INTRODUCTION
The current loop is a common signaling technique for sending This application note highlights the AD8479, a precision difference
and receiving sensor data over long distances. In a current loop, amplifier that accurately measures differential signals with the
the current contains information from a transmitter that is presence of very high input common-mode voltages (CMVs) that
relayed to a receiver through very long wires (see Figure 1). This range up to ±600 V (see Figure 2). The AD8479 serves as a front
transmission technique has an inherent insensitivity to electrical end for a current loop transmitter, thus enabling the transmitter
noise, thus making it ideal for data transmission. Unlike voltage to operate in applications with very high CMV, such as motor
signaling, current loops are immune to errors induced by IR drops controls and high voltage current sensing.
along the wires. Although the wire terminations in a loop are 800
less than ideal, all signaling currents flow through all components. VS = ±15V
IR drops do not affect the signaling current as long as the supply is 600
LONG WIRES 0
INPUT Tx Rx
SIGNAL
12865-001
–200
–400
Figure 1. Current Loop Diagram
–600
12865-002
–800
–20 –15 –10 –5 0 5 10 15 20
VOUT (V)
Rev. 0 | Page 1 of 5
AN-1344 Application Note
TABLE OF CONTENTS
Introduction ...................................................................................... 1 Current Loop Transmitter Accuracy ..............................................5
Revision History ............................................................................... 2 Conclusion .....................................................................................5
Circuit Transfer Function ................................................................ 3
REVISION HISTORY
10/15—Revision 0: Initial Version
Rev. 0 | Page 2 of 5
Application Note AN-1344
R3
5 VO –VIN
NOTES
–15V 1. R1, R2, AND R3 IS AT 1%
16.2kΩ
12685-004
Figure 3. Current Loop Transmitter
–4 VO
Because the +REF and –REF pins are tied, the output is equal to
Figure 4. Simplified AD8479 Output Network
the reference voltage (VREF) when there is no differential voltage
present at the input. Use the voltage divider theorem to calculate the following:
The output goes to the ADA4627-1, which serves as an interface 1.8 kΩ
VIN 5VO
between the AD8479 and the load. Connecting the output to the 16.2 kΩ 1.8 kΩ
ADA4627-1, as opposed to connecting it directly to the AD8479
output, helps to avoid variations on the output current, which is −VIN = 5 VO (0.1)
highly affected by the load change. The ADA4627-1 also forces −VIN = 0.5 VO (5)
the voltage for the reference pins of the AD8479, resulting in
With the virtual short, calculate the following:
the following output equation:
−VIN = +VIN
R1 R3
1 VO
R3
VOUT VO (2) +VIN = 0.5 VO
R1 RL R2 R2
Therefore,
Combining the AD8479 and ADA4627-1 enables a current loop
VO – VR1 = + VIN
transmitter front-end circuit to measure signals at very high CMVs.
VR1 = VO – (+ VIN)
VR1 = VO – 0.5 VO
VR1 = 0.5 VO
VR1 0.5 VD
1
5
1
VR1 VD (6)
10
Rev. 0 | Page 3 of 5
AN-1344 Application Note
+15V
Figure 5 shows the current path that carries the information.
Because the amplifier (ADA4627-1) has high input impedance,
+IN +VS
the current flows directly through the load, which gives an
+REF
overall circuit transfer function of
VD AD8479 VO
OUT
IO = VR1/R1 1kΩ +VIN
–IN –REF IO
1 R1 +VIN RL
VD –VS 1kΩ
VOUT
IO 10 VCM ADA4627-1
R1 –VIN
1.8kΩ –VIN
IO = VD/10R1 R2
16.2kΩ
VD
12685-005
R3
IO A
10,000 –15V NOTES
1. R1, R2, AND R3 IS AT 1%
Rev. 0 | Page 4 of 5
Application Note AN-1344
12865-007
–1000
–10 –8 –6 –4 –2 0 2 4 6 8 10
Maximum Full-Scale Error 0.05% DIFFERENTIAL INPUT VOLTAGE (V)
Adding the worst-case resistor tolerance error of 3% to the Figure 7. Output Current vs. Input Voltage for Various CMV Inputs
worst-case errors due to the offsets of active components yields: Figure 7 shows the transmitter output performance at three
Full Scale Error = 3% + 0.05% = 3.05% CMVs. At 0 V CMV, a 45.3 ppm gain error with an offset of
These errors assume that the ideal resistors were selected and 0.0038 μA is present; at 48 V CMV, a 45.4 ppm gain error with an
that the errors resulted from their tolerances. Figure 6 shows the offset of −0.2443 μA is present; and at 96 V CMV, a 45.4 ppm gain
actual error performance of the application circuit. error with an offset of −0.5262 μA is present. This performance
0.5
characteristic demonstrates that increasing the CMV has a
negligible effect on the output of the transmitter front end. This
TOTAL UNCOMPENSTAED ERROR (%FSR)
0.4 0V
48V result is due to the AD8479 allowing accurate measurement of
0.3 96V
differential signals in the presence of CMV up to ±600 V due to
0.2 the ADA4627-1, a very low offset voltage wide bandwidth
0.1 precision amplifier.
0 In addition, this application circuit has an excellent common-
–0.1 mode ratio (CMR) of 94 dB in both 0 V and 48 V CMVs and
–0.2
48 V and 96 V CMVs as measured.
–0.3 CONCLUSION
–0.4 Current loop signaling is more dependable than voltage signaling
for transmitting signals over long distances. Signals are contained
12865-006
–0.5
–10 –8 –6 –4 –2 0 2 4 6 8 10 in the loop current transmitted for long distances, disregarding the
DIFFERENTIAL INPUT VOLTAGE (V)
effects of voltage drops in the wire, a major concern for voltage
Figure 6. Input Voltage vs. Total Uncompensated Error (%FSR) vs. Input CMV signaling. When transmitting signals as voltage, the supply current
For a maximum uncompensated error of 0.47% FSR, the system induces voltage drops along the wires that usually appear as errors
shows highly dependable performance in terms of accuracy. in the signal measurement. Furthermore, current loop signaling
Despite the errors introduced by the resistors and the AD8479, has a better immunity to noise than voltage signaling. This
the system is able to maintain good accuracy over different CMV application note implements a current loop transmitter front end
values. With this performance, using the AD8479 as a current loop using the AD8479. This allows precision instrumentation over
transmitter front end enables instrumentation with high accuracy very high CMV signals. This circuit addresses the need for
up to 96 V (guaranteed to work up to ±600 V CMV). Because the precision measurements for industrial and motor applications,
majority of the errors are introduced by passive components, that is, industrial process-monitoring applications. As tested and
system performance can be improved further by using high verified, this application circuit allows precision instrumentation
precision, very tight tolerance resistors. at CMVs up to 96 V (works up to 600 V CMV) with proven
accuracy over wide input voltage and CMV ranges. The Analog
Devices, Inc., amplifier devices used in this application note are
highly dependable for robust and precision application needs.