User notice

1. The main power supply shall be three-phase AC five-wire.


The main voltage is 380V, 50Hz, permissible voltage
fluctuation is ±7%. The lighting power is 220V. The user
is responsible for providing power to the elevator's main
N power box.
2. If the escalator has a pit, the pit shall be
waterproof. If it's outdoor escalator, the pit shall set
+10
L=1.428H+4905+500=11017 0 a drainage hole, which will be connected to the
corresponding drainage system. And ensure that under any
Upper floor opening length≥7000 Lifting point of the upper top floor of circumstance, water depth of the pit does not exceed the
the escalator truss bottom of the escalator.
Safety fence
2662+500 Ceiling safety Minimum carrying capacity is 50KN 3. The lifting hole is located on the center line of the
(By customer 2243 ≥1300 escalator.
(By customer
600+500 1200 4. During the construction of the building, the user shall
protect the escalator from dirt and not allow to use the
≥350

838 escalator for other purposes (transporting materials,


900

M R1 ∅100 600 scaffolding etc.).


5. The user shall provide a grounding device, the
resistance of which shall be less than 4Ω.
1010

6. Reserve enough escalator entrance channel at site.


N 7. This drawing is not to scale, do not use measuring
≥2300
8
76

scale. All dimensions in mm, subject to change without


Outdoor escalator≥1400

400
Indoor escalator≥1100

notice.
Technical instruction
7
91

1. If the user cannot meet the minimum size of E, then


0
+5

230

Anti-climbing device under any circumstance, the horizontal distance between the
H=3930

10
00 (By seller) outer edge of the handrail and the wall or other obstacles
shall not be less than 80mm. Keeping this distance to the
height of 2.1m of the top step width, and set the top guard
600 in the illustrated position. The height shall not be less
than 0.3m.
1000
35°

R2 2. According to standard, there shall be enough area at the


M
900

entrance of each escalator for passengers. The width of the


area shall be at least equals to B+245mm, and the depth
shall be at least 2.5m (start from the end of the
1010
The pit is 2360
only for the handrail). If the width of the area increases to 2B+490mm,
ground floor
then the depth can be reduced to 2m.
3. When chooses double drive or the step width is 600mm,
≥4100 the upper of the truss shall be lengthened 500mm; When
the step width is 800mm, lengthen 200mm,;When the
horizontal span L≥15000mm, there must be a intermediate
support, length of L1<15000mm.
Pit shall be waterproof and 4. The height of all safety fences greater than (handrail
moistureproof Pit drainage hole ∅120,only for
outdoor escalator, connecting the height+100)
By customer 5. Refer to the table for motor power and other related
strong drainage system of the building
technical parameters.
Escalator construction layout drawing
Support reaction force(kN)
Upper support reaction force R1 51kN
Lower support reaction force R2 45kN
2 layer floor opening
(By customer)
1 layer floor opening Detail M
(By customer)
Finished floor level Filling the gap with clay
180 ≥1400 (By customer) (By customer) 180
≥4100 180 70 Technical specification
Escalator type DE-35°

135
Travel Height H(mm) 3930mm

300
≥1300

≥1300
≥1770
Horizontal span L(mm) 11017mm
200

Step width(mm) 600mm


To smooth the bearing surface Speed(m/s) 0.5m/s
Pre-embedded steel 20x120x1300
(By customer) Inclination(°) 35°
≥7000 The wire hole of the power and lighting at 40 Flat steps (pcs) 2
the upper area
The extended length of the wire≥2.5m
Motor power(kw) 7.5Kw
Three-phase five-wire
Main power supply(V,HZ) 380V , 50HZ
Lighting power supply(V,HZ) 220V , 50HZ
Contract no. Equipment
Detail N Customer no.
Project name
Building no. E1-2
Revise Revise Drawing no.
person
DETJ2022-62130a
∅100 date
≥50kN
FUJIXD ELEVATOR CO.,LTD.
Designed by Lv Version
Audit by YAO
Approve Page 1
Date 2022.6.23 Total 1