Technical Data 4008-30TRS1

4000 Series 4008-30TRS2


Gas Engine
Basic technical data Ratings
Number of cylinders .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 8 This is defined in ISO3046 / 1 (BS5514 /1 - 1982)
Cylinder arrangement ... ... ... ... ... ... ... ... ... ... ... .. vertical, In line Electrical ratings are based on stated alternator efficiency and are
Cycle . ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 4 stroke, spark ignition for guidance only. For Load Acceptance figures, please refer to
Induction system ... ... ... ... ... ... ... ... ... ... ... ... ... ... turbo charged Stafford Applications Engineering Department.
Compression ratio . ... ... ... ... ... ... ... ... ... ... ... ... ... .12·1 nominal
Bore... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 160 mm Operating point
Stroke ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 190 mm Engine speed ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 1500 rev/min.
Cubic capacity... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..30,561 litres Ignition timing ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 24° BTDC
Direction of rotation ... ... ... ... ... anti-clockwise viewed on flywheel Inlet manifold mixture temperature. ... ... ... ... ... ... ... ... ... ... 50 °C
Firing order ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1, 4, 7, 6, 8, 5, 2, 3 Cooling water exit temperature .. ... ... ... ... ... ... ... ... ... ... < 96 °C
Cylinder 1 .. ... ... ... ... ... ... ... ... ... ... ... ... ... furthest from flywheel Exhaust emission ... ... ... ... ... ... ... ... according to TA-Luft (NOx)
Total weight of cogeneration unit (engine only)
Estimated total weight (dry)... ... ... ... ... ... ... ... ... ... ... ... 3350 kg
Fuel data
Lower calorific value... ... ... ... ... ... . 34,710 kJ/Sm³ (45.671 kJ/kg)
Estimated total weight (wet) .. ... ... ... ... ... ... ... ... ... ... ... 3528 kg
Density ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .0,76 kg/Sm³
Overall dimensions Stoiciometric air requirement.. ... ... ... ... ... ... ... ... ... ... ...16 kJ/kg
Height mm Length mm Width mm Minimum methane number before derate .. ... ... ... ... ... ... ... ... 75

Cogeneration unit Performance


Natural gas 1671 2559 1400 Steady state speed stability at constant load . ... ... ... ... .. + 0,25%
Note: All data based on operation to ISO 3046/1, BS 5514 and DIN
Bio gas 1782 2559 1418
6271 standard reference conditions.
Electro unit
Natural gas 1671 2658 1633 Test conditions
-air temperature.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 25 °C
Bio gas 1782 2658 1633
-barometric pressure .. ... ... ... ... ... ... ... ... ... ... ... ... ... ...100 kPa
-relative humidity ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 30%
Moment of inertia (GD²)
-engine .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 4,12 kgm²
-flywheel ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 5,92 kgm²
Cyclic irregularity for engine/flywheel:
4008-30TRS1 - 447 kW ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1:215
4008-30TRS2 - 526 kW ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1:194

General installation
Continuous baseload rating
Designation Units Cogeneration unit Electrounit
TRS1 TRS2 TRS1 TRS2
Gross engine power kW 447 526 447 526
Brake mean effective pressure kPa 1170 1370 1170 1370
Combustion air flow m³/min 34 40 34 40
Exhaust gas temperature (max) after turbo °C 490 485 490 485
Exhaust gas flow (max) m³/min 90 105 90 105
Boost pressure ratio - 2,53 2,90 2,53 2,90
Overall electrical efficiency % 37,9 38,5 37,4 38,0
Mean piston speed m/s 9,5 9,5
Charge coolant flow l/sec 8,3 8,3
Nominal excess air factor (Lambda) λ 1,71 1,70 1,71 1,70
Typical gross Genset 25 °C (100 kPa)
kWe 425 500 425 500
Electrical output (unity 1.0pf)
Assumed alternator efficiency % 95,0 95,0
Continuous baseload rating: Power available for continuous full load operation. No overload available.
Energy balance Charge cooling water data
Coolant flow. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...30 m³/h
4008-30TRS1 / 4008-30TRS2 - Cogeneration unit
Coolant entry temperature... ... ... ... ... ... ... ... ... ... ... ... ... .. 45 °C
TRS1 TRS2 Charge cooler.. ... ... ... ... ... ... ... ... ... ... .. fin and tube on engine
Designation Continuous Continuous Shutdown switch setting.. ... ... ... ... ... ... ... ... coolant 96 °C rising
baseload % baseload % Coolant immersion heater capacity . ... ... ... ... ... ... ... .. 4 kW 1 off
rating rating
Energy in fuel 1119 100 1298 100 Lubrication system
Energy in power
447 39,9 526 40,5 Recommended lubricating oil: Lubricating oil requirements vary
output (Net)
with fuel used. Full specifications including oil sampling and
Energy in recommendations and condemnation limits appear on the Fuel,
350 31,3 398 30,6
exhaust Coolant and Lubricating Oil Recommendation Sheet for the 4000
Energy to Series Gas Engines.
189 16,9 211 16,3
coolant and oil
Lubricating oil capacity
Energy to charge Total system ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 165,6 litres
67 6,0 90 6,9
cooler Sump maximum .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... 154,0 litres
Sum of useable Sump minimum ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 127,0 litres
539 48,1 602 46,4
heat
Lubricating oil temperature
Sum of useable
986 88,1 1135 87,4 Maximum to bearings .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... 105 °C
energy
Lubricating oil pressure at 85 °C temperature to bearings .0,34 MPa
Energy to Oil consumption (continuous rating)
66 5,9 73 5,7
radiation
Designation TRS1 TRS2
4008-30TRS1 / 4008-30TRS2 - Electro unit After RUNNING-IN †† g/kWhr 0,14 0,14
TRS1 TRS2 Oil flow rate from oil pump l/s 3,7 3,7
Designation Continuous Continuous †† Typical 250 hours
baseload % baseload % Sump drain plug tapping size .. ... ... ... ... ... ... ... ... ... ... ... ... GA1
rating kW rating kW Oil pump .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... gear driven
Energy in fuel 1134 100 1315 100 Shutdown switch setting.. ... ... ... ... ... ... ... ... .. oil 1,93 bar falling
Energy in power Normal operating angles:
447 39,4 526 40,0 -front and rear.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 5°
output (Net)
-side tilt ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 22,5°
Energy in
353 31,1 402 30,6
exhaust
Energy to
Fuel system
193 17,0 216 16,4
coolant and oil Recommended fuel: Natural Gas LHV at 34 MJ/m³ (930 Btu/cu.ft).
Energy to charge Other fuels may be used, for example landfill or digester gas.
69 6,1 92 7,0 Ratings will vary from those shown.
cooler
Where fuels other then Natural Gas are being considered it is
Sum of useable
615 54,2 710 54,0 imperative that a full gas analysis (including details of any solid or
heat
liquid components) be obtained. Reference should then be made to
Sum of useable Perkins Engines Company Limited to determine suitability. Gas
1062 93,7 1236 94,0
energy supplies must be filtered to the same standard as the engine intake
Energy to air (i.e. Maximum particle size not to exceed 50 microns).
72 6,3 79 6,0 Gas supply pressure ... ... ... ... . 1,5 kPa to 5 kPa at full rated flow
radiation
Carburettor type .. ... ... ... ... .. Deltec with zero pressure regulator
Notes: Installation of gas supply and shut off valves to be in accordance
with local regulations.
z Not to be used for CHP design purposes (indicative figures
only). Consult Perkins Engines Company Limited. Cogeneration unit Electro unit
Designation
z Assumes complete combustion. TRS1 TRS2 TRS1 TRS2
Fuel consumption gross kJ / kW kJ / kWs kJ / kWs kJ / kWs
Cooling system At Continuous baseload
2,51 2,47 2,54 2,50
rating
Recommended coolant: 50% inhibited ethylene glycol or 50%
At 75% of Continuous
inhibited propylene glycol and 50% clean fresh water. For 2,58 2,53 2,61 2,56
base load rating
combined heat and power systems and where there is no likelihood
At 50% of Continuous
of ambient temperature below 10 °C, then clean ‘soft’ water may be 2,81 2,70 2,84 2,73
baseload rating
used, treated with 1% by volume of Perkins inhibitor in the cooling
At 25% of Continuous
system. The inhibitor is available in 1 litre bottles from Perkins. 3,63 3,38 3,66 3,41
base rating
Total coolant capacity (engine only) .. ... ... ... ... ... ... ... ... 48 litres
Fuel: Natural Gas - LHV = 34,71 MJ/m³
Maximum jacket water pressure in crankcase ... ... ... ... ... ... 1 bar Tolerance on Fuel consumption
(plus static pressure head)
Designation Cogeneration unit Electro unit
Jacket cooling water data Mass flow data Units TRS1 TRS2 TRS1 TRS2
Coolant flow ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 36 m³/h
Fuel Kg/h 88,2 102,3 89,3 103,6
Coolant exit temperature (max) . ... ... ... ... ... ... ... ... ... ... ... 96 °C
Coolant entry temperature (max) ... ... ... ... ... ... ... ... ... ... ... 88 °C Volume flow data (100 kPa)
Fuel (15 °C) Sm³/hr 116,1 134,6 117,6 136,3
84 CHARGE COOLER OUTLETS

1726.5
42 LIFTING BRACKET 42 LIFTING BRACKET

255

GOVERNOR CONTROL BOX

GAS ZERO PRESSURE REGULATOR


IGNTION CONTROL BOX

REAR FACE C/CASE


MEDIUM DUTY AIR
FILTER 1800 C.F.M.

FRONT FACE C/CASE


IGNITION COILS
CHARGE AIR COOLER FRESH WATER
INLET FLANGE

ENGINE LIFTING BRACKET


GAS INLET FLANGE (ENGINE ONLY)

602
24V STARTER MOTOR
430
4008-30TRS1 and 4008-30TRS2 Bio gas cogeneration unit - Left view

1/8-27 NPSF TAPPING CRANKSHAFT


RFOR LUB. OIL PRESS. CONN.
OIL COOLER
2 x 3/8-18 NPSF
RTAPPING LUB.OIL PUMP

2 x G 3/8 TAPPING FOR


RLUB. OIL TEMP. CONN.
TRIPLE LUB. OIL FILTERS
LUB. OIL DIPSTICK
STARTER MOTOR RELAY

G 1/2 TAPPING 698 G3/8 TAPPING


G 1 SUMP DRAIN PLUG
(BOTH SIDES)
231,5
26
4008-30TRS1 and 4008-30TRS2 Bio gas cogeneration unit - Front view

359 232

Governor
42 lifting bracket
throttle/actuator

Fresh water
outlet

cylinders
Crankcase
breather

Lub. oil filler

726.3
242

crankshaft

TV damper guard
515

168

690

Gas inlet
2559 overall length

601

88.5 fresh water outlet 254.5

Exhaust manifold
heatshield removed
for clarity

Rear face c/case


water rail

Front face c/case


Mixing screw
9.4
22
et

Ø
inl
Air
4008-30TRS1 and 4008-30TRS2 Bio gas cogeneration unit - Right view

crankshaft

25

220
Crankcase inspection
covers

880 182
C of G (wet)
4008-30TRS1 and 4008-30TRS2 Bio gas cogeneration unit - Rear view

Exhaust outlet. system pipework 1418overall width


must be adequately supported
to ensure no load is exerted
on turbocharger. (see detail) 848.5 407 to remove
407 457 Air cleaner
element

27
cylinders

Lifting
bracket

Secondary water outlet

1767 overall height


732.2

Secondary water inlet

Carburettor

455
366

crankshaft

rotation
543

8 holes equi-spaced
M12 x 30 deep
on Ø 438.15 P.C (17 1/4”) 11.25 16 holes equi-spaced
M12 x 21 deep
on Ø 679.45 P.C. (26 3/4”)
4008-30TRS1 and 4008-30TRS2 Bio gas cogeneration unit - SAE Flywheel, Exhaust Outlet and Support Pads

10

Ø 466,82
Ø 466,72

Ø 647,95
Ø 647,70
Ø 410

Ø 520

Ø 711
25,4

Detail of Sae 514 flywheel


and SAE O flywheel housing
(metric tappings)
scale 1:5

407 To
crankshaft
30

30
Ø 150

Ø 110

732.2

crankshaft

45

5
To

40

Detail of exhaust outlet


Scale 1:2

1863.5

58
6 holes Ø 22 60
Rear face c/case

crankshaft
908

454

23 64
26

148
45

90

76

88

Plan view of support pads


42 LIFTING BRACKET
1726.5
42 LIFTING BRACKET

GOVERNOR CONTROL BOX

GAS ZERO PRESSURE REGULATOR


IGNITION CONTROL BOX
MEDIUM DUTY AIR

REAR FACE C/CASE


FILTER 1800 C.F.M.

FRONT FACE C/CASE


IGNITION COILS

CHARGE AIR COOLER

ENGINE LIFTING BRACKET


G2 60° CONE FITTING FLEXIBLE (ENGINE ONLY)
GAS INLET 457 LONG
24V ALTERNATOR

FRESH WATER PUMP


602
24V STARTER MOTOR

1/8-27 NPSF TAPPING


4008-30TRS1 and 4008-30TRS2 Natural gas electro unit - Left view

RFOR LUB. OIL PRESS. CONN. CRANKSHAFT


OIL COOLER
2 x 3/8-18 NPSF
RTAPPING LUB.OIL PUMP

2 x G 3/8 TAPPING FOR


RLUB. OIL TEMP. CONN.
TRIPLE LUB. OIL FILTERS
LUB. OIL DIPSTICK
STARTER MOTOR RELAY

G 1/2 TAPPING 698 G3/8 TAPPING


G 1 SUMP DRAIN PLUG
(BOTH SIDES)
746
44 292
FRESH WATER INLET
4008-30TRS1 and 4008-30TRS2 Natural gas electro unit - Front view

42 LIFTING BRACKET
FRESH WATER OUTLET PIPE

CYLINDERS
GOVERNOR TO SUIT Ø 76 (INSIDE) HOSE
295
ACTUATOR/THROTTLE
G3/8 AND G1/2 TAPPINGS
232
IN THERMOSTAT HOUSING

FRESH WATER OUTLET

Rp1/2 TAPPINGS
IN THERMOSTAT HOUSING

LUB. OIL FILLER SECONDARY WATER OUTLET


882
SECONDARY WATER INLET

484
357
272

2 CRANKSHAFT

TV DAMPER GUARD
515

FRESH WATER INLET


65 SUMP REMOVAL
TO SUIT Ø 76 I/D HOSE

168

445 409

698

GAS INLET
2658 OVERALL LENGTH

86 FRESH WATER OUTLET

SECONDARY WATER OUTLET 15

254.5
20 SECONDARY WATER INLET

REAR FACE C/CASE


EXHAUST MANIFOLD
MIXING SCREW

FRONT FACE C/CASE


17,5

SECONDARY WATER OUTLET


TO SUIT Ø 60.3 I/D HOSE
T

9 .4
LE

22

SECONDARY WATER OUTLET 972


IN

Ø
R

TO SUIT Ø 76.2 I/D HOSE


AI

SECONDARY WATER PUMP


4008-30TRS1 and 4008-30TRS2 Natural gas electro unit - Right view

CRANKSHAFT

25

220
CRANKCASE INSPECTION
COVERS

880 182
C OF G (WET)
4008-30TRS1 and 4008-30TRS2 Natural gas electro unit - Rear view

EXHAUST OUTLET.SYSTEM PIPEWORK


MUST BE ADEQUATELY SUPPORTED
TO ENSURE NO LOAD IS EXERTED
ON TURBOCHARGER. (SEE DETAIL)

1633
OVERALL WIDTH

848.5 407 TO REMOVE


645
AIR CLEANER
27 LIFTING BRACKET ELEMENT
CYLINDERS

1671 OVERALL HEIGHT


CARBURETTOR
732.2

CRANKSHAFT

ROTATION
543

8 HOLES EQUI-SPACED
M12 x 30 DEEP
ON Ø 438.15 P.C (17 1/4”)
16 HOLES EQUI-SPACED
M12 x 21 DEEP
11.25° ON Ø 679.45 P.C (26 3/4”)
4008-30TRS1 and 4008-30TRS2 Natural gas electro unit - SAE Flywheel, Exhaust Outlet and Support Pads

10

Ø 466,82
Ø 466,72

Ø 647,95
Ø 647,70
Ø 410

Ø 520

Ø 711
25,4

DETAIL OF SAE 514 FLYWHEEL


AND SAE O FLYWHEEL HOUSING
(METRIC TAPPINGS)
SCALE 1:5

Ø 279

Ø 152

22,5°

8 HOLES Ø 17.5 EQUALLY


SPACED ON A 235 PC

DETAIL OF EXHAUST OUTLET


SCALE 1:5

1863.5

58
6 HOLES Ø 22 60
REAR FACE C/CASE

CRANKSHAFT
908

454

23 64
26

148
45

90

76

88
PLAN VIEW OF SUPPORT PADS
Derate tables
Raw water derate

4008-30TRS1 Ambient / Raw water derate

30

25

20
Derate (%)

15

10

5
50 °C

0
35 40 45 50 55 60 65
Raw w ater Tem p (°C)

Ambient temperature derate

4008-30TRS1 Altitude / Ambient derate

16

14 50 °C
40 °C
12 30 °C

10
Derate (%)

0
0 500 1000 1500 2000 2500 3000

Altitude (MASL)
Raw water derate

4008-30TRS2 Ambient / Raw water derate

30

25

20
Derate (%)

15

50 °C
10
40 °C
5
30 °C

0
35 40 45 50 55 60 65
Raw w ater Tem p (°C)

Ambient temperature derate

4008-30TRS2 Altitude / Ambient derate

25
50 °C
40 °C
30 °C
20
Derate (%)

15

10

0
0 500 1000 1500 2000 2500 3000
Altitude (MASL)
Induction system Starting requirements temperature down to 0°C
Oil: . ... ... ... ... ... ... ... refer to Perkins Engines Company Limited
Maximum air intake restriction of engine: Starter: ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1 x 24 Volts
-clean filter. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 127 mm H2O Battery: .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... 2 x 12V total Ah 232
-dirty filter .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 380 mm H2O Inrush current to starter: ... ... ... ... ... ... ... ... ... ... ... .. 1000 amps
-air filter type . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1 of dry type Cranking current: ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 600 amps
Starter cable size: .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 70 mm²
Exhaust emissions data Maximum length: ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 6 m
Ambient temperature of 25 °C
Emissions at continuous baseload rating. Notes:

If the engine is to operate in ambient conditions other then test z Engines that are not equipped with additional A:F ratio control
conditions then suitable adjustments may be necessary for any will require immersion heaters to be fitted when ambient
change in inlet air temperature or barometric pressure. temperatures are below 15 °C
z Engines fitted with additional A:F ratio control with start
Designation TRS1 TRS2 unaided down to 0 °C
Oxygen (O2) % 9,01 9,24 z The battery capacity is defined by the 20 hour rate
Oxides of Nitrogen (NOx) mg/Nm³ 480 490 z The starting ability of an engine with immersion heater will be
Hydrocarbons (THC) mg/Nm³ 1160 1100 improved by about 10 °C and the start aid specification can be
Carbon Monoxide (C0) mg/Nm³ 791 774 modified accordingly. The oil specification should be for the
minimum ambient temperature as the oil will not be warmed by
Designation Cogeneration unit Electro unit the immersion heater
Mass flow data TRS1 TRS2 TRS1 TRS2 z Breakaway current is dependant on battery capacity available.
Combustion air (25 °C) kg/h 2385 2766 2416 2802 Cables should be capable of handling the transient current
which may be up to double the steady cranking current.
Volume flow data
Combustion air (25 °C) m³/h 2040 2366 2067 2397
Electrical system
Exhaust system Type ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. insulated return
Starter motor .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 24 volts
Designation Units TRS1 TRS2 Starter motor power ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 7,5 kW
mm Number of teeth on flywheel... ... ... ... ... ... ... ... ... ... ... ... ... . 190
Maximum back pressure for total system H2O 600 400 Number of teeth on starter motor ... ... ... ... ... ... ... ... ... ... ... ... 12
Minimum cranking speed ... ... ... ... ... ... ... ... ... ... ... 120 rev/min.
Exhaust outlet flange size . ... ... ... ... ... ... ... ... ... ... . 1 x 152 mm Pull in current of starter motor solenoid.. ... . 26,8 amps at 24 volts
Hold in current of starter motor solenoid ... ... .. 9 amps at 24 volts
For recommended pipe sizes see the Installation Manual.
Designation Cogeneration unit Electro unit
Ignition system
Volume flow data
Units TRS1 TRS2 TRS1 TRS2
100 kPa
Primary system... ... ... ... ... ... ... ... ... ... ... ... ... Altronic Disn 800
Exhaust gas at turbo Primary voltage .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 24 volts
m³/h 5409 6215 5481 6296
exit temperature
Polarity ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... negative earth
Exhaust data Units TRS1 TRS2 Spark plug gap ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 0,25 mm
Ignition timing . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 24° BTDC
Exhaust temperature °C 487 478
Oxygen content in exhaust gas % 9,01 9,24
Lambda λ 1,71 1,70 Noise levels
The figures for total noise levels are typical for an engine running at
the continuous baseload power rating in a semi-reverberant
environment and measured at a distance of one metre from the
periphery of the engine (sound pressure level re: -20 x 10-6 pa).
Ambient noise level ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 70 dBA
4000 Series 4008-30TRS1
4008-30TRS2

4008-30TRS1 432 kWb 4008-30TRS2 526 kWb


Position 1 Position 1
102,8 dBA 102,3 dBA

Position 7 Position 2 Position 7 Position 2


102,7 dBA 103,8 dBA 103,5 dBA 104,8 dBA

Position 6 Position 3 Position 6 Position 3


103,3 dBA 105,7 dBA 103,5 dBA 105,4 dBA

Position 5 Position 4 Position 5 Position 4


104,5 dBA 104,5 dBA 104,2 dBA 104,2 dBA

at position 7
120

110
Noise level - dB

100

90

80

70

60
31.5 63 125 250 500 1K 2K 4K 8K 16K Hz

Engine mounting
Maximum additional load applied to flywheel due to all rotating components ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 650 kg

The information given on this Technical Data Sheet is for guidance only. For ratings other than those
shown, please contact Perkins Engines Company Limited.

Publication No. TPD1565E, Issue 2. October 2007. © Perkins Engines Company Limited.

@Perkins ® Distributed by

Perkins Engines Company Limited


Peterborough PE1 5NA United Kingdom
Telephone +44 (0) 1733 583000
Fax +44 (0) 1733 582240
www.perkins.com

All information in the document is substantially correct at the time