Transformer http://www.wtc.com.au
Frequency: 50
Phases: 3
Ratio Error not greater than 0.5% of M: 34650 33825 33000 32175 31350
Phase Displacement complies with connection symbol listed in Vector Symbol above
Separate Source HV (Kv) 70 Applied HVto LV1 and LV2 and Earth For 60 Seconds@ 50 Hz
Separate Source MV (Kv) 10 Applied LV1 to HVand LV2 and Earth For 60 Seconds@ 50 Hz
Separate Source LV (Kv) 10 Applied LV1 to HVand LV2 and Earth For 60 Seconds@ 50 Hz
Pressure tested at 20 kPa for 2 hours with a pressure drop of less than 2kPa
LV1-LV2 7500.0
Frequency: 50
Phases: 3
Pressure tested at 20kPa for 2 hours with a pressure drop of less than 2 kPa
Energy Performance to AS 2374.1.2
Guarantee Test
n50%=((0.5xSr)/(0.5xSr)+0.25xP1+P0)x100%
Impedance@ 75 dee C (%) 4.00 3.95
Sr 30
Load Loss @ 75 dee C (kW) 0.830 0.746 P1
P1 0.746
No Load Loss (kW) 0.180 0.0752 PO PO 0.075
n50% 98.29
Magnetising Current (%) 0.52
MEPS Guarantee 0.00
Ins Res. HV-E (GOhm) 172.7 HEPS Guarantee 0.00