DRW171113AC

Model Specifications Operation Mode


Single-Phase, Integrated Heatsink Type SSR Model Rated input current Rated load current Rated load voltage
Input Phase control
[Current Input Type] SRH1-A220-N 20A
Rated input current 4-20mA
Output waveform of phase control

SRH1 SERIES
SRH1-A230-N 30A 100-240VAC
When control input signal is 25% When control input signal is 50% When control input signal is 75%
SRH1-A260-N 60A Max. allowable input current 50mA
4-20mA ※1
INSTRUCTION MANUAL SRH1-A420-N 20A Pick-up current Min. 4.2mA

SRH1-A430-N 30A 200-480VAC Static off current Max. 4.0mA


SRH1-A460-N 60A Min. 0.9
Power factor
(max. 25° of difference between voltage phase and current phase)
Start-up time 60Hz: 200ms, 50Hz: 250ms ※1: The black parts of output waveform are output on the load.
SSR Derating Curve Operation time 60Hz: 16.6ms, 50Hz:20ms Power equality division type Phase equality division type
Phase control (phase equality division type, power equality division type) 100%

Load current [A]


60 ※1 100%
SRH1-A260/A460-N Operation mode
Cycle control (fixed cycle, variable cycle) Output Output
50 Output voltage Output voltage
※1: You can change operation mode by jumper pin. curve curve
40 SRH1-A230/A430-N
Default is Phase control (power equality division type).
30
Thank you for choosing our Autonics product. 25 Output
20 Output power
Please read the following safety considerations before use. 16 curve
10 SRH1-A220/A420-N Output
Rated load voltage range 100-240VACrmsᜠ (50/60Hz) 200-480VACrmsᜠ (50/60Hz)
Safety Considerations 0 10 20 30 35 40 50 60 70 80 90
100%
power
curve
100%
Ambient temperature[℃] Allowable load voltage range 90-264VACrmsᜠ (50/60Hz) 200-528VACrmsᜠ (50/60Hz)
※Please observe all safety considerations for safe and proper product operation to avoid hazards. DC 4mA
Control input
DC 20mA DC 4mA DC 20mA
Rated load Resistive load Control input
※ symbol represents caution due to special circumstances in which hazards may occur. S
 ince effectiveness of the heat radiation is decreased when multiple SSRs are installed closely, ※1 20Arms 30Arms 60Arms 20Arms 30Arms 60Arms
current (AC-51) Controls output power which is Controls phase angle which is proportional
please supply less than 50% of the rated load current.
Warning Failure to follow these instructions may result in serious injury or death. ※Above SSR derating curves obtained approval from the UL certification authority. Min. load current 0.5Arms 0.5Arms proportional to control input (4-20mA) level. to control input (4-20mA) level.
Caution Failure to follow these instructions may result in personal injury or product damage. Max. 1 cycle surge current
300A 500A 1000A 300A 500A 1000A Cycle control
Warning Operation Setting (60Hz)
Max. non-repetitive surge 2 2 2 2 2 2
Fixed cycle
350A s 1000A s 4000A s 350A s 1000A s 4000A s
1. F ail-safe device must be installed when using the unit with machinery that may cause ●D
 etach front cover current (I2t, t=8.3ms) Controls continuously the number of full cycle which is supplied to load every 1 sec by being proportional
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, Press front cover connection 4 parts at right and left side with
Peak voltage to control input (4-20mA).
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster (-) driver, and front cover is detached. 600V 1000V
※Before detaching front cover, you must cut off load current (-) driver (non-repetitive) When control input signal is 0% When control input signal is 50% When control input signal is 100%
prevention devices, etc.)
Failure to follow this instruction may result in fire, personal injury, or economic loss. and input. Leakage current (Ta=25℃) Max. 10mArms (240VACᜠ/60Hz) Max. 10mArms (480VACᜠ/60Hz)
2. Install on a device panel or DIN rail to use. Output on voltage drop [Vpk]
Failure to follow this instruction may result in electric shock or fire. Max. 1.6V
(max. load current)
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or fire. Static off-state dv/dt 500V/㎲
4. Check 'Connections' before wiring. T: Cycle (1 sec) T: Cycle (1 sec) T: Cycle (1 sec)
Failure to follow this instruction may result in fire. ※1: AC-51 are utilization category at IEC60947-4-3.
●J
 umper pin setting
5. Do not disassemble or modify the unit. Operation mode is decided by jumper position. Variable cycle
Failure to follow this instruction may result in electric shock or fire. After changing operation mode, re-supply input signal. General specifications Controls fast and accurately the subject with optimized the number of AC voltage cycle which is
Caution Phase control
supplied to load by being proportional to control input (4-20mA).
4-20mA 5 to 99% When control input signal is 10% When control input signal is 50% When control input signal is 90%
1. Use the unit within the rated specifications. input (phase equality division type)
Jumper
Failure to follow this instruction may result in fire or product damage. Phase control
2. Use dry cloth to clean the unit, and do not use water or organic solvent. 10 to 99%
(power equality division type)
Failure to follow this instruction may result in electric shock or fire.
3. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct Jumper pin Frequency reading function Yes
sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in fire or explosion. Dielectric strength (Vrms) 4000VAC 50/60Hz for 1 min (input-output, input/output-case) T cycle T cycle T cycle
① ② ③ ④
4. Keep metal chip, dust, and wire residue from flowing into the unit.
Insulation resistance Over 100MΩ (at 500VDC megger)
Failure to follow this instruction may result in fire or product damage. ① CYCLE-V: Cycle control (variable cycle)
5. Since leakage current still flows right after turning off the power or in the output OFF status, ② CYCLE-F: Cycle control (fixed cycle) Indicator Input indicator: green LED
Jumper pin Jumper
do not touch the load terminal. ③ PHASE-AD: Phase control (phase equality division type)
Failure to follow this instruction may result in electric shock. ④ PHASE-PD: Phase control (power equality division type) (default)
Vibration
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z Cautions during Use
direction for 1 hour

Dimensions (unit: mm)


-20 to 70℃, storage: -20 to 100℃
Ambient temp. (The rated load current capacity is different depending on ambient
1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
2. Install the unit in the well ventilated place.
Panel cut-out Environment temperature. Refer to ' SSR Derating Curve'.)
Rated load current 20A/30A 3. Ground to the heat sink, panel, or DIN rail.
Rated load current 20A/30A Rated load current 60A
45 100 Ambient humi. 45 to 85%RH, storage: 45 to 85%RH Failure to follow this instruction may result in electric shock.
2-M4 7 81.5 4-M4 Spacing
Ø4.5 3.5 31 Min. 1×0.5mm2 (1×AWG20), 4. While supplying power to the load or right after turning off the power of the load, do not touch the
Input terminal connection body and heat sink.
Panel max. 1×16mm2 (1×AWG6) or 2×1.5mm2 (2×AWG16)
Min. 1×1.5mm2 (1×AWG16), Failure to follow this instruction may result in a burn due to the high temperature.
100

Output terminal connection max.1×16mm2 (1×AWG6) or 2×6mm2 (2×AWG10) 5. In order to protect the product from the short-circuit current of the load, use rapid fuse of which I2t is
※Use wires compliant with load current capacity to connect to the terminal. under the 1/2 of SSR I2t. When short-circuited, replace the fuse to those of same specification with
90

90

the used rapid fuse.


Input terminal fixed torque 0.75 to 0.95N.m
6. Install dummy resistance in parallel with the load, to keep the sum of current flowing in the load and
100

Output terminal fixed torque 1.6 to 2.2N.m


80
90

dummy resistance being over SSR minimum load current.


7. Do not use near the equipment which generates strong magnetic force or high frequency noise.
7 7 Approval ᜢᜧ
20 8. This unit may be used in the following environments.
※Screw tightening torque for mounting: 1.8 to 2.5N.m • Rated load current 20A/30A : Approx. 410g ① Indoors (in the environment condition rated in 'Specifications')
Unit weight
100

• Rated load current 60A: Approx. 680g


DIN rail mounting ② Altitude max. 2,000m
DIN rail attachment ※Environment resistance is rated at no freezing or condensation. ③ Pollution degree 2
4.5 Input indicator ※For wiring the terminal, round terminal must be used. ④ Installation category III
3.5 (green)

Rated load current 60A ①


110
81.5 14.3 Input indicator 100 Connections Major Products
100

2-Ø4.5 3.5 45 3.5 (green) 31 Panel SSR Module


② Load Photoelectric Sensors Temperature Controllers
4/A2- 2/L1
Fiber Optic Sensors Temperature/Humidity Transducers
Load
Door Sensors SSRs/Power Controllers
4-20mA Input SRH1 Series Output CAP
※1 power source
※DIN rail must be grounded. 35mm ※When installing multiple SSRs, please keep Rapid fuse (AC) Door Side Sensors Counters
DIN rail space between SSRs for heat radiation. Area Sensors Timers
When installing SSRs horizontally (input 3/A1+ 1/T1 Proximity Sensors Panel Meters
DIN rail detachment
part and output part on the same height), Pressure Sensors Tachometers/Pulse(Rate) Meters
100
80
90

please supply less than 50% of the rated ※1: When connecting noise filter and capacitor, it is appropriate for EMC. Rotary Encoders Display Units
load current. CAP: Rated load voltage 100-240VAC → 1uF/250VAC Connectors/Sockets Sensor Controllers
Rated load voltage 200-480VAC → 0.47uF/500VAC Switching Mode Power Supplies
http://www.autonics.com
Control Switches/Lamps/Buzzers
※Use terminals of size specified below. HEADQUARTERS:
High Temperature Caution I/O Terminal Blocks & Cables
Terminal type Input Output Stepper Motors/Drivers/Motion Controllers 18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
While supplying power to the load or right South Korea, 48002
Graphic/Logic Panels
4.5 4.5 after turning off the power of the load, do a Min. 3.5mm Min. 5.0mm TEL: 82-51-519-3232
a b Field Network Devices E-mail: sales@autonics.com
3.5 3.5 35mm not touch the body and heat sink. Laser Marking System(Fiber, Co₂, Nd:YAG)
Failure to follow this instruction may result <Round> b Max. 7.0mm Max. 12.0mm
② DIN rail Laser Welding/Cutting System DRW171113AC
※The above specifications are subject to change and some models may be discontinued without notice. (-) driver ① in a burn due to the high temperature.
※Be sure to follow cautions written in the instruction manual and the technical descriptions (catalog, homepage).