Dimensions and shipping data
Section of Buyers guide HV Live Tank Circuit Breakers Ed 6
For more information please contact: ©Copyright 2015 ABB. All rights reserved
1HSM 9543 22-00en, Edition 6, 2014-04, Live Tank Circuit Breakers, Buyer’s Guide
NOTE! ABB AB is working continuously to improve the products. We therefore
ABB AB
reserve the right to change designs, dimensions and data without prior notice.
High Voltage Products
SE-771 80 Ludvika, Sweden
Phone: +46 (0)240 78 20 00
E-mail: circuit.breaker@se.abb.com
www.abb.com/highvoltage
LTB D and LTB E
Technical data according to IEEE
(General data, deviations may occur)
LTB 72.5D1/B
LTB 123D1/B
LTB 145D1/B
LTB 170D1/B
LTB 72.5E1
LTB 170E1
LTB 245E1
LTB 420E2
LTB 550E2
Number of breaks per pole 1 1 1 1 1 1 1 2 2
Rated voltage kV 72.5 123 145 170 72.5 170 245 362 550
Rated frequency Hz 60 60 60 60 60 60 60 60 60
Power frequency withstand voltage 1)
- To earth (Dry/Wet) kV 160/140 260/230 310/275 365/315 160/140 365/315 425/350 555/- 860/-
- Across open pole (Dry/Wet) kV 160/140 260/230 310/275 365/315 160/140 365/315 425/350 555/- 860/-
Lightning Impulse Withstand Voltage
- To earth kV 350 550 650 750 350 750 900 1300 1800
- Across open pole kV 350 550 650 750 350 750 900 1300 1800
Chopped Wave Impulse
Withstand Voltage
- To earth (2 μs) kV 452 710 838 968 452 968 1160 1680 2320
- Across open pole (2 μs) kV 452 710 838 968 452 968 1160 1680 2320
Switching Impulse Withstand Voltage
- To earth kV - - - - - - - 825 1175
- Across open pole kV - - - - - - - 900 1300
Rated continuous current A 3000 3000 3000 3000 4000 4000 4000 4000 4000
Rated s.c current kA 40 40 40 40 40 40 40 40 40
First-pole-to-clear factor 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.3
Rated closing and latching current kA 104 104 104 104 104 104 104 104 104
Duration of short-time withstand current s 3 3 3 3 3 3 3 3 3
Closing time 2)
ms < 40 < 40 < 40 < 40 < 55 < 70 < 55 < 70 < 70
Opening time 2)
ms 22 22 22 22 17 19 17 18 18
Interrupting time 2)
ms 40 40 40 40 40 40 40 40 40
Dead time ms 300 300 300 300 300 300 300 300 300
Rated standard operating duty - O-0.3 s-CO-3 min-CO or CO-15 s-CO
1)
Up to and including 245 kV, power frequency withstand voltage ratings apply for both wet and dry conditions
2)
Depending on operating mechanism
LTB 72.5D1/B
LTB 123D1/B
LTB 145D1/B
LTB 170D1/B
LTB 72.5E1
LTB 170E1
LTB 245E1
LTB 420E2
LTB 550E2
LTB 800E4
Number of breaks per pole 1 1 1 1 1 1 1 2 2 4
Rated voltage kV 72.5 123 145 170 72.5 170 245 420 550 800
Rated frequency Hz 50/60 50/60 50/60 50/60 50 60 50 60 50 60 50 60 50 60 50
Power frequency
withstand voltage 1)
- To earth and between phases kV 140 230 275 325 140 325 460 520 620 830
- Across open pole kV 140 230 275 325 140 325 460 610 800 1150
Lightning Impulse
Withstand Level (LIWL)
- To earth and between phases kV 325 550 650 750 325 750 1050 1425 1550 2100
- Across open pole kV 325 550 650 750 325 750 1050 1425 (+240) 1550 (+315) 2100 (+455)
Switching Impulse
Withstand Level (SIWL)
- To earth / Between phases kV - - - - - - - 1050/1575 1175/1760 1550/2480
- Across open pole kV - - - - - - - 900 (+345) 1300 (+450) 1175 (+650)
Rated normal current A 3150 3150 3150 3150 4000 4000 4000 4000 4000 4000
Rated s.c breaking current kA 40 40 40 40 50 40 50 40 50 40 50 40 50 40 50
First-pole-to-clear factor - 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.3 1.3 1.3
Making current peak kA 100/104 100/104 100/104 100/104 125 104 125 104 125 104 125 104 125 104 125
Duration of short-circuit s 3 3 3 3 3 3 3 3 3 3
Closing time 2)
ms < 40 < 40 < 40 < 40 < 65 < 65 < 65 < 70 < 70 < 65
Opening time 2)
ms 22 22 22 22 17 17 17 18 18 20
Break time 2)
ms 40 40 40 40 40 40 40 40 40 40
Dead time ms 300 300 300 300 300 300 300 300 300 300
Rated operating sequence - O-0.3 s-CO-3 min-CO or CO-15 s-CO
1)
Up to and including 245 kV, power frequency withstand voltage ratings apply for both wet and dry conditions
2)
Depending on operating mechanism
Dimensions (mm)
Rated voltage A B C D E F
F
72.5 kV 4647 1164 670 3283 1050 3230
E E
267
145 kV 5197 1164 1220 3833 1750 4630
170 kV 5808 1475 1520 4133 1750 4630
B
2000
707
1218
145 kV - 1750* 2000 2500
692
170 kV - 1750* 2000 2500
*) Standard 300
2530
Dimensions (mm)
Rated voltage A B C D E F F
72.5 kV 4647 1164 670 3283 1050 3266 E E
267
145 kV 5197 1164 1220 3833 1750 4666
170 kV 5808 1475 1520 4133 1750 4666
B
Dimensions (mm)
Rated voltage A B C D E F
72.5 kV 4790 1292 655 3244 1100 3590
170 kV 5400 1292 1265 3854 2500 6390
245 kV 6703 1914 1955 4544 3500 8390
Dimensions (mm)
Rated voltage A B C D E* F
72.5 kV 4790 1292 655 3244 2500 6298
170 kV 5400 1292 1265 3854 2500 6298
245 kV 6703 1914 1955 4544 3500 8298
*) Recommended phase distances
Dimensions (mm)
Rated voltage A B C D E* F
72.5 kV 4790 1292 655 3244 2500 6298
170 kV 5400 1292 1265 3854 2500 6298
245 kV 6703 1914 1955 4544 3500 8298
E E
420
A C D
1728 2508
1428
Dimensions (mm)
Rated voltage A B C D E* F
72.5 kV 4790 1292 655 3244 2500 4874
170 kV 5400 1292 1265 3854 2500 6874
245 kV 6703 1914 1955 4544 3500 7874
F
648
E E
420
A C
2511
1638
Dimensions (mm)
Rated voltage A B C D E* F
72.5 kV 4790 1292 655 3244 2500 4874
170 kV 5400 1292 1265 3854 2500 6874
245 kV 6703 1914 1955 4544 3500 7874
E E 648
420
A C
2511
1638
1243
Dimensions (mm)
Dimensions (mm)
Dimensions (mm)
10860
1600 pF
5870 6070
11001
10642
3847
2086
HPL 72.5B1
HPL 170B1
HPL 245B1
HPL 420B2
HPL 550B2
HPL 800B4
Number of breaks per pole 1 1 1 2 2 4
Rated voltage kV 72.5 170 245 362 550 800
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60
Power frequency withstand voltage 1)
- To earth (Dry/Wet) kV 160/140 365/315 425/350 555/- 860/- 960/-
- Across open pole (Dry/Wet) kV 160/140 365/315 425/350 555/- 860/- 960/-
Lightning Impulse Withstand Voltage (LIWL)
- To earth kV 350 750 900 1300 1800 2050
- Across open pole kV 350 750 900 1300 1800 2050
Chopped Wave Impulse Withstand Voltage
- To earth (2 μs) kV 452 968 1160 1680 2320 2640
- Across open pole (2 μs) kV 452 968 1160 1680 2320 2640
Switching Impulse Withstand Voltage (SIWL)
- To earth kV - - - 825 1175 1425
- Across open pole kV - - - 900 1300 1550
Rated continuous current A 4000 4000 4000 4000 4000 4000
Rated s.c current kA 63 2)
63 2)
63 2)
63 2)
63 2)
63 2)
HPL 72.5B1
HPL 170B1
HPL 245B1
HPL 300B1
HPL 420B2
HPL 550B2
HPL 800B4
Number of breaks per pole 1 1 1 1 2 2 4
Rated voltage kV 72.5 170 245 300 420 550 800
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Power frequency withstand voltage1)
- To earth and between phases kV 140 325 460 380 520 620 830
- Across open pole kV 140 325 460 435 610 800 1150
Lightning Impulse Withstand Level (LIWL)
- To earth and between phases kV 325 750 1050 1050 1425 1550 2100
- Across open pole kV 325 750 1050 1050 (+170) 1425 (+240) 1550 (+315) 2100 (+455)
Switching Impulse Withstand Level (SIWL)
- To earth / Between phases kV - - - 850/1275 1050/1575 1175/1760 1550/2480
- Across open pole kV - - - 700/(+245) 900 (+345) 900 (+450) 1175 (+650)
Rated normal current A 4000 4000 4000 4000 4000 4000 4000
Rated s.c breaking current kA 63 2)
63 2)
63 2)
63 2)
63 2)
63 2)
63 2)
Dimensions (mm)
Rated voltage A B C D E F
72.5 kV 5213 1724 655 3270 1100 3600
170 kV 6063 1724 1505 4120 2500 6400
245 kV 6703 1914 1955 4570 3500 8400
300 kV 7163 2124 2205 4820 3500 8400
Dimensions (mm)
Rated voltage A B C D E* F F
72.5 kV 5213 1724 655 3270 2500 6400
E E 420
170 kV 6063 1724 1505 4120 2500 6400
245 kV 6703 1914 1955 4570 3500 8400
300 kV 7163 2124 2205 4820 3500 8400
*) Recommended phase distances B
2508
752
4135
8043
7571
2366 2508
752
10100
795 795
1724
11001 5870
10642
3847
2086
For more information please contact: ©Copyright 2015 ABB. All rights reserved
1HSM 9543 22-00en, Edition 6, 2014-04, Live Tank Circuit Breakers, Buyer’s Guide
NOTE! ABB AB is working continuously to improve the products. We therefore
ABB AB
reserve the right to change designs, dimensions and data without prior notice.
High Voltage Products
SE-771 80 Ludvika, Sweden
Phone: +46 (0)240 78 20 00
E-mail: circuit.breaker@se.abb.com
www.abb.com/highvoltage