Wilson Transformer Co. Pty Ltd.

10 Moloney Drive,
Wodonga,
Victoria, 3690
Australia Phone (02) 6024 5944
Fax (02) 6024 7981
Transformer http://www.wtc.com.au

Routine Test Report


Serial Number: A623-0001 Customer Serial No:

Test Standard: AS 60076

kVA: 5000/2500/2500 Vector Symbol: Dy11y11

Rated Voltage: 33000 I 600 I 600

Frequency: 50

Phases: 3

Ratio Error not greater than 0.5% of M: 34650 33825 33000 32175 31350
Phase Displacement complies with connection symbol listed in Vector Symbol above

Induced Over Voltage M 1200 Applied to LVWinding For 30 Seconds@ 200 Hz

Separate Source HV (Kv) 70 Applied HVto LV1 and LV2 and Earth For 60 Seconds@ 50 Hz

Separate Source MV (Kv) 10 Applied LV1 to HVand LV2 and Earth For 60 Seconds@ 50 Hz

Separate Source LV (Kv) 10 Applied LV1 to HVand LV2 and Earth For 60 Seconds@ 50 Hz

Pressure tested at 20 kPa for 2 hours with a pressure drop of less than 2kPa

Guarantee Test Test System Accuracy

Impedance HV to (LV1+LV2)@ 5000 kVA(%) 6.75 6.68


Power: +/- 3.0%
Impedance HVto LV1@ 2500 kVA(%) 6.00 6.06 Voltage: +/- 0.5%
Current: +/- 0.5%
Impedance HVto LV2@ 2500 kVA(%) 6.00 6.06
Resistance: +/- 0.5%
Impedance LV1 to LV2@ 2500 kVA(%) >9 10.86 Temperature: +/- 1.0%

Load Loss @ 75 dee C (kW) 40.000 36.855

No Load Loss (kW) 3.750 3.4614

Magnetising Current (%) 0.50 0.24

Ins Res. HV-E (GOhm) 53.7

@2.5 kV LV1-E / LV2-E (GOhm) 37.4 / 43.6

HV-LV1 / HV-LV2 (GOhm) 7500.0 / 1460.o

LV1-LV2 7500.0

Test Temperature (Deg C) 22.90

HV Resistance A-B (Ohm) 1.083100

B-C (Ohm) 1.084000

A-C (Ohm) 1.084400

LV1 Resistance 1a2-1 b2 (Ohm) 0.000654

1b2-1c2 (Ohm) 0.000650

1a2-1c2 (Ohm) 0.000675

LV2 Resistance 2a2-2b2 (Ohm) 0.000654

2b2-2c2 (Ohm) 0.000657

2a2-2c2 (Ohm) 0.000665

The transformer has passed all of the required tests


Test Location: Wilson Transformers - Wodonga Plant
Date Tested: 3-May-2021

Tested By:. !Jim.ManaAon. Date Printed: 3-May-2021


Wilson Transformer Co. Pty Ltd.
10 Moloney Drive,
Wodonga,
Victoria, 3690
Australia Phone (02) 6024 5944
Fax (02) 6024 7981
Transformer http://www.wtc.com.au

Routine Test Report

Serial Number: 7683-0106 Customer Serial No:

Test Standard: AS 60076

kVA: 30 Vector Symbol: Dyn5

Rated Voltage: 600 / 415

Frequency: 50

Phases: 3

Ratio Error not greater than 0.5% of M: 600


Phase Displacement complies with connection symbol listed in Vector Symbol above

Induced Over Voltage M 830 Applied to LVWinding For 30 Seconds@ 200 Hz

Separate Source HV (Kv) 10 Applied HV to LV and Earth For 60 Seconds@ 50 Hz

Separate Source LV (Kv) 10 Applied LV to HV and Earth For 60 Seconds@ 50 Hz

Pressure tested at 20kPa for 2 hours with a pressure drop of less than 2 kPa
Energy Performance to AS 2374.1.2
Guarantee Test
n50%=((0.5xSr)/(0.5xSr)+0.25xP1+P0)x100%
Impedance@ 75 dee C (%) 4.00 3.95
Sr 30
Load Loss @ 75 dee C (kW) 0.830 0.746 P1
P1 0.746
No Load Loss (kW) 0.180 0.0752 PO PO 0.075
n50% 98.29
Magnetising Current (%) 0.52
MEPS Guarantee 0.00
Ins Res. HV-E (GOhm) 172.7 HEPS Guarantee 0.00

@2.5 kV LV-E (GOhm) 178.5 MEPS Compliance N/A


HEPS Compliance N/A
HV-LV (GOhm) 5000.0

Test Temperature (Deg C) 25.90 Test System Accuracy

HV Resistance A-B (Ohm) 0.2546


Power: +/- 3.0%
B-C (Ohm) 0.2541 Voltage: +/- 0.5%
Current: +/- 0.5%
A-C (Ohm) 0.2541
Resistance: +/- 0.5%
LV Resistance a-b (Ohm) 0.10744 Temperature: +/- 1.0%

b-c (Ohm) 0.10683

a-c (Ohm) 0.10812

Test Location: Wilson Transformers - Wodonga Plant


Date Tested: 6-Apr-2021

Tested By:. llnduu,, ~ Date Printed: 7-Apr-2021