Generation
ST OF CERTIFICATION
I
electronic management
Engine
ntrols
e r a ti n g S e
t
Ratings
50 Hz 60 Hz
Pressure Pressure
Model kWe kVA* rpm bar (G) Model kWe kVA* rpm bar (G)
315 GFBA 315 394 1500 14 334 GFBA 334 417 1800 12.4
*@ 0.8pf
PowerCommand® Control
with AmpSentry™ Protection
● Integrated automatic voltage
regulator
● AmpSentry Protection guards the
electrical integrity of the alternator
and power system from the effects of
overcurrent, over/under voltage,
under frequency and overload
conditions PCCP PowerCommand Control
● Control components designed to
standard configuration with optional contactor buttons shown
withstand the vibration levels typical
in generator sets
● PowerCommand Digital Paralleling Standard Protection Functions Options
Warnings Control panel PowerCommand
Standard Control Description ● High Coolant Temperature options
● Analog % of current meter (amps) ● High DC Voltage ● Audible alarm and shutdown
● Analog AC frequency meter ● Low Coolant Temperature ● Key switch-operating mode
● Analog AC voltage meter ● Low DC Voltage ● Shutdown alarm-relay
● Analog % of load meter (kW) ● Low Oil Pressure ● Running relays 4 pole D.T.
● Cycle cranking control ● Over Current ● Earth fault. Shutdown
● Digital display panel ● Oil Pressure Sender Fault ● High alternator temperature
● Emergency stop switch ● Temperature Sender Fault alarm/shutdown
● Idle mode control ● Overload Load Shed Contacts Cummins Optional Network
● Menu switch ● Temperature Sender Fault Communications
● Panel backlighting ● Up to Four Customer Fault Inputs ● Echelon LonWorks multidrop
● Remote starting ● Weak Battery communication. Communication
● Reset switch Shutdowns network up to 5000 feet (1523 m) in
● Run-Off-Auto switch ● Emergency Stop length
● Sealed front panel, gasketed door ● Fail to Crank ● Allows for local and remote
● Self diagnostics ● Low Coolant Level (option for alarm communications with
● Separate customer interconnection only) PowerCommand network products
box ● Low Oil Pressure ● Power system monitoring and control
● Voltmeter/Ammeter phase selector ● Magnetic Pickup Failure using PowerCommand software
switch ● Overcrank ● Flexible for interface with other
● Overcurrent manufacturers’ control and
Standard Performance Data
● Overspeed monitoring systems
● Short Circuit Other PowerCommand Control options
AC Alternator Data ● Underfrequency are available
● Current by Phase ● High/Low AC Voltage
● Kilowatts
● Kilowatt Hours
● Power Factor Disconnector Switch*
● Voltage Line to Line The addition of a circuit breaker is
● Voltage Line to Neutral considered unnecessary when
Engine Data PowerCommand with Amp Sentry
● Battery Voltage protection is fitted. For isolation
● Coolant Temperature purposes a switch disconnector can be
● Engine Running Hours supplied and mounted in the normal
● Engine Starts counter circuit breaker position on either side of
● Oil Pressure the control panel.
● RPM
● Oil Temperature Voltage Regulation
±0.5% with PowerCommand fitted.
EMC Compliance
The PCC control system meets EMC
Shield Regulations.
Optional
entrance box
Dimensions and Weights or circuit
breaker either
B side.
D C O/A
A1 B1
Battery protrudes 100mm
Engine data subject to change without prior notice and are not contract values.
1) Service conditions according to ISO 8528/1 and reference conditions according to ISO 3046/1:
COP : Continuous output without time limitation between the stated maintenance intervals - no overload allowed, parallel operation with the grid.
Reference conditions : altitude 1000 metres, suction air temperature 35°C, LT. cooling water inlet temperature 40°C, methane index as stated above.
Derating :
If service conditions differ from the reference conditions, the engine is derated according to ISO 3046/1 ( Third edition, Tab. 1 - Ref. D).
In first approach, the rules below can be used:
- For each additional degree of suction air temperature above 35°C (max. : 50°C) : 0.4 % of the mechanical output.
- For each additional 100 metres of altitude above 1000 metres (max. : 2500 metres) : 1.0 % of the mechanical output.
- Gas specific consumption increase : 1/5 of derating (for example: a 10% derating will increase the specific consumption by 2%).
- For a LT. cooling water inlet temperature above 40°C, or a methane index below that stated above, or off the grid installation, consult CPG
2) Low voltage alternator terminals at power factor = 1.0 according to IEC 34.1.
3) According to ISO 3046/I with a tolerance of +5% - Natural gas LHV 33 440 kJ/Nm3.
4) Tolerance ±5%.
5) Outlet : maximum temperature allowed. Inlet : for information, with 30% of glycol and with outlet T° at max allowed.
6) Inlet : maximum temperature allowed. Outlet : for information, with 30% of glycol and with max allowed inlet T°.
7) With air intake at 35°C. Tolerance ± 10°C.
8) At full load (l/h for information, with lubricating oil density = 0.83).