THE SHAFT STRUCTURE :

1.REINFORCED CONCRETE
SHAFT WITHOUT EMBEDDED
LIFT NO. STEEL PLATE
1#

TYPE CHOI-MRL
Requirements of Civil Engineering and elevator usage environment
CAPACITY 1350kg
1. Power supply should be 3-phase 5-wire 208VAC 60Hz, the permissible voltage fluctuation is 7%.
Lighting power should be single phase 110V 60Hz . CAR GROUP Simplex
2. The neutral wire and ground wire should be always separated from each other; ground wire adopts
TN-S type, the cross sectional area of ground wire should be no less than that of power line. OPERATION TYPE Full collective selective control
3. Each elevator shall be provided with separate power control switch. Power supply and lighting supply
shall be located separately on the wall where should be 2m high above top floor ground. If several DRIVE TYPE VVVF
elevators use the same Power Box, main power switches for each elevator should be easily identified.
4. Environmental requirement for traction and its control systems-The environmental temperature near top DOOR OPEN TYPE 2 panel SIDE opening
floor should be maintained between 5°C and 40°C, relative humidity to be maintained at 90%
(Temperature at 25 °C). FLOORS/STOPS/DOORS 2/2/2
5. Fixed lighting should be provided on the top floor with a switch to control the lighting.Permanent lighting
shall be provided near the controller, the lighting illumination for the controller should be at least 200LX. TOTAL SHAFT HEIGHT 9900mm
6. The shaft shall be well ventilated, ventilation holes shall be provided on the shaft top, which area is not
less than 1% of the horizontal section of the shaft. TRAVELING HEIGHT 4200mm
7. The shaft wall, pit ground and ceiling should stand enough mechanical strength. Durable, incombustible
and dust-proof material should be adopted for manufacturing. If there’s not embedded structure, OVERHEAD 4200mm
concrete strength at guide rail bracket, landing door sill and fixing point of landing door devices should
be no less than 250kg/cm². PIT DEPTH 1500mm
8. Elevator well could not be used with other irrelevant devices.
9. Horizontal sectional dimension of elevator well is the minimum clear dimension measured by plumb, CAR SIZE 1300(W) x 2250(D) x 2500(H)
allowable deviation is as follows:
0~+25mm Shaft Height ≤30m ENTRANCE SIZE 1100(W) x 2100(H)
0~+35mm Shaft Height ≤60m
0~+50mm Shaft Height >60m VOLTAGE 3-phase 5-wire 220vac ±7%
Shaft wall near door side: 0 -- +20mm
10.Well shall be provided with permanent lighting device. This lighting shall comprise one lamp at most FREQUENCY 60Hz
0.5 m from the highest and lowest points in the well with intermediate lamps at 7 m, maximum
spacing.It should be guaranteed that when all the doors are closed, the intensity of illumination at the POWER CAPACITY 12KVA
positions of 1m from the car top and pit is no less than 50Lx. A steel wire protective cover should be
provided for every lamp. SPEED 1.0 m/s
11.Pit floor should be flat and damp-proof course should be adopted. Stagnant water and leakage are not
permitted. DOOR OPERATOR OULING
12.The intensity of illumination on the ground near landing door should be no less than 50Lx.
13.If accessible spaces do exist below the car, the counterweight or the balancing weight, the base of the FIRE PROOFING None
pit shall be designed for an imposed load of at least 5000 N/m², and:
a) either there shall be installed below the counterweight buffer or under the travelling area of the
balancing weight, a solid pier extending down to solid ground, or
b) the counterweight or the balancing weight shall be equipped with safety gear.
note Lift wells should preferably not be situated above a space accessible to persons.

Note:
1.The general requirement is an integral part of purchase contract and
civil engineering drawing, which must be strictly abided by.For other
things unsettled, please refer to the relevant provisions of EN81-1.
2.If the well is not built in conformity with the civil engineering technical
conditions and drawing, the user shall be responsible for its changes
and the expenses arising therefrom.
Drn'By Apr'By
3.Should the dimension of the shaft need to be changed, please notify
our technology department in writing timely, the changes can only be Chk'By Data
made with written approval. 2022-12-19
Project Name
HOSPITAL DE CHEPO
Title
PA-22063(REV2) NS1#
Unit Sheet
millimeter 1 of 4

No.27, Development Road, Shenyang Economic & Technological Development zone China
Hook Note:
(By others)

≤50
≤50

955

Toppest guide bracket to top floor H4=3905


Top of main guide rail to top floor H5=3935
Top of main guide rail to top floor H1=3575
Top of assistant guide rail to floor H2=3390
Toppest joint guide bracket to top floor H3=2950

Top of main guide rail=2630


Top of assistant guide rail=2085
Top of main guide rail =2270
600

600
OH=4200

600

600
Inverter cabinet

2100
2100

REAR

REAR
REAR
Shaft lighting lamp with
defence cover,lowest
distance to pit surface

900+2000×3 =6900
0.5m, one at each
Guiderail Bracket 900+2000×3 =6900

2000+5000=7500

several distance,

2000+5000=7500
highest distance to
2000+5000=7500

shaft top0.5m).
Travel distance = 4200

Illumination intensity no
less than 50Lx,both at
1m above the top car
and the pit
(BY OTHER)
1 4200 1
Guiderail Bracket Pb 4200 Pb
Assistant Guide Length

Main Guide Length


Main Guide Length

FRONT REAR
FLOOR HEIGHT
STOP
2100

2100

FRONT
PP=1500

550
550

Drn'By Apr'By
Pit ladder
170

(By others)
Chk'By Data
5

2022-12-19
Drain device Project Name
VIEW OF SHAFT (Required when fireman service available, by others) VIEW OF SHAFT HOSPITAL DE CHEPO
(COUNTER WEIGHT SIDE) (NO ACCESS SPACE EXIST UNDER THE PIT) (CAR SIDE) Title
PA-22063(REV2) NS1#
Unit Sheet
millimeter 2 of 4

No.27, Development Road, Shenyang Economic & Technological Development zone China
Note:

FRONT

1200 1000
215 985 740

30 124
985 1000
C D

196
100
Q4

200
1125
∅320 ∅320
∅320
1216

160
Q6

255

2250

2950

1216
Q2 Q3 Q1

2950
160

∅320
870

1125
1390

1321

1475
100 Q5

196
124 30

C D

300 1100 100 Traveling cable


1300 Separated motor supply and
lighting supply(inside the 2200
2200 shaft)should be 2m above
top floor of hall door
(By other)
REAR
Top floor control PIT VIEW
SHAFT LAYOUT VIEW cabinet hole 400
other floor 150

C Car center line

D Door center line

1200 1000
215 985
740
320 665 665

30
Support Force

160
1216
200

Q1: 95000N Q2: 130000N

2950
∅320 ∅320 1390
∅320
1216

255

Q3: 120000N Q4: 60000N


2950
160

1475
30
Q5: 60000N Q6: 100000N
1390
1475

∅320

2200
Drn'By Apr'By
INSTALLATION VIEW OF GUIDE RAIL
2200
BRACKET( FOR CONCRETE SHAFT ) Chk'By Data
2022-12-19
TOP FLOOR MACHINE LAYOUT VIEW Project Name
HOSPITAL DE CHEPO
Title
PA-22063(REV2) NS1#
Unit Sheet
millimeter 3 of 4

No.27, Development Road, Shenyang Economic & Technological Development zone China
Note:

VIEW OF PRE-HOLE WHEN FIRE


SERVICE REQUIRED (BASE FLOOR)
Beam(by others)

≥200
40
250 2-Ø

500
TOP FLOOR HOOK LAYOUT VIEW

2400
2200
2100

1250
985 1000

100 1100 100

R4 600 600
800

R3 R2 R1
2950
450

1475

R5
VIEW OF OVERHEAD PRE-HOLE
(INCLUDE CONTROLLER INSTALLATION)
Beam(by others)

2200

≥200
250 HOOK ( BY OTHERS)
0
Ø4
2400 R1 R2 R3 R4 R5
2200
2100
2500Kg 5000Kg 2500Kg 2500Kg 2500Kg

1250
300 1100 100

Drn'By Apr'By

Chk'By Data
2022-12-19
Project Name
HOSPITAL DE CHEPO
Title
PA-22063(REV2) NS1#
Unit Sheet
millimeter 4 of 4

No.27, Development Road, Shenyang Economic & Technological Development zone China