You are on page 1of 2

Temperature Specific Volume Weight Density

0
F m3/kg kg/m3
32 0.00100010378798 999.704
40 0.00100010378798 1000.025
50 0.00100010378798 999.704
60 0.00100072807249 999.064
70 0.00100197664151 998.103
80 0.00100322521054 996.661
90 0.001005098 995.059
100 0.001006971 993.137
110 0.001009468 990.894
120 0.001011341 988.492
130 0.001014462 985.929
140 0.001016959 983.206
150 0.001020081 980.162
160 0.001023827 976.958
170 0.001026948 973.755
180 0.001030694 970.231
190 0.001034439 966.546
200 0.001038809 962.862
210 0.001042555 958.858
212 0.001043804 958.057
220 0.001047549 954.853
240 0.001056914 946.363
260 0.001066902 937.393
280 0.001077515 927.782
300 0.001089376 918.011
350 0.001123088 890.459
400 0.001163666 859.384
450 0.001212985 824.464
500 0.001275413 784.098
550 0.001358443 736.203
600 0.001475809 677.576
650 0.001669337 599.086
700 0.002286130 437.301
Main Contract 3 (MC3) Works for Development of
Document No: SE-BEB-03PL-CAL-0054
Muscat International Airport
Page 509 of 551
Domestic Water System Design Analysis for Passenger Terminal Building
Subject : Hot Water Heater Expansion Vessel Calculation
Building : Passenger Terminal Building_Zone 210

Expansion Vessel - 1 connected to EWH-1


Location: Staff and Services Level Grid T5-T6 / TAL-TAM

k Vw
Vet =
p0
1 -
p1

S.No Expansion Factor k Temperature o C


1 0.0299 80
2 0.0324 85
3 0.0359 90
4 0.0396 95
5 0.0434 100

Where:

k - expansion factor (refer to table)


Vw - volume of water, (3,714 liters)
p0 - initial (cold) pressure, 456.075 kPA
p1 - Setting of Expansion/Pressure Relief Valve, 608 kPA

0.0299 x 3,714 liters


Vet =
456.075 kPA
1 -
608 kPA

Vet = 444.41 liters

 2011 Bechtel-Enka-BEC Consortium