperature and humidity must be


achievable simultaneously

• This corresponds to a space dew point of


approximately 40°F (not achievable with
conventional chilled water system).

3
SEMCO® INTRODUCES THE ASCENDANT™ SERIES

ASCENDANT™ is a conventional cooling – active desiccant ASCENDANT™ easily allows a design consultant
dehumidification system, performance optimized to compliance with ALL ASHRAE/AIA guideline conditions
deliver and control low dew point air while minimizing while using far less energy than conventional approaches
regeneration energy input in compliance with ASHRAE/ that do not achieve a hospital’s required low space dew
AIA guidelines. point requirements.

OFFERING THE GREATEST SUBSTANTIAL ENERGY SAVINGS NO RETURN AIR PATH NEEDED
DEHUMIDIFICATION CAPACITY ASCENDANT™ operates with 25% While total energy recovery is an
ASCENDANT™ provides more than to 50% less energy cost than other important option when return air
three times the dehumidification conventional dehumidification is available, it is not required to
capacity/cfm compared to systems as a result of improved achieve efficient operation.
customized DX cooling systems, cooling efficiency (higher suction
enabling supply of much lower dew
OPTIONAL TRUE 3Å WHEEL
temperatures) and by shifting much
SEMCO True 3Å wheel decreases
points (see below). of the latent load from electrically
outdoor air cooling tons by up to
driven vapor compression over to
TIGHT LOW HUMIDITY AND 60%. True 3Å wheel also limits
lower cost regeneration energy.
TEMPERATURE CONTROL contaminant carry-over to less
Low space dew point conditions ASCENDANT™ IS DESIGNED TO: than 0.045%, and has been used in
200
are easily achieved and tightly • Offer substantial energy and hospital applications for decades.
190
controlled by the customized control first cost savings 85
algorithms, factory installed sensors, • Ensure hospitals are able to 180

and an on-board DDC controller. operate continuously around the 170


clock
REDUCED COOLING TONS 80
160
• Improve hygiene by ensuring that
Fewer tons of mechanical cooling 150
the ASHRAE required final filters
capacity are required to achieve 140
remain dry
a low supply air dew point - up 75
130
to 60% less cooling capacity
120
required compared to custom DX
70
systems. Many hours exist where 110

dehumidification is accommodated 100


RGICAL
with only the active desiccant
65 N O N-S U R O O M
S P ITA L
HO RANGE 90
wheel and no cooling is required. DESIGN PER POUND OF DRY AIR • 7000 GRAINS PER POUND
60 80
LIMIT OF
ASCENDANT™ vs. Conventional
HUMIDITY RATIO (W)-GRAINS OF MOISTURE

N 70
COMM 55O ROOM CONVENTIONAL
RAT IN G
OPE NGE SYSTEM
Cooling Approach SIGN RA
DE50
60

48° Dew Point 50


45
40 ASCENDANT™ 40
CAPABLE MOISTURE
35 SUPPRESSION 30
30
25
20° Dew Point 20 20
15
10 EM SUPPLY
5 HVAC SYST E 10
0 TO ACHIEV
-20 -15 -10 -5 DISCHARGE ROOM
OPERATING
SULT 0
DESIGN RE
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE °F


4
ASCENDANT™ FLOW SCHEMATIC
Active
Dehumidification
126ºF Wheel Regeneration
189 gr Heater
90ºF
190ºF
Regen Out 120 gr

Regeneration Outdoor Air


Regen Fan
4,879 cfm

10,200 cfm 9,070 cfm 8,870 cfm


10,000 cfm
Dehumidified Air
Supply Air
54ºF 88º
Outdoor Air
83.9º
20 gr
72ºF
* 61 gr
25 gr
Bypass Air Supply Fan
62 gr
54ºF
1,130 cfm
Cooling Coil
61 gr
Bypass Damper

* Based on optional Total Energy Recovery wheel to lower required cooling input

HOW IT WORKS:
The ASCENDANT™ system processes outdoor and/or dew point. If tight temperature control is also required, a
return air streams to a moderate leaving coil temperature small sensible only post cooling coil is employed.
condition (when needed), thereby delivering saturated
Regeneration of the desiccant wheel is also achieved
air to the active desiccant wheel which promotes highly
with high energy efficiency. A typical regeneration airflow
efficient moisture adsorption, further depressing the
quantity is only 20% - 40% of the supply airflow volume.
supply air humidity content to very low dew points
Only moderate regeneration temperatures (140˚F to a
By employing moderate chilled water or refrigerant maximum of 200˚F) are required, allowing the use of
temperatures, the efficiency of the cooling system hot water, steam, direct fired gas or waste heat (i.e. by-
employed is high. (This is in sharp contrast to product of a power generation (CHP)).
refrigeration based dehumidification systems which rely
For applications where an exhaust airstream is available
on low suction temperatures and very deep cooling coils
(i.e. hospital operating theaters) preconditioning the
to achieve lower dew points.)
outdoor air with SEMCO total energy recovery is highly
An integral modulating bypass damper allows the cool, recommended since it substantially increases overall
moderately dry air leaving the cooling coil to be mixed with system energy efficiency and substantially reduces
the appropriate quantity of warm, very dry air leaving the precooling input requirements. It also provides valuable
dehumidification wheel to deliver the required supply air winter season preheat and humidification.

5
Operating Theater Design Analysis:
Conventional vs. ASCENDANT™

Example: Fifteen operating rooms designed in accordance with FGI/AIA/ASHRAE guidelines requiring
3,333 cfm each using 20% outdoor air

Case 1: Total Energy preconditioning to Conventional AHU

• Operating theaters conditioned to achieve 65ºF and not more than 60% RH as required for Delivery Rooms by AIA/
ASHRAE guidelines

• Coldest possible chilled water used (40ºF at the chiller), and deepest cooling coil (10 row) to achieve 48ºF air off
of the coil 200

190
• Air reheated to 59ºF to accommodate sensible load in the space
85
180
• Total energy recovery is utilized to precondition the outdoor air portion as per ASHRAE 90.1
170
40

• Preconditioned air (10,000 cfm) is delivered to conventional AHUs supplying enough air to provide 3,333 cfm to
each of the 15 operating rooms to achieve the required 25 air changes/Hr. 160
80
150
35

Conventional Approach: Requires 150 Tons, 600K BTU Reheat 140


75
130
30

Outdoor air
R

entering TE Wheel 120


AI

(95˚F, 120 grains)


Y

70
DR

110
25
OF
D
20 OUN

100
to d ity

65
P

0 ire ac
R
PE

(15 qu ap

90
)
Re ng C

ns

PER POUND OF DRY AIR • 7000 GRAINS PER POUND


TU

Outdoor air
-B

60
Leaving TE Wheel
oli

80
)
(h

Co

(76˚F, 72 grains)
PY
AL

HUMIDITY RATIO (W)-GRAINS OF MOISTURE


15

70
55
TH

Mixed air conditions


EN

entering AHU coil 60


Cooling coil 50 (68˚F, 60 grains)
supply condition
10

(48˚F, 50 grains) OR space conditions 50


45 65°F at 60% RH
40 40
AHU supply
35 condition
(59˚F, 50 grains) 30
30
25 20
20
15
10 REHEAT ENERGY 10
0 5
-5 600,000 BTU/HR
0
0 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE °F


6
Case 2: ASCENDANT™ preconditioning to Conventional AHU

• Operating theaters operated in an attempt to achieve 65ºF and 60% RH as required for Delivery Rooms by AIA/
ASHRAE guidelines (Note: Colder room conditions—often desired for surgeon comfort—and lower space humidity
can be easily achieved with ASCENDANT™)

200
• Traditional chilled water used (45ºF at the chiller), thereby increasing chiller efficiency and sensible only cooling
coil (4 row) in AHUs 190
85
• No reheat required to deliver the 59ºF to the space 180

• Total energy recovery is utilized to precondition the outdoor air portion as per ASHRAE 90.1 combined 170with
40

integrated active desiccant to deliver very dry outdoor air to each AHU. All latent load handled by ASCENDANT™
160
so AHU coils are sensible only 80
150
35

ASCENDANT™ Approach: Requires only 58 Tons, No Reheat 140


75
130
30

Outdoor air
entering TE Wheel
R

120
AI

(95˚F, 120 grains)


Y

70
DR

110
25
OF
D
20 OUN

100
65
P
R
PE

90

PER POUND OF DRY AIR • 7000 GRAINS PER POUND


TU

Outdoor air
-B

Leaving
60 TE Wheel
to d it

80
)

8 ire ac
(h

(76˚F, 72 grains)
(3 qu ap
PY

)
Re ng C
AL

OR space conditions HUMIDITY RATIO (W)-GRAINS OF MOISTURE


15

ns

70
55
TH

65°F at 60% RH
oli
EN

Co

60
50
10

50
45
AHU supply
40 condition 40
(59˚F, 50 grains) Outdoor air leaving
35 ASCENDANT™ (20 tons) 30
30 Mixed air conditions (78˚F, 38 grains)
entering AHU coil
25 (68˚F, 50 grains) 20
20
15
10 10
0 5
-5
NO REHEAT ENERGY NEEDED
0
-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE °F


7
SYSTEM COMPARISON:
Conventional vs. ASCENDANT™

Case 1: Case 2:
Conventional ASCENDANT™ Preconditioning
Outdoor Air Preconditioning
Airflow provided (for ten ORs) 10,000 cfm 10,000 cfm
Pretreatment used Total energy recovery Total recovery, precooling,
active dehumidification
Cooling capacity required (at peak) None required 20 tons(1)
Regeneration capacity required (at peak) None required 352,000 btu/hr
Supply Air to Operating Rooms
Airflow provided (for ten ORs) 50,000 cfm 50,000 cfm
Outdoor air percentage 20% 20%
Cooling capacity required 150 tons(2) 38 tons(1)
Chilled water temperature required 40˚F 45˚F
Reheat energy required 594,000 btu/hr None required
Total System Summary
Cooling capacity required 150 tons(2) 58 tons(1)
Reheat/regeneration energy required 594,000 btu/hr 352,000 btu/hr
(peak, less at part load)
Total fan HP estimate 59 BHP 62 BHP
Dehumidification season cooling electrical cost(3) $32,312 $11,190
($.08/KWH)
Dehumidification season heat ($10 MMBTU) $21,408 $12,900
Total Operating Energy Cost Estimate
$53,720 $24,090
(Dehumidification season)
(1)
Reflects higher chiller efficiency with 45˚F water.
(2)
Reflects lower chiller efficiency with 40˚F water.
(3)
Assumes Philadelphia weather data, 24 hour/day operation, $.08/KWH, $10/MMBTU steam

Results from Example Analyses


Numerous important design advantages were recognized The cooling efficiency is improved with ASCENDANT™
when the outdoor air delivered to the operating theaters since the desired air temperature leaving the coil could
was preconditioned by the ASCENDANT™ technology. be achieved using traditional 45˚F chilled water while
When compared to the conventional approach, the the conventional approach needed chilled water at
ASCENDANT™ system achieved the desired space 40˚F or below. Chillers operated to deliver 40˚F require
humidity conditions using 61% fewer tons of cooling substantially more energy input (KW/ton) then do
capacity (58 vs 150), eliminated approximately 600,000 chillers delivering water at 45˚F. Many hospitals deliver
BTUs of reheat energy and cut the cost of operation these inefficient chilled water conditions to the entire
by 55%. facility simply because the need them for the operating
theaters. ASCENDANT™ solves that problem.
8
Case 3: ASCENDANT™ Exceeds AIA guidelines at the Desired Space Temperatures

Perhaps the greatest benefit offered by the ASCENDANT™ latent loads are often missed during the design process
technology is the additional dehumidification capacity which is problematic since they are significantly greater
provided so that HVAC systems are able to meet the than those associated with the occupants.
required space humidity conditions within the operating
As shown within the Case 3 psychrometric chart
theaters even when space temperatures colder than 65˚F
(below), ASCENDANT™ can easily maintain OR space
are desired. The high lighting intensity and machinery
conditions down to 62˚F and below while achieving the
common in today’s operating theaters combined with
desired 50% relative humidity level. This is possible due
protective clothing typically requires space temperatures 200
to the ASCENDANT™ system’s ability to deliver air with a
at or below 62˚F for surgeons’ comfort during strenuous
dew point as low as 20˚F. Surprisingly, these conditions
190
procedures.
85
can be efficiently maintained without the need for
180
Another key reason for providing additional substantially more cooling or regeneration energy input
dehumidification capacity is to accommodate latent than required by Case 2 and substantially less170than
40

loads infiltrating from higher humidity spaces adjacent required by the conventional approach shown in Case160
1.
to the OR when the automatic doors are opened before 80

and during surgery. Experience has shown that these 150


35

140
75
130
30

Outdoor air
entering TE Wheel
R

120
AI

(95˚F, 120 grains)


Y

70
DR

110
25
OF
D
UN

100
PO

65
R
PE

20

90

PER POUND OF DRY AIR • 7000 GRAINS PER POUND


U
BT

60
15 h) -

Outdoor air 80
(

Leaving TE Wheel
Y
LP

ty

(76˚F, 72 grains) 70 HUMIDITY RATIO (W)-GRAINS OF MOISTURE


HA

to ed ci

55
0 ir a
T

(5 qu ap
EN

Re ng C

60
ns

50 OR space conditions
i
ol

62°F at 45% RH
Co
10

50
45
40 40
35
AHU supply 30
30
condition
25 (55˚F, 35 grains) Outdoor air leaving 20
20 Mixed air conditions
15 entering AHU coil ASCENDANT™ (25 tons)
10 (66˚F, 35 grains) (85˚F, 22 grains) 10
0 5
-5
NO REHEAT ENERGY NEEDED
0
0 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE °F


9
• Pre-treats downstream air handling systems
Dedicated Outside Air System • Optional benefit of total energy recovery for more
with Optional Integrated Total Recovery energy efficient operation
• Provides preheat and humidification during the
heating season

17 16
15 12 10
18
14
13
11
3 7
2
5
6
1

4 4 8

= Optional add-on

• Incorporates post cooling and final high efficiency


filtration to allow for independent control of
Total Conditioning System both temperature and humidity, providing total
conditioning without supplemental air handlers to
laboratories or large operating theaters

14 7 11
15 12
10
13

5 9
6 6
2
7 4
8

1 Outdoor Air Damper 7 Active Desiccant Wheel 13 Recirculation Damper


2 Outdoor Air Filter 8 Supply Air Fan 14 Regen Fan
3 Optional True 3Å Wheel 9 Final Filtration 15 Optional Return Air Opening
4 Wheel Bypass Damper 10 Regen Inlet Damper 16 Return Air Filtration
5 Heating Coil 11 Regen Air Filtration 17 Exhaust Air Fan
6 Pre & Post Cooling Coil 12 Regeneration Source 18 Exhaust Air Damper

10
STANDARDS AND OPTIONS
STANDARD FEATURES OPTIONAL FEATURES
Active Desiccant Wheel • Recirculation damper to allow regeneration heat
• Fluted media composed of porous inorganic source to be used for supply air during winter
operation
fiber impregnated with high quality adsorbent
• Driven using lube-free chain for longevity and • Post-cooling coil if cooler supply air is required
ease of maintenance • Process Heating
Active Desiccant System • MERV 11-14, HEPA, and ULPA high efficiency final
• DX or chilled water pre-cooling coils filters on supply side

• Regeneration heat - hot water, steam, electric, • Return fan for partial outdoor air systems
or gas (indirect and direct) • Total energy recovery wheel when exhaust air is
• Wheel bypass damper lowering wheel available to reduce required cooling input
pressure drop and providing greater control • Custom options and configurations are supported
over supply temperature and humidity to meet your unique requirements
SEMCO Panel System
• Double-wall panel construction (4 inches thick DDC CONTROLS
with 18-gauge outer skin) Advanced integrated DDC controls are utilized to
• Double-wall removable panels provided for optimize the performance of ASCENDANT™ to achieve
large internal components the desired supply air humidity and temperature
• Gasketed double-wall access doors for all conditions while minimizing energy consumption.
compartments
Five standard parameters that are controlled:
Supply and Regeneration Air Fans 1. The fraction of the supply airflow that is processed
• Direct drive plenum supply and SWSI by the active dehumidification wheel and the
regeneration fans integral modulating bypass damper
• Variable frequency drives 2. The temperature of the air leaving
the pre-cooling coil
Filter Sections 3. The regeneration energy used
• 30 percent efficient filters are provided for (temperature)
supply and regeneration air streams 4. The supply airflow delivered

5. The regeneration airflow utilized

ASCENDANT™ UNIT SIZES AND DIMENSIONS


Dedicated Outside Air Total
Unit Unit Make up Air
Airflow CFM Range Unit Width System with True 3Å Conditioner
Size Height Unit Length
Wheel Unit Length Unit Length

005 2,720 - 5,500 62” 102.25” 259” 364.5” 351”

009 3,740 - 8,500 74” 114.25” 259” 380.5” 358.75”

013 6,130 - 10,500 88” 114.25” 263” 402.25” 360.75”

018 7,600 - 15,000 100” 138.25” 274.25” 420” 368.75”

024 9,600 - 20,000 112” 150.25” 297.75” 462.5” 387.5”

11
ASCENDANT™ APPLICATIONS

ASCENDANT™ 5

SEMCO APPLICATION REFERENCES


Odessa Medical Center. . . . Health Care. . . . . . . . . ASCENDANT™ 13. . . . . DOAS . . . . . . . . . . . . . . . Lubbock, TX
Laughlin Memorial. . . . . . . . Health Care. . . . . . . . . ASCENDANT™ 5. . . . . . Total Conditioning. . . . . . Knoxville, TN
Zeledyne. . . . . . . . . . . . . . . Industrial Mfg. . . . . . . . ASCENDANT™ 9. . . . . . DOAS . . . . . . . . . . . . . . . Nashville, TN
Carlex . . . . . . . . . . . . . . . . . Industrial Mfg . . . . . . . ASCENDANT™ 9. . . . . . DOAS . . . . . . . . . . . . . . . Nashville, TN
Red Star Yeast. . . . . . . . . . . Food Processing. . . . . ASCENDANT™-9 . . . . . DOAS . . . . . . . . . . . . . . . Clive, IA
Hilmar Cheese. . . . . . . . . . . Food Processing. . . . . ASCENDANT™ 9 . . . . . Total Conditioning. . . . . . Lubbock, TX

Since ASCENDANT™ can produce substantially drier air the The Carnegie Mellon Intelligent Workplace employs an
dehumidification capacity offered at a given airflow is many ASCENDANT™ to dehumidify ventilation air to solve serious
times greater. As a result it can typically be operated with condensation issues on their passive chilled beams
only one third to one forth the airflow required by more experienced with a prior, more conventional system.
conventional systems.

12
ASCENDANT™ has the capacity
to deliver air dehumidified
over a wide range to handle
fluctuations in latent loads for
a variety of applications. The
on-board DDC controls allow the
user to optimize temperature and
humidity levels. An optional post
cooling coil provides additional ASCENDANT™ delivers extremely dry outdoor air to each
temperature control if required to application to manage the heavy infiltration load in hot/
ensure a steady and consistent humid locations - improving comfort, extending the life of
indoor relative humidity. furnishings and greatly reducing the risk of mold and mildew.

LOW DEW POINT SPACES: temperature delivered to the beams to maintaining the relative humidity
Hospital Operating Theaters avoid condensation. at approximately 50% and avoiding
ASCENDANT™ can process three times swings over time.
To minimize reinfection and maximize
comfort, commonly hospitals require the latent load of a custom refrigeration Humidity spikes can accelerate
operating rooms to be controlled at based DOAS allowing it to prohibit
damaging chemical reactions and
50% relative humidity down to 62°F. beam condensation using the minimum
biological attack.
This equates to a dew point of 42°F in possible outdoor air quantity.
the space. ASCENDANT™ systems with post
DRY AIR STORAGE: cooling can carefully track space
Most hospitals operate with chilled Warehouse, Cave Storage
water systems and these conditions conditions and precisely control
The desire to handle dehumidification them to consistent levels due to the
cannot be achieved using chilled water
loads with the smallest airflow possible high dehumidification capacity and
alone.
(lower the dew point the better) – fewer
advanced DDC controls.
Hospitals operate chillers inefficiently, systems.
at great operating expense, to produce To preserve the products, avoid rust DRYING VENTILATION AIR:
the coldest possible chilled water and prevent condensation, the need for Hotels/Condominiums
while still not achieving the required cooling and heating of these spaces
humidity levels. There is a very high latent load
can be avoided if effective active
associated with ventilation air and
The ASCENDANT™ can deliver the dehumidification is employed.
infiltration in hotels and condominiums
low dew point air necessary to below Relative humidity is a function of both located in humid climates.
the 50% RH at 62°F while allowing moisture and temperature. Unheated
the chiller to operate at its optimum warehouses, cave storage, etc. result ASCENDANT™ can effectively deliver
efficiency level, delivering 45°F water. in high RH conditions and potential outdoor air dehumidified to very low
condensation. dew points allowing the ventilation
CONDENSATE AVOIDANCE: air alone to control space humidity
Chilled Beam Installations Warm, very dry air delivered by
ASCENDANT™ is highly beneficial and regardless of the internal sensible load.
Active or passive chilled beam designs
can substantially reduce the cost of By deep drying the ventilation air,
are most energy efficient when system
operating these facilities.
fans are sized to deliver only outdoor the packaged cooling units can be
ventilation air. TIGHT HUMIDITY CONTROL: downsized, reducing the size of
Archives/Museums/Libraries ductwork, noise produced and energy
Handling the latent load associated
consumption.
with people and infiltration with Archives, museums and libraries exist
the outdoor air volume alone often to preserve documents and artifacts Since the ventilation airflow is provided
requires dew points lower than what is for a long as possible and to avoid any continuously, ASCENDANT™ continues
achievable with conventional systems. “preventable” premature damage. to provide substantial dehumidification
Space humidity needs to be controlled HVAC systems can significantly impact even on cloudy, humid days when the
well below the dew point of the water the life of these objects by consistently call for space cooling is minimal.
13
SEMCO PRODUCTS
TO COMPLEMENT THE ASCENDANT™

ENERGY RECOVERY NEUTON™ CONTROLLED IQHC ACTIVE CHILLED BEAM


TRUE 3Å WHEEL CHILLED BEAM PUMP MODULE • Industry best capacity to energy
• Industry’s highest recovery • Zone level water control for chilled consumption ratio
performance (AHRI Certified) and beams • Utilizes the lowest air and water
Recovery Efficiency Ratios (RER) pressure to enhance the overall
• Proactive condensation control
• Contaminant carry-over to less than energy benefit of chilled beams
• Provides load matching with only
.045% • Universal duct and water
necessary amount of cooling/
• Anti-corrosion, anti-microbial anti- heating that the space requires connections for easy to installation
stick face coatings standard • Superior indoor air quality and
• Variable speed pump maximizes
• Extruded aluminum structural hub, energy savings energy efficiency.
spokes and rim system • Allows the beam coil to be dual
• Available singly, in self-contained temperature, maximizing the
conditioning units, or as retrofits of amount of both cooling and heating
existing wheels. a beam can provide

SEMCO Products Working Together: ASCENDANT, NEUTON, & Chilled Beams

Outdoor Air to Beams


68˚F, 42 grains
FAN COIL UNIT
BEAM LOOP BEAM LOOP BEAM LOOP
(multiple beams) (multiple beams) (multiple beams)

42˚F

62˚F 58˚F 62˚F 58˚F 62˚F 58˚F


50˚F
SEMCO
NEUTON
(one of three)

42˚F

ASCENDANT™ 62˚F
DOAS PRIMARY PUMP

55˚F
42˚F

BOILER CHILLER

* Component not supplied by SEMCO.


14
BETTER AIR
PRODUCTS FROM SEMCO

EP/EPD SERIES PINNACLE® PRIMARY VENTILATION SYSTEM


• Provides ultimate level of performance in the transfer of • Manages 100% of a building’s ventilation, humidity, and
energy temperature, while simultaneously reducing energy loads
• Preconditions air for a conventional air handler or can • Dual wheel dedicated outside air system designed to
perform as an independent, integrated system with a ventilate and deliver air direct to space
variety of heating and cooling options • Ideal primary air system utilized to decouple latent load of
• Indoor or outdoor installation the building with the least amount of air
• Airflow capacities range from 2,000 to 70,000 CFM • Supports ductwork reduction and central plant energy
reduction

FV SERIES eQ SERIES
• High recovery efficiency with low pressure loss • Energy savings through efficient component design and
operation
• Designed for rooftop installation in but can easily be
installed indoors and still provide a very quiet, continuous • High efficiency energy recovery with the right balance of
supply of fresh air pressure and effectiveness (RER)
• Provides a healthy, comfortable indoor atmosphere in a • Robust frame and tight sealing configurable for both
cost efficient package indoor and outdoor installation
• Airflow capacities range from 600 to 10,000 CFM • Airflow capacities range from 2,500 to 15,000 CFM

15
www.semcohvac.com
SEMCO ASCENDANT Health Care Brochure
WE BRING
AIR TO LIFE WWW.SEMCOHVAC.COM | ASCENDANT | 20160113

SEMCO® is a global leader in air


management. We specialize in the
design and manufacture of a wide
range of air climate and air movement
solutions. Our collective experience
is unrivaled.

WE BRING AIR TO LIFE


Our constant aim is to provide systems that
precisely deliver the best indoor air quality
and performance, as well as maximize
energy efficiency.

SEMCO® A Fläkt Woods Company


Corporate Headquarters
1800 East Pointe Drive
Columbia, Missouri 65201 USA
573 443 1481
sales.semco@flaktwoods.com

To learn more about SEMCO offerings and to contact your nearest representative please visit
www.semcohvac.com

SEMCO embraces a policy of continuous development and improvement, the right is reserved to supply products which may differ from those illustrated and described in this
publication. Certified dimensions will be supplied upon request on receipt of order.

© SEMCO LLC 2015 All Rights Reserved. Pinnacle, eQ, FV Series, and the SEMCO logo are registered Trademarks of SEMCO LLC.

You might also like